Insulation Coordination - PPT
Insulation Coordination - PPT
R.C.A.M. Koevoets
September 2017 August 2022
Insulation coordination
• It is … not:
• Equipment
How do we connect equipment to a system?
← Equipment: “item(s)
for generation, conversion,
transmission, distribution
or utilization of electric energy”
Two rules, two standards
• Ensure that the “normal” voltage on the system is not higher
than the “normal” voltage of the equipment. Reference: IEC 60038.
• Statistics:
evaluation of overvoltage occurance versus expected lifetime of the insulation,
with correction factors, also for expected conditions and altitude
• Determination:
of a set of voltage levels (higher than protection level)
for standard overvoltage shapes representing the result of analysis and evaluation
• Selection:
of nearest higher standard test voltages and in this way
determination of standard insulation level
What is the aim, the purpose, the goal?
• To limit failure risk to acceptable levels
• To ensure that failure only hits locations with easy, low cost, fast
repair
• Air
• Standard atmospheric conditions
• Dry and wet
• New and clean
• electric equipment
item used for such purposes as generation, conversion, transmission,
distribution or utilization of electric energy, such as electric machines,
transformers, switchgear and controlgear, measuring instruments,
protective devices, wiring systems, current-using equipment (IEV 826-
16-01)
Part 3: “Normal” Voltage
• nominal voltage of a system
a suitable approximate value of voltage used to designate or identify a system (IEV
601-01-21)
Note: The value for the rated voltage of high voltage equipment is generally assigned from the list of
highest voltages for equipment in Tables 3, 4 and 5 of IEC 60038:2009.
Note: Equipment may have more than one rated voltage value or may have a rated voltage range.
Nominal voltage and highest voltage (IEC 60038)
Range I Range II
Nominal Highest System Voltage/ Highest System Voltage/
Nominal System
System Highest voltage for Highest Voltage for
Voltage
Voltage equipment Equipment
Un Us or Um Un Us or Um
[kV] [kV] [kV] [kV]
10/11 12 … (300)
20/22 24 … 362
30/33 36 400 420
66/69 72,5 500 525/550
110/115 123 … 765/800
150/154 170 … 1100
220/230 245 … 1200
Nominal Voltage as per IEC 60038, series I and II
• Nominal system voltage (see IEC 60038) Un
Such as 11, 33, 66, 110, 132, 132, 220, 400 kV systems.
• Medium voltage (MV) (not used in the UK in this sense, nor in Australia) any set of voltage levels
lying between low and high voltage Note – The boundaries between medium- and high-voltage levels overlap and
depend on local circumstances and history or common usage. Nevertheless the band
30 kV to 100 kV
frequently contains the accepted boundary. (IEV 601-01-28)
↑ Um ≥ Us upper limit
upper
Us normal
limit
voltage
+/- normal
Un (5–10) voltage
%
lower
U…
limit
IEC 60038 IEC Standard Voltages
• Horizontal standard = Standard on fundamental principles, concepts,
terminology or technical characteristics, relevant to a number of
technical committees and of crucial importance to ensure the
coherence of the corpus of standardization documents
•
Part 4: Overvoltage
• Systems are equipped with earth wires, structures, spark gaps, arresters
and this gives some protection against very high overvoltage
• But still overvoltages occur due to lightning strikes, failures and switching
operations
• The overvoltages have typical shapes and the overvoltage levels can be
estimated
• Typical test voltages and test levels and shapes can be formulated for the
equipment
• Test voltage levels must be higher than the overvoltage protection levels
Overvoltage limitation by the system construction
When do we speak about overvoltage?
• Phase to phase: any voltage exceeding Us . √2
• Ks safety factor
• Kc co-ordination factor
Procedure overview
Insulation level
(Set of standard Test Voltages)
Um, LI, SI, AC See IEC 60071 and specific equipment standards
kV kV kV
(r.m.s. value) (r.m.s. value) (peak value)
Example:
60
12 28 75
95
Standard insulation levels as per IEC 60071-1
Range II (for Um above 245 kV)
- Phase-to-earth insulation
The standard voltages are different for : - Phase-to-phase insulation
- Longitudinal insulation
Highest voltage Standard rated
for Standard rated switching impulse withstand voltage lightning impulse
equipment withstand voltage
(Um)
longitudinal phase-to-earth phase-to-phase
insulation insulation insulation
kV kV kV (ratio to the kV
(r.m.s. value) (peak value) (peak value) phase-to-earth (peak value)
peak value)
Example:
1300
420 950 1050 1,50
1425
(Basic) insulation level as per IEEE (not IEC)
• BIL : Basic Lightning Impulse Insulation Level
- Arresters
- Air gaps
- Insulator strings
• Internal insulation
Internal distances of the solid, liquid, or gaseous insulation of equipment
which are protected from the effects of atmospheric and other conditions
(IEV 604-03-03 modified)
Insulation coordination Principles
Insulation: three main situations
• To earth (between a phase and earth);
• phase to earth insulation
• clearance to ground
Y1 ← System 1
B1
← Longitudinal insulation (R1-R2, Y1-Y2, B1-B2) (3)
between Systems
R2
← System 2
Y2
B2 ← insulation Phase to Phase (R2-Y2, Y2-B2, B2-R2) (1)
← insulation Phase to Earth (R2-E, Y2-E, B2-E) (2)
Across open contacts
• Circuit-breakers (within the same system?)
