(5.2) All-Day Transformer Efficiency
(5.2) All-Day Transformer Efficiency
|
COURSE OUTCOME 2
Intermediate Operation of Single-Phase Transformers;
Operation of Three-Phase Transformers
|
EEA107-4
Electrical Apparatus and Devices (Lecture)
|
ALL-DAY TRANSFORMER EFFICIENCY
Distribution transformers must be ready at all times during the 24-hr day
to provide electrical service for lighting and power. The primaries of such
transformers are always energized, although the secondary may supply
practically little or no load much of the time particularly where the
transformers serve residential lighting and power circuits.
Since the core losses are supplied continuously and the load is very light
during the greater part of the day, it is considered good practice to design
such transformers so that the constant losses are very low. When this is
done, the transformer will usually operate at maximum efficiency in a
range of about one-half the rated kVA.
|
ALL-DAY TRANSFORMER EFFICIENCY
|
4. A 5-kVA, 2300/230-V, 60 Hz, standard distribution transformer was
tested with the following results: short-circuit test input = 112 W; open-
circuit test input = 40 W. Then, this transformer operates with the
following loads during a 24-hr period:
1.5 times rated kVA p.f. = 0.8 1 hr
1.25 times rated kVA p.f. = 0.8 2 hr
at rated kVA p.f. = 0.9 3 hr
0.5 of rated kVA p.f. = 1 6 hr
0.25 of rated kVA p.f. = 1 8 hr
no load - 4 hr
Calculate the all-day efficiency.