Ac-1 System Reference
Ac-1 System Reference
Related Documents:
Andover Continuum Power Supply Reference, 30-3001-702
Andover Continuum NetController II Operation & Technical Reference, 30-3001-995
Andover Continuum Enclosure and Display Module Reference, 30-3001-711
Andover Continuum I/O System Installation Sheet, 30-3001-716
The information in this document is furnished for informational purposes only, is subject to change
without notice, and should not be construed as a commitment by Schneider Electric. Schneider
Electric assumes no liability for any errors or inaccuracies that may appear in this document.
st
On October 1 2009, TAC became the Buildings Business of its parent company Schneider
Electric. This document reflects the visual identity of Schneider Electric. However, there remain
references to TAC as a corporate brand throughout the Andover Continuum software. In those
instances, the documentation still refers to TAC - only to portray the user interface accurately. As
the software is updated, these documentation references will be changed to reflect appropriate
brand and software changes. All brand names, trademarks, and registered marks are the property
of their respective owners.
Schneider Electric
One High Street
North Andover, MA 01845
(978) 975-9600
Fax: (978) 975-9782
http://www.schneider-electric.com/buildings
ii Schneider Electric
Regulatory Notices
iv Schneider Electric
TCX 865
ANDOVER CONTINUUM
I/O Systems
This manual describes the installation, care and use of all Andover Continuum I/O
modules.
The Andover Continuum Ethernet-based intelligent building system allows you to mix and
match various combinations of DIN rail-mounted modules⎯high density I/O, CPU and
power supply, and your choice of several user interface modules⎯in a single controller
location to meet your building’s control and monitoring needs. With the Andover
Continuum system, as your network grows, simply add or replace I/O modules as
needed.
The Andover Continuum I/O modules feature a casing designed for natural convection
cooling, and a 3-position front cover for easy, hands-free access. Built-in quick-release
fasteners at the back of each I/O module are provided for DIN rail mounting⎯no tools
required. These fasteners also snap into a locked position for panel mounting. Input and
output connectors are located at the bottom of each I/O module and are removable for
easy field access and maintenance. All Andover Continuum modules are designed for
mounting in an optional NEMA 1-style Andover Continuum enclosure.
The Andover Continuum I/O modules communicate with the Andover Continuum
NetController and NetController II CPU modules. (This manual uses the generic name,
NetController for both series of CPU modules.) Like all Andover Continuum modules, the
I/O modules snap together directly via built-in connectors on either side; so network
expansion is quick and easy. Both power transmission and communication signals
between the power supply module, NetController CPU module, and all I/O modules feed
through this connection. For added convenience in certain applications, such as door
control or lighting control, a single module or groups of I/O modules can be remotely
located and connected using approved cable and powered from a local power supply.
Each I/O module features its own push-button for quick and easy network
commissioning.
This document covers the standard Input and Output modules. For information
regarding the special Andover Continuum enclosure door-mounted display
modules consult the Andover Continuum Enclosure and Display Module
Reference.
The Andover Continuum I/O system comprises a series of modules separated by function
that connect via a common electrical communications network. Each functional
component (module) is enclosed in a plastic case containing all of its connections to the
outside world. Modules are connected to a central controller via a standard five-conductor
connector.
The Andover Continuum system includes at least one power supply and a single CPU
module. I/O modules provide the controller with the ability to interface with the outside
world. They connect directly and communicate with the CPU. The following is a typical
architecture drawing of an Andover Continuum System:
Andover Continuum I/O modules included in this document are INPUT, OUTPUT and
MIXED. Display modules are covered in the Andover Continuum Enclosure & Display
Module Reference 30-3001-711.
2 Schneider Electric
The INPUT modules available are:
• UI-8-10; Universal Input Module * † **
• UI-8-10-10V; Universal Input Module * † **
• DI-6-AC; AC Digital Input Module (12-120V)
• DI-6-AC-HV; AC Digital Input Module (120/240V)
• DI-8; Digital Input Module * †
• DM-20; Digital Input/Output Module * †
• MI-6; MilliAmp Input Module *
* These modules are also listed for smoke control applications. The model number for a smoke
control listed part includes an ‘-S’ suffix.
