The document provides technical specifications for temperature controllers and sensors including temperature ranges, accuracy, operating conditions, diagrams of controller connections, and lists of controller references and their specifications. It also details programmable parameters for refrigeration control including sensor calibration, set points, compressor protection delays, and fault responses.

Uploaded by

EDGAR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views

Programacion General

The document provides technical specifications for temperature controllers and sensors including temperature ranges, accuracy, operating conditions, diagrams of controller connections, and lists of controller references and their specifications. It also details programmable parameters for refrigeration control including sensor calibration, set points, compressor protection delays, and fault responses.

Uploaded by

EDGAR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

HOJA TÉCNICA 1400H101 Edición 01 (02 de 08) www.ako.

es

GENERAL TECHNICAL SPECIFICATIONS

Temperature range: -50ºC to +99ºC


Sensor type: NTC
Total accuracy (Sensor + controller): ±1ºC
Sensor lead extension with cable AKO-15586: Max. decrease 0.35ºC for each 100m
Operating ambient temperature range: 5ºC to 50ºC
Storage temperature range: -30ºC to 70ºC
Installation category: II in accordance with the CEI 664 standard

REFERENCE DIAGRAMS ON FOLLOWING PAGE

The following diagrams represent concepts, each controller includes its diagram with terminal numbering for correct
connection.

1 2

Sensor 0V Sensor
12V Supply
24
Supply

3 4

Control Control
Sensor 0V Sensor
12V Supply
24
Supply

5 6

S1-TEM COOL
Control
Sensor S2-DEF R2
Supply Supply
Digital input

7 8

S1-TEM COOL
S1-TEM COOL
S2-DEF DEF
S2-DEF Supply
Supply DEF FAN
Digital input
Digital input FAN
S3 ALARM

9 Slave relay 10
To controller

S2-DEF COOL S1-TEM COOL

S1-TEM FAN Supply DEF


Supply
DEF S2-DEF
FAN
HOJA TÉCNICA 1400H101 Edición 01 (03 de 08) www.ako.es

REFERENCES AND SPECIFICATIONS

Wall mounting installation Installation with the slave relay for Panel mounting installation
DIN 43880 rail mounting

REFERENCES: SPECIFICATIONS
AKO-14012 Thermometer 12/24V 1 • • • •
AKO-14023 Thermometer 230V 2 • • • •
AKO-14031 Thermometer 230V 2 • • • •
AKO-14112 1 Relay 12/24V 3 • • • • •
AKO-14123 1 Relay 230V 4 • • • • •
AKO-14128 1 Relay 230V 5 • • • • •
AKO-14129 1 Relay 230V 4 • • • • •
AKO-14212A 2 Relays 12V 6 • • • • • • • • •
AKO-14223 2 Relays 230V 6 • • • • • • • • •
AKO-14312B 3 Relays 12V 7 • • • • • • • • • • •
AKO-14323B 3 Relays 230V 7 • • • • • • • • • •
AKO-14412 4 Relays 12V 8 • • • • • • • • • • • • •
AKO-14423 4 Relays 230V 8 • • • • • • • • • • • • •
AKO-14530+AKO-15128 230V 9 • • • • • • • •
AKO-14602 Thermometer 230V 2 • • • •
AKO-14610 1 Relay 230V 4 • • • • •
AKO-14632 3 Relays 230V 10 • • • • • • • •
SPECIFICATIONS
Diagram for previous page
2 Digits, from -50ºC to + 99ºC
3 Digit decimal pt. from -49,9ºC to 99,9ºC
Sensor 1, NTC 1,5m included, non-adjustable
Sensor 1, NTC 1,5m included, adjustable
Sensor 2, NTC not included
Sensor 3, NTC not included
Power supply 12 ± 20%, 50/60Hz
Power supply 12/24 ± 10%, 50/60Hz
Power supply 230 ± 10%, 50/60Hz
Relay 1, Control (compressor) R 8(3)A, 250V, cos ϕ=1, SPST
Relay 1, Control (compressor) R 8(3)A, 250V, cos ϕ=1, SPDT switch
Relay 1, Control (compressor) R16(4)A, 250V, cos ϕ=1,
Relay 1, Control (compressor) R16(4)A, 250V, cos ϕ=1, SPDT switch
Relay 1, Control (compressor) R20(6)A, 250V, cos ϕ=1,
Relay 1, Control (compressor) R 30 max.18(5)A, 250V, cos ϕ=1, SPST
Relay 2, Defrost or fans R 8A, 250V, cos ϕ=1, SPDT switch
Relay 2, Defrost R 8A, 250V, cos ϕ=1, SPDT switch
Relay 2, Defrost R 8A, 250V, cos ϕ=1, SPST
Relay 3, Fan R 6A, 250V, cos ϕ=1, SPST
Relay 3, Fan R 8A, 250V, cos ϕ=1, SPST
Relay 4, Alarm R 6A, 250V, cos ϕ=1, SPST
Internal acoustic alarm
Digital input (for voltage-free contacts)
Real time clock
Communications conector
HOJA TÉCNICA 1400H101 Edición 01 (04 de 08) www.ako.es

