Frequency Converter with Direction

and Synchronization Monitor


KFU8-UFT-2.D
< 2-channel signal conditioner
< Universal usage at different power supplies
< Dry contact or NAMUR inputs
< Input frequency 1 mHz ... 1 kHz
< Current output 0/4 mA ... 20 mA
< Relay contact and transistor output
< Start-up override
< Configurable by PACTware or keypad
< Line fault detection (LFD)

Function
This signal conditioner analyzes 2 digital signals (NAMUR sensor/mechanical contact) and functions as a rotation direction indicator, slip monitor,
frequency monitor or synchronization monitor.
Each proximity sensor or switch controls a passive transistor output. The 2 relay outputs indicate if the input signal is above or below the trip value
or the rotational direction.
The analog output can be programmed to be proportional to the input frequency or slip differential.
The unit is easily programmed by the use of a keypad located on the front of the unit or with the PACTware™ configuration software.
Line fault detection of the field current is indicated by a red LED.
For additional information, refer to the manual and www.pepperl-fuchs.com.

Application
The device processes 2 input frequencies up to a max. of 1 kHz. The following functions are provided by the device:
l Frequency measurement with freely adjustable trip value monitoring for high and low alarm as well as for frequency current conversion

(0/4 mA to 20 mA)
l Slip monitoring: The slip is calculated from the 2 input frequencies at channel I and II. If the freely parameterisable trip value is exceeded,

the respective output switches.


l Rotation direction signalling: The rotation direction is evaluated from the 2 input signals with the same frequency and a phase shift of 90°.

The corresponding outputs switch according to the direction of rotation.


l The frequency monitoring can be used in combination with rotation direction signalling or slip monitoring.

l Synchronisation monitor: The synchronisation monitor compares the pulse counts of the 2 inputs. If the measured difference in the pulses

is greater than the programmed value the corresponding outputs are switching.
The 2 electronic outputs serve to repeat the input signals.

Connection
Release date: 2023-05-31 Date of issue: 2023-05-31 Filename: 231201_eng.pdf

KFU8-UFT-2.D
400 Ω ≤ R ≤ 2 kΩ 10
1+ 11 I
12
I 10 kΩ 10 kΩ 16
17 II
3- 18
19+
400 Ω ≤ R ≤ 2 kΩ III
4+ 20-
IV
II 10 kΩ 10 kΩ 21+
7- V
6- mA
8+
13+
14-
15+
23
24
AC/DC

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 1
KFU8-UFT-2.D
Technical Data
General specifications
Signal type Digital Input
Supply
Connection terminals 23, 24
Rated voltage Ur 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Rated current Ir approx. 130 mA
Power dissipation 2.2 W / 3.5 VA
Power consumption 2.5 W / 4 VA
Interface
Programming interface programming socket
Input
Connection side field side
Connection input I: terminals 1+, 3-
input II: terminals 4+, 6-
input III: terminals 13+, 14- (control input 1)
input IV: terminals 15+, 14- (control input 2)
Input I, II 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Open circuit voltage/short-circuit current 8.2 V / 10 mA
Switching point/switching hysteresis logic 1: > 2.5 mA ; logic 0: < 1.9 mA
Pulse duration min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
Input frequency rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Input III, IV
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current 18 V / 5 mA
Output
Connection side control side
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 19+, 20-
output IV: terminals 21+, 20-
output V: terminals 7-, 8+
Output I, II signal, relay
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Mechanical life 5 x 107 switching cycles
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output III and IV signal , electronic output, passive
Contact loading 40 V DC
Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof)
0-signal: blocked output (off-state current ≤ 10 µA)
Output V analog
Release date: 2023-05-31 Date of issue: 2023-05-31 Filename: 231201_eng.pdf

Current range 0 ... 20 mA or 4 ... 20 mA


Open loop voltage max. 24 V DC
Load max. 650 Ω
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Transfer characteristics
Input I and II
Measurement range 0.001 ... 1000 Hz
Resolution slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Accuracy slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Measuring time frequency measurement: < 100 ms
Influence of ambient temperature 0.003 %/K (30 ppm)
Output I, II
Response delay ≤ 200 ms
Output V
Resolution < 10 µA

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 2
KFU8-UFT-2.D
Technical Data
Accuracy < 30 µA
Influence of ambient temperature 0.005 %/K (50 ppm)
Galvanic isolation
Input I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input III, IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IV reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III, IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III, IV/input III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III, IV/V basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output V/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/output III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Indicators/settings
Display elements LEDs , display
Control elements Control panel
Configuration via operating buttons
via PACTware
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Release date: 2023-05-31 Date of issue: 2023-05-31 Filename: 231201_eng.pdf

Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals
where applicable. For information see www.pepperl-fuchs.com.

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 3
KFU8-UFT-2.D
Assembly

Front view Removable


terminals
green

1 2 3 4 5 6
LED green:
Power supply KFU8-UFT-
LC display
2.D

1 2 PWR
IN/
LED yellow/red: CHK
1 2

Input pulses/ OUT


3 4
fault signal ESC

RS232
LED yellow: OK Keypad
Output I ... IV

7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24
Programming jack Removable
terminals
green

Matching System Components


DTM Interface Device type manager (DTM) for interface technology
Technology

PACTware 5.0 FDT Framework

K-ADP-USB Programming adapter with USB interface

K-DUCT-GY Profile rail, wiring comb field side, gray

Accessories
Release date: 2023-05-31 Date of issue: 2023-05-31 Filename: 231201_eng.pdf

K-250R Measuring resistor

K-500R0%1 Measuring resistor

KF-ST-5GN Terminal block for KF modules, 3-pin screw terminal, green

KF-CP Red coding pins, packaging unit: 20 x 6

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 4
Frequency Converter with Direction and Synchronization Monitor KFU8-UFT-2.D

Characteristic Curve
Maximum Switching Power of Output Contacts

I (A)
4
3

1
1
0.5
0.4
0.3

0.2
0.15

0.1

0 50 100 150 200 250 U (V)

Resistive load DC
Resistive load AC
1 max. 105 switching cycles
Release date: 2023-05-31 Date of issue: 2023-05-31 Filename: 231201_eng.pdf

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

5
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]

You might also like