Pcs7 Profinet Blueprints Doc en 91sp2
Pcs7 Profinet Blueprints Doc en 91sp2
SIMATIC PCS 7 –
Guidelines and
Blueprints
Siemens
SIMATIC PCS 7 V9.1 SP2 Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/72887082 Support
Legal information
Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG ("Siemens"). They are
non-binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.
Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
© Siemens 2023 All rights reserved
foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.
Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.
Security information
Siemens provides products and solutions with industrial security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
under https://www.siemens.com/cert.
Table of contents
Legal information ......................................................................................................... 2
1 Introduction ........................................................................................................ 6
1.1 Process automation requirements for the fieldbus ............................... 6
1.2 PROFINET as a fieldbus ...................................................................... 6
1.3 PROFINET in SIMATIC PCS 7 ............................................................ 7
2 Overview of PROFINET functionalities in SIMATIC PCS 7 ............................ 8
2.1 System connections ............................................................................. 9
2.1.1 Simple system connection S1 .............................................................. 9
2.1.2 Media redundancy with MRP ............................................................. 10
2.1.3 Simple system redundancy S2 ........................................................... 11
2.1.4 Redundant PROFINET R1 configuration ........................................... 12
2.2 Configuration in Run – CiR................................................................. 13
2.3 High-precision timestamping .............................................................. 13
2.4 PA ready ............................................................................................. 14
3 Hardware for Using PROFINET in SIMATIC PCS 7 ....................................... 15
3.1 AS 410 Automation System ............................................................... 16
3.2 Distributed IO system ......................................................................... 18
© Siemens AG 2023 All rights reserved
1 Introduction
1.1 Process automation requirements for the fieldbus
Digitalization starts in the field
Scalability and availability are typical requirements of process automation. This
also includes the increasing flexibility for future plant expansions with ever shorter
commissioning and downtimes.
In order to meet these classic requirements, digitalization plays an increasingly
important role. The basic approach of digitalization is the integrated digital
communication from the control level down to the sensor and actuator in the field.
Benefits
• Quicker and easier device replacement
• Real-time and deterministic response
• IT standards, such as TCP/IP protocol, are supported
• Physical and/or logical segmentation of the plant
• High availability and flexibility for plant expansions
© Siemens AG 2023 All rights reserved
Symbol used:
Example configuration
Standard automation system AS 410 and ET 200SP HA with one interface module
Figure 2-1
© Siemens AG 2023 All rights reserved
Media redundancy is a function that ensures network and system availability. The
Media Redundancy Protocol (MRP) enables the connection of devices based on
ring topologies. If the transmission link in the ring is interrupted at one point,
for example, due to a break in the ring cable or the failure of a node, the
redundancy manager immediately activates the alternative communication path.
The switchover lasts a maximum of 200 ms. The use of MRP is not affected by
system redundancy (S1, S2 or R1) and it can be used with all three. You can find
further information about MRP in chapter 5.4.
Symbol used:
Example configuration
AS 410 Single Station and ET 200SP HA with one interface module
Figure 2-2
© Siemens AG 2023 All rights reserved
Symbol used:
Example configuration
AS 410 Redundancy system and ET 200SP HA with one interface module each.
One with the connection via an open ring structure (left) and one with the
connection via a switch in star structure (right).
Figure 2-3
© Siemens AG 2023 All rights reserved
Symbol used:
Example configuration
AS 410 Redundancy system and ET 200SP HA with two interface modules.
Figure 2-4
© Siemens AG 2023 All rights reserved
Symbol used:
Symbol used:
High-precision timestamping finds its application, for instance, in the event of a
message overload in the system. If a large number of messages is generated
within one second, it is only possible to identify the first message and therefore
also its cause by means of the timestamp.
Note For more information about the quantity structures and configuration rules, see
the following FAQ:
"Which quantity frameworks and configuration guidelines apply for high-precision
time stamping with an accuracy of 1 ms when using the ET 200SP HA and
PROFINET?"
https://support.industry.siemens.com/cs/ww/en/view/109750520
Note Manual
"SIMATIC Process Control System PCS 7; High-Precision Time Stamping When
Using the ET 200SP HA"
https://support.industry.siemens.com/cs/ww/en/view/109772337
2.4 PA ready
For unlimited use in process automation, IO devices must support at least the
following functionalities:
• Simple system redundancy S2
• Media Redundancy Protocol (MRP)
• Configuration in Run (CiR)
Siemens uses the PA ready symbol to identify the IO devices which meet the
requirements of process automation regarding availability and changes during
operation.
Symbol used:
Siemens, therefore, places similar requirements on both the PROFIBUS &
PROFINET International (PI) and PROFINET IO devices in process automation.
The PI subdivides IO devices into Conformance Classes (CC) depending on their
range of functions: CC-A, CC-B and CC-C. There is also the CC-B (PA), an
extension of the CC-B, which applies in particular to process automation. It
contains the system redundancy requirement and optionally also MRP and CiR.
Less stringent requirements for PA ready apply if IO devices are connected to the
end of a line or in a star topology:
© Siemens AG 2023 All rights reserved
Advantages
• A hardware platform for all application uses application sizes and performance
© Siemens AG 2023 All rights reserved
ranges
• Specially developed for process automation
• Conformal coating
• Extended temperature range (0 °C to +70 °C)
• PROFINET functions (S1, S2, R1, CiR, and SoE)
Communication
The CPU 410 has two PN/Ethernet interfaces with an integrated 2-port switch.
Up to 250 IO devices can be connected per PROFINET interface. The
CPU 410-5H has 8 KB and the CPU 410E has 1.5 KB for the I/O address range
per PN interface.
Figure 3-2
© Siemens AG 2023 All rights reserved
The CPU also has a 12 Mbps PROFIBUS interface and allows up to 96 nodes to
be connected. The distributed process I/O can be either linked directly with
PROFINET, PROFIBUS DP or via a subordinate bus system, such as PROFIBUS
PA.
Note You can find further device-specific instructions for use in chapter 5.6.2.
Modular design
Figure 3-3
© Siemens AG 2023 All rights reserved
(1) BusAdapter
(2) Interface module
(3) IO modules
(4) Terminal blocks without IO module
(5) Server module
(6) Subrack module for two interface modules
(7) Subrack modules with terminal blocks
Benefits
Communication
Note For the configuration of the ET 200SP HA, you need SIMATIC PCS 7 version 9.0
or higher.
Note Additional device-specific notes for use can be found in chapter 5.6.3.
Note Refer to chapter 5.6.7 for additional information on the use of BusAdapters.
© Siemens AG 2023 All rights reserved
Figure 3-4
© Siemens AG 2023 All rights reserved
Benefits
Communication
The ET 200M distributed IO system enables the integration of standard and fail-
safe signal modules.
Figure 3-5
Benefits
• Modular design and up to 12 modules per interface module
• Use of F modules (PROFIsafe)
© Siemens AG 2023 All rights reserved
Communication IM 153-4 PN HF
To connect the ET 200M to the fieldbus, there are interface modules for
PROFIBUS DP or PROFINET. The interface module IM 153-4 PN HIGH FEATURE
is used for connection via PROFINET. The IM153-4 PN STANDARD version is not
approved for SIMATIC PCS 7.
The IM153-4 PN HF has a PN/Ethernet interface with integrated 2-port switch.
When using this interface, the connection can be established via simple system
connection S1 and simple system redundancy S2. It is also possible to connect
with media redundancy (MRP).
