Erreka Premis Swing Manual 2017 With SSS-5M1 Safety Sensors
Erreka Premis Swing Manual 2017 With SSS-5M1 Safety Sensors
Design with
Quality in mind
INDEX:
MECHANICAL SECTION
2
ELECTRONIC SECTION
3
GENERAL SAFETY WARNINGS
Carefully read this instruction manual for the safe installation and operation of the automatic door.
Improper installation and incorrect use of the product could cause serious injury.
Keep the instruction manual for future reference.
The installer must provide all the information about operation and provide the system user with the user manual delivered with the
product.
MEANING OF THE SYMBOLS USED IN THESE INSTRUCTIONS
DANGER: Indication of dangerous situations that could cause material damage and personal injury.
WARNING: Identifies the procedures that must be understood and followed to prevent product damage or malfunctions.
The mechanical and electric installation must be performed by specialised personnel in accordance with current directives
and regulations.
The installer must make sure that the structure to be automated is stable and robust and if necessary, make it this way by making
structural modifications.
Keep product and packaging materials out of children's reach, as they might be a source of danger.
Do not let the children stay or play within the range of the door.
This product was designed and built exclusively for the purpose described in this documentation. Any other use that is not specifically
indicated could adversely impact the condition of the product and the safety of people.
ADSF accepts no responsibility for incorrect product installation and usage, as well as for any damages caused by changes made
without its prior consent.
ADSF is not responsible for the construction of the fixtures to be motorised.
The IP31 degree of protection requires that the operator is installed only on the inner side of buildings.
This product cannot be installed in explosive environments or atmospheres, or in the presence of flammable gases or fumes.
Make sure that the characteristics of the electric distribution network are compatible with the technical data indicated in this manual
and that upstream of the system there is an omnipolar switch with an opening distance of the contacts of at least 3mm and a residual
current device.
Connect the ground conduit of the electric system.
The automatic door must be checked, started up and tested by skilled and well-prepared personnel.
A technical dossier must be prepared for every automation as required by the Machine Directive.
Disconnect the power supply before working on the automation and before opening the cover.
Maintenance is of fundamental importance for the proper operation and safety of the automation. Check the efficiency of all parts every
six months.
Use only original spare parts for maintenance and when replacing product components.
Cleaning operations must be performed with the power supply disconnected, using a damp cloth. Do not deposit or let water or other
liquids penetrate into the operator or the accessories that are part of the system.
Risk assessment
The automatic swinging doors must be designed and installed in a way to protect users against the risk and danger of crushing, impact
and shearing between the door and adjacent parts near the door.
The person responsible for starting-up the automation must perform a risk assessment based on the place of installation and the type
of users that could use the automatic door.
The operator can be adjusted in order to satisfy the Low energy requirements (movement force and speed control),
as indicated by standard EN16005; however, if the door will be used by the elderly, children or disabled individuals,
protective devices (sensors) that comply with standard EN12978 must be installed.
The dangers of crushing and shearing related to the secondary closing edge must be prevented
either structurally or by supplementary protective measures (rubber covers, for example).
Any residual risks must be properly signalled.
4
1) MODEL DESCRIPTION
The operators have an electro-mechanical motor for opening the pedestrian swing doors.
Depending on the type of operator, reclosure is performed with a spring or a motor.
The electronic control equipment is located inside the operator.
A list of the operator models for swinging doors produced by ADSF is provided below:
• PREMIS - 120
with reclosing spring, for maximum leaf weight of 120 Kg.
• PREMIS - 250
with reclosing spring, for maximum leaf weight of 250 Kg.
All operator models can be used with a slide pull arm or with an articulated push arm.
The model is to be selected based on the weight and length of the door leaf, the type of reclosure (spring or motor-only) and if an
emergency battery is required.
The operator must be installed in indoor environments.
All models are reversible, therefore in the case of a power failure the door can be opened manually.
Before starting with assembly check the technical drawings in paragraph 5. A drawing of the application is provided for every type of
arm, with the installation dimensions and a chart that provides the weight limits based on the length of the door leaf, depending on the
operator model.
The technical data provided in the charts refers to a typical installation, but the data can be influenced by variables present in every
system, such as friction, environmental conditions, alignment of the leaf hinge, etc....
2) TECHNICAL SPECIFICATIONS
POWER SUPPLY 115/230Vac +/-10%, 50-60Hz
POWER 120W
POWER SUPPLY OF EXTERNAL ACCESSORIES 24Vdc, 1A
ELECTRIC MOTOR 24Vdc
OPERATOR DIMENSIONS (LxHxD) 550 x 110 x 120 mm
WEIGHT models Premis 120 - 250 9.5 Kg.
PROTECTION DEGREE IP31
AMBIENT TEMPERATURE -15°C +50°C
FREQUENCY OF USE continuous
LIMIT SWITCH AND ANTICRUSHING SAFETY encoder controlled
REACTION TO OBSTACLES reversal of direction
OPENING TIME for 95° 4 - 12 seconds adjustable
CLOSING TIME for 95° 5 - 15 seconds adjustable
PAUSE TIME 0 - 20 seconds adjustable
5
MECHANICAL SECTION
1 LOGIC CARD
2 PWN-T ELECTRICAL WIRING AND POWER SUPPLY CARD
3 RECLOSURE SPRING (models Premis 120 - 250
4 SPRING PRELOAD REFERENCE LINE
5 GEARMOTOR WITH ENCODER
6 MOTION TRANSMISSION SHAFT OUTPUT
7 INNER WIRING BETWEEN THE L-NEP and PWN-T CARDS
8 SPRING PRELOAD LOCKING SCREW
9 PLASTIC PLATE
10 TRANSFORMER
6
4 GENERAL SAFETY RECOMMENDATIONS
Only begin to install the actuator after you have carefully read this instruction manual.
Both the mechanical part and the electrical part must be installed in a perfectly workmanlike manner,
in compliance with the current laws in force. Failure to comply with these latter may result in danger
hazards for persons or property.
The installer must be a competent person who has been adequately trained. He must check to make
sure that the structure on which the actuator is installed is strong and stable. If necessary, structural
modifications must be made to strengthen it. The installer must also check that all zones where there
is a risk of crushing, dragging, shearing or other dangers, are protected by means of electronic safety
devices, safety freeboards or barriers. These devices must be installed in compliance with the current
laws and in a perfectly workmanlike way, also in relation to the place of use, the type of use and the
operating logic of the product. The forces developed by the complete system as it operates must
comply with the current standards and, where this is not possible, the zones affected by these forces
must be protected with electronic safety devices. Moreover, dangerous zones must be indicated, as
established by the current laws in force.
Before the actuator is connected, make sure that the electricity main possesses characteristics that are
compatible with those described in the technical specifications of this manual, and that there is a
differential circuit-breaker and adequate protection against overcurrents on the supply side of the
system. Remember to turn off the power supply before installing or servicing the actuator and
whenever the cover must be opened.
Electrostatic charges can damage the electronic components on the boards. Wear a grounded
antistatic bracelet if you must work on the electronic boards. Never place the hands or other parts of
the body in moving parts, such as belts, pulleys, gears, etc.
Servicing the actuator is of fundamental importance if the system is to operate correctly and safely.
The periodical check of the efficiency of all parts should be carried out every 6 months.
ADSF UK LTD declines all liability for improper installation or use of the product, or for damage
deriving from unauthorized modifications to the system. Only use genuine spare parts if
replacements or repairs are required. The manufacturer cannot be held liable for the way the doors or
gates to be automated are constructed, or for damages caused by failure to build the doors and gates
in compliance with good workmanlike techniques. Protection degree IP32 requires that the actuator
only be installed inside buildings.
ADSF UK LTD declines all liability for damage caused by assembly on the outside,
without adequate protections.
Always make sure that the product is in a good condition before it is installed.
This product cannot be installed in places with an explosive atmosphere or in the presence of
inflammable fumes or gases.
This product must be disposed of according to the current laws in force at the end of its useful life.
Do not leave parts of the product or its packaging within children’s reach, as they could become a
danger hazard. Do not stay within the range of the door and do not impede the door movement
voluntarily. Do not let the children stay or play within the range of the door.
7
6.0 ARMS
8
ARTICULATE PUSH ARM PREMIS L6
Make use of the articulated arm for automations that open toward the outside as seen from the operator side
69 106
261 220
50
0 ....250 mm
1) Fixing drawings available on request
150
120
100
50
Arm will extend up to 250mm for deep recess
mm
0 500 1000 1500
9
ARTICULATE PUSH ARM PREMIS L6
CABLE
PASSAGE
SLOT
Standard operator
Operator with battery module
For this application, please consider that the PWN-T wiring card board
must be on the hinged side of the door for a correct movement direction
when opening.
