Green Power 20
Green Power 20
0 and Delphys BC
Modbus - TCP / Jbus serial link
Installation and operating manual GB
Index
1. Foreword 4
2. Safety Requirement 4
2. 1. Using conditions 4
2. 2. DELPHYS Green Power Operating Reference 4
3. Environment 4
3. 1. Recycling of electrical products and equipment 4
4. Introduction 5
4. 1. General purpose 5
4. 2. Modbus protocol 5
4. 3. Data decoding 5
7. Conventions 11
ENGLISH
9. 5. Ups Configuration 22
9. 6. Preliminary Remarks 22
9. 7. Ups Status 23
9. 8. Ups Alarms 24
9. 9. Ups Measurements 25
9. 10. Ups Enabled Controls Table 26
9. 11. To Send Control To Ups 26
13. ANNEXE 45
13. 1. MODBUS TCP Card WEB PAGE 45
13. 2. MODBUS TCP IDA specification 46
We thank you for the trust you have in our Uninterruptible Power Systems.
This equipment is fitted with up to date technology. Rectifier and inverter subsets are provided with power semicon-
ductors (IGBT) including a digital micro-controller.
CAUTION : “This is a product for restricted sales distribution to informed partners. Installation restrictions or addi-
tional measures may be needed to prevent disturbances”.
SOCOMEC reserves the right to modify their specifications at any time as far as this contributes to
technical progress.
2. Safety Requirement
2. 1. Using conditions
Do read carefully these operation instructions before using the JBUS/MODBUS interface.
Whatever the repairs, they must be made only by authorised staffs, which have been suitably trained.
For an optimal operation, it is recommended to maintain the ambient temperature and humidity of the DELPHYS
Green Power environment below the values specified by the manufacturer.
This equipment meets the requirements of the European directives applied to this product. As a consequence it is
labelled as follows:
3. Environment
4. 1. General purpose
This document provides required information of the MODBUS protocol serial link or Ethernet network.
Before connecting a supervision equipment or BMS system (Building management system) to the UPS, it is neces-
sary to install and set up the serial interface or network configurations in the case of a network connection..
ENGLISH
4. 2. Modbus protocol
This document does not explain the MODBUS protocol management. Please refer on
www.modbus.org web site for more information.
The data field is composed of 1 word, defined by a MSB (most significant byte) and a LSB (lowest significant byte),
and displayed in the following order on the serial link.
1 WORD DATA
b7 MSB b0 b7 LSB b0
b15 b0
4. 3. Data decoding
5. 1. ‘Com-Slots’ localisation
The « Com-Slots » integrates all communication interfaces and it is located on the right side.
2
1
Please, see on the manual of the concerned UPS to see the correct localisation of the «com slot 2»
There is only one MODBUS serial link interface for a parallel system configuration. One serial interface
is used for the whole installation. The access to the data of the UPS module or unit is managed by the
table addressing .
In a parallel installation with centralized bypass, it is recommended to install the serial card in slot 2
of the bypass.
NOTE : there is only one connection per interface (RS232 or RS422 or RS485)
ENGLISH
–– Standard PC connection
–– Sub-D 9 pins connector
–– Pin 2 : Rx
–– Pin 3 : Tx
–– Pin 5 : GND RTX + RTX -
–– 2 wires connection
–– « dip-switch 1 » allows connecting the terminal resistor
–– Insulation via “opto-coupler”
–– 2 polarization resistors could be removed easily (if needed).
TX + TX -
–– 4 wires connection
–– « dip-switch 1 and 2 » allows connecting the terminal
resistor
–– Insulation via “opto-coupler”
–– 4 polarization resistors could be removed easily (if needed). RX + RX -
Before making any connection, please check the cabling. A wrong connection or cabling can damage
the serial link interface.
Please, see on the manual of the concerned UPS to see the correct localisation of the «com slot»
6. 1. ‘Com-Slots’ localisation
The « Com-Slots » integrates all communication interfaces and it is located on the right side.