Note For an overview of approved modules, please refer to the manual "SIMATIC
Process Control System PCS 7 Released modules (V9.1 SP2)"
https://support.industry.siemens.com/cs/ww/en/view/109821117
Note Manual
"SIMATIC Distributed I/O Device ET 200M"
https://support.industry.siemens.com/cs/ww/en/view/1142798
Communication
The CFU is connected to the PROFINET fieldbus via one BusAdapter. This
enables electrical connection via Industrial Ethernet or optical connection via fiber-
optic cable. Both versions have an integrated 2-port switch.
This allows the connection to be established via simple system connection S1 or
simple system redundancy S2. It is also possible to connect with media
redundancy (MRP).
Note Refer to chapter 5.6.7 for additional information on the use of BusAdapters.
© Siemens AG 2023 All rights reserved
The Compact Field Unit PA (CFU PA) is a field distributor for process-oriented,
distributed connection of digital I/O signals and PROFIBUS PA field devices to the
PROFINET fieldbus.
The CFU PA facilitates engineering and commissioning thanks to plug-and-
produce. For instance, PROFIBUS PA field devices are addressed automatically
and can then be detected (system-assisted) using standardized PROFIBUS PA
profiles and integrated into the process control system.
Figure 3-6
(1) BusAdapter
(2) Interface module
(3) Power supply
(4) Connections for reference potential (mass)
(5) Connections for freely configurable digital I/O channels
(6) Connections for each PROFIBUS PA field device
Benefits
Note A SIMATIC PCS 7 Version 9.0 or higher is required for the configuration of the
Compact Field Unit.
When using PCS 7 V9.0 without the Service Pack, you will also need the
Hardware Upgrade Package (HUP) for the SIMATIC Compact Field Unit.
Note Manual
"SIMATIC Distributed I/O SIMATIC Compact Field Unit (CFU)"
https://support.industry.siemens.com/cs/ww/en/view/109802597
The Compact Field Unit DIQ (CFU DIQ) is a field distributor for the process-
oriented, decentralized connection of digital IO signals to the PROFINET fieldbus.
Figure 3-7
(1) BusAdapter
(2) Interface module
(3) Power supply
© Siemens AG 2023 All rights reserved
Advantages
Note To configure the DIQ Compact Field Unit, you need, at minimum,
SIMATIC PCS 7 from version 9.0 SP2 and Update Collection 1.
The following link contains the latest software update for SIMATIC PCS 7 V9.0
SP2:
https://support.industry.siemens.com/cs/ww/en/view/109765887
Note Manual
"SIMATIC Distributed I/O SIMATIC Compact Field Unit (CFU)"
https://support.industry.siemens.com/cs/ww/en/view/109802597
✓ ✓ ✓
✓ ✓ ✓
✓ ✓ ✓
✓ ✓ ✓
Note The functions System Redundancy S2 and Configuration in Run (CiR) are
supported as of firmware version V4.0.
Note Refer to chapter 5.6.7 for additional information on the use of BusAdapters.
Figure 3-8
© Siemens AG 2023 All rights reserved
Note You can find the application example for the Service Bridge and the prepared
configuration files at the following link:
https://support.industry.siemens.com/cs/ww/en/view/109747975
Benefits
• Centralized access to the PROFINET networks with a secure separation of the
networks
• Manual assignment of name and IP address
• Use of the scan and online features of the STEP 7 Topology Editor
• Use of commissioning tools (e.g. PRONETA)
• Extended network diagnostics (for example, SINEC NMS via separate
network)
• Access to the web servers of PROFINET devices
• Installation of firmware updates
Note The use of the Service Bridge is optional and not a prerequisite for using
PROFINET.
© Siemens AG 2023 All rights reserved
Figure 3-10
© Siemens AG 2023 All rights reserved
Benefits
Communication
The Y switch has two slots for one BusAdapter each. By default, the rear ports of
the BusAdapter form the primary interface and the front ports form the secondary
interface. The primary interface consists of two ports that are isolated from a
network point of view, which connect to R1 networks. The secondary interface
allows the connection of S2-capable devices with the optional use of media
redundancy (MRP).
As of firmware V4.2, the Y switch supports the DNA redundancy function. This
functionality allows two Y switches – for connection of S2-capable devices to R1
networks – to be used (see Figure 3-10).
One Y switch assumes the roles of MRP manager and DNA manager, while a
second Y switch assumes the roles of MRP client and DNA client. The connection
to the two decoupled networks is possible if at least one Y switch is in operation.
In regular operation, the DNA ports of the DNA client are blocked; the DNA ports of
the DNA manager are in the "Forwarding" state. If the DNA client does not receive
any more MRP telegrams from the manager (for example, because the manager
was turned off), it switches both DNA ports to the "Forwarding" state.
DNA redundancy is only possible with an MRP ring.
It must always be ensured that both Y-switches can reach each other during
their operation in the MRP ring. A double fault in the MRP ring will result in a
situation where neither of the two Y switches can reach the other. If this
error is corrected, it can cause a short loop in the network and lead to
CAUTION device failures.
The elimination of the double fault should be carried out in a planned
manner and a Y-switch should be de-energized during the elimination
process.
© Siemens AG 2023 All rights reserved
1 S2
2 R1
Note The functionality of the Y switch must not be confused with that of the Y link
(PROFIBUS DP). Only S2-capable devices can be operated through the Y
switch.
Note It is recommended to use the standard configuration for the ports of the R1 and
S2 interfaces. Otherwise, resetting to factory settings could cause undesired
reactions.
Note When the Y switch is used, the subnets of the R1 network must be physically
separated from each other. Furthermore, both subnets of the R1 network and the
secondary S2 network must use the same IP address range.
Note Refer to chapter 5.6.7 for additional information on the use of BusAdapters.
Note Further information on the Y switch configuration can be found in chapter 5.6.8.
© Siemens AG 2023 All rights reserved
Customer benefits
PROFINET is intended for real-time communication in automation systems. Its
application is not limited to wired networks, it can also be used in wireless
networks. PROFINET via IWLAN has many advantages.
• higher performance and improved diagnostics options
• flexible integration of stationary and mobile nodes
• significant cost savings - for the installation and operations
• safety applications with PROFINET are possible via a single medium, including
wireless
•
© Siemens AG 2023 All rights reserved
The high-performance models of the SCALANCE W700 IEEE 802.11n series offer
reliability with their industrial design and iFeatures for industrial applications. They
can be used in the control cabinet. Mounting on the wall and ceiling is possible, as
well as use outdoors.
Easy handling is guaranteed when configuring via Web Based Management or via
central configuration and monitoring with SINEC NMS.
Figure 3-12
© Siemens AG 2023 All rights reserved
Benefits
• Integration of IO devices in locations that are difficult to access or with moving
nodes
• Connection of S2 devices
• Very robust housing
• EEC variants:
– Conformal coating
– Extended temperature range (-40 °C to +70 °C)
Communication
The SCALANCE IWLAN products themselves only support system redundancy S1.
The PROFINET IO devices on an IWLAN client as, of firmware V6.5 or higher, can
be S2 devices if iPCF is activated.
A maximum of 8 IO devices are enabled behind an IWLAN client.
Note You can find notes for use in the Blueprints in chapter 5.5.7
Note Additional notes for the configuration of IWLAN products can be found in chapter
5.6.10.
