Unit 3 - Control Systems - WWW - Rgpvnotes.in
Unit 3 - Control Systems - WWW - Rgpvnotes.in
Unit 3
Syllabus: Frequency response analysis
Correlation between time and frequency response, Polar plots, Bode Plots, all-pass and minimum-phase
systems, log-magnitude versus Phase-Plots, closed-loop frequency response.
Frequency domain stability analysis, Nyquist stability criterion, assessment of relative stability using Nyquist
plot and Bode plot (phase margin, gain margin and stability).
270
Page 1 of 9
Example 3.1 Draw the Polar Plot for the closed loop transfer function
�� �� =
� �+ �+
Solution: Consider the open loop transfer function of a closed loop control system.
� � =
+ +
Step 2 − The following table shows the magnitude and the phase angle of the open loop transfer function at
� = rad/sec and � = ∞ rad/sec.
Frequency(rad/sec) Magnitude Phase Angle
0 ∞ −
∞ 0 −
√ 10/3 −
at
(√ , − . The first and the second
terms within the brackets indicate the
magnitude and phase angle respectively.
The required polar plot is shown in figure
ex 3.1.
Page 2 of 9
(i) � � =�
Consider the open loop transfer function =
Magnitude = �
Phase angle � = degrees
If K=1, then magnitude is 0 dB.
If K>1, then magnitude will be positive.
If K<1, then magnitude will be negative.
K>1
20 log K
K=1 ∞ <K< 1
0 log ω 0 log ω
-20 log K
0<K<1
Figure 3.3.2.(a) Magnitude Vs. Frequency Figure 3.3.2.(b) Phase Vs. Frequency
The magnitude plot is a horizontal line, which is independent of frequency. The 0 dB line itself is the
magnitude plot when the value of K is one. For the positive values of K, the horizontal line will shift 20logK
dB above the 0 dB line. For the negative values of K, the horizontal line will shift 20logK dB below the 0 dB
line. The Zero degrees line itself is the phase plot for all the positive values of K.
(ii) � � =�
Consider the open loop transfer function = .
Magnitude = ��
Phase angle � =
At ω= . rad/sec, the magnitude is -20 dB.
Page 3 of 9
M(dB) φ (degrees)
20
9
0
0 .1 1 10 Log ω
-20 0 log ω
The magnitude plot is a line, which is having a slope of 20 dB/dec. This line started at ω= . rad/sec having
a magnitude of -20 dB and it continues on the same slope. It is touching 0 dB line at ω= rad/sec. In this
case, the phase plot is 900 line.
(iii) � � = + ��
Consider the open loop transfer function G(s)H s = +sτ.
Magnitude = � √ + � � dB
−
Phase angle � = �� degrees
For ω< /τ, the ag itude is dB a d phase a gle is deg ees.
For ω> /τ, the ag itude is logωτ dB and phase angle is 900.
The following figure shows the corresponding Bode plot.
φ (degrees)
M(dB)
20 dB/dec 20 dB/dec
20 90
Page 4 of 9
Example 3.2 Draw the Bode Plot for the system whose open loop transfer function is given as
� � =
� �+ �+�
Solution: Consider the open loop transfer function of a closed loop control system.
= =
+ + + + .
therefore
=
+ + .
This is a type 1 system with K=5. Put = �
therefore
� � =
� + � + . �
1. The corner frequencies are
� = = /
� = = /
.
2. Starting frequency
Starting frequency is taken as the lower than the lowest frequency. As the lowest frequency is 1 rad / sec,
the starting frequency will be 0.1 rad / secs.
3. Initial Slope
Since the type of the system is one, the initial slope will be − / .
5. Next slope
The next corner frequency � = / is due to the denominator term / + � , therefore the slope
will change by − / . The new slope will be now − / , and it will continue up to the
next corner frequency.
6. Next slope
The next corner frequency � = / is due to the denominator term / + � , therefore the slope
will change by − / . The new slope will be now − / , and it will continue for the all
frequencies greater than � = / .
7. Phase Angle
The Phase Angle � = ∠ � � for the frequencies between � = . / to � = / is
calculated by
�=∠ � � =− − tan− � − tan− . �
Therefore all the details can be summarized in the table below
Factor Corner Frequency Slope Angle
(rad/seconds) (db/decade) (degree)
_ − / −
�
/ − / − tan− �
+ �
Page 5 of 9
/ − / − tan− . �
+ . �
� 0.1 0.5 1 2 3 5 10
� − . − . − . − − . − . − .
The Magnitude curve and the phase curve are plotted in the diagram given below:
Page 6 of 9
Page 7 of 9
of the characteristic equation. As the order of the characteristic equation increases, it is difficult to find the
roots. So, let us correlate these roots of the characteristic equation as follows.
The Poles of the characteristic equation are same as that of the poles of the open loop transfer
function.
The zeros of the characteristic equation are same as that of the poles of the closed loop transfer
function.
We know that the open loop control system is stable if there is no open loop pole in the right half of the S
plane.
I.e. P = 0 ⇒ N = −)
We know that the closed loop control system is stable if there is no closed loop pole in the right half of the
S plane.
i.e., Z = 0 ⇒ N = P
Nyquist stability criterion states the number of encirclements about the critical point (1+j0) must be equal
to the poles of characteristic equation, which is nothing but the poles of the open loop transfer function in
the right half of the S plane. The shift in origin to (1+j0) gives the characteristic equation plane.
Page 8 of 9
Page 9 of 9