• Rogowski profile
• Sphere gap
• Conductor - conductor
• Conductor - structure
• Rod - structure
• Rod - rod
Electrodes (shapes) and electrical fields
and gaps (clearance, distance)
← more homogenous field? less →
Rogowski- Conductor- Conductor- Rod-
Plane-plane Sphere-gap Rod-rod
profile conductor structure structure
Minimum clearance as per IEC 60076-3 phase to phase and phase to earth based on lightning impulse voltage (trendline)
2000
1800
1600
1400
1200
1000
800
600
400
200
sphere gap, a.c., d.c., impulse negative sphere gap, positive, impulse rod gap, d.c. pos/neg minimum clearance [cm]
Part 8: Insulation
• Some definitions
• Insulation in air
• Electric strength
• Some values
Insulation: Some definitions
2000
1500
rod-structure
1000 conductor-structure
500
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
minimum clearance [mm] phase to erarth and phase to phase
IEC 60071-1 table A.2
Range II, Um 300 kV and above
1800
rated switching impulse withstand voltage [kV] phase to erath
1600
1400
1200
1000
conductor-structure
800
rod-structure
600
400
200
0
0 1000 2000 3000 4000 5000 6000 7000
minimum clearance [mm] phase to earth
IEC 60071-1 table A.3
Range II, Um 300 kV and above
3000
rated swiching impulse withstand voltage [kV] phase to phase
2500
2000
1500
rod-conductor
conductor-conductor parallel
1000
500
0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
minimum clearance [mm] phase to phase
Clearance for switchgear
IEV ref definition
the distance between two conductive parts along
441-17-31 clearance a string stretched the shortest way between these
conductive parts
clearance the clearance between any conductive parts of
441-17-32
between poles adjacent poles
the clearance between any conductive parts and
clearance
441-17-33
to earth
any parts which are earthed or intended to be
earthed
the total clearance between the contacts, or any
clearance between open
441-17-34
contacts
conductive parts connected thereto, of a pole of a
mechanical switching device in the open position
isolating distance
the clearance between open contacts meeting the
441-17-35 (of a pole of a mechanical
switching device) safety requirements specified for disconnectors
“clearance” for insulators
IEV ref definition
• Flashover
• Puncture
Discharges
IEV Ref definition
(electric) abrupt change of all or part of an insulating medium into a conducting medium
212-11-33
breakdown resulting in an electric discharge
breakdown voltage at which electric breakdown occurs under prescribed test conditions, or in
212-11-34
voltage use
212-11-38 (electric) movement of charge carriers through parts of an otherwise insulating material
discharge Note – An electric discharge may be partial or disruptive
passage of an electric arc following electric breakdown
disruptive
212-11-46 Note – Depending on the amount of energy contained in the discharge, it will be
discharge
described as a discharge of low or high energy, based on the maximum current,
and the amount of damage to the insulating material.
electric breakdown between conductors in a gas or a liquid or in vacuum, at least
212-11-47 flashover
partly along the surface of solid insulation
212-11-48 sparkover disruptive discharge in a gaseous or liquid insulating material
disruptive discharge occurring through a solid insulation material, producing a
212-11-49 puncture path of permanent damage
Note – The term puncture is also used as a synonym for electric breakdown in
solids.
Other discharges
• partial discharges (PD)
• (visible) corona
APPENDIX 1:
TESTING
Testing
• After the insulation level (set of assigned test voltages) has been
established, dielectric testing may be performed accordingly
• In the Scope of IEC 60060-1:2010 (High-Voltage Test Techniques), is written: “This Standard is
applicable to dielectric tests with direct voltage, alternating voltage, impulse voltage, and
combinations of these voltages”.
• However, in clause 5, dealing with these tests, the expression dielectric tests is not used any
more. Here, a definition of dielectric tests cannot be found.
• In IEV 614-03-28, lightning impulse, is defined as “voltage pulse of a specified shape applied
during dielectric tests with a virtual front duration of the order of 1 μs and a time to half value of
the order of 50 μs” and in IEV 614-03-30, switching impulse is defined as “voltage pulse of a
specified shape applied during dielectric tests, with a time to crest of 100 μs to 300 μs, and a
time to half value of a few milliseconds”.
• Also here is referred to dielectric tests without giving the definition.
Test on the insulation: dielectric tests (2)
What is in a name? What is in a definition?
