Programacion General
Programacion General
es
The following diagrams represent concepts, each controller includes its diagram with terminal numbering for correct
connection.
1 2
Sensor 0V Sensor
12V Supply
24
Supply
3 4
Control Control
Sensor 0V Sensor
12V Supply
24
Supply
5 6
S1-TEM COOL
Control
Sensor S2-DEF R2
Supply Supply
Digital input
7 8
S1-TEM COOL
S1-TEM COOL
S2-DEF DEF
S2-DEF Supply
Supply DEF FAN
Digital input
Digital input FAN
S3 ALARM
9 Slave relay 10
To controller
Wall mounting installation Installation with the slave relay for Panel mounting installation
DIN 43880 rail mounting
REFERENCES: SPECIFICATIONS
AKO-14012 Thermometer 12/24V 1 • • • •
AKO-14023 Thermometer 230V 2 • • • •
AKO-14031 Thermometer 230V 2 • • • •
AKO-14112 1 Relay 12/24V 3 • • • • •
AKO-14123 1 Relay 230V 4 • • • • •
AKO-14128 1 Relay 230V 5 • • • • •
AKO-14129 1 Relay 230V 4 • • • • •
AKO-14212A 2 Relays 12V 6 • • • • • • • • •
AKO-14223 2 Relays 230V 6 • • • • • • • • •
AKO-14312B 3 Relays 12V 7 • • • • • • • • • • •
AKO-14323B 3 Relays 230V 7 • • • • • • • • • •
AKO-14412 4 Relays 12V 8 • • • • • • • • • • • • •
AKO-14423 4 Relays 230V 8 • • • • • • • • • • • • •
AKO-14530+AKO-15128 230V 9 • • • • • • • •
AKO-14602 Thermometer 230V 2 • • • •
AKO-14610 1 Relay 230V 4 • • • • •
AKO-14632 3 Relays 230V 10 • • • • • • • •
SPECIFICATIONS
Diagram for previous page
2 Digits, from -50ºC to + 99ºC
3 Digit decimal pt. from -49,9ºC to 99,9ºC
Sensor 1, NTC 1,5m included, non-adjustable
Sensor 1, NTC 1,5m included, adjustable
Sensor 2, NTC not included
Sensor 3, NTC not included
Power supply 12 ± 20%, 50/60Hz
Power supply 12/24 ± 10%, 50/60Hz
Power supply 230 ± 10%, 50/60Hz
Relay 1, Control (compressor) R 8(3)A, 250V, cos ϕ=1, SPST
Relay 1, Control (compressor) R 8(3)A, 250V, cos ϕ=1, SPDT switch
Relay 1, Control (compressor) R16(4)A, 250V, cos ϕ=1,
Relay 1, Control (compressor) R16(4)A, 250V, cos ϕ=1, SPDT switch
Relay 1, Control (compressor) R20(6)A, 250V, cos ϕ=1,
Relay 1, Control (compressor) R 30 max.18(5)A, 250V, cos ϕ=1, SPST
Relay 2, Defrost or fans R 8A, 250V, cos ϕ=1, SPDT switch
Relay 2, Defrost R 8A, 250V, cos ϕ=1, SPDT switch
Relay 2, Defrost R 8A, 250V, cos ϕ=1, SPST
Relay 3, Fan R 6A, 250V, cos ϕ=1, SPST
Relay 3, Fan R 8A, 250V, cos ϕ=1, SPST
Relay 4, Alarm R 6A, 250V, cos ϕ=1, SPST
Internal acoustic alarm
Digital input (for voltage-free contacts)
Real time clock
Communications conector
HOJA TÉCNICA 1400H101 Edición 01 (04 de 08) www.ako.es
C5 Protection delay time (value for the option selected for parameter C4) 0min 0min 99min • • • • •
"COOL" relay status with faulty sensor 1 (1 relay equipment)
C6 0 0 1 •
0=OFF/ON (average last 24 hours) 1=OFF/ON (to C7 and C8 program)
Increase button - When the key is pressed for at least 5 seconds, it displays
-When pressed for at least 5 seconds, a manual defrost is the current SET POINT and LED 2/PR flashes.
started with programmed duration.
- Pressing the or keys permits the SET POINT to be adjusted
-In programming, it increases the value being displayed. to the required value.
-In 2, 3 and 4 relay models, it cancels the alarms, but they
remain displayed. - Pressing the and keys simultaneously sets the new value.
When this operation is carried out, the display will return to the
current temperature and LED 2/PR will cease flashing.