† These modules are listed for UL 294 Access Control Applications. See also: Andover
Continuum UL 294 Access Control Systems Reference, 30-3001-746.
(**) These modules are listed for UL 1076 Applications. See also: Andover Continuum UL 1076
Burglar Alarm Systems Reference, 30-3001-800.
Note: In order to meet agency requirements in the United States, it is necessary that
the modules along with the power supply and CPU be housed in another metal
enclosure i.e., a NEMA box or the Andover Continuum enclosure. Only Schneider
Electric enclosure models ENC-0DISP and ENC-3DISP are approved for UL 294 Access
Control Systems.
The two types of I/O module plastic cases are illustrated below:
Status Indicators
& switches
Status indicators and operator switches are located on the indicator panel. Other
switches available for module configuration may be accessed by lifting the hinged door of
the smaller module.
Connections to
controlled/sensed
equipment
4 Schneider Electric
On the back of each module are molded DIN rail guide fingers. The design allows the
module to easily hook onto and slide along a standard DIN rail. The fingers also allow the
module to be mounted directly to a panel using them as a bracket. A stand-off is molded
into the locking finger. To mount the module on a panel, extend the locking fingers and
insert screws through the standoffs as shown below:
DIN Rail Mounting: With the mounting brackets (locking fingers) extended outward, hook
the module onto the DIN rail as shown below:
Press the lower mounting bracket(s) inward until it locks the module in place.
6 Schneider Electric
Overall Dimensions
The overall dimensions of the two types of I/O cases are as shown:
6.70''
(170.2 mm)
6.70''
(170.2 mm)
2.50 ''
(63.5 mm) 9.0 ''
(228.7 mm)
The Display modules are designed to fit into openings left by removing panels in the front
door.
The enclosure is a 6” deep NEMA box with integral display panels, DIN rails, cable
troughs and a battery storage compartment.
DIN Rail
Cable Trough
Battery
Storage
The enclosure features three DIN rails and cable management accessories. Use of the
new enclosure is not required; however, it provides a convenient method of constructing
small local systems.
8 Schneider Electric
The front door of the enclosure contains removable sections into which special operator
display and control modules may be mounted. Alternately, Plexiglas panels may be used
to view the status lights of all internal modules when the door is closed.
5HPRYDEOH
'LVSOD\3DQHOV
Spacers for
Additional Displays
Typically, Input wires should enter from only one of the wiring troughs, and should come
from the left side of the rack.
Output wires should enter from the other wiring trough, and should come from the right
side of the rack.
A good system would be to install all your input modules on one DIN rail, output modules
on the next rail, and so on.
The power-I/O connector is a five pin male assembly that is designed to easily insert
directly into the left side connector of any I/O module. The signals within this
connector are as follows:
PIN Function
5 +24 VDC 5
4
3
2
4 24 VDC Return 1
3 Shield
2 Comm B
1 Comm A
The main system power supply generates a +24 VDC source for the CPU. This
power source is received through the input power connector on the left side of the
CPU module and sent through to pins 4 and 5 of this connector.
All Andover Continuum I/O modules can operate at 24V. Some have extended ranges to
allow operation at lower voltages. Refer to the individual specifications for each module.
Communications between the CPU and I/O modules is through a two-signal serial
interface that is factory configured as either RS 485 ACC-LON or LON FTT-10A.
Pins 1 and 2 (Comm B and Comm A) provide the electrical connection for this interface.
Pin 3 (Shield) is the communications signal shield connection. This is not an Earth
ground connection. Proper shielding requires that the installer connect all shields
together. The CPU (if grounded properly) provides the single Earth ground point for all
modules. Each I/O also has its own Earth ground connection.
10 Schneider Electric
Connection of I/O Modules
When installing I/O modules it is imperative that the installer supply a solid Earth ground
connection to the pins provided.
The CPU can directly connect to I/O without the use of cables through a system of built-in
plugs and jacks. All I/O modules include two complementary module inter-connectors.
Creating a system is as simple as physically plugging the modules together.
