LT Xlpe Cable: Design Code: Lvis09Cxswyl002C1.5Sa004S Document ID:TE/QMS/F/02

This document provides specifications for an LT XLPE cable with 2 cores of 1.5 square mm copper conductor each. It details the materials and properties of the conductor, insulation, inner and outer sheaths, armor, and overall cable. Electrical and mechanical parameters are also specified.

Uploaded by

y8jkfz98m9
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
252 views2 pages

LT Xlpe Cable: Design Code: Lvis09Cxswyl002C1.5Sa004S Document ID:TE/QMS/F/02

This document provides specifications for an LT XLPE cable with 2 cores of 1.5 square mm copper conductor each. It details the materials and properties of the conductor, insulation, inner and outer sheaths, armor, and overall cable. Electrical and mechanical parameters are also specified.

Uploaded by

y8jkfz98m9
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

LT XLPE CABLE

Document ID:TE/QMS/F/02 DESIGN CODE: LVIS09CXSWYL002C1.5SA004S


Particulars 2 Core X 1.5 Sq.mm
Name of Manufacturer Polycab India Ltd
Type of cable 2XWY
Voltage Grade V 1100
No of cores X size in sqmm 2 Core X 1.5 Sq.mm
Conductor
Plain annealed Copper as per Class 2 of
a) Material
IS:8130/2013
b) Max. D.C. resistance of conductor at 12.1
20° C (ohm/km)
c) Shape of the conductor Stranded Circular
Insulation
a) Material XLPE as per IS 7098(Pt-1)/88, Latest
b) Nominal thickness (mm) 0.7
c) Core identification Red,Black
Inner Sheath
a) Material Extruded PVC Type ST2 as per IS:5831/84
b) Minimum thickness (mm) 0.3
Armouring
a) Material Galvanised Steel
b) Type of armouring Round Wire
c) Nominal size of armour (mm) 1.40
d) Tolerance on armour dimensions +/- 0.040
Outer Sheath
Extruded FR-LSH PVC Type ST2 as per
a) Material
IS:5831/84
b) Thickness (mm) 1.24 (Min.)
c) Colour of outer sheath. Red
Electrical Parameters
a) Max. a.c. resistance of conductor at 90° 15.4
C (ohm/km)
b) Calculated Cable reactance (ohm/km) 0.105
c) Impedance of cable (ohm/km) 15.4
d) Approx. Cable Capacitance (mfd/km) 0.18
Rev.No.:00 Issued Date:02/04/2018

Note: -The values given above are subject to tolerances as per the relevant standards.
www.polycab.com | Toll Free No - 1800 267 0008 | Email: [email protected]
Maximum conductor temperature under 90°C
normal operating conditions
Maximum conductor temperature at the 250°C
termination of short circuit
Short Circuit rating of conductor for the 0.21
duration of 1 sec (kA)
Continuous Current carrying capacities :-
a) In Ground at 30°C (A) 31
b) In Air at 40°C (A) 27
Applicable Standard IS 8130/2013,IS 7098 Part I/88, IS 5831/84, IS
3975/1999 etc. with latest up to date
amendments
Approx. overall diameter of the cable in mm 12.5 ± 2.0
Minimum bending radius 12 times Overall diameter
Max. Tensile strength
i) for Cables pulled with stocking 9 x D², D is the cable OD in mm
(Newtons)
ii) for Cables pulled with pulling eyes (N) 150

Embossing POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE


FR-LSH
Printing YEAR POLYCAB ELECTRIC 1100 VOLTS GRADE
XLPE FR-LSH CABLE SIZE CABLE TYPE WITH
SEQUENTIAL MARKING at every one meter
interval.

Standard Drum Length (Mtr.) 1000 ± 5%


Non- Standard Drum Length (Mtr.) Maximum 5% of order quantity
FR-LSH Properties
a) Oxygen Index Min. 29% as per ASTM D- 2863
b) Temperature Index Min. 250 Deg.C as per ASTM D- 2863
c) Smoke Density Rating Max. 60% as per ASTM D- 2843
d) Acid Gas Generation Max. 20% as per IEC- 754- 1
e) Flammability test As per IEC:332-I

Rev.No.:00 Issued Date:02/04/2018

Note: -The values given above are subject to tolerances as per the relevant standards.
www.polycab.com | Toll Free No - 1800 267 0008 | Email: [email protected]