Benefits
Communication
The IE/PB LINK HA has an internal PROFINET interface with integrated 2-port
switch and a slot for the optional use of a BusAdapter. If a BusAdapter is inserted,
the integrated PROFINET interface is automatically deactivated and the
BusAdapter takes over the communication. BusAdapters enable electrical
connection via Industrial Ethernet or optical connection via fiber-optic cable. Both
versions have an integrated 2-port switch.
The IE/PB LINK is connected via simple system connection S1 or simple system
redundancy S2. The connection with media redundancy (MRP) is also supported.
Note The Configuration in Run functionality is only supported on the H-System and not
on the standard automation system.
Note Further device-specific instructions for use can be found in chapter 5.6.4
Note Refer to chapter 5.6.7 for additional information on the use of BusAdapters.
Note Manual
"SIMATIC NET: Industrial Ethernet / PROFIBUS IE/PB LINK"
https://support.industry.siemens.com/cs/ww/en/view/109744280
the integrated DP slaves are handled like IO devices with Ethernet interface.
Figure 3-14
Benefits
• Integration of a subordinate PROFIBUS network and access to all connected
PROFIBUS nodes
• Cross-network programming device communication using S7 routing
• Use as router for data records for the parameterization of field devices via
SIMATIC PDM by means of data record routing
• Connection via optical or electrical BusAdapter
Communication
The IE/PB LINK PN IO has an internal PROFINET interface with integrated 2-port
switch and a slot for the optional use of a BusAdapter. If a BusAdapter is inserted,
the integrated PROFINET interface is automatically deactivated and the
BusAdapter takes over the communication. BusAdapters enable electrical
connection via Industrial Ethernet or optical connection via fiber-optic cable. Both
versions have an integrated 2-port switch.
The IE/PB LINK PN IO is connected via a simple system connection S1.
Connection with media redundancy (MRP) is supported.
Note Further device-specific instructions for use can be found in chapter 5.6.5
Note Refer to chapter 5.6.7 for additional information on the use of BusAdapters.
Note Manual
© Siemens AG 2023 All rights reserved
Figure 3-15
© Siemens AG 2023 All rights reserved
In the configuration, both sides of the PN/PN coupler are configured separately as
individual IO devices in the respective subnet. The data exchange is realized via
configured input/output modules, whereby the communication is independent of the
IP addresses or the network structure behind the PN/PN Coupler.
This allows, for example, third-party systems to be integrated into an existing
PROFINET network in the form of Package Units.
Figure 3-16
Frei verwendbar
Benefits
• Cyclic communication
• Redundant power supply
• Electrical isolation between both PROFINET networks
• Device replacement without programming device
• Connection via optical or electrical BusAdapter
Communication
The PN/PN coupler is connected to the PROFINET fieldbus via a bus adapter on
each side, which is plugged into each interface module. This enables an electrical
connection via Industrial Ethernet or an optical one via fiber-optic glass cables.
Both versions have an integrated 2-port switch.
This supports the connection via a simple system connection S1 or simple system
redundancy S2 (as of firmware V4.2). Redundant connection with media
redundancy (MRP) is also possible.
Note Manual
© Siemens AG 2023 All rights reserved
Product note
Note "PROFINET over APL (Advanced Physical Layer) Support in PCS 7 V9.1 SP2"
https://support.industry.siemens.com/cs/ww/en/view/109812677
© Siemens AG 2023 All rights reserved
Approach
The PROFINET Blueprints show prepared standard solutions for the connection of
PROFINET devices to a (fail-safe) automation system. In order to make these
standard blocks optimally available for planning, they are structured according to
the programmable controller model and the type of system connection. Chapter 4.2
includes an overview of the blueprint configuration.
Since each system places individual requirements on availability and
segmentation, and these are not always covered by a single blueprint, it is possible
to combine the network structures shown in the blueprints. Chapter 4.6 contains an
example of a system based on blueprints.
The following questions will help you choose a suitable blueprint:
• What are your requirements for availability?
• Standard or fault-tolerant automation system?
• How many devices are to be integrated?
• Is a physical or logical segmentation necessary?
© Siemens AG 2023 All rights reserved
Figure 4-2
4.3.1 Entry
Network topology
Figure 4-3
© Siemens AG 2023 All rights reserved
Explanation
The cheapest and simplest variant among the Blueprints consists of one CPU with
up to 49 devices. The maximum number of devices is limited by the MRP ring,
which may contain a maximum of 50 nodes. No additional infrastructure
components, such as switches, are required are required if using the 2-port
switches integrated in the nodes. In the topology shown above, an optional switch
is also provided as an access point for the integration of the Service Bridge, as
otherwise no free ports are available.
Benefits
• No additional hardware required (without Service Bridge access)
• No single point of failure in the network
• Optional integration of the Service Bridge (with additional switch)
4.3.2 Standard - A
Network topology
Figure 4-4
© Siemens AG 2023 All rights reserved
Explanation
This blueprint serves as a template for standard automation systems with 50 to 100
devices. The number of devices is achieved by having two MRP rings with logical
segmentation, whereby each ring is connected to the ports of the same CPU
interface via a switch. The MRP limit of 50 nodes per ring applies.
It is recommended to install the first switches with the CPU in the control cabinet.
This ensures protection of this route and a reduction of error probability at this
single point of failure.
One of the unassigned ports in the switches can be used as access for the Service
Bridge.
Benefits
• Logical segmentation into two networks
• Access for Service Bridge
4.3.3 Standard - B
Network topology
Figure 4-5
© Siemens AG 2023 All rights reserved
Explanation
This blueprint serves as a template for standard programmable controllers up to
250 devices. The device count is achieved by having four MRP rings, each of
which is connected via a central switch to the same interface of the CPU (multiple
MRP rings). The MRP limit of 50 nodes per ring applies. Using star structures,
additional nodes can be connected to each of the respective MRP rings.
With multiple MRP rings, should the central switch fail, communication with nodes
in the other rings is no longer possible.
A free port on a switch can be used for access to the Service Bridge. Or, as in the
topology shown above, another optional switch can be put in place as an access
point in case there are no free ports available.
Benefits
• Minimal use of hardware for the full quantity structure
• Optional integration of the Service Bridge (with additional switch)
4.3.4 High-end
Network topology
Figure 4-6
© Siemens AG 2023 All rights reserved
Explanation
This blueprint serves as a template for standard automation systems with more
than 100 devices. An MRP ring is constructed as a backbone consisting of a CPU
and a series of switches. The devices are connected in separate logical segments
starting from the switches in the backbone.
With further switches connected in star configuration, the installation of MRP rings
is intended for the connection of devices. Alternatively, it is also possible to connect
devices in star configuration.
In this topology, MRP rings limit the quantity structure because they support a
maximum of 50 nodes. Even the PROFINET interface of the CPU limits the
quantity structure, as it supports a maximum of 250 devices.
Benefits
• Logical segmentation into "n" networks
• Access for Service Bridge
4.4.1 Entry
Network topology
Figure 4-7
© Siemens AG 2023 All rights reserved
Explanation
The cheapest and simplest variant of the blueprints for a fault-tolerant automation
system is one H-system and up to 250 PROFINET devices, which are integrated in
a line between the two IO Controllers. This variant of the connection is also called
an open ring structure.