In vertical extended systems, I/O modules may be located above or below other modules.
In this case, cable assemblies bridge the I/O modules together.
I/O
The cables necessary to connect the CPU and external I/O modules are attached using a
plug-in screw terminal connector. Connection between the modules is one-to-one
straightforward wiring as shown below:
5 5
4 4
3 3
2 2
1 1
Connectors are available from Schneider Electric under part number 01-0010-840.
* Power requirements for Display Modules can be found in the Andover Continuum Enclosure and
Display Module Reference, 30-3001-711.
** Listed power value does not include any devices attached and powered by the module
(card readers or DIO-20). Refer to the formulas on the next page for calculation.
12 Schneider Electric
Calculating Additional Power Supply Requirements
The DM-20 and all the AC Series access control modules have the built-in capability to
power an external device. The module power requirements listed in the table on the
previous page does not include power consumption information for these devices. In the
case of external card readers and keypads, it is not possible for us to determine the
power requirements of all the combinations of manufacturer’s products you might
connect. However, we can provide a simple formula to determine any additional power
the module may draw when powering those devices.
AC-1A:
AC-1Plus: Module X Reader/Keypad 24 X 0.05 (50 mA reader) = 1.20W
Supply Voltage Current (Amps)
DM-20 Refer to the DIO-20 section of this document for additional power requirements
Cable Recommendations
Data Cable (Pins 1, 2 and 3)
You must use shielded cable for the data lines (pins 1, 2 and 3) to provide reliable
communications and to ensure compliance with the Class A FCC limits (USA).
ACC-LON (RS-485)
The data cable should be 24-gauge (0.25 mm), single-twisted-pair, tinned, shielded
copper wire with an impedance of 100-120 Ωs and a nominal velocity of propagation
of 78%.
Capacitance of the cable should be below 12.5 pF/ft (41 pF/m) between conductors
and below 22 pF/ft (72 pF/m) between the conductor connected to ground and the
next conductor.
The following cable meets all of the data cable specifications:
Belden 9729, double twisted pair, shielded
The gauge of the power cable is determined by the power it carries. As indicated
previously, the longer the wire the more voltage drop. Do not allow the power supply
voltage measured at the furthest remote module to drop more than the allowable amount:
24 VDC modules: 2V (1V for the power run and 1V for the return run)
10-28 VDC modules: 12V (6V for the power run and 6V for the return run)
Voltage=Current x Resistance
A table providing some guidelines for choosing wire gauge is included on the next page.
14 Schneider Electric
Power Wiring Guideline Table
The following is a conservative estimate of typical power consumptions and their related
wire gauge and number of feet:
24 VDC Modules
Total I/O Power Draw (Watts)
10 20 30 40 50
AWG Resistance
per 1000 ft Distance in Feet (meters)
(305 m)
14 2.5 585 (178) 255 (78) 145 (44) 90 (27) 57 (17)
16 4 366 (111) 159 (48) 91 (28) 56 (17) 36 (11)
18 6 244 (74) 106 (32) 60 (18) 38 (12) 24 (7)
20 10 146 (44) 64 (20) 36 (11) 23 (7) 14 (4)
22 15 98 (30) 43 (13) 24 (7) 15 (6) 10 (3)
24 24 61 (19) 27 (8) 15 (5) 9 (3) 6 (2)
10 - 28 VDC Modules
Total I/O Power Draw (Watts)
10 20 30 40 50
AWG Resistance
per 1000 ft Distance in Feet (meters)
(305 m)
14 2.5 3885 (1184) 1905 (581) 1245 (379) 915 (279) 717 (219)
16 4 2428 (740) 1191 (363) 778 (237) 572 (174) 448 (137)
18 6 1619 (493) 794 (242) 519 (158) 381 (116) 299 (91)
20 10 971 (296) 476 (145) 311 (95) 229 (70) 179 (55)
22 15 648 (198) 318 (97) 208 (63) 153 (47) 120 (37)
24 24 405 (123) 198 (60) 130 (40) 95 (29) 75 (23)
These tables are intended as a guide. There is no way to account for every Andover Continuum I/O
permutation. External noise suppression may be required if the power wiring is run in a noisy
environment.