OPENING
DIRECTION UNUSABLE leaf length
and weight
10
STANDARD SLIDING PULL ARM PREMIS L5 OPEN IN
Make use of the sliding arm for automations that open toward the inside as seen from the operator side
(standard) 546
A 261
X=51.5 mm
23 123 115 115 123
69 106
18.5
12
X 0..200
A+C 9 mm
X=99.5 mm
20.5
261
150
120
100
50
mm
0 500 1000 1500
11
S6 DEEP RECESS 150mm - 250mm PULL SLIDING ARM OPEN IN
Make use of the bent arm for automations that open toward the inside as seen from the operator side
(standard)
A
X=51.5 mm
A+C
X=99.5 mm
150
120
100
50
mm
0 500 1000 1500
12
6) MOVEMENT TRANSMISSION ARMS
6.1) PREMIS S5 SLIDE PULL ARM
13
6.4) SLIDING GUIDE FOR PULL ARM
a) Fix the sliding guide (1) on the leaf through the holes (6-7),
following the dimensions indicated in the technical drawings in
paragraphs 5.1, 5.2, 5.3.
b) Insert the runner (3) for the pull arm tapered pin inside the sliding
guide.
c) Insert the striker (5) inside the sliding guide and fix it in the end
of stroke opening position using the dowel.
d) Position the cover casing (2) on the sliding guide (1).
e) Insert the two side panels (4) on the ends of the sliding guide.
14
6.6) PREMIS S5 PIVOT EXTENSIONS 50mm
Use the PREMIS S5 extension if a larger distance is required between the operator and the arm in comparison to what can be
obtained using the standard and premis tapered pins.
Couple the extension to the standard or PREMIS S5 tapered pin (depending on the distance to be reached, see the technical
drawings in par. 5).
For the assembly, follow the steps shown in the following figures:
couple the PREMIS extension with the tapered pin and insert the central screw (E), tighten the two M6 X 65 side screws (F),
insert the extension in the arm and tighten the two M6 X 20 screws (G).
E F G
15
7) PREPARING AND ASSEMBLING THE OPERATOR
Remove the operator from its packaging and remove the screws
retaining the cover.
Remove the aluminium cover from its seat, pulling it firmly upwards
and without applying pressure on the sides, if possible.
Identify the correct side for connecting the pin, based on the type of
arm used and the type of operator assembly. Carefully review the
technical drawings in paragraph 5.
Removing the spring preload locking screw would make the pulley
and gears move inside the operator, representing a hazard to
fingers or other body pars near the moving components.
Based on the arm to be used and the operator fixing position, refer
to the relative assembly table (par. 5.1 to 5.5), which indicates
where the holes must be made for the assembly of the operator and
the drive arm.
For arm assembly refer to paragraph 6.
To fix the devices use the screws and anchors suitable for the type
of support.
After fixing the operator and arm, follow the next steps for connecting
the arm pin to the shaft output of the operator .
There are wedges in the arm's tapered pin that must be perfectly
matched with those in the operator output shaft. These serve the
purpose of making sure that the arm's tapered pin always moves
together with the operator's motion transmission shaft.
Insert the arm's tapered pin in the operator output shaft making sure
that the wedges in the two parts are correctly matched and then
firmly tighten the screw fixing the arm's tapered pin.
During this operation, the operator and arm pulleys can move. Keep
fingers and body parts away from the moving components during
this operation and keep the leaf blocked manually.
17
Move the spring locking screw from the locked position to the free
position.
The door leaf is free to close due to the force of the spring.
Make sure that the door closes completely even when open only a
few degrees.
If leaf movement is regular along the entire stroke, both when opening
as well as when closing, continue with the electrical connections as
described in the electronic part section of the paragraph “Electric
connections”.
If the spring load must be increased or reduced, remove the arm
from the operator. This operation is described in the following
paragraph.
Spring locking
Move the spring preload locking screw from the free position to the
locked position, making sure that the screw is inserted in the pulley.
Insert the Allen wrench (6mm.) inside the hole of the tapered pin
without removing the arm rod.
Unscrew the arm's fastening screw, applying greater force in the
final phase in order to remove the tapered pin.
Repeat the steps described in par. 7.4, 7.5 and 7.6 to select the
spring reclosure force and to connect the arm.
18
10) HOW TO RESET THE SPRING PRELOAD (only for models PREMIS 120 AND 250 )
Read this paragraph only if the reclosing spring must be unloaded due to the failure to comply with the correct installation procedures.
b) Make sure that the manual program selector on the side of the
operator is located in the central “0” position.
e) Press and hold down the PS1 button (START) on the PWN-T
card, the control unit will beep 5 times and start the spring
loading manoeuvre.
If the spring goes beyond the level indicated by the red line during
the operation, it can be slowly unloaded by moving the manual
program selector to position I .
In position II , the spring is quickly rewound!
Keep fingers and body parts away from moving components.
f) Move the locking screw from the free position to the locked
position, paying attention that the screw is inserted in the
pulley.
g) After this operation, the initial set-up must be repeated (see
the INITIAL SET-UP paragraph).
19
ELECTRONIC SECTION
11) ELECTRIC ARRANGEMENTS
2 7
NOTE: 1
The grey part indicates the survey
zone of radar and sensors.
The number of cables and the
relevant section in mm is indicated
for every device.
4
8
3
9
The power supply line must be protected against short circuit and dispersion to ground.
On the power supply mains, provide for an omni-polar switch/selector with contact opening distance of at least of 3 mm.
Use self-extinguishing cables for electric connections.
Separate the mains power supply line from the very-low voltage line relative to control and safety accessories.
On the plastic side panels of the PREMIS operator there are the holes that must be broken open, through which the electric
cables must be inserted. The installer must make the power supply cable stable inside the operator and, particularly, limit the peeling of
cable primary sheath so that the air and surface distances are not reduced if a connector detaches from the terminal.
If operator is installed on a door leaf, perform electric connection by a branching box with suitable flexible unions and pipes, available on
the market.
20
Connector Block Not Supplied
273
12.1) EXAMPLE WIRING FULLY AUTOMATIC SYSTEM
21
273
12.2) EXAMPLE WIRING WITH HARD WIRE PUSH PADS
22
273
12.2) EXAMPLE WIRING WITH LARCO WIRELESS RECIVER
23
13) PWN-T POWER SUPPLY MODULE AND ELECTRIC WIRING
VOLTAGE CHANGE
115V 230V
GROUND
115/230V
OPEN
S12
In case of 230Vac mains voltage, put the 4-pole connector of the transformer primary in the J3 connector (230V) of PWN-T board (factory
setting).
In case of 115Vac mains power supply, put the 4-pole connector of the transformer primary in the J2 (115V) connector of PWN-T board.
TERMINAL BOARD M1
230 Vac power supply: phase to terminal F, neutral to terminal N, ground connection with terminal ground symbol.
Ground the operator by connecting the ground cable from the line to the Faston connector on the plate the PWN-T board is fastened to.
A cable, connected with ground terminal of PWN-T board, is connected with the second faston.
The electric line is protected by 2A fuse F1.
TERMINAL BOARD M2
Terminals 1-3-4
MANUAL PROGRAM SELECTOR, located on operator side panel (factory wiring):
closed contact on position I to terminal 1 (AUX1);
central contact to terminal 3 (common);
closed contact on position II to terminal 4 (AUX2);
For more information on the operating modes of manual program selector, refer to "Program selectors" paragraph.
Terminals 2-3
Input of SAFETY SENSOR FOR CLOSING, N.C. contact.
The operation of safety sensor for closing must be enabled by PREMIS S12 digital programmer (function F18 ON).
The activation during closing provokes the door reopening.
Terminals 5-7
Input of SAFETY SENSOR FOR OPENING, N.C. contact.
The operation of safety sensor for opening must be enabled by PREMIS S12 digital programmer (function F18 ON).
The activation during opening stops the door leaf movement; when the sensor deactivates, the opening restarts at low speed.
Terminals 6-7
OPEN input.
Input contact logic state can be selected as N.O. (default condition) or N.C. by PREMIS S12 digital programmer (function 30).
The activation allows opening the door of all operating programs. Ideal for emergency input signal.
24
TERMINAL BOARD M3
Terminals 8-11
EXTERNAL RADAR input, N.O. contact.
It controls the door opening.
It is not active when the program selector is on “Exit only” and “Night lock”.
Terminals 9-11
INTERNAL RADAR input, N.O. contact.
It controls the door opening.
It is not active when the program selector is on “Entrance only” and “Night lock”.
Terminals 10-11
START input, N.O. contact.
It controls the door opening , for stop /start function
It is not active when the program selector is on “Night lock”.
TERMINAL BOARD M4
TERMINAL BOARD M6
Terminal 25
TEST output for safety sensors set for monitoring.
For more information, refer to "Safety sensors" paragraph.
Terminals 26-27
AUX 3 input, N.O. contact.
It is enabled in applications with interlock (function F26 = ON and F29 = ON).
It controls the door opening in all operating programs.
For more information, refer to "Interlock system" paragraph.
Terminals 28-29
Open Collector output of door status, it activates with open door and deactivates with closed door.
Connect a max. 100mA charge between 29 (O.C.) and 28 (positive + 24V) terminals.
In Interlock function (F26=ON), terminal 29 is used for connection of interlock operation; for more information, refer to “Interlock
system” paragraph.
TERMINAL BOARD M7
TERMINAL BOARD M8
Terminals 18-19-20
Free contact of relay RL1 for electric lock connection; (18 = Common, 19 = N.O., 20 = N.C.).
CONNECTORS
25
14) LOGIC BOARD
PART DESCRIPTION
Connector J7 = PREMIS wiring for Master Slave communication in two-leaf swing door.
For more information, refer to "DOUBLE LEAF DOOR SET" paragraph.
Connector J8 = encoder wiring insertion.
Connector J10 = wiring of electric signals from connector J4 of PWN-T module.
Connector J11 = wiring of motor power supply from connector J5 of PWN-T module.
Connector J12 = insertion for EN/RF1 radio receiver.
For more information, refer to "EN/RF1 radio receiver" paragraph.
Jumper J13 = it selects the logic status of safety sensor monitoring signal.
For more information, refer to "Safety sensors" paragraph.
Connector J14 = motor wiring insertion.
Jumper J15 = it selects two speed levels for door closing without power supply.
For models PREMIS 120 and 250 with closing spring only.
Jumper J15 activated = low speed.
Jumper J15 deactivated = high speed.
Led 3 – Led 4 = display of encoder signals.
Led 5 = display of MP1 microcontroller operation (micro A):
led on = correct operation;
led off or slowly flashing = fault on logic board.
Buzzer = warning buzzer.
MP1 = microcontroller “A”
Mp2 = microcontroller “B”
SW1 = dip-switch for operator type selection:
1 OFF / 2 OFF = single leaf operator or Master operator in double leaf
1 ON / 2 OFF = Slave operator in double leaf
The S12 digital programmer is a tool necessary to the installer to configure the
operation of the automatic door and perform the set-up of operations, functions and
parameters, to perform system diagnostics and have access to events memory
containing information on automated device and its operation.
Access to the programming menu is protected by safety technical password so that
specialized and authorized personnel only can operate on the automated device.
The S12 digital programmer can also be used by the final user, but only for choosing
the operating mode of automatic door; the user can also select the preferred language
and set up a user password to prevent the use of digital programmer by unauthorized
persons.
For each subject-matter described in the following paragraphs the use of digital
programmer (hereinafter PREMIS S12) is explained in the specific case.
26
16) COMMISSIONING OF AUTOMATED DOORS (INITIAL SET-UP)
FOR SINGLE DOOR'S SEE PAGE 28
FOR DOUBLE DOOR SET'S SEE PAGE 55
After completing the mechanical installation and performing electric connections, manually shift the door leaf for its entire stroke, to ensure
that no friction appears on the movement.
SET-UP operation is compulsory to allow the operator electronic control unit to acquire stroke points.
When the set-up begins, the door must be closed and during the stroke learning cycle, no obstacle shall appear in the leaf movement area.
The PREMIS operator is equipped with a function allowing it to learn the position of the side wall during the initial set-up.
This function is useful as it allows to store the wall position at the end of the opening stroke, and as a consequence to precisely set the point
at which the tripping of the opening safety sensor causes the leaf to decelerate in the last few degrees of the opening stage.
It is important that you adjust the safety sensor detection field before starting the operator set-up cycle.
If the PREMIS operator controls a single-leaf automatic door, dip 1 and 2 on SW1 dip-switch of L-NEP logic board must be set on
OFF.
If two PREMIS operators are to control a double-leaf automatic door, refer to the“Double-leaf door set” paragraph..
Follow chapter 16.1 only if the digital programmer is new and powered for the first time.
Follow chapter 16.2 if digital programmer has already been used before.
use F2 and
Press EXIT * buttons to move the arrow in correspondence with the language desired.
Power the PREMIS operator by mains voltage, the control unit buzzer emits
some quick, short beeps.
The display signals the lack of communication between the S12 and operator control units
since the serial code of logic board is not stored on S12.
Press button for about 5 seconds to enter the general programming menu.
F1 button allows moving forward among menu symbols.
Select RS485 symbol.
Give a quick pulse to ENTER button to enter the “Serial communication setup”
section, see paragraph16.3.
The PREMIS S12 programmer automatically detects the presence of operator electronic control unit (fig. A) and stores the serial code of
the logic board (fig. B).
When acquisition of serial code is completed, the display must show the closed padlock symbol on letter M and open padlock on letter S, for
a single leaf door (fig. C).
Press EXIT button to exit “Serial communication set-up” section and enter the general programming menu.
27
16.4) INITIAL SET-UP FOR SINGLE DOOR OPERATION
From general programming menu, F1 button allows moving forward among menu symbols.
Select INITIAL SET-UP symbol.
Give a quick pulse to ENTER button to enter the “Initial setup” section.
In this section, F1 / F3 buttons allows selecting the function ON / OFF status, while
button allows moving to the following function.
Press F2 button to return to previous function.
28
Select ON only if a safety sensor has been installed on opening.
We recommend that you adjust the safety sensor detection field before starting the set-up, to
allow the operator to precisely store the position of any side wall.
29
16.5) FUNCTIONAL TESTING
Refer to “Program selectors” paragraph describing the selector types provided to select the automatic door operating mode.
To start an opening manoeuvre, give a pulse to PS1 button (Start) of PWN-T module or engage door opening devices.
Ensure that door opening and closing cycle is properly performed and that pulse organs and safety sensors operate; to adjust sensor
detection field, refer to the instructions delivered with the sensor.
The opening safety sensor detects the presence of any side wall at the end of the opening stroke thanks to the automatic learning function
during the initial set-up.
Should you need to change the optical adjustment of the safety sensor after performing the initial set-up of the operator, you can manually
change the opening safety sensor inhibition distance by editing the P03 parameter (see paragraph "Parameter setting").
During door movement, intermittent signals could be heard as emitted by the buzzer to indicate that the limit power delivered by operator has
been reached, especially if leaf dimensions and weight are close to the limits allowed.
A short noise signal by the buzzer during start in opening is to be considered as normal, as the pick-up phase is the moment requiring
maximum force.
Adjust the thrust power by P04 parameter of the S12 programmer (see . “Parameters setting” paragraph).
To deactivate the buzzer noise signal when the power limit is reached, set up F34 function to ON (see “Functions setting”).
The buzzer noise signal for almost the entire stroke means that the leaf exceeds the limits allowed or installation levels shown on technical
installation drawings are not met or frictions exist on the fixture; in this case, the movements of automatic door are difficult and the
opening/closing cycle could not be completed.
Impact safety: ensure that stop and reverse of moving direction are performed if the leaf movement is hindered.
The S12 programmer allows checking the inputs status to ensure proper operation of all devices connected with the PREMIS
operator.
To enter "Inputs diagnostics" while the automatic door operating program is shown on display, keep F2 button pressed for about 3
seconds.
F3 button is exclusively used with a double-leaf swing door; if an M appears on top right, MASTER input ports are displaying, in case of
an S, input ports concern SLAVE operator. A single touch on the F3 button switches from M to S.
In case of single-leaf automation, an M appears on top right.
The display shows the symbols of all operator inputs, with the relevant terminal number.
If an input is used, the corresponding symbol lights up with an arrow on a side.
External radar
Internal radar
Start
OPEN
AUX 3
unused
30
17) PROGRAM SELECTORS
The program selector allows the door user to select the operating mode.
The following can be used, according to the choice: manual selector integrated in the PREMIS, or thePREMIS S14 mechanical selector or
the S12 digital programmer .
Each program selector is described in details below.
The 3-position manual program selector is the basic solution provided for onboard operator.
The operation of this selector is enabled by F01 function OFF (default preset).
ELECTRIC CONNECTIONS
For any check on proper connection and operation of key mechanical selector, enter inputs diagnostics (see par. 16.5) to ensure
that different key positions correspond to activation of the following symbols:
and
= no active symbol
and
OPERATING MODE
Insert and rotate the key in the S14 selector to select the program desired.
The key can be taken out of the selector when in any position in order to prevent the work program from undesired changes.
31
17.3) PREMIS S12 DIGITAL PROGRAMMER – USED LIKE PROGRAM SELECTOR
The S12 digital programmer can be installed in the system and used by the user like a program selector, as an alternative to manual and
mechanical selector if you need a more complete tools in terms of functions and graphs.
To enable the S12 operation like a program selector, set up F01 function ON (see “Functions setup” paragraph).
Select the automatic door operating mode by pressing once the button.
Each time a button is pressed, it switches from a work program to the next one.
32
Operation of other buttons located on PREMIS S12 program selector panel
*
To activate pedestrian opening, press the button.
*
the symbol on the display indicates that the function is on.
In a double leaf door, the first leaf (Master) only opens if the opening command is given by
internal or external radar inputs.
The pedestrian opening only operates in bi-directional, single-direction and open door
automatic programs.
To deactivate pedestrian opening, press again the
* button.
For more information, refer to "Pedestrian opening" paragraph.
F2
Deactivation of step-by-step operation
Give a pulse to F2 button to deactivate the step-by-step operation previously activated by
F13 function ON (see para. “Functions setting”) and enable the door automatic closing.
Press F2 button again to activate step-by-step operation. Symbol F2 on display goes off.
F1
Door opening command
Press F1 button to open the door, but only in bi-directional and single-direction programs (if
F33 function OFF).
Press F1 button to open the door in all operating programs, both automatic and night lock (if
F33 function ON).
F3
It is only used in one MASTER / SLAVE double-leaf door automated device
F3 button has no function on the main work program selection screen, it is only used to
switch from MASTER to SLAVE and to check that communication between operators and
the S12 programmer is working properly.
Letter M is displayed on top right side when Master operator is selected, letter S appears
when Slave operator is selected.
If the system is working properly, door working program is displayed both with M and S, in
case of fail communication the message "NO COMUNICATION" is displayed for the non-
working-properly operator.
SCHEDULED MAINTENANCE
If the display shows the message "SCHEDULED MAINTENANCE", contact the authorized service
center to request maintenance on the system.
33
18) GENERAL PROGRAMMING MENU
To enter the general programming menu while the automatic door operating program is shown on display, keep button pressed for
about 5 seconds.
The programming menu consists of different sub-menus divided by subject (Diagram 1).
Select the section you want to have access to by using F1 button >> .
The menu icon selected is highlighted and the section title is shown on display top side.
To exit the general programming menu and return to the operating program view, press EXIT button.
DIAGRAM 1
F1 F1 F1 F1
» » » »
F1 F1 F1
» » »
34
19) FUNCTIONS AND REGULATIONS
To enter please digit the 10-digits technical password (for detailed information please check paragraph “Password management”
Push Button F2 = entering the setting for functions F (see paragraph “Functions Setting”);
Push Button = entering the setting for Parameters P (see paragraph “Parameters Setting”);
Push Button F1 = to run door opening;
Push Button F3 = it is used only in case of double leaf door application to set up the parameters on Master or Slave operator; letter M or S
displayed bottom right indicates which operator has been selected. Letter M will appear on display on top right position if
the automation is single leaf
Push Button = to return to the general setting menu.
In this section the display describes the scope of the selected function;
push button F1 is setting the function in OFF;
push button F3 is setting the function in ON;
push button F2 allows proceeding to the following function;
push button allows returning to the previous function;
OFF Choosing the program selector: manual built-in selector or mechanical key switch PREMIS S14
F01
ON Choosing the program selector: digital selector PREMIS S12
OFF Singe leaf door (just on display; repeat initial set-up in order to change it)
F02
ON Double leaf door (just on display; repeat initial set-up in order to change it)
OFF Master operator in double leaf door application (just on display; repeat initial set-up in order to change it)
F03
ON Slave operator in double leaf door application (just on display; repeat initial set-up in order to change it)
35
FUNCTION STATUS DESCRIPTION *' SLAVE
Active function if F01 = OFF. Operation mode for the manual built-in selector in position II
OFF
II= Night Lock program
F07
Active function if F01 = OFF. Operation mode for the manual built-in selector in position II
ON
II= Open Door program
For operators with battery = in case of power failure the door keep on working normally with battery power
OFF
supply
F08
For operators with battery = in case of power failure the door opens and remains open in Automatic Door
ON
program
Battery monitoring = in case of empty or damaged battery the control unit buzzer beeps prior to ten
OFF
following opening cycles
F09
Battery monitoring = in case of empty or damaged battery the door opens and remains open in Automatic
ON
Door program
For operators with battery = in case of power failure or with almost empty battery the door keep on
OFF
working normally
F10
For operators with battery = in case of power failure or with almost empty battery the door opens and
ON
remains open
Selecting the program "Night Lock" the door remains closed and can be opened just with the
OFF
OPEN input
F11
Selecting the program "Night Lock" the door opens and remains open for 10" before closing in order to
ON
grant escape from building
F14 Step by step function mode with separate commands. The external radar input activates door opening,
ON whereas the internal radar input activates door closure. The command input (Start, OPEN and LARCO
remote control) operate in standard mode
For double leaf door application: partial opening deactivated if key switch selector S14 is
OFF connected
F15 For double leaf door application: partial opening activated on Master leaf if key switch selector
ON S14 is connected (active function if F01=OFF). For further details please check paragraph "Pedestrian
opening"
Active function if F15=ON. Partial opening on Master leaf active with key switch selector S14 in
OFF program "Free manual door"
F16
Active function if F15=ON. Partial opening on Master leaf active with key switch selector S14 in
ON
program "Night Lock"
OFF For operators with spring closure: door closure is obtained just through spring power
F17 For operators with spring closure: motor is assisting the spring in door closure. This function is useful in all S
ON those cases where the only spring power is not enough to grant full door closure
(i.e. in presence of strong air flows or in case of other unfavourable conditions)
OFF Closure safety sensor input deactivated; if a closure safety sensor is not installed
F18 S
ON Closure safety sensor input activated; if a closure safety sensor is installed
36
FUNCTION STATUS DESCRIPTION *' SLAVE
OFF Opening safety sensor input deactivated; if a opening safety sensor is not installed
F19 S
ON Opening safety sensor input activated; if a opening safety sensor is installed
Test on closure safety sensor deactivated. For sensors without monitoring function carried out by the
OFF
automation control unit
F20 Active function if F18=ON. Test on closure safety sensor activated. For sensors with monitoring function
S
ON carried out by the automation control unit (cat. 2 / pl. c). For detailed information please check paragraph
"Safety Sensors Device"
Test on opening safety sensor deactivated. For sensors without monitoring function carried out by the
OFF automation control unit
F21 Active function if F19=ON.Test on opening safety sensor activated. For sensors with monitoring function S
ON carried out by the automation control unit (cat. 2 / pl. c). For detailed information please check paragraph
"Safety Sensors Device"
Active function if F20 or F21=ON. Safety sensor test with LOW logic level.
OFF For detailed information please check paragraph "Safety Sensors Device"
F22 S
Active function if F20 or F21=ON. Safety sensor test with HIGH logic level.
ON For detailed information please check paragraph "Safety Sensors Device"
Active function if F26=ON. Delayed door opening for 0,5" after opening command.
OFF Please check paragraph "Interlock System"
F27
Active function if F26=ON. Prompt door opening at opening command.
ON Please check paragraph "Interlock System"
OFF Active function if F26=ON. Standard function mode for the electric lock in interlock system
F29
Active function if F26=ON. Electric lock deactivated if both doors are closed in automatic program modes.
ON Please check paragraph "Interlock System"
OFF OPEN input configuration; normally closed contact. When a device with N.C. contact is installed
F30
ON OPEN input configuration; normally open contact. When a device with N.O. contact is installed
For double leaf application: in case of power failure the two leaves starts simultaneously in the first opening
OFF phase
F31
For double leaf application: in case of power failure the two leaves starts respecting the offset in the first
ON opening phase
37
FUNCTION STATUS DESCRIPTION *' SLAVE
OFF Internal and external radars are deactivated during closing phase in "Night Lock" program
F32
Internal and external radars are activated during closing phase in "Night Lock" program, causing the door
ON reopening
OFF Push button F1 of digital selector the S12 enables door opening only during automatic program modes
F33
Push button F1 of digital selector the S12 enables door opening both during automatic program modes and
ON during "Night Lock" program
OFF Activates buzzer warning relative to the reached motor power limit (please check paragraph "Functional Testing")
F34 S
ON Deactivates buzzer warning relative to the reached motor power limit
*' For double leaf swing door application. In the column Slave of the present spreadsheet, the functions marked with letter S, have to be
separately configured on Slave operator. All other functions not marked with letter S, have to be set on Master operator and are common for
both units.
38
19.2) PARAMETERS SETTING
P01 Fig.1 Opening speed. Increase this value for a faster door opening speed. S
P02 Fig.2 Closing speed. Increase this value for a faster door closing speed. S
Thrust power during opening. Increase this value for higher motor thrust power
P04 during opening (and closing if set closing by motor) cycle. S
Pause time, can be regulated between 0 and 60 seconds. It is the time in which the
P05 door remains open before closing.
Closing voltage at door closed. Increase this value to keep the motor thrust active
P06 with door close. S
Wind stop function at door closed. At 0% (default value) the function is disabled.
P07 Fig.5 Increasing this value the motor is applying an opposite force to wind strength in order to S
keep the door leaf closed.
Push & go. At 0% (default value) the function is disabled. Distance from where a door
P08 Fig.3 pushed by hand start to open automatically. Setting range between 2° and 15°. S
Final thrust for electric lock coupling (active if F04=ON). Increase this value for a
P09 higher leaf speed in the last closing phase so that an easier coupling to electric lock is S
enabled.
39
PARAMETER Ref. Drawing DESCRIPTION *'SLAVE
Closing stroke to release electric lock (active if F04=ON). At 0% (default value) the
P10 function is disabled. Increase this value to adjust the closing stroke power of 0,5 second S
closing before opening cycle. Used to easily release the electric lock.
Slowing down distance in closing. Slowing down distance in closing. Distance from
P13 Fig.2 where the leaf start the low speed in closing. Increase this value to adjust door leaf S
slowing distance.
Motor thrust distance during end closing (active if F17=OFF for spring closing
units). At 0% (default value) the function is disabled. Increase this value to adjust
P14 Fig.6 the range in which motor is activated to support door closing, especially in S
unfavorable conditions like strong air flows. By value 100% the motor is active for
the whole closing phase. The motor thrust power can be adjusted by parameter P15.