REFERENCES AND PROGRAMMABLE PARAMETERS

AKO-14412, AKO-14423 4 relays, up to 3 sensors Compressor + Defrost + fans + Alarms


AKO-14312B, AKO-14323B 3 relays, up to 2 sensors Compressor + Defrost + fans
AKO-14530, AKO-14632 3 relays, up to 2 sensors Compressor + Defrost + fans
AKO-14212A, AKO-14223 2 relays, up to 2 sensors Compressor + Defrost by electric heat or air
AKO-14112, AKO-14123, AKO-14128, AKO-14129, AKO-14610, 1 relay, 1 sensor Defrost by compressor stop
AKO-14031 Adjustable thermometer
AKO-14012, AKO-14023, AKO-14602 Thermometers
PARAMETERS VALUES
REFRIGERATION (Compressor) Min. Def. Max.
C0 Sensor 1 calibration (Offset) -20ºC 0ºC +20ºC • • • • • •
C1 Sensor 1 differential (Hysteresis) 1ºC 2ºC 20ºC • • • • •
C2 Set point upper limit ( it cannot be set above this value) xxºC 99ºC 99ºC • • • • •
C3 Set point lower limit ( it cannot be set below this value) -50ºC -50ºC xxºC • • • • •
Compressor protection delay type:
C4 0 0 1 • • • • •
0=OFF/ON (from de last to switch-off) 1=ON (at swicht-on)

C5 Protection delay time (value for the option selected for parameter C4) 0min 0min 99min • • • • •
"COOL" relay status with faulty sensor 1 (1 relay equipment)
C6 0 0 1 •
0=OFF/ON (average last 24 hours) 1=OFF/ON (to C7 and C8 program)

"COOL" relay status with faulty sensor 1 (2, 3, 4, relay equipment)


C6 0=OFF 1=ON 2=OFF/ON (to C7 and C8 program) 0 1 2 • • • •

"COOL"relay (compressor) ON time in in case of sensor 1 failure


C7 if C7=0 and C8 0, the relay will always be OFF de-energised
0min 10min 99min • • • • •
"COOL"relay (compressor) ON time in in case of sensor 1 failure
C8 if C8=0 and C7 0, the relay will always be ON energised
0min 5min 99min • • • • •
DEFROST Min. Def. Max.
d0 Elapsed time between 2 starts (1 relay equipment ) 0h 1h 99h •
d0 Elapsed time between 2 starts (2, 3, 4, relays equipment ) 0h 6h 99h • • • •
d1 Maximum duration (1 relay equipment ) 0min 0min 99min •
d1 Maximum duration (2, 3, 4 relays equipment ) 0min 30min 99min • • • •
Type of message during defrost: (0=display the actual temp.)
d2
(1=display the defrost start temp.) (2=display the message dF or dEF) 0 2 2 • • • • •
d3 Maximum time of message added at end of defrost 0min 5min 99min • • • • •
d4 Sensor 2 final defrost start temperature (if it is programmed in P4) -50ºC 8ºC 99ºC • • • •
Defrost on equipment switch on:
d5 0 0 1 • • • •
(0=no, first defrost according d0) (1=yes, first defrost according d6)
d6 Defrost start delay on equipment switch-off if d5=1 0min 0min 99min • • • •
Defrost type: 0=Electric heat 1=Hot gas bypass
d7 0 0 1 • • • •
In 2-relay models for air defrosting, it is necessary to program F3
Time calculation between defrost periods:
d8 (0=Total real time) 1=Compressor operation sum) 0 0 1 • • • •
Drip time, compressor stop and FAN/R2 relay off when defrost ends
d9 0min 1min 99min • • • •
In 2-relay, R2 operates in all cases of P6
d10 1st defrost hour start time 0 off 23 •
d11 2nd defrost hour start time 0 off 23 •
d12 3rd defrost hour start time 0 off 23 •
d13 4th defrost hour start time 0 off 23 •
d14 5th defrost hour start time 0 off 23 •
d15 6th defrost hour start time 0 off 23 •
FANS (Evaporator) Min. Def. Max.
F0 Sensor 2 fan stop temperatures (if it is programmed in P4) -50ºC 4ºC 99ºC • • • •
Sensor 2 (F0) differential for switching the FAN/R2 relay
F1 1ºC 2ºC 50ºC • • • •
A1 and A2 Differential In 2-relay models if P6=1 and P4=1
F2 Stop fans if compressor stops? (0=no) (1=yes) (In 2-relay if P6=1) 0 0 1 • • •
F2 Stop fans if compressor stops? (0=yes) (1=no) 0 1 1 •
F3 Fan status during defrost (0=stopped) (1=running) 0 0 1 • • •
F3 Fan status during defrost (0=running) (1=stopped) 0 1 1 •
F4 Start-up delay after defrost (applicable if greater than d9) 0min 3min 99min • • • •
F5 Stop fan if door opens? (0=no) (1=yes) 0 0 1 • • •
HOJA TÉCNICA 1400H101 Edición 01 (05 de 08) www.ako.es