The following diagrams are typical installations that indicate the correct placement of the
terminator:
The I/O Bus that needs to be terminated is the one formed by the cable attaching the
remote module to the CPU. In this case, a terminator resistor is connected across the
communications lines (pins 1 & 2) directly at the NetController and again at the remote
I/O module.
CPU 5 5
4 4
3 3
2 2
1 1
120 Ω
Resistor Remote
I/O 120 Ω
Resistor
Module
16 Schneider Electric
CPU with Local and 1 ACC-LON Remote I/O Module:
The I/O Bus that needs to be terminated is the one formed by the cable that starts at
the NetController and ends at the remote module. The bus that extends from the
NetController through the local I/O stack does not need termination. In this case, the
terminator resistor is connected directly across the communications lines (pins 1 & 2) at
the NetController and again at the remote I/O module.
Local Local
CPU I/O
5
I/O 4
120 Ω
Resistor
Remote
I/O 120 Ω
Module Resistor
The I/O Bus that needs to be terminated is the one formed by the cable that starts at
the NetController and ends at the first remote module. The bus that extends from the
NetController through the local I/O stack and the one that starts at the first remote
module and extends through subsequent modules do not need termination. In this
case, the terminator resistor is connected directly across the communications lines
(pins 1 & 2) at the NetController and again at the first remote I/O module.
CPU Local 5
I/O 4
120 Ω
Resistor
Remote Remote
I/O I/O 120 Ω
Module Module Resistor
18 Schneider Electric
CPU with Two Remote ACC-LON Modules Separated by Distance:
The I/O Bus that needs to be terminated is the one formed by both cables on either
end of the first remote I/O module. In this case, the bus begins at the NetController,
flows by the first remote module and ends at the second. The terminator resistor is
connected directly across the communications lines (pins 1 & 2) at the NetController
and again at the last remote I/O module. If the last module is actually a stack of
directly connected I/O modules, the terminator is placed at the first module of the
stack as indicated in the scenario described on the previous page.
CPU 5
120 Ω
Resistor
5
5
4
4
3
3
2
2
1
1
Remote Remote
I/O 120 Ω
I/O Resistor
Module Module
The best solution for reducing installation and maintenance costs and simplifying system
modifications is a flexible topology communication system. Echelon's free topology
transceiver (FTT) technology offers just such a solution, and provides an elegant and
inexpensive method of interconnecting the different elements of a distributed control
system.
The Echelon LON FTT-10A free topology architecture allows you to wire Andover
Continuum I/O modules with virtually no topology restrictions.
Unlike ACC-LON, the FTT-10A system uses a free topology wiring scheme that supports
star, loop, and/or bus wiring. This design has many advantages. First, the installer is free
to select the method of wiring that best suits the installation, reducing the need for
advanced planning and allowing last minute changes at the installation site. Second,
retrofit installations with existing wiring plants can be accommodated with minimal, if any,
rewiring. This capability ensures that FTT-10A technology can be adapted to both old and
new projects. Finally, free topology permits Andover Continuum systems to be expanded
in the future by simply tapping into the existing wiring where it is most convenient to do
so. This reduces the time and expense of system expansion, and from the customer's
perspective, keeps down the life cycle cost of the free topology network.
20 Schneider Electric
FTT-10A Cable Termination (see important notice on the previous page)
When locating an I/O module remotely on a LON FTT-10A-based system, it is necessary
to add an external terminator to the wiring to compensate for the distance. The terminator
can be connected at both ends or at one central point.
* The Schneider Electric implementation of the Lon FTT-10A network can connect to a Link-
Power network; however, it does not use the Link Power.
Termination Termination
Non-Link Power network Link Power network
Resistor = 52.30±1%, 1/8W Resistor = 52.30±1%, 1/8W
Capacitors = 100 μF 50V min.
R1 52.3 Ω ± 1%
In a doubly terminated bus topology, two terminations are required, one at each end of
the bus. Using 24 AWG cable the maximum loop impedance is 150 Ωs.