• In IEC 60071-1:2010 clause 3.37 the standard voltage withstand test, is defined as
“dielectric test performed in specified conditions to prove that the insulation complies with
the standard rated withstand voltage”
• Hence, from the above, including the previous sheet, it must be concluded, that the
meaning of the expression dielectric tests is given by the list of above mentioned tests.
(Type) Testing: The Impact
• And thermal, chemical and mechanical influences, and impact of partial discharges, corona
includes:
- realising that all materials are subject to aging and hence realising that these
“cannot be applied up to maximum theoretically permissible field strength”
Equipment: Insulation materials
Please note:
• Clearance requirements
- for l.i. levels up to and including 750 kV: rod to structure values
- for l.i. levels above 750 kV: conductor to structure values
(Power)Transformers and Reactors
• Transformer Construction
core type
shell type
• Short-circuit testing
as per IEC 60076-5
based on transformer category (rating)
• Critical insulation:
liquid insulation:
oil (Mineral or Synthetic oil) or other liquids (with different Fire Point)
solid insulation:
• Insulation
Varnish and Resin (epoxy or polyester)
Insulation classes F (155 ˚C) or H (180 ˚C)
permittivity
material nature electric strength [kV/mm] comments
Ɛ
for conductor
enamel solid
insulation
for insulation
barriers,
polyester solid 25 - 30 3,2 – 4,3
spacers and
duct sticks
for insulation
combined with glass barriers or
epoxy resin solid fibre or quartz 20 - 45 3,3 – 3,9 complete
powder vacuum cast
windings
Rotating electric machines: (IEC 60034)
Insulation Systems
Stator winding Rotor winding
Synchronous
Random wound Form-wound Hydro-generators
machines
Strand insulation / Turn insulation
Strand insulation
Ground wall insulation
Ground wall insulation
Coil separator
Strand insulation Rotor Pole Turn Insulation
Coil separator Top, Mid-stick and bottom Packing
- mounting: IM-code
- cooling: IC-code
- protection: IP-code
- to avoid short-circuit between winding turns and winding turn to ground (iron core)
- to prevent winding movement in the rotor and stator.
Rotating electric machines:
insulation, some values
permittivity For comments
material nature electric strength [kV/mm]
Ɛ see next sheet 1)
asbestos solid 4 3–5 obsolete
asphalt solid 2,68
shellac solid 10 – 15 3–4
epoxy resin solid 20 – 45 3,3 – 3,9
polyester resin solid 25 3–7
cotton solid varnished 4 2,5 – 3,8
mica solid normal 30 – 40 7 2)
23°C 50%RH
polyimide
solid thin sheets 150 – 300 3,6 3)
Kapton HN
(12,7 – 125 µm)
Thickness
polyamide
solid 0,05 – 0,76 mm 17 - 33 1,6 – 3.7 4)
Nomex 410
calandered paper
Thickness
polyamide
solid 0,13 - 0,58 mm 9 1,2
Nomex 411
uncalandered
Rotating electric machines:
insulation, some comments
1) None of the materials listed are used separately. The insulation
systems of rotating machines comprise always a combination of
materials, each having its own particular function
2) Pure mica is nowadays hardly ever used in rotating machines. In
most applications use is made of mica paper-based tapes where
mica paper is combined with glass cloth or polyester (PET) or
polyimide (Kapton) films, pre or post impregnated with
epoxy/polyester/silicon resins. Electric strength is mainly
determined by the impregnation resin and carrier material. Mica
is present in the system to make it insensitive to prolonged partial
discharges over its entire life
3) Insulation sheet material with a thickness lower than 0,1 mm tends
to have far higher breakdown field strengths than thicker
samples, irrespective of the nature of the material
4) NOMEX is a paper made of aramide (aromatic polyamide) fibres
Instrument transformers: purpose, standards
• Application, purpose
• Please Note:
• Principle (conventional)
- Inductive with electromagnetic circuits and windings
- Analog output
- Bushing porselain or composite (silicon rubber), sometimes with helical creepage distance ribs
• Notes:
- dielectric strength of SF6 at a pressure > 300 kPa is higher than that of oil
- breakdown voltage of SF6 is about 2,5 times higher than that of N2 or air
- for interrupting purposes SF6 is approx 100 times better than air
- SF6 pressure in GIS is normally from 400 to 600 kPa (4 – 6 bar)
Switchgear: symbols as per IEC 62271
• Please note:
permittivity
material nature electric strength [kV/mm] comments
Ɛ
synthetic
polypropylene fluid > 40 2,1 low tan(delta)
impregnation
Capacitors: some important tests
• Discharge tests
• Accessories
Fittings, (anti)corona rings, anti arc gaps (spark gaps)
• Materials
permittivity
material nature electric strength [kV/mm] comments
Ɛ
IEC 60502: for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV)
IEC 60840: for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV)
IEC 62067: for rated voltages above 150 kV (Um = 170 kV) up to 500 kV (Um = 550 kV)
• Please note: