At03 Z1pa
At03 Z1pa
www.anly.com.tw
2
Table of Content
Chapter 0 Overview
Chapter 1 Specification
Detail Specification
Detail Features
Ordering Information
Chapter 2 Installation
Mounting Procedure
Terminals
Chapter 3 Programming
Terminology
Power-up Sequence
Hierachal Tree Menu
Device Hold
Device Lock
Parameter Flow Chart
Parameter Description, Range, Initial Value
Examples
Chapter 4 Input
Chapter 5 Output
Chapter 6 Alarm
Alarm Type
Alarm Mode
Chapter 7 Communication
Sample Commands
Parameters and Addresses
3
Chapter 0 : Overview
ANLY AT03 series is an 1 input, 2 output, 3 alarm, auto-tuning PID
temperature controller designed to accommodate comprehensive
needs in process automation and system integration.
AT-903
AT-403
PV
PV
SV
SV
AT-703
PV
SV
SET SET
AT-503
PV
PV
AT-603
AT - 703
SV
SV
SET SET
AT - 503 AT - 603
4
Chapter 1 : Specification
Detaile Information
Detail Specification
Type AT - 403 / AT - 503 / AT - 603 /
AT - 703 / AT - 903
Operating voltage 100 ~ 240VAC
Rated Frequency 50 / 60 Hz
Power Consumption Approximately 3.5VA
Sensor input Thermocouple : K, J, T, R, E, S, B, N
RTD : Pt100, JPt100
Linear : Voltage, Current
Control output Relay, Voltage, Linear, Motor Control
Alarm output 250VAC, 5A
Alarm fucntion See Table on Page 49
Control method PID, PI, P, On/OFF, Dead band
Setting Digital setting with front keys
Communication RS-232 or RS-485 (both optional)
Indicator 4-digit 7-segment-display
Ambient temperature -10OC ~ +50OC
Storage temperature -25OC ~ +65OC
Ambient humidity 34%~80% relative humidity with no
icing or condensation
Storage humidity 35%~95% relative humidity with no
condensation
5
Detail Specification (Continue)
Weight AT-403: ~170g
Detail Features
Measuring accuracy Within 0.3% of present value
or +-2OC, whichever is greater
Propotional Band 0.0 ~ 3000 sec (0.1 sec increment)
Integral Time 0 ~ 3600 sec (1 sec increment)
Derivative Time 0 ~ 900 sec (1 sec increment)
Control Period 0 ~ 150 sec (1 sec increment)
Sampling Period 300ms
Memory Protection EEPROM non-volatile memory
(at least 100,000 write cycle)
Ordering Information
ANLY AT03 can be customized to specific needs and requirements.
The ordering code consists of a 10-digit numeral in 3-4-3 format :
AT- □ 0 3 - □ □ □ □-□ □ □
“03” is the designation for AT03 series controllers. The following
explains the representation of the remaining 8 numerals.
6
AT- ■ 0 3 - □ □ □ □-□ □ □
Dimension The dimension size is a meas-
urement for the device face
4 = 96x48mm (1/8 DIN)
plate. Note that AT-402 is verti-
5 = 48x48mm (1/16 DIN) cal while AT-603 is horizontal,
6 = 48x96mm (1/8 DIN) although they have the same
DIN size.
7 = 72x72mm
9 = 96x96mm (1/4 DIN)
AT- □ 0 3 - ■ □ □ □-□ □ □
1 is for both thermocouple and
Input
RTD sensor inputs. However,
1 = T/C or RTD the sensor type also needs to
2 = 0~100mV be specificied by users under
Level menu. 2 through 9 are for
3 = 0~20mA linear inputs.
4 = 4~20mA
5 = 0~5V
6 = 0~10V
7 = 1~5V
8 = 2~10V
9 = 0~1V
7
AT- □ 0 3 - □ ■ ■ □-□ □ □
A relay output on Ouput 1 is
Output 1 Output 2
standard on all AT03. It can
(1 is standard) 0 = None be changed to any of the 9
1 = Relay 1 = Relay types. Note that motor control
on Output 1 uses 3 terminals.
2 = Pulsed 2 = Pulsed Therefore, Motor Control option
3 = 0~20mA 3 = 0~20mA is not available with Output 2.
Therefore, “90” is the code for
4 = 4~20mA 4 = 4~20mA motor controlo output.
5 = 0~5V 5 = 0~5V
6 = 0~10V 6 = 0~10V
7 = 1~5V 7 = 1~5V
8 = 2~10V 8 = 2~10V
9 = Motor Control
AT- □ 0 3 - □ □ □ ■-□ □ □
1 alarm is standard on all AT03.
Alarm
There can be upt o 3 alarms
1 = 1 alarm on AT-403, AT-603, AT-703 and
2 = 2 alarms AT-903. However, AT-503 can
only have up to 2 alarms.
3 = 3 alarms
8
AT- □ 0 3 - □ □ □ □-■ □ □
In Other option, there can be
Other
inputs for DC24V, current trans-
0 = None former and Remote Set Point
1 = DC 24V (R-SP). Current transformer is
used as the heater break alarm.
2 = Current Transformer R-SP is used to change SV
A = Remote Set Point 0~20mA remotely with volatage or cur-
rent. AT-403 is availiable with
B = Remote Set Point 4~20mA Other option but this will negate
C = Remote Set Point 0~5V Ouput2.
D = Remote Set Point 0~10V
E = Remote Set Point 1~5V
F = Remote Set Point 2~10V
AT- □ 0 3 - □ □ □ □-□ ■ □
Communication module, such
Communication
as RS-232 and RS-485 module,
0 = None is availiable for direct link up
1 = RS-485 with PC for programming.
2 = RS-232
AT- □ 0 3 - □ □ □ □-□ □ ■
Program is the option that
Program
gives the controller segment
0 = None programming.
1 = Program
9
Some models, due to their limited terminals, cannot be ordered with
all the features. Such limitations are:
Chapter 2 : Installation
d
A C D
c
B E
b
a
Device Measurement Panel Cutout Measurement
Type A B C D E a b c d
AT-403 48 96 10.5 83 90 46+0.5 91+0.5 120 70
AT-503 48 48 10.5 83 45 46+0.5 46+0.5 70 70
+0.5 +0.5
AT-603 96 48 10.5 83 43 91 46 70 120
AT-703 72 72 10.5 83 67 68+0.5 68+0.5 100 100
AT-903 96 96 10.5 83 90 91+0.5 91+0.5 120 120
All measurements in millimeter (mm)
10
Mounting Procedure
1. Make sure the front panel is no more than 10mm thick. Also,
each of the two brackets needs additional 6mm clearance
outside of the shell casing on each side.
3. Insert the controller into the cutout from the front side of the panel
4. Align the bracket so the notches are in their slots and the wide
side towards the front panel.
5. Pinch the prongs and slide the bracket forward till the bracket
is firmly against the backside of the front panel.
Terminals
For wire terminations, the recommended terminals are fork or ring
terminals with #6 stud size, narrow tongue, and with insulation. Wire
gauge should be at least AWG 18.
Insulation Tube
3.7mm
^
6 .0mm
11
Of all 5 types of ANLY AT03, there are 3 styles of terminal arrange-
ments. AT-503 has 14 usable terminals; AT-403/603/903 have 19
usable terminals; AT-703 has 18 usable terminals. Each terminal
has numbering on the edge of the casing for easy identification.
100~240 VAC
R-SP / CT
COM
50/60 Hz
50/60 Hz
1 13 + 1 10
24VDC
AL1
2 11
2 14 -
OPEN
AL2
+ 3 12
OUT1 Transmission
OPEN NO
+ 3 15
OUT1
NO COM
AL3
- 4 13
COM
- 4 16 NC
R-SP / CT
+ 5 14 +
Transmission
OUT2
NC 24VDC
+ 5 17
OUT2
CLOSE
- 6 15 -
CLOSE
- 6 18 T/R A+ 7 RS-485 16 A
7 AL1 19 T/R B- 8 17 - B
8 AL2 20 T/R A+ SG 9 18 + B
RS-485
9 COM 21 T/R B-
A
10 22 SG
INPUT
B
11 - 23 AT-503
AL3
B
12 + 24
RS-485
100~240 VAC
COM
50/60 Hz
1 13 14 7
T/R A+ T/R B-
AL1
2 8
AL2
+ 3 9
OUT1
- 4 10 A
Transmission
+ 5 11 - B
OUT2
- 6 12 + B
12
Chapter 3 : Programming
Terminology
AT-703
PV
SV PRG
MAN
SET
ANLY ELECTRONICS CO.
Shift Key
used to shift in and out of the adjust mode
Down Key
used to decrease a value or to scroll down. When not in
programming mode, press-and-hold to call up lock or hold function.
Up Key
used to increase a value or to scroll up.
When not in programming mode, press-and-hold to go back
to the standby display.
Press-and-Release
press a key and release it immediately
Press-and-Hold
press a key and hold it untill the display has changed
Menu mode
a heirarchal tree menu with the PV display showing the menu title
and the SV display showing the submenu or the parameter.
Adjust mode
when the value at the SV diaply is flashing and ready to be adjusted
with the down or up button.
Standby mode
when the red PV display is sowing the temperature’s present value
and the SV display is showing the set value. At this mode, the
controller can ne changed to Menu mode or Operation mode.
Operation mode
when the device is running
14
Power-up Sequence
When the controller is powered up, it goes through 4 diagnostic stages.
1st stage: All displays light up. Users can verify that all
display LEDs are functional.
15
Special Control (SPC) submenu
16
Device Hold
In Standby mode, press-and-hold Down to enter Hold mode. In the
Hold mode, the SV display will be flashing HoLd, meaning all opera-
tion has been suspended.
Device Lock
Under Level menu, press-and-hold Down to enter the lock param-
eter submenu. The parameter is freely adjustable from 0 to 9999.
However, only 10 numbers will lock the device in specific ways.
The following table details the number and the corresponding table
function.
17
Parameter Flow Chart
18
Same Group
19
Parameter Description, Range, Initial Value
PV
SV
USER submenu
(Parameter) (Range) (Initial Value)
OutL
At
Man
AL1S
AL1F = 1, 2
Alarm 1 Set Value AL1S = -200 ~ 200 10.0
AL1F = 3, 4
AL1S = Losp ~ Hisp
AL1F = 10
AL1S = 1 ~ 8 segment
20
USER submenu
(Parameter) (Range) (Initial Value)
AL1L
AL1u
For AL2* and AL3* : please refer to the AL1* description above
SoAK
rAmP
“rAmP” sets the rate of change for PV when the controller is without
program function. For example, if ramp is set at 10, the PV will
increase 10 degree per minute. However, if PV is higher than SV,
the PV will decrease 10 degree per minute.
21
USER submenu
(Parameter) (Range) (Initial Value)
PVoF
PVrr
SVoF
Ct
“Ct” is used to detect if the heater is broken. The value ranges from
0.0A ~ 100.0A. (“Ct” is only availiabe if the option is ordered)
22
USER submenu
(Parameter) (Range) (Initial Value)
HbA
“Hba” ranges from 0.1A ~ 100.0A. For example, when the control
output is on and “Ct” <= “Hba”, the heater is broken. The alarm
is triggered. Or when the control output is off and “Ct” >= “Hba”,
the alarm is then triggered. (“Hba” is only availiabe if the option is
ordered)
LbA
Lbd
Parameters for Loop break Alarm. For example, when out1 = 0.0%
and “lba” has elapsed, PV should be below “lbd”. If PV is till within
“lbd”, the alarm is triggered. When out1 = 100% and “lba” time has
elapsed, PV should be higher than “lbd”. if PV is till within “lbd”, the
alarm is triggered. (“lba” and “lbd” is implemented through firmware
only)
rPtm
“rptm” displays how many times the program has repeated thus far.
This parameter only works whenthe controller has program function
turned on.
23
CONTROL submenu
(Parameter) (Range) (Initial Value)
P1
i1
d1
Ct1
HSt1
AtoF
Ar
24
CONTROL submenu
(Parameter) (Range) (Initial Value)
P2
i2
d2
Ct2
HSt2
25
CONTROL submenu
(Parameter) (Range) (Initial Value)
100%
db
SV
0%
0
heating cooling
SSV
Sout
Stme
“Stme” sets the time interval when the soft start is deemed failed.
When the “Stme” time is reached and the PV has not reached
“SSV”, the soft start has failed and the controller will revert to SV.
26
CONTROL submenu
(Parameter) (Range) (Initial Value)
100% 100%
STME STME
0% 0%
SSV SV SSV SV
ruCy
“ruCy” sets the running cycle time in motor valve control, the time
from close to open or from opento close.