Connecting the open ports to an MRP ring would not provide any advantages in
this case, but rather limit the number of devices to 48 (50–2 IO controllers) instead
of 250 devices and delay the failover time in case of error due to a reconfiguration
of the MRP ring. The MRP ring also leads to an increased configuration effort
(potential sources of error) because the MRP domain would have to be configured
and the response watchdog times adjusted.
The CPU has an unassigned port at the beginning and at the end of the line to
provide access for the Service Bridge. This blueprint does not require additional
components for the network structure design, however no logical segmentation is
intended.
Benefits
• No additional hardware required
• No single point of failure in the network
• Access for Service Bridge
4.4.2 Default
Network topology
Figure 4-8
© Siemens AG 2023 All rights reserved
Explanation
When compared to the entry variant, this blueprint assigns switches for the logical
segmentation of the network. Together with the H-system, the switches form an
open ring, from which the devices are connected via MRP rings or star structures.
As opposed to the high-end variant, this blueprint leads to single point of failures
due to the switches that connect the segments to the open ring.
Benefits
• Logical segmentation into "n" networks
• Access for Service Bridge
4.4.3 High-end
Network topology
Figure 4-9
© Siemens AG 2023 All rights reserved
Explanation
The switches in this blueprint are used for the logical segmentation of the network.
Together with the H-system, the switches form an open ring, from which the
devices are connected via MRP rings. In order to avoid a single point of failure, two
switches are used per MRP ring.
Benefits
• Logical segmentation into "n" networks
• No single point of failure in the network
• Access for Service Bridge
4.5.1 Default
Network topology
The following shows three variants for this blueprint. The first variant (Figure 4-10)
for the exclusive use of R1 devices, and the second variant (Figure 4-11) for the
additional integration of devices with simple system redundancy S2 via a Y switch
(SCALANCE XF204-2BA DNA). In the third variant (Figure 4-12), devices with
simple system redundancy S2 are integrated with redundant Y switches (DNA
redundancy).
Figure 4-10
Figure 4-11
Figure 4-12
© Siemens AG 2023 All rights reserved
CPU 410-5H
SB SB
PROFINET, electrical, redundant
ET 200SP HA
CFU
XF204-2BA XF204-2BA DNA
XF204-2BA DNA
SB
Access for Service Bridge
Explanation
This Blueprint shows the standard variant for connecting R1 devices to a fault-
tolerant automation system.
From the CPUs of the H system onwards, the R1 devices are connected via two
separate line structures. In order to increase availability, we recommend reverse
cabling (as shown in the blueprint). With reverse cabling, all devices remain
available if a device is removed. It is technically possible to have a configuration
with two MRP rings instead of the lines, but this is not provided in this blueprint
because it would require increased engineering effort (possible sources of error),
lead to a slower failover time and restrict the number of devices in the ring to 50.
The second variant is designed with a Y switch downstream from two XF204-2BA
switches, which enables connection of devices that only support simple system
redundancy S2.
The third variant shows a setup with a redundant Y switch, which allows availability
to be increased.
The unused ports of the CPU can be used for the Service Bridge to access both
subnets of the R1 network.
Benefits
• No additional hardware required (in a purely R1 network)
• No single point of failure, thanks to DNA redundancy
© Siemens AG 2023 All rights reserved
4.5.2 High-end
Network topology
Figure 4-13
© Siemens AG 2023 All rights reserved
Explanation
This Blueprint shows a variant for integrating R1 devices into a fault-tolerant
automation system with simultaneous logical segmentation in "n" networks.
A line consisting of switches is established for each CPU. These linearly arranged
switches act as a backbone for the logical segmentation of the system.
When setting up two MRP rings as a backbone (dashed line), the following points
must be observed:
• The MRP ring leads to increased configuration effort, since the MRP domain
must be configured and the response watchdog times must be adapted.
• In the event of a fault, the increased response watchdog time for the IO
devices is added to the failover time of the fault-tolerant system.
On the other hand, there is only a minimal increase in availability from the MRP
ring. The advantages of this MRP solution are minimized by the issues addressed
above.
The network downstream from the switches is divided into three segments. A
segment consisting of just R1 capable devices is connected to the switches of the
backbone MRP ring via two simple lines. The two other segments show the
possibility of integrating S2-capable devices with a Y switch into the R1 network. In
this case, MRP rings are installed downstream from the Y switch to allow the S2
devices to be connected.
The backbone MRP rings have ports in the switches that enable the Service Bridge
to access both subnets of the R1 network.
Benefits
• Logical segmentation into "n" networks
• No single point of failure (except Y switch)
• Access points for Service Bridge
© Siemens AG 2023 All rights reserved
Figure 4-14
1
2
3
© Siemens AG 2023 All rights reserved
Explanation
(1) The local PROFINET subnet of the standard AS 410 is modelled on the
blueprint from chapter 4.3.2. The first logical segment is an MRP ring
consisting of distributed IO devices and an IE/PB link with subordinate
PROFIBUS DP network.
The second logical segment is used for the connection of a Motion Control
Cabinet (MCC). The path between the switch near the CPU and switch in the
MCC area is done optically through fiber-optic cables. In this case, it is
optionally possible to build an MRP ring. The SINAMICS frequency converters
and SIMOCODE motor management systems in the MCC area are connected
to the switch in star configuration. Thanks to this star-shaped connection
topology, it is possible to switch off individual devices for maintenance
purposes without affecting the rest.
(2) The local PROFINET subnet of the H system corresponds to the blueprint in
chapter 4.5.1 and is used for connecting distributed I/O devices of type ET
200SP HA via redundant PROFINET R1 configuration.
(3) The communication between the central control room and the field is provided
by two mutually separated optical MRP rings. The standard AS 410 and a CPU
of the H-System communicate together via an MRP ring. The second MRP ring
is only used by the second CPU of the H system. This means that two
separate networks are available for the connection of R1 devices in the field.
(4) In practice, the transition from the two separate R1 subnets to a shared subnet
is achieved with a Y switch (XF204-2BA DNA). Behind the Y switch, devices
© Siemens AG 2023 All rights reserved
5 Guide
5.1 Configuration in Run – CiR/H-CiR
Configuration in Run (CiR) is a function that enables the system and configuration
(e.g. the addition or modification of hardware) to be changed during operation
without causing a system shutdown. This function is available to varying degrees
for both standard automation systems and H-systems. Replacing hardware when
replacement parts are needed is also possible without CiR.
A requirement for the function "Configuration in Run" (CiR) with PROFINET is the
deployment of the 410 CPU with firmware V8.2 or later and PCS 7 V9.0 or later.
Note The H-CiR loading process must run with the H-CiR Wizard.
The changes that are possible as a CiR/H-CiR operation depend on whether the
(changed) IO device has CiR functionality. Several changes can be made within a
CiR/H-CiR process. It is recommended to always perform changes simultaneously
on one string.
The following Table gives an overview:
Table 5-1
CiR/ H-CiR operation IO Device without IO Device with CiR
CiR
Add Device ✓ ✓
Remove device ✓ ✓
Add submodule ✓
Remove submodule ✓
Reassign submodule parameters ✓
Interface configuration
(e.g. enable/disable ports, topology ✓
configuration)
© Siemens AG 2023 All rights reserved
Note IO devices (S1) configured on one side of the H-System lose the connection
during the H-CiR process. This behavior is independent of whether the IO
devices are CiR-capable or not
Furthermore, it is not recommended to operate S1 devices unilaterally on the H
system. Exceptions are switches in an R1 network, which can only be connected
unilaterally. (See chapter 5.5.6)
Besides the changes that are possible as a CiR operation on the standard
programmable controller, it is also possible to add and remove IO controllers and
IO systems in fault-tolerant systems as an H-CiR operation.