Motor thrust power in closing. (active if F17=OFF for spring closing units). At 0%
(default value) the function is disabled. Increase this value for higher motor thrust
P15 Fig.6 power during closing phase. In swing closing units, this parameter is active only when S
door closure is achieved with motor thrust.
Motor thrust time during end closing. Increase this value to adjust time during
P16 which the motor thrust is active in the last closing phase, thus overcoming any friction S
and achieving complete door closure. At value 100% time would be 1,5''.
Motor thrust during end opening. The defaul value (12%) is low in order to reduce
leaf juddering during end opening phase. This parameter value has to be increased in
P17 case of any difficulty in the last door opening phase and thus increasing motor thrust S
power.
Distance between leaf physical end stop and opening end-running. Increase
P18 this value to increase the gap between the physical end stop on the floor and the S
position of the leaf with the door full open. This setting can be adjusted for about 5°.
Leaf opening delay. For double leaf application. Increase this value to adjust opening
P19 delay between Slave and Master unit. This setting is necessary in case of overlapping
leaves. At minimum value 0% both leaves start opening at the same time.
Leaf closing delay. For double leaf application. Increase this value to adjust closing
P20 delay between Master and Slave unit. This setting is necessary in case of overlapping
leaves. At minimum value 0% both leaves start closing at the same time.
Assisted spring closure (active just if F17=OFF for spring closing units). Increase this
P21 value for higher thrust power, to granting the initial closing phase, in all those situations S
where the spring power is not enough to start closing process.
Push & close. If the door is manually pushed to close direction, an automatic
P22 Fig.3 closure is activated. Increase this value to adjust closing corner needed for door leaf to S
start automatic closing. Setting range between 2° and 15°.
40
PARAMETER Ref. Drawing DESCRIPTION *'SLAVE
Opening acceleration ramp: Increase this value for higher acceleration during
P23 opening cycle. S
Wind stop at door open. Increase this value to achieve a higher opposite force to wind
P24 Fig.5 direction in order to keep door open. S
Closing friction adjustment (for spring closing units). This parameter regulates the
P25 opposite force applied by motor toward a complementary pushing force toward closing S
direction. Increase this value to achieve a higher leaf resistance.
Safety sensor test time (adjustment enabled if F20 and/or F21=ON). This parameter
can be used only if safety sensors with test monitoring option checked by the control
P26 unit are installed and in case the default value 0% causes safety test failure. For further S
information please check paragraph "Safety Sensors".
Deactivation time for Interlock system in case that one of the door cannot close
properly (adjustment enabled if F26=ON). By 0% (default value) the function is disabled.
P27 Increase this value to achieve a higher time after which the interlock function is disabled
if one of the two doors cannot close due to high flow of person walking through it.
At value 100% time is 2 minute. Please check paragraph "Interlock system".
Assisted manual opening (just with spring closing units). Increasing this value to obtain
P28 a lighter manual opening. At minimum value 0% the assisted manual opening is not S
active.
This parameter allows you to select the number of cycles of opening/closing after which the
display of the program selector S12 show the message "SCHEDULED
MAINTENANCE ".
OFF (default), the message is not displayed.
P33
Select the number of cycles in dependence on the operations of the door and the conditions
of use:
8K (8000 cycles), 16K (16.000 cycles), 32K (32.000 cycles), 64K (64.000 cycles), 128K
(128.000 cycles), 256K (256.000 cycles), 512K (512.000 cycles).
*' For double leaf swing door application. In the column Slave of the present table, the functions marked with letter S,
have to be separately configured on Slave operator. All other functions not marked with letter S, have to be set on Master
operator and are common for both units.
41
The following drawings show the regulation areas of some parameters described in the spreadsheet in order to better understand its
purpose. In the spreadsheet the column “Ref. Drawing” is indicating the drawing number to be checked for any parameter for which a
relative drawing has been added.
0% B
100%
C A
100%
B
A
0%
A
C
A=Adjusting area of opening speed A=Adjusting area of closing speed A= Adjusting area of Push&Go controlled
controlled by P01 parameter controlled by P02 parameter by P08 parameter, before automatic
B= Adjusting area of slowing down B=Adjusting area of slowing down opening
distance controlled by P12 parameter distance controlled by P13 parameter B= Adjusting area of Push&Close
C= Adjusting area of approach speed C= Adjusting area of approach speed controlled by P22 parameter, before
A+C = Opening time A+C = Closing time
automatic closing.
50%
B 10%
1%
A = Area from where, if safety sensor in A= Intervention area of Wind Stop with Rate (in %) of intervention area, controlled
opening detect an obstacle, the door opens opened door. The opposing force is by P14 parameter, in which the motor
at low speed instead of stop moving
depending of potentiometer P03 value. controlled by P24 parameter. operated during closing stroke. Motor
B= Intervention area of Wind Stop with power can be adjusted by P15 parameter.
closed door. The opposing force is
controlled by P07 parameter.
42
20) LANGUAGE
Use F2 and
* buttons to move arrow to the language desired.
Press EXIT (SET) button to return to general programming menu.
WARNING!
It is recommended to change the default technical password and be very careful not to forget it.
It is a 5-character password used by the user to prevent unauthorized persons from having access to the S12 programmer and change the
work program.
Using a primary password is optional and must be enabled by system's owner.
Default preset primary password is “A-A-A-A-A”.
WARNING!
When enabling the password, be very careful not to forget the access combination.
It is a 5-character password that the system's owner may divulge to persons to be authorized to use the S12 programmer.
The service password only allows changing the automatic door work program.
Default preset service password is “A-A-A-A-A”.
To change the service password, it is necessary to have access by primary password.
Use
* button to move the selection arrow downward, F2 button to move the arrow upward.
43
21.1) HOW TO CHANGE THE TECHNICAL PASSWORD
• It is required to repeat the new password, so type the previous combination again.
• If the password typed is correct, “PASSWORD OK” is shown on display for one
second and the general programming menu is restored.
From this moment on, when having access to general programming to enter initial set-up, functions and adjustments, settings of
serial communication and maintenance section, the new password stored needs to be typed.
The password is not required afterwards, when toggling among sections without exiting the general programming menu.
If the password typed is not correct, “PASSWORD ERROR” is shown on display and the general programming menu is restored.
Type the new primary password, selecting a combination of 5 characters from the
letters A-B-C-D.
44
It is required to repeat the new password, so type the previous combination again.
If the password typed is correct, “PASSWORD OK” is shown on display for one
second, thus reverting to the PASSWORD MANAGEMENT section; through the
EXIT button the general programming menu is restored.
On the contrary, if the password typed does not match the previous one,
PASSWORD ERROR is displayed, thus reverting to PASSWORD MANAGEMENT
section. The procedure needs to be carried out again.
Type the new service password, selecting a combination of 5 characters from the
letters A-B-C-D.
It is required to repeat the new password, so type the previous combination again.
If the password typed is correct, “PASSWORD OK” is shown on display for one
second, thus reverting to PASSWORD MANAGEMENT section.
Pressing the EXIT button the general programming menu is available again.
If the password typed does not match the previous one, PASSWORD ERROR is displayed, thus reverting to PASSWORD MANAGEMENT
section. The procedure needs to be carried out again.
45
21.4) ENABLING USER (primary and service) PASSWORD USAGE
*
Press ON button to enable the user password usage and return to PASSWORD MANAGEMENT menu.
To return to work program view, press EXIT button twice.
From this moment on, whenever the user wants to access theS12 digital programmer to change the automatic door work program,
the primary or service password must be typed.
When the user decides to enable the password usage, it is recommended to change the combination of both primary and
service password.
Press OFF (F1) button to disable user password usage. To return to general programming menu press the EXIT button twice.
From this moment on, the access to the S12 digital programmer as program selector is free.
46
22) INFORMATION AND EVENTS MEMORY
The S12 digital programmer allows displaying information on automation and accessing to events memory, where fault errors are stored.
*
After displaying the automatic door work program, press button for 5” to enter the information area (Diagram 2).
ν
* button allows forwarding to the following information or event in events memory.
^ F2 button allows forwarding to the following information or event in events memory.
F3 button is only used with two-leaf swing door and the symbol on the top right side of display shows M if Master operator information is
displayed, or S if Slave operator is involved.
Every touch on F3 button allows shifting from M to S and vice versa.
In case of single-leaf automation, letter M is shown on the top right side of display.
F1 button allows shifting to events memory to display error messages and return to information area by pressing it again
EXIT button allows returning to main view of door work program.
DIAGRAM 2
F2 F2 F2 F2 F2
I1 I2 I3 I4 I5 I6
F1 F1 F1 F1 F1 F1
ERROR ERROR ERROR ERROR ERROR ERROR
F1 F1 F1 F1 F1
INFO INFO INFO INFO INFO
F2 F2 F2 F2
E1 E2 E3 E4 E5
The diagram shows the path for access to information and events memory display; texts in figures relate to the memory cells that appear on
the display in the left side when accessing the display of information or errors.
47
Refer to the following tables for a list of information and error messages.
INFORMATION AREA
Display opening/closing door cycles since last maintenance. This counter must be reset
I2 Partial cycles every maintenance by authorized personnel (See "Maintenance" chapter)
I3 Total cycles Display total opening/closing door cycles since first time operation.
I4 Release Micro "A" Display Micro "A" software release of logic board L-NEP.
I5 Release Micro "B" Display Micro "B" software release of logic board L-NEP.
The events memory stores the last 5 error messages in chronological order.
When all the 5 memory cells are full of messages, the following event stored shall be located in E1 cell, the other memory events are
shifted by one position and the event in E5 cell shall be deleted.
The events memory stores messages, divided into warnings and errors.
The errors stored are shown by symbol directly from main screen of work program; enter the events memory to show the relevant
message.
The warnings stored are not shown in the main screen of work program, but only stored in events memory.
48
MEMORY EVENTS
Message of warnings or errors that can be read by the digital programmer PREMIS S12 ( E1-E2-E3-E4-E5)
WARNINGS
SIMBOL SCREEN MESSAGE MEANING SOLUTION
Generic malfunction that caused a reset of There is an automatic recovery system in case of
RESET SOFTWARE the microcontroller. temporary malfunction.
The door detect an obstacle during the If the problem persists, check if there is any obstacle
OBSTACLE IN OPENING opening cycle that caused the reversal that stop the door and remove it, or control the
direction of the leaf. smoothness of the leaf.
The door detect an obstacle during the If the problem persists, check if there is any obstacle
OBSTACLE IN CLOSING closing cycle that caused the reversal that stop the door and remove it, or control the
direction of the leaf. smoothness of the leaf.
ERRORS
SIMBOL SCREEN MESSAGE MEANING SOLUTION
The system automatically resets and, after a few seconds,
The cyclical testing of the detection circuit
FAULT CURRENT current has failed. repeat again the test. If the problem persists it is a defect
on the logic board .
The control of the driving signal of the motor The system automatically resets and, after a few seconds,
FAULT POWER has detected a fault. repeat again the test. If the problem persists it is a defect
on the logic board .
ERROR ENCODER Encoder signals are not detected or the Check that the cables and connector of the motor and
OR MOTOR motor does not turn. encoder are well inserted and not damaged.
The battery is damaged (only for operators Verify the efficiency of the battery and the control
FAULT BATTERY with battery module). module
The control of the braking during closing cycle The system automatically resets and repeat again the test
FAULT BRAKING in every cycle. If the problem persists it is a defect on the
has detected a fault.
logic board .
The communication line between master Check that the L7 cable is connected between
ERROR COMMUNICATION master and slave and that the configuration setting for
and slave is missing.
MASTER-SLAVE (with double door only) double swing unit is correct.
A fault is present on the slave operator. Access memory events on the slave operator and check
GENERAL ERROR SLAVE (with double door only) what type of problem is displayed.
49
23) MAINTENANCE
To enter, type 10-character technical password (for more information, refer to “Password management” paragraph).
Access to this section only for setting to zero the errors in the events memory, for setting to zero the partial counter of opening/closing cycles
performed by the door and for deleting the initial set-up performed when operation starts.
The reset of events memory and partial counter must be performed by specialized personnel only during routine maintenance, after
performing all checks on system operation.
To block the door in closing position, PREMIS operator is ready to drive an electric strike, an electric lock or an magnetic lock.
F06 = ON M7 M8
If automatic release of electric lock is required when door is closed, with the work
program mode set to “Manual”, so to predispose door to be opened manually.
If digital programmer S12 is used it's possible activate the automatic release
of electric lock at the end of closing stroke, also in the automatic work programs.
Push F2 button on S12 programmer to activate the function (F2 symbol
appear on display).
Electric lock
Push again F2 button on S12 programmer to disactivate the function (F2 24dc
symbol disappear on display). Electric strike
P09
Adjust the speed of the door in the last degrees of the closing stroke to facilitate electric lock coupling.
P10
Power during the 0,5 seconds of stroke on closing before opening to release electric lock.
At 0% value the function is disabled, between 01 to 100% the power increase proportionally.
P11
Delay between electric lock and motor activation in opening.
At 0% value the function is disabled, between 01 to 100% the power increase proportionally until 4 seconds.
50
24.2) MAGNETIC LOCK
In the working program “Manual” the magnetic lock isn't powered with door closed,
so to move door manually.
Activating “Push & Go” function (P08 parameter), the magnetic lock isn't powered
with door closed in the automatics working program to allow manually opening. It
work only in the “Night lock” program.
This section describes how to connect and configure properly some of the safety sensors in compliance with the standard EN12987
available on the market, to ensure a level of safety corresponding to PL = c, Category 2 as required by the standard EN16005.
For other option and settings available on F22 (S09) = OFF Test level LOW
the safety sensor, see the instructions supplied
with the sensor OA-EDGE-T.
SETTING ON THE BOARD
Jumper J13 = position P
51
25.2) SENSOR 4SAFE ON SW
DIP 1 = OFF Sensor installed closing side F20 (S07) = ON For safety sensor in closing
For other option and settings available on F22 (S09) = OFF Test level LOW
the safety sensor, see the instructions supplied
with the sensor 4SAFE ON SW.
SETTING ON THE BOARD
Jumper J13 = position P
Wiring between the sensor and the terminal block of the PWN-T board on PREMIS operator
The parameter 26 on digital programmer S12 adjusts the timing of testing of the safety sensor . In case of failure of safety test on
the sensor TOPSCAN-S may need to increase the value of this parameter.
The test of the safety sensors occurs at the beginning of each cycle of opening and closing of the door.
If the sensor does not respond properly to the test the buzzer on the operator control unit will beep, and the speed of the leaf will be slow (at
safety speed) for the entire cycle.
52
26) PREMIS S3 BATTERY MODULE
Electric connection
Connect the J1 connector of the the S3 module to the J6 connector of the PWN-T power supply unit through the special cables.
The battery cable must be connected to the J2 connector of the S3.
PWN-T
PREMIS S3
J6
J1
Connect the cable
from connector J1 to
connector J6 of the
operator
Operation
The PREMIS S3 module trips in case of mains power failure, allowing the PREMIS operator to keep running.
The battery operating time depends on various factors, like the number of operations performed, the leaf weight, the connected external
devices , etc....
As a rough guide, the charged battery can supply power for about 30 consecutive door opening/closing cycles, or for about two hours with
the door stopped.
IMPORTANT!
Enable this function by setting function F12=ON on the digital programmer S12.
The inputs suitable for use by disabled people must be connected to the START or OPEN input terminals.
Even the remote control combined with the LARCO radio receiver can be used as disable people input.
Adjust the pause time (parameter P05 on the digital programmer S12 ) to hold the door open for a sufficient time to allow the
disabled person to be able to pass through the door before the automatic closing.
If at the end of the opening cycle or during the pause time, the safety sensor in closing detects the presence of the disabled people,
the pause time is reduced to 3 seconds (even if is set at higher value) after which the door closes .
The door closes immediately without taking into account the pause time if the opening is activated by external radar input , internal
radar input or with a manual push if push & go function is enable.
53
INSTRUCTION MANUAL
PR110, PR112, PR114, PR116
6. Circuit diagram for your reference, All Premis models are Normally Open)
PR116
Learning key
Transmitter
LED F E D C B A + -
PR116
PR110
:
Learning rolling code
2. Press any button on key fob or push-pad. LED light on receiver will flash on and off
54
29) DOUBLE LEAF DOOR SET
To manage the operation of a swing door with two leaf two operators is needed, one must be configured as Master and the other must be
configured as a Slave.
In the case of overlapping leaf, the operator applied to the door leaf that overlap the other (the one that opens first) must be configured as
Master.
When double swing door with overlapped leaf is used as escape route too, the installer must check that force required to open the
door manually with the slave operator 's leaf ( with Master operator's leaf overlapped) not exceed 150 N , measured at the leading
edge at right angles to the door leaf and at a height of 1000 +/- 10 mm.
In case of force over 150 N only the leaf of the Master operator must be use as escape route and consequently the identification
symbol must be put just on this leaf."
Master and Slave operators must be connected together with the L7 Sync cable.
Connect the two terminals of the cable to connector J7 on the L-NEP logic card.
The digital programmer S12 must be connected to the Master operator.
WIRING CABLE
L7
OPERATOR MASTER OPERATOR SLAVE
SAFETY SAFETY
SENSORS SENSORS
POWER PROGRAM OPENING OPEN START
SUPPLY SELECTOR RADAR COMMAND COMMAND
LINE
ELECTRO-LOCK
MASTER SLAVE
WING 1 (MASTER) WING 2 (SLAVE)
After completing the mechanical installation and after that electrical connections are made, manually check that the movement of both
leaves is friction-free for all the stroke.
Before power up the operator set the switch SW1 on the logic board L-NEP as indicated on the following table.
55
Follow now the next steps to complete the operator set up.
2. If the digital programmer S12 has been used before, the display will show "No Communication”
because the new serial numbers of the operator's board L-NEP are not stored in the programmer.
Press and hold for about 5 seconds the SET push button to enter the general programming menu, and from there select the submenu
"Serial communication setting" (as indicated in par. 18).