Motor Valve
COM
R
Close Out2
Close
Open
Open COM
Out1
T
rPt
“rPt” set the number of times the program will repeat execution.
27
CONTROL submenu
(Parameter) (Range) (Initial Value)
StAt
PVSt
Start Point Selection (only in Program mode) rSEt = start from 0 rSEt
PV = start from PV
wAit
“wAit” sets the time the SV will wait for PV if PV chanes slower than
SV.
Pid
“Pid” selects between PID (Pid) and Level PID (LPid). Level PID
allows upto 4 level of different PID.
28
CONTROL submenu
(Parameter) (Range) (Initial Value)
EndP
OUTPUT submenu
(Parameter) (Range) (Initial Value)
AL1F
AL1H
Out
Alarm 1 Hysteresis 0.0 ~ 200.0 0.0
AL1t
AL1M
29
OUTPUT submenu
(Parameter) (Range) (Initial Value)
Act
Outm
O1LS
O1HS
AO
30
OUTPUT submenu
(Parameter) (Range) (Initial Value)
O2LS
O2HS
t1SS
“t1SS” sets the segment the alarm will be activated. For example, if
the alarm activation is desired in Segment 2, set “t1SS” at 2.
t1On
“t1On” sets the time the alarm will be activated. For example, if the
alarm activation is desired after 3 minute in Segment 2, set “t1On”
at 3min and “t1SS” at 2. Note that the Program Time in Segment 2
(tP2) may be longer than 3 minute.
t1ES
31
OUTPUT submenu
(Parameter) (Range) (Initial Value)
“t1es” sets the segment the alarm will be deactivaed. For example,
if the alarm deactivation is dersired in Segment 6, set “t1ES” at 6.
t1oF
“t1oF” sets the time the alarm will be deactivaed. For example, if
the alarm deactivation is desired after 7 minute in Segment 6, set
“t1oF” at 7min and “t1ES” at 6. Note that the Program Time in Seg-
ment 6 may be longer than 7 minute.
INPUT submenu
(Parameter) (Range) (Initial Value)
inP1
Input 1 Selection K2
LoSP
32
INPUT submenu
(Parameter) (Range) (Initial Value)
HiSP
LoAn
HiAn
A1LS
A1HS
unit
O
Unit Selection C / OF O
C
dP
33
INPUT submenu
(Parameter) (Range) (Initial Value)
FiLt
inP2
A2LS
A2HS
bAud
Addr
Address 0 ~ 31 0
34
SPECIAL CONTROL submenu
(Parameter) (Range) (Initial Value)
LEV1
LEV2
LEV3
LVSL
L1P1
L1i1
35
SPECIAL CONTROL submenu
(Parameter) (Range) (Initial Value)
L1d1
L1Ar
L1P2
L1i2
L1d2
36
PROGRAM submenu
(Parameter) (Range) (Initial Value)
SEG
tiME
EndS
SV1
tP1
tS1
PROGRAM submenu
(Parameter) (Range) (Initial Value)
38
A. Example : How to set “SV” at 200OC
39
C. Example : How to set “AT” (auto tuning)
40
Press-and-hold to Press-and-hold to Press-and-hold to
show “P1” on PV continue other param- return to PV/SV initial
window eters in this level window
41
(3) Enter “inP” level
42
Press-and-hold to Press-and-hold to Press-and-hold to
show “baud” PV continue other parameters return to PV/SV initial
window in this level window
43
Press ro show SV Press to set SV for Press to set time for
flickering, the press segment 1 ramp of segment 1
key to set ending
segment
44
Press-and-hold to Press-and-hold to Press-and-hold to
show “1-2” on PV window continue other parameters return to PV/SV initial
at this level window
45
Press to increase or Press to enter “LOCK” Press-and-hold to
press to decrease setting return to PV/SV initial
code number window
46
Chapter 4 : Input
AT03 series is designed to accept thermocouples sensor, RTD
sensors, linear voltage and linear current inputs. The input type is
specified partly through hardware and needs to be specified at the
time of ordering.
For linear input, all vairotions are soecified through hardware at the
time of ordering.