Note For further information on the various possibilities of CiR, such as the mutable
CPU parameters in H-CiR, refer to the manual:
"SIMATIC PCS 7 Process Control System CPU 410 Process Automation"
https://support.industry.siemens.com/cs/ww/en/view/109815344
Note It is recommended that the "CiR capability" of the system is checked before each
CiR operation or Save and Compile. This way, you can still reject the changes.
Note Before making any changes in the HW Config, it is recommended to archive the
project. This allows you to restore the old project even if the CiR/H-CiR loading
capability is lost after saving.
Note In addition, observe the documentation of the devices (or modules) used; in
some cases, there may be specific features or restrictions for CiR.
Note For more information about Configuration in Run with configured topology,
please refer to the following FAQ:
"What do you have to consider for non-CiR-compatible IO devices in conjunction
with PROFINET and configured topology?"
https://support.industry.siemens.com/cs/ww/en/view/109749355
Note The re-parameterization of the internal PN interface of the CPU 410 is only
possible with H-systems as H-CiR process.
Note If multiHART or HART variables are not used, the address spaces for the
corresponding HART subvariables must still be reserved.
CAUTION When using CiR, it is recommended to force the V2.2 LLDP mode.
Figure 5-3
© Siemens AG 2023 All rights reserved
The reason is that the 410 CPU and newer IO devices support both modes and
that the HW Config automatically determines the mode from the configured devices
by default. Version V2.3 is used if all IO devices support it. If an IO device does not
support this mode, version V2.2 is used. For Configuration in Run, this is especially
important if only IO devices with V2.3 support are to be configured. In such case,
even the CPU uses version V2.3. If you had to add an IO device that only supports
LLDP mode V2.2, the CPU would change the LLDP mode to V2.2 and the system
would lose its CiR capability. The same applies to a scenario in which all IO
devices with V2.2 are removed from a mixed IO system.
The LLDP mode defined via HW Config can be displayed using the menu
command "PROFINET IO LLDP mode...", accessible from the context menu of the
PROFINET IO system.
Figure 5-4
© Siemens AG 2023 All rights reserved
ET 200SP HA
When connecting the ET 200SP HA via simple system connection S1 or simple
system redundancy S2, Configuration in Run is supported with up to 1000 byte
user data. If connected as an R1 device, the entire quantity structure of 1440 bytes
is available.
Automatic commissioning
Thanks to automatic commissioning, the devices do not have to be initialized
individually. Rather, the IO controller undertakes the initialization for the entire IO
system.
The IP addresses and device names are assigned without requiring a removable
medium (e.g. Micro Memory Card) with a saved device name or a programming
device (PG). The topology of the IO system, which is configured offline and then
loaded into the IO controller, forms the basis for automatic commissioning. By
comparing the loaded target topology and the actual topology determined via
LLDP, the IO controller can identify the IO devices without names and assign the
configured names and IP addresses accordingly. This reduces time requirements
and also the number of possible sources of error during commissioning.
Note The port interconnection of the real system must match the topology
configuration. An incorrect name could be assigned if errors occur.
Note FAQ
"How do you prepare STEP 7 for the export of topology data/flows for
SINETPLAN?"
https://support.industry.siemens.com/cs/ww/en/view/109740338
Note Topology configuration is only possible within a project, i.e. the stations on a
shared PROFINET network must be within the same project.
R1 network
In the case of an R1 network structure, it must be noted that the graphic view refers
to two separate subnets when scanning the topology or during the target/actual
comparison.
When the Service Bridge is used, access to both subnets can be enabled
simultaneously, so that the scan finds all devices.
If the ES is connected directly to the PROFINET network without using the Service
Bridge, the scan must be performed in both subnets, otherwise only the devices in
the corresponding segment are found. Devices behind a Y switch are visible in
both scans. Devices on the plant bus are not found. If the ES is connected
downstream from the Y switch, all devices in the PROFINET network are found
during the scan.
Switches
• Deactivate SET/RESET switch
• Use the HTTPS protocol for accessing the Web Based Management (disable
HTTP access)
• Change the default password for the Web/CLI access to the switches
• Use the "Loop Detection" function
• Disable write access to SNMP tags
All PN devices
• Disable unused ports and lock with Hardlock if necessary
Commissioning
• Before physically connecting the ring, it must be already configured.
Note You can find further measures for increasing operational reliability in the manual:
"SIMATIC Process Control System PCS 7 Compendium Part F – Industrial
Security (V9.1 SP2)"
https://support.industry.siemens.com/cs/ww/en/view/109815443
Note Please also note the security guideline from PROFIBUS & PROFINET
International (PI):
https://www.profibus.com/download/profinet-security-guideline/
Loop detection is a function of the SCALANCE switches, which serves for detecting
loops in the network and limiting their effects. A loop is an error in the network
configuration that occurs when a network cable connects two ports on the same
switch, or when several connections that are not managed by a protocol
(e.g. MRP) exist between two switches.
Broadcast packets sent through loops can lead to a broadcast storm within
seconds, thus overloading the network.
Loop detection allows these negative effects of a loop to be confined to a specific
area in the network. This function can be configured in the SCALANCE switches,
e.g. via Web Based Management (WBM), or in the HW Config in the port
properties of the switch.
Loop detection must be enabled in the interface properties in the HW Config.
Figure 5-6
© Siemens AG 2023 All rights reserved
This allows two types of loops to be detected and treated with different responses
(disable port/no response):
• Local Loop – LD telegram is detected at a different port
• Remote Loop – LD telegram is detected on the same port
It is recommended to block the respective ports in response to a detected loop.
Here, a distinction can be made between whether the ports remain permanently
blocked or, after a programmed time interval, change back to the state they were in
before the loop was detected.
If the permanent blocking response is selected, note that the port must be re-
enabled through the WBM, or the cable must be pulled from the corresponding port
and then re-inserted.
Figure 5-9
© Siemens AG 2023 All rights reserved
Note Loop detection cannot be activated with the ring ports of a switch.
As a rule of thumb, the switches in the network (from "bottom to top") should use
increasingly larger thresholds for the number of detected LD telegrams. With this
control, the local switches react first and switch off the specific port before the
higher-level switch disconnects the entire cell.
Due to the maximum reconfiguration time of 200 ms, the response watchdog time
must be set to at least 200 ms for all nodes in the ring and devices downstream
from the ring. Otherwise, the CPU may detect the failure of IO devices by mistake
during reconfiguration.
Diagnostic interrupts
When configuring an MRP ring, it is recommended to select the "Diagnostic
interrupts" checkbox in the MRP Manager's media redundancy settings. The
diagnostic interrupt option is a requirement in order for an alarm to be generated in
the operator station when the ring is interrupted.
Figure 5-14
Some switches support the "multiple MRP rings" function. This function lets one
switch be the MRP manager for up to four different MRP rings. The switch with
multiple MRP rings is the central point for all four MRP rings.
Figure 5-16
© Siemens AG 2023 All rights reserved
In the Figure above, the switch in the center is configured for multiple MRP rings.
The switch must fill the role of MRP manager (not MRP manager auto) for all four
rings. This means that all other nodes in each of the rings must be configured as
MRP clients.
