PowerPoint Presentation
PowerPoint Presentation
The curves are roughly straight while the load is increased from zero to about
one-third to one-half the concrete’s ultimate strength (𝑓𝑐′). After this range the
behavior of concrete is nonlinear.
All the concretes reach their ultimate strengths (𝑓𝑐′ ) at strains of about 0.002.
Reinforced Concrete I Chapter 1 Lecture No.1
Concrete does not have a definite yield strength; the curves run to the point of
rupture at strains of from 0.003 to 0.004. It will be assumed for the purpose of
future calculations in this text that concrete fails at 0.003 (ACI 10.2.3):
𝜀𝑐𝑢 = 0.003
The weaker grades of concrete are less brittle than the stronger ones—that is,
they will take larger strains before breaking.
2. The tangent modulus: is the slope of a tangent to the curve at some point
along the curve—for instance, at 50% of the ultimate strength of the concrete.
3. Secant modulus: The slope of a line drawn from the origin to a point on the
curve somewhere between 25% and 50% of its ultimate compressive strength.
Section 8.5.1 of the ACI Code states that the following expression can be
used for calculating the modulus of elasticity of concretes (Ec) weighing (wc)
from1500 to 2500 kg/m3 and with 𝑓𝑐′ in N/mm2 or MPa (megapascals):
𝐸𝑐 = 𝑤1.5(0.043)√𝑓′
𝑐 𝑐
2. Beams are long, horizontal, or inclined members with limited width and
depth. Their main function is to support loads from slabs.
3. Columns are critical members that support loads from beams or slabs.
They may be subjected to axial loads or axial loads and moments.
5. Footings are pads or strips that support columns and spread their loads
directly to the soil.
6. Walls are vertical plate elements resisting gravity as well as lateral loads as
in the case of basement walls.
1. Types of loads
The structures are subjected to the following types of loads: dead loads, live loads,
and environmental loads.
1. Dead loads
Dead loads are loads of constant magnitude that remain in one position.
Dead loads include: the weight of the structure, and any permanent
attachments. For a reinforced concrete building, dead loads include: frames,
walls, floors, ceilings, stairways, roofs, and plumbing.
2. Live loads
Live loads are loads that can change in magnitude and position. Live loads
include: occupancy loads, warehouse materials, construction loads, overhead
service cranes, equipment operating loads and other.
3. Environmental loads
Environmental loads are loads caused by the environment in which the
structure is located. Environmental loads include: rain, snow, wind,
temperature change, and earthquake.
Environmental loads are live loads not caused by gravity or operating
conditions.
2. Load Combinations
Where:
Example 1:
Determine the required design strength for a column for which PD = 120 k, PL = 40 k,
and wind PW = 60 k compression or 80 k tension.
Homework 2:
The estimated service or working axial loads and bending moments for a particular
column are as follows: PD = 100 k, PL = 40 k, MD = 30 ft-k, and ML = 16 ft-k.
Compute the axial load and moment values that must be used in the design.
Note:
Service (working) loads: the actual loads that are assumed to be applied to a
structure when it is in service.
Reinforced Concrete I Chapter 2 Lecture No.4
In general, load factors (> 1) amplify loads, while reduction factors (< 1)
reduce strength.
Example 1:
Determine the required nominal strength for a column for which PD = 120 k, PL = 40
k, and wind PW = 60 k compression or 80 k tension.
Example 2:
The estimated service or working axial loads and bending moments for a particular
column are as follows: PD = 100 k, PL = 40 k, MD = 30 ft-k, and ML = 16 ft-k.
Compute the nominal axial load and the nominal moment values.