47
Parameter INP1 under INP submenu
O O
Type INP1 C F
K K1 0 ~ 200 32 ~ 392
K2 0 ~ 400 32 ~ 752
K3 0 ~ 800 32 ~ 1472
K4 0 ~ 1000 32 ~ 1832
K5 0 ~ 1200 32 ~ 2192
J J1 0 ~ 200 32 ~ 392
J2 0 ~ 400 32 ~ 752
J3 0 ~ 800 32 ~ 1472
J4 0 ~ 1000 32 ~ 1832
J5 0 ~ 1200 32 ~ 2192
T T1 -50 ~ 50 -58 ~ 122
T2 -100 ~ 100 -148 ~ 212
T3 -200 ~ 400 -328 ~ 752
R R 0 ~ 1700 32 ~ 3092
E E 0 ~ 1000 32 ~ 1832
S S 0 ~ 1700 32 ~ 3092
B B 0 ~ 1800 32 ~ 3272
N N -200 ~ 1300 -328 ~ 2372
Pt Pt1 -50 ~ 50 -58 ~ 122
Pt2 0 ~ 100 32 ~ 212
Pt3 0 ~ 200 32 ~ 392
Pt4 0 ~ 400 32 ~ 752
Pt5 -200 ~ 600 -328 ~ 1112
jPt -200 ~ 500 -328 ~ 932
Linear Lin -1999 ~ 9999
48
Chapter 5 : Output
AT03 series has highly customizable outputs for customers’ specific
needs. It may have upto 2 control outputs. The desired ouputs
needs to be specified at the time of ordereing and set by the users
under OUTPUT submenu according to the hardware.
Output hardware ordering information
AT- □ 0 3 - □ ■ ■ □-□ □ □
Output 1 Output 2
(1 is standard) 0 = None
1 = Relay 1 = Relay
2 = Pulsed 2 = Pulsed
3 = 0~20mA 3 = 0~20mA
4 = 4~20mA 4 = 4~20mA
5 = 0~5V 5 = 0~5V
6 = 0~10V 6 = 0~10V
7 = 1~5V 7 = 1~5V
8 = 2~10V 8 = 2~10V
9 = Motor Control
49
7 Single output with transmitter and soft start
8 Program control
9 Program control with trsnamitter
Chapter 6 : Alarm
AT03 models can have upto 3 alarms. Each alarm can be programmed
to different function and different mode.
Alarm Function
Parameter AL1F, AL2F and AL3F under OUT submenu
ALARM FUNCTION DESCRIPTION
AL1F AL2F AL3F Description
0 0 0 No Alarm
1 1 1 Deviation High Alarm
2 2 2 Deviation Low Alarm
3 3 3 Absolute High Alarm
4 4 4 Absolute Low Alarm
5 5 5 Deviation high/low Alarm
6 6 6 Band Alarm
7 7 7 System Failure Alarm
8 8 8 Loop break alarm
9 9 9 Heater Break Alarm
10 10 10 Segment Ending Alarm
11 11 11 Program Ending Alarm
12 12 Not Time Signal Alarm
Availiable
13 13 Program Mode Running alarm
50
1. Deviation High Alarm
SV+AL1S
OFF ON
PV
SV
2. Deviation Low Alarm
SV+AL1S
ON OFF
PV
SV
3. Absolute High Alarm
OFF ON
PV
AL1S
4. Absolute Low Alarm
ON OFF
PV
AL1S
5. Deviation High/Low Alarm
SV-AL1L SV+AL1U
ON OFF ON
PV
SV
6. Band Alarm
SV-AL1L SV+AL1U
OFF ON OFF
PV
SV
7. System Failure Alarm
51
8. Loop break alarm
Non-alarm area
ON OFF ON
PV-LBD PV PV+LBD
ON OFF OFF ON
C.T. C.T.