If the digital programmer S12 is new and is powered for the first time, you will be required to choose your preferred language as
specified in paragraph 16.1, then you will automatically enter the "Serial communication setting".
The programmer S12 recognizes the presence of the two operators in the system (Fig. A) and acquires automatically the serial
number of the logic boards (fig. B).
At the end of the acquisition of the logic boards serial numbers, the display will show the symbol closed padlock on the icons with letters M
and S (fig. C) and the programmer will be able to manageboth master and slave operators.
Press EXIT (SET) push button to exit from “Serial communication setting” and come back to the general programming menu .
4. INITIAL SET-UP
From the general programming menu , enter in the “INITIAL SET UP” section (as indicated in par. 18)
Enter the 10 digits of the technique password to access the configuration set-up.
(for more information on using technique password, see the par. “Password management” 21 and 21.1).
In this section the push-button F1 / F3 set the OFF / ON state of the function.
With the push-button you go to the next function, with the F2 you return to the previous function.
56
The function S05 must be selected ON if a safety sensor in closing is installed.
Selecting this functionis valid for both Master and Slave operators.
The function S09 is displayed only if the function S07and/or S08 = ON.
Select the logical state of the test used to monitor the safety sensors.
The setting depends on the characteristics of the sensor.
Select OFF for sensors "4SAFE SW ON" or "OA-EDGE T.
Select ON for the sensor "TOP SCAN-S".
For more information, refer to par. "Safety sensor devices".
Configuration of the contact on the OPEN input between terminals 6-7 of the PWN-T board.
Select ON with normally open contact, or if you do not useOPEN INPUT.
Select OFF if you are using a device with a normally closed contact.
The Master operator starts opening at slow speed after 4 beeps of start signal. At the end of the opening cycle, a prolonged 3 seconds
beep, will signal the end of the Master operator set-up. The Master operator leaf remains opened to permit the set-up of the slave
operator.
The Slave operator starts opening at slow speed after 4 beeps of start signal. At the end of the opening cycle, a prolonged 3 seconds
beep, will signal the end of the Slave operator set-up.
The set-up is now completed, the closing cycle start automatically providing to close as first the slave operator and then after a delay
time the master operator.
57
29.3) FUNCTIONAL TESTING
Select the automatic operation of the door using the program selector.If you use the manual switch, set the program at state l.
Refer to par. "Program Selectors " that describe the types of selectors available to set the operating mode of the automatic doors.
To start an opening cycle give an impulse by the push-button PS1 (Start) on the module PWN-T of the Master operator, or operate the other
opening control devices ( as radar, mat, etc.).
Verify that opening and closing cycle takes place correctly.During the opening cycle the Slave leaf start with a predetermined delay with
respect to Master leaf, as well as in the closing cycle is that the Master leaf that start with a predetermined delay with respect to Slave leaf.
The delay between the leaves at the start is crucial to avoid that it can come across each other. To change the preset delay door go to "Switch
and potentiometer" and set: On the parameter P19 the desired value of delay in opening ; on the parameter P20 the desired value of delay in
closing (see par. 19.2 "Parameters setting").
Verify that the input device and safety sensors are functioning; to adjust the detection range of the sensors, refer to the instructions supplied
with the sensor.The detection of the opening safety sensor due to the arrest of the movement only of the leaf on which it is installed.
The detection of the closing safety sensor causes the inversion of the movement in opening of both doors.
During the movement of the door an intermittent buzzer sound may be hear. It's an indication that the limit power use by the operator it's near
the maximum available, Occur especially if the size and the weight of the leaf are approaching the limits permitted.
A short beep of the buzzer when leaf starting is to be considered normal because the inrush phase is the time in which it is required more
strength. Adjust the power stroke with parameter P04 by the programmer (par.19.2 see "Parameters setting").
Power stroke P04 must be set on both master and slave operators separately (see par. 19 "Functions and regulation").
To turn off the audible buzzer that signal the power limit, set the F34 ON (see par. "Functions setting"), in this case independently on the two
operators.
The sound of the buzzer for almost the entire cycle means that the leaf exceeds the permissible limits, or that the installation dimensions
given in the drawings of installation have not been met, or that are present to much friction on the frame, in which case the automatic door
has difficulty moving and may fail to complete the cycle of opening and
Safety in case of impact: verify that opposing an obstacle to the movement of a door, the operator stop and reverse the direction of travel of
both doors
Every time, after powering the system, the first cycle of opening occurs at slow speed and can be selected with the function F31 if the leafs
starts together, or starts respecting the leaf delay.
F31 = OFF in the first cycle of opening the doors start together.
F31 = ON in the first cycle of opening the doors start, respecting the leaf delay.
It is recommended to keep the default setting (F31 OFF) if the door is not provided with coordinator mechanical closure, which guarantees
the correct position of the doors during the manual closure in the absence of power.
The operation of set-up must be repeated in the case of variation of one of the following conditions:weight of the door, opening
angle of the leaf, spring loading, replacement of the logic board or the mechanical unit inside the operator
To repeat the set-up, follow the steps described in the previous section. 29.2 (points 4, 5, 6).
With a double door it's possible to select the pedestrian opening, in which only Master operator open.
If is installed the program selector S12 (F01 = ON), press the
* push-button to activate the pedestrian opening.
If is installed the manual selector switch or the mechanical key S14 (F01 = OFF), in order to activate the pedestrian opening is
necessary to set the F15 = ON.
Then you have to choose what position on the selector must be enabled pedestrian opening:
F16 = OFF: pedestrian opening in position 0 on the manual selector program.
pedestrian opening in position on the mechanical selector S14.
F16 = ON : pedestrian opening in position II on the manual selector program.
pedestrian opening in position on the mechanical selector S14.
58
29.5) CONSIDERATION ON THE USE OF PREMIS S12 PROGRAMMER IN A DOUBLE DOOR SYSTEM.
With the digital programmer it is possible to operate separately on operators Master and Slave as regards the following sections of
the programming menu and general area information.
pressing the F3 button you switch from Master to Slave and vice versa
Master operator Slave operator
b) MAINTENANCE
pressing the F3 button you switch from Master to Slave and vice versa
Master operator Slave operator
If the display shows the letter M on the S12 operations it's related to the Master, if display show letter S operation performed it's related to
the slave operator.
Also the informations and the events can be accessed individually.Once you enter in the information menu as described in par. 22, press the
F3 button to selected on which operator you want to display information and events.At the top right of the display will show the letter M if the
information regarding the Master operator, the letter S if they relate to the operator Slave.
pressing the F3 button you switch from Master to Slave and vice versa
Master operator Slave operator
In double leaf application, reset error log first on SLAVE (S) unit and then on MASTER (M) unit.
To reset error log, select “ERROR RESET” and press OK.
59
30) INTERLOCK SYSTEM
The interlock system is used when two automatic doors must open one at a time, so they must not open together.
AUX1 X X= D i s c o n n e c tmanual
COMUNE X selector from the terminals
AUX2 X AUX1, COMMON, AUX2.
F SWITCH F
ON/OFF
M2 AUX1 M2 AUX1
SEN./CL SEN./CL
COMMON COMMON
AUX2 AUX2
SEN./OP SEN./OP
OPEN OPEN
TEST COMMON TEST COMMON
M6 GND M6 GND
RAD.EX RAD.EX
AUX3 RAD.IN AUX3 RAD.IN
24V START 24V START
O.C. COMMON O.C. COMMON
M7 M3 M7 M3
- GND - GND
A A
M8 S12 M8 S12
B B
M4 +13V M4 +13V
OUT 24V LOCK LOCK OUT 24V LOCK LOCK
The figure show electrical connection between two independent operators in Interlock configuration.
Terminal 29 (O.C.) on PWN-T of door 1 must be connected at terminal 4 (AUX2) of door 2.
Terminal 29 (O.C.) on PWN-T of door 2 must be connected at terminal 4 (AUX2) of door 1.
Terminals 3 (Common) on both PWN-T must be connected to each other.
By connecting a switch (SWITCH ON/OFF) between the terminals 3 (COMMON) and 1 (AUX1) on both PWN-T, it is possible to disable
the Interlock function ( with the contact closed) and to re-enable the function ( with the contact open).
The use of this switch is optional, it is used only to disable temporarily the interlock detection and to allow the free passage between the two
doors.
To use Interlock functioning it's necessary to install digital programmer S12 as a program selector on each door.
It is not possible use the manual selector or mechanical selector with key S14.
EXTERNAL EXTERNAL
RADAR RADAR
INTERNAL
RADAR
Independent internal radar for each door is used when the distance between two doors is enough to not allow interference in detection from
both radar.
Set the function F26 = ON in both operators.
Select which of two doors firstly opening in case of simultaneous command on both:
F27 = OFF: Opening with 0,5 seconds of delay after command.
F27 = ON : Opening immediately after command.
Set function F27 =ON on the door which opens first, F27 = OFF on the other door.
60
Choose whether you want to store, or not, the opening control on the radar in a door when the other door still in movement.
F28 = OFF: disable storage opening command.
To open a door is necessary to activate again the radar when the other door is closed.
