Harmonic Filter Selection Guide (APF)
Harmonic Filter Selection Guide (APF)
POWERMyriad
DISTRIBUTION AND PROTECTION
Pro Condensed 12 pt Capitals White
1
Step 1 – How much compensation is needed (A)?
step
2
step
2
3
Step 3 – 3 wire or 4 wire?
step
The four-wire option is required when there is an imbalance in the network.
Network imbalance is when differing line voltages across phases occurs, caused by unbalanced loads,
single phase and phase-to-phase connections. This information can be found on your meter or power
quality audit report.
• Mining
3 wire For balanced networks
• Industrial
• Food and beverage
• Manufacturing
• Commercial
4 wire
For an unbalanced network with a • Office
fully rated neutral wire • Education
• Shopping centers
4
Step 5 – IP rating requirement?
step
The environment that the cabinet would be installed has a major impact on the IP rating. NHP offers options
for IP30 or IP54 floor standing cabinets and an IIP3, 50A wall mount unit. It is not recommended for any of
the IP rated cabinets to be installed outdoors with direct sunlight or without cover for rain.
5
Step 5 – Colour of cabinet
step
3
Ordering Guide
Wall Mount System
For a wall mount Active Power Filter (APF) solution, the power module is included in the enclosure. Additional accessories are
required with the 50A wall mount module.
Module
50 IP31 PQ-APFWM-50-31-G-4-X-X-T-1A
Grey
100 IP30 PQ-APFWM-100-30-G-4-X-X-T-1A
Note: A maximum of two systems can be connected in parallel, for a larger compensation, please select a floor standing system.
3 Wire PQ-APFM-100-X-G-3-F-FC-X-1A
100A
4 Wire PQ-APFM-100-X-G-4-F-FC-X-1A
Cabinet
Max. Number of
Max Capacity (A)
Modules IP rating Colour Catalogue No.
200 2 PQ-SVGC-200-30-G-X-F-FC-X-1A
200 2 PQ-SVGC-200-30-O-X-F-FC-X-1A
IP30
500 5 PQ-SVGC-500-30-O-X-F-FC-X-1A
Orange
700 7 PQ-SVGC-700-30-O-X-F-FC-X-1A
4
Ordering Examples
Example 1:
To get a 200A, 3 wire APF system with 100A spare capacity and a fixed type, IP30, Orange cabinet
Order: 2 x PQ-APFM-100-X-G-3-F-FC-X-1A and 1 x PQ-SVGC-300-30-O-X-F-FC-X-1A
Example 2:
To get a 50A 4 wire APF wall mount system.
Order: 1 x PQ-APFWM-50-31-G-4-X-X-T-1A, 1 x 3313192900SP and 1 x PQCMA101ANB21B0
5
Cable and breaker Selection Guide
Appropriate cable and breaker selection are a vital part of ensuring the system will operate at its optimal capacity.
Table 1 shows the required breaker rating and a guide to cable sizes for the respective APF system.
Note: The cable sizes are a guide only, always refer to AS/NZS3008 for specific requirements. Individual de-rating
based on method of installation, cable lengths, volt drop, ambient temperature and cable configuration must be
allowed for when sizing cable.
Note: For 3P3W APF, there are cooling fans in the cabinet, and rated voltage of these fans is AC220V, so a 1.5mm2 cable
should be connected to 3P3W APF cabinet’s Neutral terminal powering AC220V fans in the cabinet. For 3P4W APF, Neutral
cable diameter should follow the guideline in the above table.
CT Selection Guide
The correct CTs must be selected according to electric condition of installing site. Requirements of CT
selection for APF are shown in Table 2.
Specification Requirement
CT Primary Current: 5A
CT Ratio
CT Primary Current ≥ 1.7* Maximum Load Current
Note: Recommended secondary current of CT is 5A. When actual CT secondary current is 1A, CT ratio setting should be changed
accordingly, for example, if the actual CT ratio is 500:1A, the CT ratio setting in APF Touch Panel HMI should be 2500:5A.
6
Critical Installation Information
The placement of the CTs during the installation is critical to the operation of the system.
The following examples are for the most common installations. Unlike the SVG systems, the CT placements for APF are the same for both
balanced and unbalanced loads. For applications where more than one APF is required, there are capacitor banks present or any other
variations to the scenarios outlined above, please refer to the full CT selection and installation guide.
1. Closed loop
In this scenario, 3 CTs shall be installed at grid side (R/S/T phases), and another 3 CTs shall be installed at APF input side.
All the CTs P1 should be facing grid side with same CT ratio.
Refer to Figure 1-1 for single line diagram (SLD) and Figure 1-2 for detailed connection.
P2
CT
T_S2 T_S1
S_S2 S_S1
R_S2 R_S1
CT Terminal Block in
APF P1 APF Wall Mount
Device // // //
CT
R-CT-S1
R-CT-S1
R-CT-S1
R-CT-S2
R-CT-S2
R-CT-S2
S-CT-S1
S-CT-S1
S-CT-S1
S-CT-S2
S-CT-S2
S-CT-S2
T-CT-S1
T-CT-S1
T-CT-S1
T-CT-S2
T-CT-S2
T-CT-S2
P2
-+
Loads Loads Loads
CT Terminal Block in APF Cabinet
APF from left to right: XT_PIN1 to XT_PIN18
Figure 1-1 CT Connection for closed loop, without cap Figure 1-2 CT Connection for closed loop, without cap bank scenario
bank scenario – SLD – Detailed
If CT connection is following this pattern, CT related parameters should be set according to following table for Touch Screen HMI .
7
2. Open loop
In this scenario, 3 CTs shall be installed at the load side (R/S/T phases), P1 should be facing the grid side. Refer to Figures 2-1 and 2-2
for single line diagram (SLD) and detailed connection.
CT
GRID S1 S2
R
S1 S2
//
S
//
T
S1 S2 LOAD
P1 P2
//
Loads Loads
APF CT
APF
R-CT-S1
R-CT-S1
R-CT-S1
R-CT-S2
R-CT-S2
R-CT-S2
S-CT-S1
S-CT-S1
S-CT-S1
S-CT-S2
S-CT-S2
S-CT-S2
T-CT-S1
T-CT-S1
T-CT-S1
T-CT-S2
T-CT-S2
T-CT-S2
Cabinet
T_S2 T_S1
S_S2 S_S1
R_S2 R_S1
Figure 2-1 CT Connection for open loop, without cap SVG Wall Mount
CT Terminal CT Terminal to right: XT_PIN1 to XT_PIN1
If CT connection is following this pattern, CT related parameters should be set according to following table for Touch Screen HMI.
8
Services and training solutions to improve your business
To support our range of This access to NHP’s expertise, At NHP, we understand the
quality products, NHP also offer a wide combined with our extensive complexities of your project and
range of service and training options, local stockholding further enables our product and service offering
including technical support, field service,
customers to experience a holistic is designed to help you overcome
maintenance contracts, repair services
and training – all of which are delivered
approach across their automation, them. If your project is focused on
by qualified technicians. industrial switchgear, training a profitable, safe and sustainable
and commissioning business operation, NHP’s customised value
requirements, for complete add service and training offering is
peace of mind. the place to start.
[email protected] [email protected]