Decrease button
-When pressed for at least 5 seconds, it displays the SET Adjusting thermometer ref. AKO-14031 calibration
POINT temperature value.
-In programming, it decreases the value being displayed. Pressing the two keys simultaneously for at least 10 seconds dis-
plays the calibration value (default = 0ºC). Each press of the keys
-In 2, 3 and 4 relay models, it cancels the alarms, but they or will change the temperature display by 1ºC between -20ºC
remain displayed. and +20ºC. The two keys should be pressed simultaneously again
in order to accept the new value.
MODELS WITH 1 RELAY:
LED 1 Increase button PARAMETERS
LED 2 The parameters should only be programmed or modified by
personnel who are fully conversant with the operation and pos-
PRG sibilities of the equipment.
ºC SET
LEVEL 1 PARAMETERS:
Decrease button - Pressing the and keys simultaneously for at least 10 seconds
will cause LED 2/PR to indicate the programming phase and the
LED 1 Permanent: Indicates defrost in operation. first parameter “C0” will appear on the display.
LED 2 Permanent: Indicates compressor relay is ON. - Pressing the key accesses the next parameter and the key
Flashing: Set Point or parameter programming phase. will produce a return to the previous parameter.
- If the and keys are simultaneously pressed in the last para-
MODELS WITH 2, 3 AND 4 RELAYS: meter “EP”, the controller will return to the temperature display
situation and the LED 2/PR will cease to indicate the program-
LED PR LED DT
ming phase
PR DT Increase button
LEVEL 2 VALUES:
LED COOL
- In order to display the current value of any parameter, the keys
LED FAN and keys should be simultaneously pressed with the required
PRG
LED DEF parameter selected. Once it is displayed, it can be modified by
ºC SET
LED ALARM pressing the or keys.
Decrease button - Pressing the and keys simultaneously sets the new value.
When this operation is performed, the programming returns to
LED DT Permanent: Indicates last defrost ended by time. Level 1 (parameters).
LED PR Flashing: Set Point or parameter programming NOTE: If a key is not pressed for 25 seconds in any of the previous
phase. steps, then the equipment will automatically return to the current
LED COOL Permanent: Cooling relay COOL (compressor) temperature display situation without modifying any of the values.
energised.
Flashing: Because of the temperature detected
by Sensor 1 (TEM), the COOL relay CURRENT LEVEL 1 LEVEL 2
should be energised, but is not due to TEMPERATURE PARAMETERS VALUES
a programmed parameter.
10 Sec.
LED FAN Permanent: FAN relay energised.
Flashing: Because of the temperature detected SIMULTANEOUSLY SIMULTANEOUSLY SIMULTANEOUSLY
ACCEPT
VALUE
VALUE
PROGRAMMING
SIMULTANEOUSLY
SET POINT
CHANGE
CURRENT
THE NEW
ACCEPT
AKO-14916
Programming
Power supply
Programming
AKO-14XXX AKO-14XXX
AKO-14112 AKO-14123 With communication connector. With communication connector
COMMUNICATION
AKO-5003 RS485
Software for controllers and data loggers
RS485
using a PC type computer.
AKO data loggers with
MODBUS communications
On request protocol and RS485 output
software with:
External alarms by
telephone, fax or internet. RS485 CMOS
Display boards.
Power management.
AKO-14917 AKO controllers
PLC management. CMOS/RS485 with MODBUS
converter module communications protocol
Remote teleprocessing.
RS485 CMOS
ACCESSORIES DIMENSIONS
35
Ø7
37
11 60
Ø4
79
AKO-14910
120
In transparent plastic for 3 14
panel mounting units
17
Sheath for housing sensors in tanks
detail of fixing
23
140
screw holes
10
37 80
Ø8
90
50,5
58
AKO-15590
120-230/12V, 3VA
Power supply converter 70 58
Panel mounting
90
AKO-15589 17 58
, 6VA
33
14 to 30 /12
Sensor extension cable
75 61,5
28,5
AKO-15586
3 x 0,5mm2 cable with insulation
+ copper braid + PVC sheath. 70,5
NTC Sensors
AKO-14901 L=1,5m
AKO-14902 L=2,0m
Ø6
AKO-14903 L=3,0m
AKO-14906 L=6,0m L 14
Ø5
100 mm
3m 190 mm
AKO-14915
Stainless steel tapered probe with 3m silicone cable
351400101 REV. 00 2002 D.L.: 41303-2002 Nos reservamos el derecho de suministrar materiales que pudieran diferir levemente de los descritos en nuestras hojas técnicas.