ENGLISH
2
1
Please, see on the manual of the concerned UPS to see the correct localisation of the «com slot 2»
These settings are compulsory to make the Modbus TCP communication available
DEFAULT SETTING
DHCP mode by default. No IP address set by default
Mode MODBUS TCP
Port TCP 502
DISCOVERY TOOL
Download AGILIPLUG utility from SOCOMEC web site.
Unzip the file on your computer (only Windows)
run AGILIPLUG Finder program
INTERFACE CONFIGURATION
The MODBUS TCP Interface detects automatically the baud arte of serial link.
Opening the web page, allows to change IP settings.
login: root
password: public
ENGLISH
Error function code Error code Cause
80 + code function 1 Function error
80 + code function 2 Addresses error
80 + code function 3 Wrong data
80 + code function 6 busy
80 + code function 8 Write register error
1 2 3 4 5 6 7 8 9 10 11 12
MSB 0 LSB 0 MSB 1 LSB 1 MSB 2 LSB 2 MSB 3 LSB 3 MSB 4 LSB 4 MSB 5 LSB 5
S015 S000 S031 S016 S047 S032 S063 S048 S079 S064 S095 S080
I000 UPS identification 10 WORDS 0x1100 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
I010 UPS Description 6 WORDS 0x110A 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
I016 Location 6 WORDS 0x1110 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
ENGLISH
I022 Serial number 10 WORDS 0x1116 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
D00 Minutes / seconds 1 WORDS 0x1360 Byte value MSB = minutes, LSB = seconds
D01 Hours / day 1 WORDS 0x1361 Byte value MSB = day, LSB = hours
MSB = month,
Month / day of
D02 1 WORDS 0x1362 Byte value LSB = day of the week
week
1=Monday...7=Sunday
ENGLISH
S084 Battery test in progress 4
S085 Battery test in stand-by 5
S086 6
S087 7
S088 8
S089 9
S090 10
S091 11
S092 Local maintenance bypass Q5 clos. 12
S093 Remote maintenance bypass closed 13 Only on parallel
S094 Q21 switch closed 14 Only on parallel (if present)
S095 Q22 switch closed 15 Only on parallel (if present)
S096 Auxiliary input 1 active 0 0x1146
S097 Auxiliary input 2 active 1
S098 Auxiliary input 3 active 2
S099 Auxiliary input 4 active 3
S100 Auxiliary input 5 active 4
S101 Auxiliary input 6 active 5
S102 Auxiliary input 7 active 6
S103 Auxiliary input 8 active 7
S104 Auxiliary input 9 active 8
S105 Auxiliary input 10 active 9
S106 Auxiliary input 11 active 10
S107 Auxiliary input 12 active 11
S108 12
S109 13
S110 14
S111 Acknowledgement alarm request 15
ENGLISH
A076 12
A077 13
A078 14
A079 15
A080 Preventive maintenance 0 0x114D
A081 1
A082 Maintenance bypass alarm 2
A083 Rotation phase fault 3
A084 Rectifier or Bypass Input supply not OK 4
A085 5
A086 6
A087 7
A088 8
A089 9
A090 10
A091 11
A092 12
A093 13
A094 Output since xx minutes on auto bypass 14
A095 Unit General alarm 15
A096 Fly Wheel disconnected 0 0x114E
A097 Fly Wheel Critical 1 If set
A098 Fly Wheel preventive 2
A099 3
A100 4
A101 Aux. input alarm 5 If set
A102 6
A103 7
A104 8
A105 9
A106 10
A107 11
A108 12
A109 kW - kVA configuration Error 13
A110 Eco-mode configuration Error 14
A111 Option board alarm 15
Format Format
Code Description Unit Address
T015=0 T015=1
M071 Inverter frequency x10 Hz 7 ##.# ##.#
M072 Bypass input supply voltage U12 V 8 ### ###
M073 Bypass input supply voltage U23 V 9 ### ###
M074 Bypass input supply voltage U31 V A ### ###
ENGLISH
M075 Bypass input supply voltage V1 V B ### ###
M076 Bypass input supply voltage V2 V C ### ###
M077 Bypass input supply voltage V3 V D ### ###
M078 Bypass input supply frequency x10 Hz E ###.# ###.#
M079 Ambient T° °C F ##.# ##.#
M080 Vdc + V 0x1250 ### ###
M081
M082 Battery voltage string + V 2 ### ###.#
M083
M084 Battery current + A 4 # ### # ###.#
M085
M086 6
M087 7
M088 8
M089 9
M090 A
M091 Battery T° °C B ##.# ##.#
M092 Average battery T° °C C ##.# ##.#
M093 Battery capacity Ah D # ### # ###.#
M094 Battery capacity % E ### ###
M095 Remaining backup time mn F ### ###
M096 0x1260
M097 1
M098 2
M099 3
M100 4
M101 5
M102 6
M103 7
M104 8
M105 9
M106 A
M107 B
M108 C
M109 D
M110 E
M111 F
9. 1. Reminder
In UPS parallel system configuration, there is only one MODBUS interface. The addresses mapping gives the pos-
sibility to read data from each unit and system. There is no link between the MODBUS salve number and the unit
number.
