C-FIX 1.117.0.

0
Database version
2023.6.16.16.1
Date
25/01/2024

GTIPL B2 Noida , BLOCK -02 (NSL-NOIDA), NOIDA

fischer Building Materials India PVT


Ltd.

Prestige Garnet Unit NO- 401, 4th Floor


36, Ulsoor Road
560042 Bengaluru
Phone: +91 08 04 15 11 99 12 01
[email protected]
www.fischer.in

Comment
Revised Design Calculation For Monorail system as per current site condition.

Design Specifications
Anchor
Anchor system fischer Injection system FIS V
Injection resin FIS V 360 S
Fixing element Threaded rod FIS A M 16 x 200 R,
stainless steel, Property Class R-70(Gr304)
Calculated anchorage 150 mm
depth
Design Data Anchor design in Concrete according European Technical
Assessment ETA-02/0024, Option 1,
Issued 13/05/2020

Geometry / Loads / Scale units


mm, kN, kNm

Value of design actions (including

partial safety factor for the load) Seismic

Not drawn to scale

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 1
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
25/01/2024

GTIPL B2 Noida , BLOCK -02 (NSL-NOIDA), NOIDA

Input data

Design method EN 1992-4:2018


Base material C25/30, EN 206
Concrete condition Non-cracked, dry hole
Temperature range 24 °C long term temperature, 40 °C short term temperature
Reinforcement Normal or no reinforcement. No edge reinforcement
Drilling method Hammer drilling
Installation type Push-through installation
Annular gap Annular gap not filled
Type of loading Accidental/Seismic
Seismic Performance C1
Category
Seismic option a1) Capacity Design
Seismic actions > 20%
αvg ≤ 0.25 g
Fastening Type A
Base plate location Base plate flush installed on base material
Base plate geometry 250 mm x 150 mm x 10 mm
Profile type None

Design actions *⁾
# NEd VEd,x VEd,y MEd,x MEd,y MT,Ed Type of loading
kN kN kN kNm kNm kNm
1 5.75 0.00 0.00 0.00 0.00 0.00 Accidental/Seismic

*⁾ The required partial safety factors for actions are included

Resulting anchor forces


Tensile action Shear Action Shear Action x Shear Action y
Anchor no. kN kN kN kN
1 2.88 0.00 0.00 0.00
2 2.88 0.00 0.00 0.00

max. concrete compressive strain : 0.00 ‰


max. concrete compressive stress : 0.0 N/mm²
Resulting tensile actions : 5.75 kN , X/Y position ( 0 / 0 )
Resulting compression actions : 0.00 kN , X/Y position ( 0 / 0 )

Resistance to tension loads

Proof Action Capacity Utilisation βN


kN kN %
Steel failure * 2.88 58.82 4.9
Combined pull-out and concrete cone failure 5.75 38.18 15.1
Concrete cone failure 5.75 70.73 8.1

* Most unfavourable anchor

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 2
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
25/01/2024

GTIPL B2 Noida , BLOCK -02 (NSL-NOIDA), NOIDA

Steel failure

( NRd,s,eq )

NRk,s,eq,C1 γMs,eq NRd,s,eq NSd βN,s


kN kN kN %
110.00 1.87 58.82 2.88 4.9

βN,s
Anchor no. % Group N° Decisive Beta
1 4.9 1 βN,s;1
2 4.9 2 βN,s;2

Combined pull-out and concrete cone failure

( NRd,p,eq )

Eq. (7.13)

Eq. (7.14)

Eq. (7.14a)

Eq. (7.15)

Eq. (7.16)

Eq. (7.20)

Eq. (7.17)

Eq. (7.18)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 3
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
25/01/2024

GTIPL B2 Noida , BLOCK -02 (NSL-NOIDA), NOIDA

Eq. (7.21)

Eq. (7.5)

NRk,p,eq,C1 Ψc γMp,eq NRd,p,eq NSd βN,p


kN kN kN %
57.27 1.000 1.50 38.18 5.75 15.1

βN,p
Anchor no. % Group N° Decisive Beta
1, 2 15.1 1 βN,p;1

Concrete cone failure

( NRd,c,eq )

Eq. (7.1)

Eq. (7.2)