Every linked MRP rings requires its own MRP domain and its own ring instance in
the switch governing multiple MRP rings.
Figure 5-17
Each of the ring instances and MRP domains must be assigned to the respective
ring ports.
1 2
© Siemens AG 2023 All rights reserved
5.5.2 Segmentation
Physical segmentation
The AS 410 has two internal PROFINET interfaces, which enable you to set up two
physically separate segments. Up to 250 IO devices can be integrated per
interface/segment. It is not possible to use the CP 443-1 for more PROFINET
segments. If a system segmentation is required in more than two system sections,
it is recommended to also implement logical segmentation.
Logical segmentation
By using switches, it is possible to divide the system into any number of logical
segments. This division is possible irrespective of the system connection (S1, S2 or
R1). It is recommended to place the switches responsible for the segmentation
close to the CPU.
Figure 5-19
The update time is the time interval in which IO devices/IO controllers are cyclically
supplied with new data. PROFINET offers the option to individually configure the
update time for each IO device.
To set the update time of IO devices, HW Config has three modes: "automatic",
"fixed update time" and "fixed factor".
When the default "automatic" setting is enabled, HW Config automatically
calculates an optimized, i.e. quickest possible update time.
This can be adjusted manually by selecting the "fixed update time" or "fixed factor"
mode.
When selecting the update time, the following factors should be considered:
• Process requirements
• Number of PROFINET IO devices
• Quantity of configured user data
In order to keep the network load as low as possible, it is also recommended to
select the update time for each IO device as follows:
• As short as necessary.
• As long as possible.
Note The update time of IO devices without cyclic IO data is automatically 128 ms and
usually does not need to be changed.
The cyclic network load generated should be taken into consideration right from the
planning phase of the system. PROFIBUS & PROFINET International (PI)
recommends the following limit values for the network load of cyclic real-time
communication in the PROFINET Installation Guidelines:
• < 20 % – no handling required.
© Siemens AG 2023 All rights reserved
Note Download
"PROFINET Installation Guidelines"
https://www.profibus.com/download/profinet-installation-guidelines/
HW Config automatically calculates the cycle times for small PROFINET networks
if they are fully configured within a project. It is not necessary to check the network
load again.
If a shared network is used by multiple programmable controllers that are
configured in different subprojects or if there is a high Non Realtime Traffic (NRT),
for instance, due to webcams, the network load must be checked.
The network load calculation can be performed, for instance, with SINETPLAN
(chapter 6.1.1).
5.5.6 R1 Networks
Physical configuration
When establishing an R1 network structure, it is recommended to establish
physically separate networks for the two subnets. This has the advantage that in
the event of a network fault (e.g. due to a loop), the other network remains
available for communication. As for the cabling, we recommend dual cabling, as
shown in the following Figure. Dual cabling ensures that all other nodes remain
available in the event of a failure or station replacement.
Figure 5-20
© Siemens AG 2023 All rights reserved
IP addresses
When configuring the IP addresses of R1 networks, the following notes must be
observed:
• In a purely R1 configuration without a Y switch and without embedded S2
devices, the two subnets can be in the same IP address ranges or in different
ones.
• In a mixed configuration (R1 and S2 devices), the two subnets must be in the
same IP address range. A common PROFINET IO system is configured in the
HW Config.
Switches in an R1 network
Switches in an R1 network structure have only one connection to a CPU due to the
network separation. They can, therefore, only be integrated as S1 devices on one
side. This is independent of whether or not they support system redundancy S2.
Figure 5-21 shows an example configuration with two XF204-2BA switches in an
R1 network structure (1 and 2) and a Y switch (XF204-2BA DNA) (3).
Figure 5-21
1
© Siemens AG 2023 All rights reserved
3
2
Figure 5-22
1
2
© Siemens AG 2023 All rights reserved
IWLAN can be used in the PROFINET environment. For reliable operation, please
observe the notes in chapter 3.7, especially the use of iFeatures, possible
response times, and the provision of free channels for the applications. The IWLAN
products of the SCALANCE W700 IEEE 802.11n only support system redundancy
S1 itself. The IO devices behind an iPCF client can be connected via S2 system
redundancy. For this, it is mandatory that the SCALANCE W700 products have
firmware V6.5.0 or higher.
Note Further notes for the configuration of the IWLAN products can be found in
chapter 5.6.10.
Two separate IWLAN networks (two SSIDs) are set up using two separate IWLAN
access points (IWLAN AP). The separate networks are identified by the different
SSIDs. An IWLAN client is connected to each of the WLAN networks. In this
example, there is an S2 device under each of the IWLAN clients.
The IWLAN AP does not support MRP and must, therefore, be integrated remotely.
In this case as well, two separate IWLAN networks are established. This ensures
the network separation of the two R1 networks.
In this case, the IWLAN AP and clients, as well as the switches shown, can only be
connected as S1 devices.
Using PROFINET affords the capability of detailed network diagnostics within the
PLC. The PROFINET IO devices can report the "link down" status or an incorrectly
connected neighbor (among others) for every port, as long as the topology is
configured.
Messages are also displayed in the maintenance station, provided that monitoring
has been enabled on the corresponding ports.
Figure 5-26
Monitoring must be enabled individually for every port in the port's properties.
© Siemens AG 2023 All rights reserved
You can find an overview of the PROFINET devices and PROFINET functions
relevant to SIMATIC PCS 7 in the following FAQ on the Industry Online Support
portal:
https://support.industry.siemens.com/cs/ww/en/view/109747976
5.6.2 AS 410
Firmware version
For the use of PROFINET, firmware V8.2 or higher is recommended. The following
PROFINET functions are only available with firmware V8.2 and higher:
• Redundant PROFINET R1 configurations
• Configuration in Run in standard systems (CiR)
• Configuration in Run in H systems (H-CiR)
• High-precision timestamping (SoE)
The firmware can be updated by performing a firmware update.
Note Instructions
© Siemens AG 2023 All rights reserved
https://support.industry.siemens.com/cs/ww/en/view/85196540
Download
https://support.industry.siemens.com/cs/ww/en/view/109476571
5.6.3 ET 200SP HA
Subrack module
The interface of the ET 200SP HA consists of the IM 155-6 PN HA interface
module together with the subrack module and the BusAdapter. The interface
serves for communication between the CPU and the connected ET 200SP HA IO
modules via PROFINET.
Different subrack modules are required depending on the system connection – this
must be taken into account during the planning phase.
The following two variants exist:
• Subrack module for an IM 155-6 PN HA – for simple S1 system connection or
simple S2 system redundancy
• Subrack module for two IM 155-6 PN HA - for redundant PROFINET R1
configuration
Configuration in Run
When connecting the ET 200SP HA via simple system connection S1 or simple
system redundancy S2, Configuration in Run is supported with up to 1000 byte
user data. If connected as an R1 device, the entire quantity structure of 1440 bytes
is available.
IO redundancy
© Siemens AG 2023 All rights reserved
When using the terminal blocks for IO redundancy (TB45), care must be taken so
that the L+ supply voltage terminals are separated from each other. The supply
voltage must be connected to both terminals.
Furthermore, only terminal blocks for individual IO modules or only terminal blocks
for IO redundancy may be used within a potential group.