Termination Termination
Non-Link Power network Link Power network
Resistor = 105 Ω±1%, 1/8W Resistor = 105 Ω±1%, 1/8W
Capacitors = 100 μF 50V min.
R1 105 Ω ± 1%
A doubly terminated bus may have stubs of up to 3 meters from a bus to each node.
The free topology transmission specification includes two components that must be met
for proper system operation. The distance from each transceiver to all other
transceivers and to the termination (including the LPI-10 termination, if used) must not
exceed the maximum node-to-node distance. If multiple paths exist, e.g., a loop
topology, then the longest path should be used for calculations. The maximum total
wire length is the total amount of wire connected per segment.
The following pages contain diagrams of typical installations that indicate the correct
placement of the terminator:
22 Schneider Electric
Example of Maximum Total and Node-to-Node Lengths
Maximum Wire
Length
I/O
I/O Node-to-Node
Length
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O 3
2 52.3 Ω
1
24 Schneider Electric
CPU with Several Remote FTT-10A I/O Modules and Doubly Terminated Bus*:
I/O
I/O
I/O
I/O
I/O 3
2 105 Ω
1
26 Schneider Electric
Module Configuration
This section of the document describes the procedure of configuring each module so that
it will be recognized by the Andover Continuum hardware. The following procedure is
common to all modules. Follow these instructions in the order given to assure proper
operation of the module.
It is assumed that you have knowledge or have access to someone who does have
knowledge of the operation of the CyberStation workstation. It is also assumed that your
CyberStation has configuration capabilities, is operating, logged-in and that the
NetController connecting to the modules you are trying to configure has already been
configured.
Remove power from the I/O Bus where the module is to be installed
Step 1 On the I/O Bus: Connect the IOU Module
Connect the IOU Module to the I/O Bus.
Step 2 On the I/O Bus: Restore Power
Restore power to the I/O Bus.
Step 3 From CyberStation: Create the IOU Module
Log onto a CyberStation and create a new IOU module via the IOUModule
editor.
Step 4 From CyberStation: Assign an IOU number to the Module
During the creation process, you assign a unique number to the module being
configured.
Step 5 If the module is not easily accessible: Enter the module ID into the
Module ID text field.
Enter the module ID found on the label inside the cover of the module into the
field and click the Apply button, then skip to Step 8.
Step 6 If the module is easily accessible: Click the Learn Button on CyberStation
After creating the module and assigning the number, click the Learn button. A
dialog box displays requesting the operator to press the Commission button on
the physical module.
Step 7 On local Modules: Press the Commission button on the Module
Press the Commission button found on the front panel of the module. Clicking
this button sends information from the module to CyberStation. When you push
the Commission button, the dialog box should disappear indicating that it
received the information from the module.
Remove power from the I/O Bus where the module is to be installed
28 Schneider Electric
Commissioning a Replacement I/O Module - CyberStation
When you replace an I/O module**, proceed as follows:
Remove power from the I/O Bus where the module is to be installed
Note: This procedure is for all modules except when replacing an AC-1 with an AC-1. For
that procedure, follow the instructions in the next section.
Remove power from the I/O Bus where the module is to be installed
Note: This procedure is for all modules except when replacing an AC-1 with an AC-1
Plus. For that procedure, follow the instructions in the next section.
Note: The AC-1 Plus has operational differences from AC-1 and AC-1A modules (i.e.
Degrade mode). Please refer to the AC-1, AC-1A and AC-1 Plus sections of this manual
for further information.
30 Schneider Electric
Replacing an AC-1 with an AC-1 Plus Module – Command Terminal
When you substitute an AC-1 Plus for an AC-1 module, proceed as follows:
Remove power from the I/O Bus where the module is to be installed
Caution
Do not externally ground any input signal connected to the module. This may
damage the unit. Signal return terminals are not connected to Earth Ground.
When installing Andover Continuum I/O modules it is imperative that the installer supply
a solid Earth ground connection to the pins provided.
32 Schneider Electric
Electro Static Discharge (ESD) Warning
To avoid damaging electronic components due to the discharge of static
electricity, always ground yourself before touching any boards or other internal
components of Schneider Electric devices.