AL1S
1~8 segment
AL1T
0.00 Flicker alarm
(other) ON delay time
99.59 Continuous alarm
OFF AL1T ON
TEMP
Program End
•
• Time
Alarm
OFF ON
52
12. Time Signal Alarm
TEMP
Program End
Program Start •
• Time
Alarm
OFF ON
Alarm Mode
Parameter AL1M, AL2M and AL3M under OUT submenu
ALARM MODE DESCRIPTION
AL1M AL2M AL3M Descrition
0 0 0 Normal
53
ALARM MODE DESCRIPTION (continue)
Chapter 7 : Communication
Baud Rate 2400 bps, 4800 bps, 9600 bps, 19200bps, 38400 bps
Data Frame
0 B0 B1 B2 B3 B4 B5 B6 B7 1
54
Sample Commands
RTU Request : Read command
0 1 2 3 4 5 6 7
Station Function Address Count CRC16
Number 0X03 (MSB~LSB) (MSB~LSB) (LSB~MSB)
0 1 2 3 4 5 6
Station Function Byte Data 1 Data 2
Number 0x03 Count (MSB~LSB) (MSB~LSB)
55
RTU Request : Write command
0 1 2 3 4 5 6 7
Station Function Address Count CRC16
Number 0X06 (MSB~LSB) (MSB~LSB) (LSB~MSB)
0 1 2 3 4 5 6 7
Station Function Address Count CRC16
Number 0X06 (MSB~LSB) (MSB~LSB) (LSB~MSB)
56
PARAMETERS AND ADDRESSES
LEvL 00 rPtm 18 AL1F 30 t2On 48
LoCK 01 P1 19 AL1H 31 t2ES 49
Sv 02 i1 1A Al1t 32 t2oF 4A
OutL 03 d1 1B AL1m 33 inP1 4B
At 04 Ct1 1C AL2F 34 LoSP 4C
mAn 05 HSt1 1D AL2H 35 HiSP 4D
AL1S 06 AotF 1E AL2t 36 LoAn 4E
AL1L 07 Ar 1F AL2m 37 HiAn 4F
AL1U 08 P2 20 AL3F 38 A1LS 50
AL2S 09 i2 21 AL3H 39 A1HS 51
AL2L 0A d2 22 AL3t 3A unit 52
AL2U 0B Ct2 23 AL3m 3B dp 53
AL3S 0C HSt2 24 Act 3C FiLt 54
AL3L 0D db 25 Outm 3D inP2 55
AL3U 0E SSv 26 O1LS 3E A2LS 56
SOAK 0F Sout 27 O1HS 3F A2HS 57
rAmP 10 Stme 28 AO 40
PvoF 11 rUCy 29 O2LS 41 bAud 59
Pvrr 12 rPtm 2A O2HS 42 Addr 5A
SvoF 13 StAt 2B t1SS 43 LEv1 5B
Ct 14 PvSt 2C t1On 44 LEv2 5C
HbA 15 wAit 2D t1ES 45 Lev3 5D
LbA 16 Pid 2E t1oF 46 LvSL 5E
Lbd 17 EndP 2F t2SS 47 L1P1 5F
57
PARAMETERS AND ADDRESSES
L1i1 60 L4P2 78 Sv7 90 1-20 A8
L1d1 61 L4i2 79 tP7 91 1-21 A9
L1Ar 62 L4d2 7A tS7 92 1-22 AA
L1P2 63 SEG 7B Sv8 93 2-14 AB
L1i2 64 TimE 7C tP8 94 2-15 AC
L1d2 65 EndS 7D tS8 95 2-16 AD
L2P1 66 Sv1 7E 1-2 96 2-17 AE
L2i1 67 tP1 7F 1-3 97 3-20 AF
L2d1 68 ts1 80 1-4 98 3-21 B0
L2Ar 69 Sv2 81 1-5 99 3-22 B1
L2P2 6A tP2 82 1-6 9A 3-23 B2
L2i2 6B tS2 83 1-7 9B 3-24 B3
L2d2 6C Sv3 84 1-8 9C 3-25 B4
L3P1 6D tP3 85 1-9 9D 3-26 B5
L3i1 6E tS3 86 1-10 9E 3-27 B6
L3d1 6F Sv4 87 1-11 9F Pv 100
L3Ar 70 tP4 88 1-12 A0
L3p2 71 tS4 89 1-13 A1
L3i2 72 Sv5 8A 1-14 A2
L3d2 73 tP5 8B 1-15 A3
L4P1 74 tS5 8C 1-16 A4
L4i1 75 Sv6 8D 1-17 A5
L4d1 76 tP6 8E 1-18 A6
L4Ar 77 tS6 8F 1-19 A7
58
Appendix A Error Code
Input1 error
Input2 error
RAM failed
Interface failed
59
Note :
60
Note :
61
Note :
62
Note :
63
ANLY Electronics Co., Ltd.
N0. 19, Lane 202, Fushou St.,
Xinzhuang Dist., New Taipei City 242, Taiwan
Content are aubject to change without notice
Phone : 886-2-2996-3202 Printed in Taiwan
Fax : 886-2-2996-2017 M-AT03-P-A