The interface is plugged in the UPS unit 1 “com slots 2” in case of modular system (see bellow).
ENGLISH
1 2
3
m = number of unit
Example:
0x3100 = ID of unit 3
0x3140 = UPS States
0x3143 = unit 3 states
9. 6. Preliminary Remarks
The UNIT data are the same as described for single unit.
Following tables describe only the UPS part (common for all units)
ENGLISH
S005 Energy Saver 5
S006 UPS in normal mode 6
S007 UPS Starting procedure in progress 7
S008 UPS on maintenance bypass proc. in progress 8
S009 9
S010 10
S011 11
S012 UPS Bypass input supply absence 12 Synthesis of all
S013 UPS Rectifier input supply absence 13 units
S014 14
S015 Remote control enabled 15
S016 Unit 1 operating 0 0x0141
S017 Unit 2 operating 1
S018 Unit 3 operating 2
S019 Unit 4 operating 3
S020 Unit 5 operating 4
S021 Unit 6 operating 5
S022 Unit 7 operating 6
S023 Unit 8 operating 7
S024 8
S025 9
S026 10
S027 11
S028 12
S029 13
S030 14
S031 15
S032 Unit 1 available 0 0x0142
S033 Unit 2 available 1
S034 Unit 3 available 2
S035 Unit 4 available 3
S036 Unit 5 available 4
S037 Unit 6 available 5
S038 Unit 7 available 6
S039 Unit 8 available 7
ENGLISH
M003 Output voltage L1 V 3 ### ###
M004 Output voltage L2 V 4 ### ###
M005 Output voltage L3 V 5 ### ###
M006 Output current L1 A 6 # ### # ###.#
M007 Output current L2 A 7 # ### # ###.#
M008 Output current L3 A 8 # ### # ###.#
M009 Output frequency x10 Hz 9 ##.# ##.#
M010 Output Power factor L1 A +/- #.## +/- #.##
M011 Output Power factor L2 B +/- #.## +/- #.##
M012 Output Power factor L3 C +/- #.## +/- #.##
M013 Output Active Power L1 kW D # ### # ###.#
M014 Output Active Power L2 kW E # ### # ###.#
M015 Output Active Power L3 kW F # ### # ###.#
M016 Output Apparent P. L1 kVA 0x210 # ### # ###.#
M017 Output Apparent P. L2 kVA 1 # ### # ###.#
M018 Output Apparent P. L3 kVA 2 # ### # ###.#
M019 Output Crest Factor 3 #.# #.#
M020 Output load rate L1 % 4 ### ###
M021 Output load rate L2 % 5 ### ###
M022 Output load rate L3 % 6 ### ###
M023 UPS load rate % 7 ### ###
M024 UPS Output power kVA 8 # ### # ###.#
M025 9
M026 A
M027 B
M028 C
M029 D
M030 E
M031 F
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using the Human Machine
Interface. Local controls are then locked.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not allowed,
the function will be ignored.
10. 1. Reminder
In UPS parallel system configuration, there is only one MODBUS interface. The addresses mapping gives the pos-
sibility to read data from each unit and system. There is no link between the MODBUS salve number and the unit
number.
The interface is plugged in the ‘com-slots 2’ of bypass cabinet.