Note For further information about wiring rules, refer to the manual:
"SIMATIC ET 200SP HA ET 200SP HA Distributed I/O system"
https://support.industry.siemens.com/cs/ww/en/view/109817158
The IE/PB LINK HA allows for the connection of up to 125 PROFIBUS slaves and
up to 64 PROFIBUS slaves as S2 devices. It must be ensured that only compact
slaves (e.g. drives) are supported with SIMATIC PCS 7. This means that the
connection of modular slaves (e.g. an ET 200M) via the IE/PB- LINK HA is not
possible. To integrate modular PROFIBUS slaves into the system, you can use the
internal interface of the CPU. S7 routing and data record routing are supported via
the IE/PB LINK HA.
The IE/PB LINK HA supports the system redundancy S2, as well as Configuration
in Run (PROFINET and PROFIBUS side).
Note The Configuration in Run functionality is only supported on the H-System and not
on the standard automation system.
Note The addressing of DP or PA slaves downstream from the IE/PB link PN IO is not
possible.
that of all PROFIBUS devices must be adjusted to over 200 ms when using MRP.
5.6.6 Switches
4
1
© Siemens AG 2023 All rights reserved
5.6.7 BusAdapters
The BusAdapters for PROFINET IO allow you to freely select the connection
technology for the device. For the interface modules, multiple variants of the
BusAdapters are available.
Examples:
• BusAdapter with standard RJ45 plug (BA 2xRJ45)
• BusAdapter with FastConnect connector for direct connection of the bus cable
(BA 2×FC)
• BusAdapter with connector for fiber-optic cable (BA 2xLC)
• BusAdapter with one standard RJ45 plug and one plug for fiber-optic cable (BA
LC/RJ45)
• BusAdapter with a Fast Connect plug for direct connection of the bus cable
and a plug for fiber-optic cable (BA LC/FC)
• BusAdapter with standard RJ45 plug for distances up to 1000m (BA 2xRJ45VD
HA)
Figure 5-28
© Siemens AG 2023 All rights reserved
Note The ET 200SP HA and the CFU only support 100Mbit/s when using the
BusAdapter BA 2xRJ45VD HA. This must be taken into account when planning
the maximum cable lengths and the type of cable used.
Note Further information about the BA 2xRJ45VD HA BusAdapter can be found in the
manual:
"SIMATIC: Network components SIMATIC BusAdapter"
https://support.industry.siemens.com/cs/ww/en/view/109759611
Figure 5-29
1. Y-Switch 2. Y-Switch
© Siemens AG 2023 All rights reserved
Figure 5-30
Topology configuration
The IWLAN AP and clients can be configured as IO devices. The advantage is that
the topology can be configured up to the IWLAN AP and behind the IWLAN client.
This is necessary for the automatic device exchange of the IO devices behind the
IWLAN client. The IWLAN route or an assignment of clients to an AP cannot be
© Siemens AG 2023 All rights reserved
ensures easy device replacement by removing the C-Plug from the defective
device and inserting it into a new device.
Points to consider include the following:
• Activation of iPCF is necessary for real-time communication (PROFINET).
• "Layer 2 Tunnel" must be activated on the IWLAN client.
• Maximum 8 IO devices behind one IWLAN client.
• The minimum recommended update time of IO devices behind an IWLAN
Client is 32ms; these times have to be adjusted depending on the application.
Note For more information on configuration, see the application example "IWLAN:
Setup of a Wireless LAN in the Industrial Environment"
https://support.industry.siemens.com/cs/ww/en/view/22681042
Table 5-2
PG/PC interface Function Applications
setting
PC internal (local) Automatic selection of the • Loading of stations and
(Recommended setting access point based on the automation systems
in the PCS 7 interfaces configured in the
environment) Station Configuration
Editor
TCP/IP or RFC1006 Use of the TCP/IP protocol • Online mode of the
for access via the set Topology Editor1)
interface • PLC download with the
(IP-addresses-based) "Show accessible nodes"
function
• Use of the "Edit Ethernet
Node" function
ISO Use of the ISO protocol for • PLC download without an
access via the set interface IP address via the "Show
(MAC-address-based) accessible nodes" function
• Use of the "Edit Ethernet
Node" function
1) When using the Service Bridge, the separate network adapter must be used to
access the PROFINET networks.
6.1 Planning
6.1.1 SINETPLAN (Siemens Network Planner)
SINETPLAN (Siemens Network Planner) is a tool for calculating the network load,
which can already be implemented during the planning phase. SINETPLAN
enables predictive planning through a simple simulation-based network load
calculation. Critical locations, where a network load check is recommended or
necessary, are highlighted in color depending on the data throughput.
It is necessary to calculate/check the network load, especially for complex
networks consisting of several projects and existing NRT (Non Realtime)
communication (for instance, from video systems). HW Config automatically
calculates the cycle times for networks if they are fully configured within a project.
There is no need to use additional tools for the network load calculation.
Benefits
• Online scan function
• Import the topology and real-time data flows from STEP 7 or PCS 7 projects
• Port-by-port simulation
• Identification of areas with critical network load
• Reporting function
© Siemens AG 2023 All rights reserved
Note Download
"Siemens Network Planner – Download SINETPLAN V2.0 Trail"
https://support.industry.siemens.com/cs/ww/en/view/109763136
FAQ
"How do you prepare STEP 7 for the export of topology data/flows for
SINETPLAN?"
https://support.industry.siemens.com/cs/ww/en/view/109740338
The Concept & Design Tool (CDT) makes it simple, intuitive and fast to put
together hardware and software for your projects in SIMATIC PCS 7 and supports
you across all project phases.
Siemens process control technology sets the clock, visualizes and provides open-
and closed-loop control for processes so that process facilities can operate reliably,
efficiently and safely in the event of a fault. Each industry needs a custom solution
perfectly tailored to its requirements.
The Concept & Design Tool (CDT) lets you rapidly create process control system
architectures and then flexibly adapt them over and over again until you have
precisely the architecture and configuration that will protect your investment over
the entire plant lifecycle.
Benefits
• Quick setup of software and hardware configurations
• Precise composition of components to fit technical and cost considerations
• Generation of complete, coherent, ready-to-order bills of materials (BoM) –
which can be updated at any time
• CDT results can be exported to detailed price quotes
• Easy to operate, even with elementary DCS knowledge
Application example
Note "Concept & Design Tool for the design of the process control system architecture"
https://support.industry.siemens.com/cs/ww/en/view/109802553
TIA Selection Tool is the free, intelligent configurator for the Siemens automation
portfolio.
The TIA Selection Tool software quickly and intuitively guides the user through the
automation project, producing an error-free device selection and configuration. No
© Siemens AG 2023 All rights reserved
Benefits
• Configure a complete project with a few keystrokes. No manual or special
knowledge required
• Order directly from Siemens Industry Mall
• Smart selection wizard for flawless configuration and ordering
Product note
"TIA Selection Tool – quick, easy, smart"
Note
https://support.industry.siemens.com/cs/ww/en/view/109767888
6.2 Commissioning
Various tools with different ranges of functions are available for commissioning.
The following Table compares the tools.
Table 6-1
Product functions SIMATIC PCS 7 SINEC PNI Basic PRONETA Basic
Independent of the set ✓ ✓
PG/PC interface
Assign IP address ✓ ✓ ✓
Assign PROFINET device ✓ ✓ ✓
names
Topology ✓ ✓
IO Test (without IO ✓
controller)
Firmware update of ✓
SCALANCE products
Enabling SNMP ✓
Changing passwords for ✓
SCALANCE products
© Siemens AG 2023 All rights reserved
All the required functions for commissioning a PROFINET network are integrated in
SIMATIC PCS 7. In SIMATIC PCS 7, it is possible to assign device names and IP
addresses manually or automatically via the automatic commissioning feature.