REFERENCES AND PROGRAMMABLE PARAMETERS

AKO-14412, AKO-14423 4 relays, up to 3 sensors Compressor + Defrost + fans + Alarms


AKO-14312B, AKO-14323B 3 relays, up to 2 sensors Compressor + Defrost + fans
AKO-14530, AKO-14632 3 relays, up to 2 sensors Compressor + Defrost + fans
AKO-14212A, AKO-14223 2 relays, up to 2 sensors Compressor + Defrost by electric heat or air
AKO-14112, AKO-14123, AKO-14128, AKO-14129, AKO-14610, 1 relay, 1 sensor Defrost by compressor stop
AKO-14031 Adjustable thermometer
AKO-14012, AKO-14023, AKO-14602 Thermometers
PARAMETERS VALUES
ALARMS (Visual, acoustic or relay) Min. Def. Max.
A1 Maximum, ºC above the Set Point in sensor 1 0=off 0=off 99ºC • • • •
A2 Minimum, ºC below the Set Point in sensor 1 0=off 0=off 99ºC • • • •
Start-up temperature alarm delay
A3
(if programmed in A1, A2) 0=off 0=off 120min • • • •
A4 Temp. alarm delay from end of defrost 0=off 0=off 99min • • • •
A5 Temp. alarm delay from the temperature at which they operate 0=off 30min 99min • • • •
A6 Temp. alarm delay from digital input disable (door if P9=1) 0=off 0=off 126min • • •
A7 Temp. alarm delay from digital input enable (door if P9=1) 0=off 0=off 126min • • •
A8 Alarms if defrost ends for maximum time: (0=no ) (1=yes) 0 0 1 • • •
Relay 4 alarm polarity configuration:
A9
(0=with alarm relay ON) (1=with alarm relay OFF ) 0 0 1 •
OTHER FEATURES Min. Def. Max.
P0 Type of operation: (0=Cold) (1=Heat) 0 0 1 •
P1 Relay for all function on power supply switch on 0min 0min 99min • • • • •
P2 Programmed parameter block : (1=yes, block) (0=no, unblock) 0 0 1 • • • • •
P3 Initial parameters: (1= yes, configure to "Def" and exit progr.) 0 0 1 • • • • •
Connected sensors: (1=Sensor 1) (2=Sensor 1+Sensor 2)
P4
(3=Sensor 1 +Sensor 2 +Sensor 3)
1 2 3 • • •
P4 Connected sensors: (0=Sensor 1) (1=Sensor 1+Sensor 2) 0 1 1 •
P5 Adress for equipment with communication 0 0 126 • • •
Relay 2 (R2) function:
P6
(0=defrost by electric heat) (1=fan control) 0 0 1 •
P7 Temperature display mode: (0=Whole) (1=One decimal) 0 0 1 • • •
P8 Displayed sensor: (1=Sensor 1) (2=Sensor 2) (3=Sensor 3) 1 1 3 • • •
P9 Digital input configuration: (0=disabled) (1=door) (2=external alarm) 0 0 2 • • •
P10 Contact with open door or disabled alarm: (0=open) (1=closed) 0 0 1 • • •
P11 Transfer parameters: (0=disabled) (1=send) (2=receive) 0 0 2 • • •
P12 Program version (information) • • •
r1 Clock configuration, Hour 0 x 23 •
r2 Clock configuration, Minute 0 x 59 •
EP Exit programming • • • • •
MESSAGES
Fixed - Indicates defrost is being carried out. In order to display “dF” o“dEF”
dF
when defrosting, it is essential that parameter d2 is set to option 2.
• • • • •
AE Intermittent with temperature- External alarm (if P9=2) • • •
Intermittent with temperature- The sensor 1 temperature is between 99ºC< temp.<110ºC
AH
or exceeds the parameter temperature programmed in C2 •
AH Intermittent with temperature- The sensor 1 temperature exceeds that programmed in A1 • • • •
AL Intermittent with temperature- The sensor 1 temperature is lower than that programmed in C3 •
AL Intermittent with temperature- The sensor 1 temperature is lower than that programmed in A2 • • • •
Ar Intermittent with temperature- Low-charge clock battery or non-programmed clock alarm •
E1 Sensor 1 failure (open circuit, crossed, temp.> 110ºC ó temp.<-55ºC) • • • • • •
E2 Sensor 2 failure (open circuit, crossed, temp.> 110ºC ó temp.<-55ºC) • • • •
E3 Sensor 3 failure (open circuit, crossed, temp.> 110ºC ó temp.<-55ºC) •
E5 Incorrect sensor configuration ( see P4, P8 ) • • •
EE Memory failure • • • • • •
Messages E2 and E3 are displayed if P4 has been suitable programmed. Equipment operation under
these conditions is the same as if P4 had been programmed with option 1 • • • •
HOJA TÉCNICA 1400H101 Edición 01 (06 de 08) www.ako.es