ENGLISH
By-pass
1
2
m=1
- - - - number of module
m=8
m = 15 Bypass data
Example:
0x3100 = ID of unit 3
0x3140 = UPS States
0xF143 = Bypass 3 states
Following tables describe only the UPS part (common for all units)
ENGLISH
S005 Energy Saver 5
S006 UPS in normal mode 6
S007 UPS Starting procedure in progress 7
S008 UPS on maintenance bypass proc. in progress 8
S009 9
S010 10
S011 11
S012 UPS Bypass input supply absence 12 Synthesis of all
S013 UPS Rectifier input supply absence 13 units
S014 14
S015 Remote control enabled 15
S016 Module 1 operating 0 0x0141
S017 Module 2 operating 1
S018 Module 3 operating 2
S019 Module 4 operating 3
S020 Module 5 operating 4
S021 Module 6 operating 5
S022 Module 7 operating 6
S023 Module 8 operating 7
S024 8
S025 9
S026 10
S027 11
S028 12
S029 13
S030 Bypass working 14
S031 15
S032 Module 1 available 0 0x0142
S033 Module 2 available 1
S034 Module 3 available 2
S035 Module 4 available 3
S036 Module 5 available 4
S037 Module 6 available 5
S038 Module 7 available 6
S039 Module 8 available 7
S046 Bypass available 14
ENGLISH
M003 Output voltage L1 V 3 ### ###
M004 Output voltage L2 V 4 ### ###
M005 Output voltage L3 V 5 ### ###
M006 Output current L1 A 6 # ### # ###.#
M007 Output current L2 A 7 # ### # ###.#
M008 Output current L3 A 8 # ### # ###.#
M009 Output frequency x10 Hz 9 ##.# ##.#
M010 Output Power factor L1 A +/- #.## +/- #.##
M011 Output Power factor L2 B +/- #.## +/- #.##
M012 Output Power factor L3 C +/- #.## +/- #.##
M013 Output Active Power L1 kW D # ### # ###.#
M014 Output Active Power L2 kW E # ### # ###.#
M015 Output Active Power L3 kW F # ### # ###.#
M016 Output Apparent P. L1 kVA 0x0210 # ### # ###.#
M017 Output Apparent P. L2 kVA 1 # ### # ###.#
M018 Output Apparent P. L3 kVA 2 # ### # ###.#
M019 Output Crest Factor 3 #.# #.#
M020 Output load rate L1 % 4 ### ###
M021 Output load rate L2 % 5 ### ###
M022 Output load rate L3 % 6 ### ###
M023 UPS load rate % 7 ### ###
M024 UPS Output power kVA 8 # ### # ###.#
M025 9
M026 A
M027 B
M028 C
M029 D
M030 E
M031 F
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using the Human Machine
Interface. Local controls are then locked.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not allowed,
the function will be ignored.
ENGLISH
S051 Load not supplied 3
S052 4
S053 5
S054 Output switch 3 closed 6
S055 7
S056 8
S057 9
S058 10
S059 1
S060 12
S061 Bypass switch activated 13
S062 14
S063 Servicing alert 15
S064 0 0xF144
S065 1
S066 2
S067 3
S068 4
S069 5
S070 6
S071 7
S072 Unit in normal mode 8
S073 9
S074 10
S075 1
S076 12
S077 13
S078 14
S079 Bypass in servicing mode 15
ENGLISH
A036 Insufficient Resources 4 Only on parallel
A037 5
A038 6
A039 7
A040 8
A041 Bypass critical 9
A042 Common critical 10
A043 FAN alarm 11
A044 Back feed protection open 12
A045 ACS synchro source fault 13
A046 14
A047 15
A048 0 0xF14B
A049 1
A050 2
A051 3
A052 4
A053 5
A054 6
A055 7
A056 8
A057 9
A058 10
A059 11
A060 Bypass preventive 12
A061 13
A062 14
A063 15
A064 0 0xF14C
A065 1
A066 2
A067 3
A068 4
A069 5
A070 6
ENGLISH
M035 Output voltage L1 V 3 ### ###
M036 Output voltage L2 V 4 ### ###