Eq. (7.4)

Eq. (7.5)

Eq. (7.6)

Eq. (7.7)

NRk,c,eq,C1 γMc,eq NRd,c,eq NSd βN,c


kN kN kN %
106.09 1.50 70.73 5.75 8.1

βN,c
Anchor no. % Group N° Decisive Beta
1, 2 8.1 1 βN,c;1

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 4
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
25/01/2024

GTIPL B2 Noida , BLOCK -02 (NSL-NOIDA), NOIDA

Resistance to combined tensile and shear loads

Proof successful

Information concerning the anchor plate


Base plate details
Plate thickness specified by user without proof t = 10 mm

Profile type None

Technical remarks
The transmission of the anchor loads to the supports of the concrete member shall be shown for the ultimate limit state and
the serviceability limit state; for this purpose, the normal verifications shall be carried out under due consideration of the
actions introduced by the anchors. For these verifications the additional provisions given in the current design method shall
be taken into account.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate (if present) must
be sufficiently stiff. The C-Fix anchor plate design is based on a proof of stresses and does not allow a statement about the
stiffness of the plate. The proof of the necessary stiffness is not carried out by C-Fix.

During the design process, the following hints and warnings were issued:

• Additionally to the proof against seismic actions a proof against static actions is required.
• Please take care for the concrete condition! Seismic actions and non-cracked concrete has to be double checked!

Technical remarks for seismic impact


The Eurocode EN 1992-4 provides a design method for anchors, which are used to transmit seismic actions to concrete
members. The Eurocode EN 1992-4 is intended for safety relevant applications in which the failure of anchors will result in
collapse or partial collapse of the structure, cause risk to human life or lead to significant economic loss.
The provisions in the Eurocode EN 1992-4 do not apply to the design of anchors placed in critical regions of concrete
elements where concrete spalling or yielding of reinforcement might occur during seismic events such as e.g. in plastic hinge
zones. Anchors should therefore be placed outside of these regions.

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 5
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
25/01/2024

GTIPL B2 Noida , BLOCK -02 (NSL-NOIDA), NOIDA

Installation data
Anchor
Anchor system fischer Injection system FIS V
Injection resin FIS V 360 S (other cartridge sizes Art.-No. 94405
available)
Fixing element Threaded rod FIS A M 16 x 200 R, Art.-No. 90456
stainless steel, Property Class R-70

Accessories FIS MR Plus Art.-No. 545853


FIS Extension tube 9mm Art.-No. 48983
Dispenser FIS DM S Art.-No. 511118
Compressed-air cleaning tool Art.-No. 93286
compressed air (oil-free), min. 6 bar By job site
BSD 18 Art.-No. 1493
SDS Chuck with internal thread M8 Art.-No. 530332
Quattric II 18/200/250 Art.-No. 549956
or alternatively
FHD 18/320/450 Art.-No. 546600
Hammer drilling with or without
suction
Alternative cartdriges FIS V 410 C Art.-No. 521431
The shown cartdriges are
alternative to the highlighted
one above with the same approval
number.

Installation details
Thread diameter M 16
Drill hole diameter d0 = 18 mm
Drill hole depth h2 = 160 mm
Calculated anchorage hef = 150 mm
depth
Drilling method Hammer drilling
Drill hole cleaning 4 times blowing,
4 times brushing,
4 times blowing
required activities according the
given instruction in the approval
No borehole cleaning required in
case of using a hollow drill bit, e.g.
fischer FHD.
Installation type Push-through installation
Annular gap Annular gap not filled
Maximum torque Tinst,max = 60.0 Nm
Socket size 24 mm
Base plate thickness t = 10 mm
Total fixing thickness tfix = 10 mm
Tfix,max
Volume of resin per drill 20 ml/10 scale divisions
hole

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 6
C-FIX 1.117.0.0
Database version
2023.6.16.16.1
Date
25/01/2024

GTIPL B2 Noida , BLOCK -02 (NSL-NOIDA), NOIDA

Base plate details


Base plate material Not available
Base plate thickness t = 10 mm
Clearance hole in base df=20 mm
plate

Attachment
Profile type None

Anchor coordinates

x y
Anchor no. mm mm
1 -90 0
2 90 0

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 7