Reinforced Concrete I Chapter 2 Lecture No.5
𝑃𝐿
1 Under point load
4
Reinforced Concrete I Chapter 2 Lecture No.5
𝑃𝑎𝑏
2 Under point load
𝐿
𝑤𝐿
4 2 8
At center
5 PL At support A
Reinforced Concrete I Chapter 2 Lecture No.5
6 Pa At support A
𝑤𝐿
7 At support A
2
Where:
b: width of compression face of a beam
h: total thickness of beam
d: effective depth measured from extreme compression fiber to centroid of
tensile reinforcement
As: area of tensile reinforcing
𝜌: Percentage of tensile steel “ reinforcement ratio”
𝐴𝑆
𝜌=
𝑏𝑑
Reinforced Concrete I Chapter 2 Lecture No.5
(+M)
(-M)
Reinforced Concrete I Chapter 2 Lecture No.6
Assume that a small transverse load is placed on a concrete beam with tensile
reinforcing and that load is gradually increased in magnitude until the beam
fails. As this happen the beam will go through three behavior stages before
collapse:
1. Uncracked Concrete Stage
2. Concrete Cracked–Elastic Stresses Stage
3. Beam Failure—Ultimate-Strength Stage
𝑓𝑟 = 0.7𝜆√𝑓𝑐′
Example:
Assuming the concrete is uncracked, (a) compute the bending stresses in the extreme
fibers of the beam for a bending moment of 70 kN.m. The normal weight concrete
has 𝑓𝑐′ = 28 MPa and the modulus of rupture 𝑓𝑟 = 0.7√𝑓𝑐′.
(b) Determine the cracking moment of the section.
HW: calculate (a) the cracking moment for a beam of an overall depth equals 600
mm, and a width of 400 mm. if this beam is simply supported of 10 m length and
subjected to a concentrated load P at mid span, determine the value of this load that
will cause cracks to form.
Reinforced Concrete I Chapter 2 Lecture No.7
ACI 10.2.3 requires that the tensile reinforcing bars are yielded (𝑓𝑠 = 𝑓𝑦)
before the concrete on the compression side of the beam is crushed (𝜀𝑐𝑢 =
0.003).
After the concrete compression stresses exceed about 0.5𝒇′𝒄, stresses no longer
vary linearly as the distance from the neutral axis (N.A.).
𝒇𝒄′ − 𝟐𝟖
𝖰𝟏 = 𝟎. 𝟖𝟓 − 𝟎. 𝟎𝟓 ( ) ; 𝟎. 𝟔𝟓 ≤ 𝖰 𝟏 ≤ 𝟎. 𝟖𝟓
𝟕
EXAMPLE:
Determine the nominal moment strength Mn of the beam shown, if 𝑓𝑐′ =28
MPa and fy = 420 MPa.
● Modes of Failure:
1. Ductile Failure:
If the amount of steel is low enough, steel would yield before crushing of
concrete, resulting into a ductile failure mode in which there is large
deformation.
2. Brittle Failure:
If the amount of steel is high enough, steel remains elastic at the time of
crushing of the concrete, causing a brittle sudden failure.
● Section Types:
● Reinforcement ratios:
ρb= (
0.85 β1 f c'
fy )( ) 600
600+f y
f c'
ρmax =0.364 β 1
fy
EXAMPLE 2: Determine the nominal flexural strength Mn and the design flexural
strength φMn for the shown beam section. f'c =28 MPa , f y =420 MPa .
Reinforced Concrete I Chapter 2 Lecture No.7
1. Balanced Section: the tensile steel will reach its yield point at the same time
the extreme compression concrete fibers attain a strain equal to 0.003.
Derivation of 𝝆𝒃:
600
𝑐= 𝑑 … (1)
600 + 𝑓𝑦
𝜌𝑓 𝑦𝑑
𝑎=
0.85 𝑓𝑐𝘍
𝑎 𝜌𝑓𝑦𝑑
𝑐= =
𝛽1 0.85𝛽1𝑓′ … (2)
𝑐
Example:
Determine the nominal flexural strength Mn and the design flexural strength φMn for
the shown beam section. f 'c = 21 MPa , f y = 420 MPa .
Reinforced Concrete I Chapter 2 Lecture No.6
Examples
1. For the section shown below, 𝑓 ′ = 35 𝑀𝑃𝑎, 𝑓 = 420 𝑀𝑃𝑎. Compute the
𝑐 𝑦
following:
a. Cracking moment 𝑴𝒄𝒓
b. Area of steel 𝑨𝒔
c. Tension force T
d. Compression force C
e. Depth of Whitney block a
f. 𝖰𝟏
g. Distance from extreme fiber to neutral axis c
h. Percentage of tensile steel 𝝆
i. Nominal flexural strength 𝑴𝒏
j. Design flexural strength ∅𝑴𝒏
k. Coefficient of resistance 𝑹𝒏
l. Yield strain of steel 𝝐𝒚
m. Strain in tension reinforcement 𝝐𝒔
n. Plot the stress distributions" Actual + Whitney" at nominal moment
Reinforced Concrete Slab: are large flat plates that are supported by
reinforced concrete beams, walls, or columns, by masonry walls, by structural
steel beams or columns, or by the ground.