M037 Output voltage L3 V 5 ### ###
M038 Output current L1 A 6 # ### # ###.#
M039 Output current L2 A 7 # ### # ###.#
M040 Output current L3 A 8 # ### # ###.#
M041 Output frequency x10 Hz 9 ##.# ##.#
M042 Output Power factor L1 A +/- #.## +/- #.##
M043 Output Power factor L2 B +/- #.## +/- #.##
M044 Output Power factor L3 C +/- #.## +/- #.##
M045 Output Active Power L1 kW D # ### # ###.#
M046 Output Active Power L2 kW E # ### # ###.#
M047 Output Active Power L3 kW F # ### # ###.#
M048 Output Apparent Power L1 kVA 0xF230 # ### # ###.#
M049 Output Apparent Power L2 kVA 1 # ### # ###.#
M050 Output Apparent Power L3 kVA 2 # ### # ###.#
M051 Output Crest Factor 3 #.# #.#
M052 Output load rate L1 % 4 ### ###
M053 Output load rate L2 % 5 ### ###
M054 Output load rate L3 % 6 ### ###
M055 Unit load rate % 7 ### ###
M056 Unit Power S Output kVA 8 # ### # ###.#
M057 Unit Power P Output kW 9 # ### # ###.#
M058 A
M059 B
M060 C
M061 D
M062 E
M063 F
M064 0xF240
M065 1
M066 2
M067 3
M068 4
M069 5
M070 6
Format Format
Code Description Unit Address
T015=0 T015=1
M071 7
M072 Bypass input supply voltage U12 V 8 ### ###
M073 Bypass input supply voltage U23 V 9 ### ###
M074 Bypass input supply voltage U31 V A ### ###
M075 Bypass input supply voltage V1 V B ### ###
M076 Bypass input supply voltage V2 V C ### ###
M077 Bypass input supply voltage V3 V D ### ###
M078 Bypass input supply frequency x10 Hz E ###.# ###.#
M079 Ambient T° °C F ##.# ##.#
M080 0xF250
M081 1
M082 2
M083 3
M084 4
M085
M086 6
M087 7
M088 8
M089 9
M090 A
M091 B
M092 C
M093 D
M094 E
M095 F
M096 0xF260
M097 1
M098 2
M099 3
M100 4
M101 5
M102 6
M103 7
M104 8
M105 9
M106 A
M107 B
M108 C
M109 D
M110 E
M111 F
ENGLISH
S051 Load not supplied 3
S052 Module is available 4
S053 Module isolated from inst. 5
S054 Output switch 2 closed 6
S055 Rectifier ON 7
S056 Battery charging 8
S057 Battery charged 9
S058 10
S059 Inverter ON 11
S060 Inverter switch/contactor closed 12
S061 13
S062 14
S063 Servicing alert 15
S064 Rectifier input supply fault 0 0xm144
S065 Bypass input supply out of tolerance 1
S066 2
S067 Bypass input supply is synchro ref 3
S068 4
S069 5
S070 “UPS general power off” input active 6
S071 Generator set active 7
S072 Module in normal mode 8
S073 Module in eco-mode 9
S074 10
S075 Module in stand-by mode 11
S076 12
S077 13
S078 14
S079 Module in servicing mode 15
ENGLISH
A036 4
A037 5
A038 6
A039 Rectifier critical 7
A040 Inverter critical 8
A041 9
A042 Common critical 10
A043 FAN alarm 11
A044 Back feed protection open 12
A045 13
A046 14
A047 15
A048 Operating on battery 0 0xm14B
A049 Battery alarm 1
A050 Battery room 2
A051 Battery discharged 3
A052 End of autonomy time 4
A053 Battery test failure 5
A054 Earth leakage fault 6
A055 Battery circuit open 7
A056 On battery with mains OK 8
A057 DC voltage not OK 9
A058 Rectifier preventive 10
A059 Inverter preventive 11
A060 12
A061 Common preventive 13
A062 Mimic panel 14
A063 Ambient T° max 15
A064 BHC general alarm 0 0xm14C
A065 1
A066 2
A067 3
A068 4
A069 5
A070 6
ENGLISH
M035 Output voltage L1 V 3 ### ###
M036 Output voltage L2 V 4 ### ###