FRONT PANEL FUNCTIONS

Increase button - When the key is pressed for at least 5 seconds, it displays
-When pressed for at least 5 seconds, a manual defrost is the current SET POINT and LED 2/PR flashes.
started with programmed duration.
- Pressing the or keys permits the SET POINT to be adjusted
-In programming, it increases the value being displayed. to the required value.
-In 2, 3 and 4 relay models, it cancels the alarms, but they
remain displayed. - Pressing the and keys simultaneously sets the new value.
When this operation is carried out, the display will return to the
current temperature and LED 2/PR will cease flashing.
Decrease button
-When pressed for at least 5 seconds, it displays the SET Adjusting thermometer ref. AKO-14031 calibration
POINT temperature value.
-In programming, it decreases the value being displayed. Pressing the two keys simultaneously for at least 10 seconds dis-
plays the calibration value (default = 0ºC). Each press of the keys
-In 2, 3 and 4 relay models, it cancels the alarms, but they or will change the temperature display by 1ºC between -20ºC
remain displayed. and +20ºC. The two keys should be pressed simultaneously again
in order to accept the new value.
MODELS WITH 1 RELAY:
LED 1 Increase button PARAMETERS
LED 2 The parameters should only be programmed or modified by
personnel who are fully conversant with the operation and pos-
PRG sibilities of the equipment.
ºC SET
LEVEL 1 PARAMETERS:
Decrease button - Pressing the and keys simultaneously for at least 10 seconds
will cause LED 2/PR to indicate the programming phase and the
LED 1 Permanent: Indicates defrost in operation. first parameter “C0” will appear on the display.
LED 2 Permanent: Indicates compressor relay is ON. - Pressing the key accesses the next parameter and the key
Flashing: Set Point or parameter programming phase. will produce a return to the previous parameter.
- If the and keys are simultaneously pressed in the last para-
MODELS WITH 2, 3 AND 4 RELAYS: meter “EP”, the controller will return to the temperature display
situation and the LED 2/PR will cease to indicate the program-
LED PR LED DT
ming phase
PR DT Increase button
LEVEL 2 VALUES:
LED COOL
- In order to display the current value of any parameter, the keys
LED FAN and keys should be simultaneously pressed with the required
PRG
LED DEF parameter selected. Once it is displayed, it can be modified by
ºC SET
LED ALARM pressing the or keys.
Decrease button - Pressing the and keys simultaneously sets the new value.
When this operation is performed, the programming returns to
LED DT Permanent: Indicates last defrost ended by time. Level 1 (parameters).
LED PR Flashing: Set Point or parameter programming NOTE: If a key is not pressed for 25 seconds in any of the previous
phase. steps, then the equipment will automatically return to the current
LED COOL Permanent: Cooling relay COOL (compressor) temperature display situation without modifying any of the values.
energised.
Flashing: Because of the temperature detected
by Sensor 1 (TEM), the COOL relay CURRENT LEVEL 1 LEVEL 2
should be energised, but is not due to TEMPERATURE PARAMETERS VALUES