One-way slab: a slab supported on two opposite sides only and bending is in
one direction only; perpendicular to the supported edge.
Two-way slab: a slab supported by beams on all four edges and bending is in
both directions.
If a rectangular slab is supported on all four sides, but the long side is two or
more times as long as the short direction, this slab will act as a one-way slab.
1. Main reinforcement
Reinforcing for flexure is placed perpendicular to supports;
parallel to the long direction of the 1 meter wide beam (strip).
Spacing is not more than 5 times the slab thickness or 500 mm.
As = 𝝆𝒎𝒊𝒏 × 𝑏 × ℎ
1
Reinforced Concrete I Chapter 2 Lecture No. 10
Example :
Design the one-way slab shown in the figure below. It is to support a live load of 10
kN/m2 .Do not use the ACI-Code thickness limitation for deflection and assume
concrete weighs 23.5 kN/m3 . 𝑓 ′ = 28 MPa , 𝑓 = 420 MPa. Use 𝜌 = 𝜌 .
𝑐 𝑦 𝑚𝑎𝑥
2
Reinforced Concrete I Chapter 2 Lecture No.9
1. Beam Proportions: most economical beam sections are usually with ratio of
d to b in the range of 1.5 to 2 for beam of length (6 – 7.5m). For longer spans
better economy is obtained if deep, narrow sections are used with a ratio of (3-
4).
3. Estimated Beam Weight: Beam must support itself and the external loads.
Assume minimum overall depth h as specified by ACI- code.
ℎ ℎ
𝑏≅ ~
2 1.5
Estimated beam weight =𝑏 × ℎ × 𝛾𝑐
Where 𝛾𝑐 : 𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 𝑤𝑒𝑖𝑔ℎ𝑡 𝑝𝑒𝑟 𝑐𝑢𝑏𝑖𝑐 𝑚𝑒𝑡𝑒𝑟
No need to revise if the difference between the actual Mu and
calculated Mu is 1~1.5 %.
4. Selection of Bars
Use Table B.4
It is usually preferred to use bars of one size only
ANALYSIS OF T-BEAMS
Reinforced concrete floor systems consists of slabs and beams that are placed
monolithically, as a result, slab and beams act together to resist loads.
T- beams: beams have extra widths at their tops called flanges, and the part
below is called web or stem. These two parts act together to resist the loads.
Stirrups in the webs extend up into the slab.
L-shaped beam: a T beam at the edge of a reinforced concrete slab which has
a flange on only one side.
1
Reinforced Concrete I Chapter 3 Lecture No. 11
Analysis of T –beams:
2
Reinforced Concrete I Chapter 3 Lecture No. 11
Example 1:
Determine the design strength of the T-beam shown below. 𝑓𝑦 = 420 MPa,
𝑓𝑐′ = 35 MPa.
Example 2:
Determine the design strength of the T-beam shown below. 𝑓𝑦 = 420 MPa,
𝑓𝑐′ = 28 MPa.
3
Reinforced Concrete I Chapter 3 Lecture No. 12
DESIGN OF T-BEAMS
1. Dimensions:
o The flange thickness has been selected in the slab design as it is the
slab thickness.
o The width of the web is normally selected based on shear requirement
not on the basis of moment requirements; a sufficient area is used to
provide a certain minimum shear capacity. It is also possible that the
width of the web may be selected on the basis of the minimum width
required to place the reinforcing bars.
o Sizes may be preselected to simplify formwork for architectural
requirements or for deflections.
1. Area of steel :
o Trial-and-error process is often used starting by estimation the lever
arm (z) measured from the center of the gravity of the compression
block to the center of the gravity of the steel .
0.9 𝑑
o 𝒛 ≥ {𝑑 − ℎ 𝑓 }
2
𝑀𝑛
o Trial steel area : 𝐴 𝑆 =
𝑓𝑦× 𝑧
Example 1:
A floor system shown below, consists of 100 mm concrete slab supported by
a continuous T-beam with 7.5 m span, 1.2 m on centers. Web dimensions, as
determined by negative –moment requirements at the supports, are 𝑏𝑤 =
275 mm, and 𝑑 = 500 mm. What tensile steel area is required at midspan to
resist a factored moment of 725 kN.m. 𝑓𝑦 = 420 MPa, 𝑓𝑐′ = 21 MPa.