M037 Output voltage L3 V 5 ### ###
M038 Output current L1 A 6 # ### # ###.#
M039 Output current L2 A 7 # ### # ###.#
M040 Output current L3 A 8 # ### # ###.#
M041 Output frequency x10 Hz 9 ##.# ##.#
M042 Output Power factor L1 A +/- #.## +/- #.##
M043 Output Power factor L2 B +/- #.## +/- #.##
M044 Output Power factor L3 C +/- #.## +/- #.##
M045 Output Active Power L1 kW D # ### # ###.#
M046 Output Active Power L2 kW E # ### # ###.#
M047 Output Active Power L3 kW F # ### # ###.#
M048 Output Apparent Power L1 kVA 0xm230 # ### # ###.#
M049 Output Apparent Power L2 kVA 1 # ### # ###.#
M050 Output Apparent Power L3 kVA 2 # ### # ###.#
M051 Output Crest Factor 3 #.# #.#
M052 Output load rate L1 % 4 ### ###
M053 Output load rate L2 % 5 ### ###
M054 Output load rate L3 % 6 ### ###
M055 Unit load rate % 7 ### ###
M056 Unit Power S Output kVA 8 # ### # ###.#
M057 Unit Power P Output kW 9 # ### # ###.#
M058 Rectifier input supply volt. U12 V A ### ###
M059 Rectifier input supply volt. U23 V B ### ###
M060 Rectifier input supply volt. U31 V C ### ###
M061 Rectifier V1 V D ### ###
M062 Rectifier V2 V E ### ###
M063 Rectifier V3 V F ### ###
M064 Rectifier input supply frequency x10 Hz 0xm240 ##.# ##.#
M065 Rectifier input supply current L1 A 1 ###.# ###.#
M066 Rectifier input supply current L2 A 2 ###.# ###.#
M067 Rectifier input supply current L3 A 3 ###.# ###.#
M068 Inverter output voltage U12 V 4 ### ###
M069 Inverter output voltage U23 V 5 ### ###
M070 Inverter output voltage U31 V 6 ### ###
Format Format
Code Description Unit Address
T015=0 T015=1
M071 Frequency inverter x10 Hz 7 ##.# ##.#
M072 V 8 ### ###
M073 V 9 ### ###
M074 V A ### ###
M075 V B ### ###
M076 V C ### ###
M077 V D ### ###
M078 Hz E ###.# ###.#
M079 Ambient T° °C F ##.# ##.#
M080 Vdc + V 0xm250 ### ###
M081
M082 Battery voltage string + V 2 ### ###.#
M083
M084 Battery current + A 4 # ### # ###.#
M085
M086 6
M087 7
M088 8
M089 9
M090 A
M091 Battery T° °C B ##.# ##.#
M092 Average battery T° °C C ##.# ##.#
M093 Battery capacity Ah D # ### # ###.#
M094 Battery capacity % E ### ###
M095 Remaining backup time mn F ### ###
M096 0xm260
M097 1
M098 2
M099 3
M100 4
M101 5
M102 6
M103 7
M104 8
M105 9
M106 A
M107 B
M108 C
M109 D
M110 E
M111 F
ENGLISH
NETWORK CONFIGURATION
where:
0046 corresponds to the transaction number
0000 corresponds to the protocol identifier
0006 corresponds to the number of bytes (length of the message)
Note:
The CRC is suppressed in the encapsulated MODBUS frame.
where:
0046 corresponds to the transaction number
0000 corresponds to the protocol identifier
0006 corresponds to the number of bytes (length of the message)
A worldwide presence
8 production sites
• France (x3)
27 subsidiaries
• Australia • Belgium • China • France
80 countries
where our brand is distributed
• Italy • Germany • India • Italy • Netherlands
• Tunisia • Poland • Romania • Singapore
• India • Slovenia • Spain • Switzerland • Thailand
• China (x2) • Tunisia • Turkey • UK • USA
Non contractual document. © 2018, Socomec SAS. All rights reserved. - Document printed on paper from sustainably managed forests.
www.socomec.co.uk