a programmed parameter.
10 Sec.
LED FAN Permanent: FAN relay energised.
Flashing: Because of the temperature detected SIMULTANEOUSLY SIMULTANEOUSLY SIMULTANEOUSLY

by Sensor 2 (DEF), the FAN relay


THE NEW
CHANGE
DISPLAY

ACCEPT
VALUE

VALUE

should be energised, but is not due to


a programmed parameter
LED DEF Permanent: Indicates defrost in operation.
LED ALARM Permanent: ALARM relay energised (or acoustic CURRENT NEW
VALUE VALUE
alarm).
Flashing: Alarm detected, relay de-energised,
but display maintained.

PROGRAMMING

ADJUSTING THE SET POINT TEMPERATURE


The factory default value is 0ºC.
5 Sec.
TEMPERATURE

SIMULTANEOUSLY
SET POINT
CHANGE
CURRENT

THE NEW
ACCEPT

DISPLAY CURRENT NEW SET EXIT


SET POINT SET POINT POINT PROGRAMMING
HOJA TÉCNICA 1400H101 Edición 01 (07 de 08) www.ako.es

PARAMETERS TRANSFER SERVERS

AKO-14911 AKO-14916 AKO-14918


This is connected by means of the AKO-80018, Tabletop server which is connected by A portable server without supply to which,
230/12V, to the power supply and it is pro- means of the AKO-80018, 230/12V, to the the parameters programmed in powered
grammed with the parameters that can be power supply. Permit to transfer parame- units with communication connector can
transferred to the AKO-14112 and AKO- ters previously recorded in one server AKO- be copied. The parameters may then be
14123 units without these having to be po- 14918, to the other controllers with com- transferred from the server to other identical
wered. munication connector without these having powered units.
to be powered.

230V Supply 230V Supply


AKO-80018 AKO-80018
AKO-14918
AKO-14918
AKO-14911

AKO-14916

Programming

Transfer Transfer Transfer

Power supply

Programming
AKO-14XXX AKO-14XXX
AKO-14112 AKO-14123 With communication connector. With communication connector

COMMUNICATION

The units provided with a communications PC type


connector, permit data transmission and computer
AKO-80021
reception using the standard MODBUS RS232/RS485
protocol and to carry out management from converter module
PC software. This makes a centralised
system for display, logging, alarms, remote
teleprocessing … RS485 RS232

AKO-5003 RS485
Software for controllers and data loggers
RS485
using a PC type computer.
AKO data loggers with
MODBUS communications
On request protocol and RS485 output
software with:

External alarms by
telephone, fax or internet. RS485 CMOS
Display boards.
Power management.
AKO-14917 AKO controllers
PLC management. CMOS/RS485 with MODBUS
converter module communications protocol
Remote teleprocessing.

RS485 CMOS

Up to 126 units and 1200m length.


When over 32 units are installed the
appropriate repeaters are needed.
HOJA TÉCNICA 1400H101 Edición 01 (08 de 08) www.ako.es

ACCESSORIES DIMENSIONS

Front protector Wall mounting

35
Ø7
37
11 60

Ø4
79
AKO-14910

120
In transparent plastic for 3 14
panel mounting units
17
Sheath for housing sensors in tanks
detail of fixing
23
140
screw holes
10
37 80
Ø8

Gas1/2" thread DIN rail slave relay


AKO-155908
Stainless steel material
Power supply transformer
47 34
Ø3

90
50,5
58

AKO-15590
120-230/12V, 3VA
Power supply converter 70 58

Panel mounting
90

AKO-15589 17 58
, 6VA
33

14 to 30 /12
Sensor extension cable
75 61,5
28,5

AKO-15586
3 x 0,5mm2 cable with insulation
+ copper braid + PVC sheath. 70,5

NTC Sensors

AKO-14901 L=1,5m
AKO-14902 L=2,0m
Ø6

AKO-14903 L=3,0m
AKO-14906 L=6,0m L 14

Modified polyolefin sheath and cable


Tapered probe NTC sensor
Ø3

Ø5

100 mm
3m 190 mm
AKO-14915
Stainless steel tapered probe with 3m silicone cable

351400101 REV. 00 2002 D.L.: 41303-2002 Nos reservamos el derecho de suministrar materiales que pudieran diferir levemente de los descritos en nuestras hojas técnicas.