Functions
• Browse network for reachable devices via "Show accessible nodes"
• Manual assignment of device names and IP addresses via "Edit Ethernet
Node"
• Reading in the actual topology with the Topology Editor
• Topology comparison between target and actual topology using the Topology
Editor
SINEC PNI (Primary Network Initialization) Basic is a free tool for initializing
Siemens network components; one of its uses is for assigning device names and
IP addresses. A password change can be performed for several devices (including
SCALANCE products) at the same time. A firmware upgrade of SCALANCE and
RUGGEDCOM products is also possible.
SINEC PNI is independent of other configuration tools (i.e. SIMATIC PCS 7) and
can be installed and used on all standard Windows PCs.
Functions
• Browse network for accessible devices
• Assign device names and IP addresses
• Restoring to factory settings
• Launch Web Based Management
• Initial password change (SCALANCE & RUGGEDCOM)
• Firmware upgrade (e.g. for the SCALANCE product families)
• Download and upload of configuration for SCALANCE products and others
• Download and upload of files needed to diagnose problems (e.g. for
SCALANCE)
© Siemens AG 2023 All rights reserved
Advantages
• Simple operation
• Does not need STEP 7 or PCS 7 to be installed
• Available free of charge
Note Download and manual
"SINEC PNI Basic"
https://support.industry.siemens.com/cs/ww/en/view/109817719
Functions
• Online topology overview
• Assign device names and IP addresses
• I/O test, e.g. when performing a loop check
• Topology comparison with topology imported from STEP 7/PCS 7 or reference
topology saved in PRONETA
Advantages
• Graphical user interface
• Does not need STEP 7 or PCS 7 to be installed
• Does not need to be installed
• Available free of charge
Note When assigning device names, the PROFINET naming conventions must be
observed. PRONETA does not test whether the naming conventions have been
observed. Characters that are not in line with the naming conventions are
replaced by others.
FAQ
PROFINET naming conventions
https://support.industry.siemens.com/cs/ww/en/view/36062700
Note For the I/O test, it is imperative that the IO device does not communicate with
any IO controller.
© Siemens AG 2023 All rights reserved
6.3 Operation
6.3.1 SINEC NMS
Note Download
"SINEC NMS V1.0 Software (incl. 21 days trial license) Download"
https://support.industry.siemens.com/cs/ww/en/view/109762387
Manual
"SIMATIC NET: Network management with SINEC NMS"
https://support.industry.siemens.com/cs/ww/en/view/109762749
Application example
"Getting Started: Understanding and Using SINEC NMS"
https://support.industry.siemens.com/cs/ww/en/view/109762792
SINEMA Server is a tool for 24/7 monitoring of Industrial Ethernet and PROFINET
networks during operation. SINEMA Server allows networks to be automatically
exported, documented, individually structured for each plant and visualized.
Furthermore, the SINEMA Server sends alerts and analyzes errors and changes in
the network.
The use of SINEMA Server requires permanent access to the PROFINET fieldbus.
For security reasons, it is recommended not to run it directly on the plant bus, but
rather to connect it via a separate Service Bridge.
Figure 6-4
© Siemens AG 2023 All rights reserved
Functions
• Inventory and documentation of all network nodes
• Topological representation of the network
• Read out status information
• Evaluation and display of diagnostic states
• Display of statistics for any time period
• Validation of network parameters
• Configuration of devices via CLI (Command Line Interface) / firmware
management
Advantages
• Continuously updated documentation at a central location and avoidance of
additional archives
• Fast, easy check of network status over extended time periods
• Firmware update of network components from a central location
Note Download
"SINEMA Server Trial Version"
https://support.industry.siemens.com/cs/ww/en/view/109767382
Manual
"SIMATIC NET: Network management SINEMA Server"
https://support.industry.siemens.com/cs/ww/en/view/109748925
Application example
"GettingStarted: Understanding and Using SINEMA Server V14"
https://support.industry.siemens.com/cs/ww/en/view/109746780
© Siemens AG 2023 All rights reserved
Wireshark is a free program that for analyzing data traffic on a protocol level. To
perform an analysis, you must log the data traffic on the network with a TAP or
mirrored port in a switch.
Benefits
• Standard network analysis tool
• Analyze the data traffic on a protocol level
• Free of charge
Note Download
"Wireshark"
https://www.wireshark.org/
© Siemens AG 2023 All rights reserved
7 Appendix
7.1 Comparison of PROFINET and PROFIBUS
The Table below compares PROFIBUS and PROFINET.
Table 7-1
PROFIBUS DP PROFINET
Data channels One channel between Multiple channels between
master and slave IO controller and IO
devices
Data per device 244 bytes Input/Output 1440 bytes Input/Output
Data per controller 8 KB 8 KB
(interface)
Number of nodes Maximum 125 slaves per Maximum 250 IO devices
interface per interface (AS 410)
Maximum 31 slaves per Unlimited number of IO
segment devices in the network
Cable length >1000 m (depending on Electrical: Maximum
transmission rate) 100 m1)
FOC: Some km
© Siemens AG 2023 All rights reserved
7 Appendix
7.2.1 Two standard programmable controllers with simple S1 system connection and MRP
Figure 7-1
Frei verwendbar
© Siemens AG 2023 All rights reserved
7 Appendix
7.2.2 Three standard programmable controllers with simple S1 system connection – PLCs in the MRP ring
Figure 7-2
7 Appendix
7.2.3 Three standard programmable controllers with simple S1 system connection – separate optical MRP ring
Figure 7-3
7 Appendix
Figure 7-4
Frei verwendbar
PROFINET in SIMATIC PCS 7 Guidelines and Blueprints
Article ID: 72887082, V2.5, 06/2023 121
© Siemens AG 2023 All rights reserved
7 Appendix
Figure 7-5
7 Appendix
Figure 7-6
Frei verwendbar
PROFINET in SIMATIC PCS 7 Guidelines and Blueprints
Article ID: 72887082, V2.5, 06/2023 123
© Siemens AG 2023 All rights reserved
7 Appendix
7.2.7 Two fault-tolerant systems with redundant PROFINET R1 configuration and simple S2 system redundancy and DNA
redundancy
Figure 7-7
7 Appendix
7.2.8 Standard programmable controller with simple S1 system connection and fault-tolerant system with S2 system
redundancy
Figure 7-8
Technical Support
The Technical Support of Siemens Industry provides you fast and competent
support regarding all technical queries with numerous tailor-made offers
– ranging from basic support to individual support contracts.
Please send queries to Technical Support via Web form:
siemens.com/SupportRequest
Service offer
Our range of services includes the following:
• Plant data services
• Spare parts services
• Repair services
• On-site and maintenance services
• Retrofitting and modernization services
• Service programs and contracts
You can find detailed information on our range of services in the service catalog
web page:
support.industry.siemens.com/cs/sc
The Siemens Industry Mall is the platform on which the entire siemens Industry
product portfolio is accessible. From the selection of products to the order and the
delivery tracking, the Industry Mall enables the complete purchasing processing –
directly and independently of time and location:
mall.industry.siemens.com