F28 = ON: enable storage opening command.
To open one of the two doors can activate the radar even when the other door still moving;
the opening will be automatically executed as soon as the door in moving stop in closed position.
It's possible to override the interlock function (one of the door open even if the other door has not yet closed) in case one door have it's
sensors activated for a time set by parameter P27. The interlock function come back to normal when the door arrived to fully close.
P27 = 0% : function is disabled and second door opening only after first closed.
P27 = 01% : second door opening after 10 seconds from first door open, if its radar is continuously detect.
P27 = 100%: second door opening after 2 minutes from first door open, if its radar continuously detect.
EXTERNAL INTERNAL
RADAR RADAR
START
COMMON DETECTOR
It's possible to use a single sensor that cover the common inside area to open the door. Connected the sensor in parallel at Start input in both
modules PWN-T of each operator, may be necessary when distance between two doors does not allow use of two independent radar.
61
31) MEANING OF THE ACOUSTIC SIGNAL
On the logic board is present a buzzer which emits acoustic signals, which corresponds to a meaning depending on the number
of beeps emitted and the duration of the sound.
5 BIP short Pressing the push button PS1 on the PWN-T board with the
operator without initial set-up and manual program selector in
position 0 (manual).
BIP extended For as long as you hold down the push button PS1 on the
PWN-T board, with operator without initial set-up and manual
program selector in position I or II.
4 BIP short Warning signal that door start to move slowly in the initial phase
of the cycle set-up.
Extended or blinking sound The limit of power that the operator is able to supply to the motor
(during movement) is exceeding during the movement of the leaf. This warning is
activated if the function F34 = OFF. To disable this acoustic
signal set F34 = ON
To guarantee and to keep a secure functioning in door's lifetime it recommended make maintenance every 6 months.
The installer can set the number of cycles of opening/closing after which on the programmer S12 shows the message "SCHEDULED
MAINTENANCE" (parameter 33).
Warning!
Before work on the operator cut main power line.
- Check that the door wing is stable and that the movement is fluent and with no friction from ”door open” position up to
“door closed” position.
- Check that speeds, timing, and safety functions are well adjust.
- Verify if door with spring closes at damping speed without power supply.
At the end of the maintenance reset the counter of partial cycles and reset the memory events (see paragraph 23 "MAINTENANCE")
Warning!
Any part that appear damaged or worn must be changed.
Make use only of original spare parts; for this purpose check price list.
62
WC System: Installation Instructions
Auto Door system:
Overview: Swing Door: the system is designed to leave the Door unlocked enabling
Manual or Assisted entry, when entering the facility the Door should be shut before
the “Touch to Lock” sensor will work therefore inhibiting pranksters. This is achieved
by a Normally closed Door status Micro-switch.
When incorporating a Sliding Door the additional Activate timer PCB can be
adjusted to keep the door open on entry until the “Touch to Lock” sensor is activated
to ensure the user engages the Lock.
NB: A link on the PCB enables Flashing or Solid status LEDs.
An Access control system may fitted to give a Secure Door scenario.
+ Ov Optional
Mag / Fail Safe Lock Key A B C
To Open
Contact Lock Switch A No C A Door on
C Nc Ov +V Nc C
B Nc Sounder Nc B operation
Break
CC No C
Glass
No C +V Ov L+ R BL C No
External Internal
C = 0v.
Removed
when Locked
Fit
Link
Re Ov C Nc No +V Re Ov C Nc No +V
Emergency Entry
Key
Switch
Controller
10 15
Cover B
1 Hinge
Power supply ( AC/DC 12~ PCB unit
Terminal 2 24[V] )
7
30 Block 3 Relay Output ( Common )
4 Relay Output ( Normal Open )
Screw Holes Wiring Hole PCB unit
3 - φ2.6 φ10
Wires to 1 5 Relay Output ( Normal Close )
the controller
Wire Sheath 6 TEST Input ( - )
Unit : [mm] Jamb Hole Wire
7 TEST Input ( + ) Cover Sheath
3. DIPSWITCH SETTINGS
Test Input With TEST Optical
B Without TEST Without TEST
Interference
SSS-5 SSS-5
EN16005
A
B
0v A B
To avoid cross interference between two
Wire as explained in section
2.2 above “”
A
0v sensors in close proximity different 2 2
1 frequency settings should be selected
Set Non-Detection
distance A
Door Leaf
6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8 6 7 8
EN16005
50mm 100mm 150mm 200mm 250mm 300mm 400mm 500mm
Check that the detection range
conforms to EN16005 A
5 Long Belt
6 Short Belt
7 Plastic closing
ADSF PREMIS 120 Standard swing door operators are suitable for a wide variety of applications (particularly for
external facing entrance doors) including: high volume, retail, trade, hotels, offices, airports, stations, hospitals,
schools, colleges, garden centres and leisure facilities. Low energy or fully automatic operation.
All equipment is designed to meet the rigorous safety requirements of BS 7036:1996 and is installed by
Automatic Door Suppliers Association (ADSA) accredited engineers. EN16005 Compliant 2014
As standard
Drive System
• Motor open Spring close
• Housed in 110mm high x 120mm deep x 550mm wide
Operation
• Over head face mounted
• Push arm to open out / Pull slide arm to open in
• Extended pivot available for operators mounted on lintel
• Push and go facility
Options
Safety & Security
• Interfacing with fire alarm via a relay
• Interfacing with BMS, audio/video /intercom entry systems via a relay
• Integration of electric locking facility (possible with optional locking module)
• Interlocking with other door types
TECHNICAL SPECIFICATIONS
POWER SUPPLY 115/230Vac +/- 10%, 50-60 Hz
POWER 50W
POWER SUPPLY OF EXTERNAL ACCESSORIES 24Volt dc
MAXIMUM WEIGHT OF DOOR WING 120Kg
WORK TYPOLOGY Intensive use
OPERATOR DIMENSIONS 550x120x110mm
WORKING TEMPERATURE -20°C / +50°C
ELECTRIC MOTOR 24Volt dc With Encoder
PROTECTION DEGREE IP32
NBS Specification
ADSF PREMIS 250 Heavy duty swing door operator
ADSF PREMIS 250 Heavy duty swing door operators are suitable for a wide variety of applications (particularly for
external facing entrance doors) including: high volume, retail, trade, hotels, offices, airports, stations, hospitals,
schools, colleges, garden centres and leisure facilities. Low energy or fully automatic operation.
All equipment is designed to meet the rigorous safety requirements of BS 7036:1996 and is installed by
Automatic Door Suppliers Association (ADSA) accredited engineers. EN16005 Compliant 2014
As standard
Drive System
• Motor open Spring close
• Housed in 110mm high x 120mm deep x 550mm wide
Operation
• Over head face mounted
• Push arm to open out / Pull slide arm to open in
• Extended pivot available for operators mounted on lintel
• Push and go facility
Options
Safety & Security
• Interfacing with fire alarm via a relay
• Interfacing with BMS, audio/video /intercom entry systems via a relay
• Integration of electric locking facility (possible with optional locking module)
• Interlocking with other door types
TECHNICAL SPECIFICATIONS
POWER SUPPLY 115/230Vac +/- 10%, 50-60 Hz
POWER 75W
POWER SUPPLY OF EXTERNAL ACCESSORIES 24Volt dc
MAXIMUM WEIGHT OF DOOR WING 250Kg
WORK TYPOLOGY Intensive use
OPERATOR DIMENSIONS 550x120x110mm
WORKING TEMPERATURE -20°C / +50°C
ELECTRIC MOTOR 24Volt dc With Encoder
PROTECTION DEGREE IP32
RETURNS NOTE
COMPANY NAME:
CONTACT NAME:
ADDRESS:
POSTCODE:
TEL:
FAX: E-MAIL:
Send to Auto Doors & Shopfronts UK LTD Unit 3 Millers Court, Windmill Road, Kenn, Clevedon BS21 6UL
Registered Office: 20 –22 Bedford Row, London WC1R 4JS. Registration No. 5287944 VAT No. 811346 362
MAINTENANCE PROGRAM
Each 6 month:
Warning!
Before work on the operator cut main power line.
- Check that the door wing is stable and that the movement is fluent and with no friction
from ”door open” position up to “door closed” position.
- Check that speeds, timing, and safety functions are well adjust.
Warning!
Any part that appear damaged or worn must be changed.
Make use only of original spare parts; for this purpose check price list.
Site Address
Date
Job No
Door Location
Door Type
Safety Devices
Photocells Y/N Photocell Height (mm) Presence Sensor On Door Safety Sensors
Escape System
Break Out Doors Y/N Break Out Force (N) Battery Back-Up Battery Settings (F-O / CONT)
Engineers Notes
www.adsf.co.uk
LOG BOOK
Operators Installed
Activation Devices
Sensor Push Pad Keyfob Access Control
Safety Devices
Threshold Sensor Side Screen Sensor On Door Sensor Barriers
Escape System
Break Out Doors Y/N Break Out Force (N) Battery Back-Up Battery Settings (F-O / CONT)
Manufacturer: ADSF Unit 3 Millers Court Windmill Road Bristol BS21 6UL
LOG BOOK