1
Reinforced Concrete I Chapter 3 Lecture No. 13
COMPRESSION STEEL
1. Definitions:
Compression Reinforcement: reinforcement added to the compression
side of beams to increase moment capacity, increase ductility or decrease
long-term deflections.
Doubly beam: concrete beams that have both tensile and compression
reinforcing.
1
Reinforced Concrete I Chapter 3 Lecture No. 13
2
Reinforced Concrete I Chapter 3 Lecture No. 14
𝑉𝑛 = 𝑉𝑐 + 𝑉𝑆
𝑉𝑢 = ∅𝑉𝑛 = ∅𝑉𝑐 + ∅𝑉𝑆
𝑉𝑐:Shear strength provided by the concrete = shear force that concrete can
resist without web reinforcing
√𝒇𝒄′
𝑽𝑪 = (𝝀 )𝒃𝒘𝒅
𝟔
1
Reinforced Concrete I Chapter 3 Lecture No. 14
2
Concrete and Steel C onstructions
0670416
Shear in Beams
Introduction
•to carry the loads safely, the beam must be designed for both types
of forces.
•The design for shear must ensure that shear failure does not occur
before flexural failure.
Introduction
Types of Shear Cracks
Flexure-Shear Cracks
The most common type, develops from the tip of a flexural crack at the
tension side of the beam and propagates towards mid depth until it is
checked on the compression side of the beam.
ΦVn Vu
Vu = factored shear force at section
Vn = nominal shear strength
Φ = strength reduction factor for shear = 0.75
Av f y d sin α cos α
Vs
s
Av fy d
90 o Vs
s
•The ACI Code, Section 11.1.3.1, permits taking the critical section for
nominal shear strength calculation at a distance d from the face of the
support.
•This recommendation is based on the fact that the first inclined crack is
likely to form within the shear span of the beam at some distance d away
from the support.
•If shear reinforcement is not provided, brittle failure will occur without
warning.
0.062 f , cb wS 0.35b wS
AV ,min
f yt f yt
Av,min f yt A f
Smax v , min y t
2bwd f 'c
Vs
3
2bw d f 'c
•Case 3:if Vs
3
the dimensions of the cross section should be increased.
Types of Shear Reinforcement
Vertical Stirrups
Inclined Stirrups
Bent up bars
Stirrup types
Design Summary
The design procedure for shear using vertical stirrups according to the ACI
Code can be summarized as follows:
1. Calculate the factored shearing force,Vu, from the applied forces acting
on the structural member.The critical design shear value is at a section
located at a distance d from the face of the support.
Design Summary
3)
Av f y d
5) Calculate stirrup spacing: S
Vs
Design Summary
Av f y A
0.062
A f
v y Av f y
,
0.062bw f 'c
,
0.35bw
A f
v y
Av f y
,
0.062bw f 'c 0.35bw
If L is C .L to C .L then
the distance from the
face of the support to
the critical section:
= 0.5*support width + Shear Reinforcement Requirements
effective depth d
Example
W d=47.5 kN /m
WL=25 kN/m
550
4Φ25
350
Example
Example
Example
Reinforced Concrete I Chapter 4 Lecture No.15
Design a round spiral column: PD= 500 kN, PL= 650 kN, f’c= 35 MPa, and fy = 420 MPa. Initially
assume ρg = 0.03.
1.64 × 106 N = (0.75) (0.85) [(0.85) (35) (70686− Ast) + (420) Ast]
Design of spiral
Use # 10 spiral:
𝐷𝐶 = 300 − 2 × 40 = 220 𝑚𝑚
𝜋 × 2202
𝐴𝑐 = = 38013 𝑚𝑚2
4
70686 35
Minimum ρs = 0.45 ( − 1) × = 0.0322
38013 420
4as(Dc − d b)
ρs =
s D C2
4 × 71 × (220 − 9.5)
0.0322 =
𝑠 × 2202
s = 38.4 mm use s = 30 mm
25mm ≤ s ≤ 75mm ok