On each I/O module, the left-most pin is labeled with a ground symbol and
should have a short earth ground connection made to it. The wire should be as
short as possible, ideally 6 inches or less, and the wire gauge should be a
minimum of 18 AWG.
Earth Ground
Later shipments of I/O Modules include a grounding clip built into the DIN Rail
clamp of the module. If the Din Rail itself is grounded you will no longer need to
ground the I/O modules. You will still need to ground the CPU Modules.
34 Schneider Electric
UI-8-10
UI-8-10, UI-8-10-10V
Universal Input Modules
The UI-8-10, Andover Continuum’s universal input module, provides 8 universal inputs,
software configurable as voltage, thermistor, digital, or counter point types. Each point
can also be configured as a supervised input for security monitoring, providing indication
of on/off and trouble conditions. This module is a perfect choice for any mix of
temperature, pressure, flow, status points, and similar inputs in a control system, with a
0-5 volt input range and 10 bit A/D conversion.
The UI-8-10-10V model is available for 0–10V applications. It provides the identical point
type selection; but is equipped with individual voltage divider DIP switches on each input,
allowing each to be configured for a 0–10 volt range.
FEATURES
• 8 Universal Inputs
• 10 bit Resolution
O
N
2
N
2
3
3
4
4
5
5
6
6
7
7
8
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 10-28V. 24V for UL864 and UL294
installations.
Power Consumption: 0.7 Watt (29 mA) @ 24VDC (max.); normally provided by Andover
Continuum power supply module.
Overload Protection: 0.5 A resettable fuse with transient voltage suppressor (TVS) and
reverse polarity protection.
INPUTS
Number of Inputs: 8 Universal inputs; 10 bit resolution
Input Types: Voltage, Thermistor, Digital, Counter, and Supervised
Input Protection: 24V AC/DC allowed to any single input
(40V transient voltage suppressor on each input – UI-8-10-10V)
Input Impedance: 5 MΩ w/pull-up disabled; 10 KΩ w/pull-up enabled – UI-8-10
(4.4 KΩ in 0-10V mode UI-8-10-10V)
Input Connections: Two-piece, 13-position removable terminal block
Thermistor:
Type: 10 KΩ, Type III Thermistor
Range: -30 to 230°F
(-34 to 110°C)
Resolution: 40 to 100°F range 0.20°F typical
(4 to 38°C) (0.11°C typical)
Accuracy: 40 to 100°F range ± 1.0°F (includes 0.36° error for thermistor)
(4 to 38°C) (±0.55°C)
Supervised:
Input Type: Single or Double Resistor Supervision, Parallel or Series Circuit
36 Schneider Electric
UI-8-10
I/O Connections
The actual input connections are located on a thirteen-position removable screw terminal
connector located at the bottom of the module.
The inputs are labeled IN1, IN2, IN3, and so forth. Each pair of inputs is followed by its
return connection labeled RET, resulting in a sequence of IN1, IN2, RET, IN3, IN4, RET,
and so on.
The connector allows for an Earth ground connection, eight inputs and four signal
returns.
The diagram screen printed on the module indicates where each input number is located
on the terminal block. These connections are also listed below.
Connection Description
Earth Ground
1. IN 1
2. IN 2
3. RETURN
4. IN 3
5. IN 4
6. RETURN
7. IN 5
8. IN 6
9. RETURN
10. IN 7
11. IN 8
12. RETURN
1
O
N
2
N
2
3
3
4
4
5
5
6
6
7
7
8
Input Circuitry
UI-8-10 Inputs are essentially voltmeters. Universal inputs can be configured through
software to become one of five different input circuits:
Temperature
Voltage
Digital
Counter
Supervised
During configuration, the value of the Electrical Type attribute you select tells the
controller how to interpret the reading from each input.
The following is a simplified schematic of both the UI-8-10 and the UI-8-10-10V Universal
inputs:
UI-8-10 UI-8-10-10V
The main difference between the two is the UI-8-10-10V circuit includes a switch
selectable front-end voltage divider that effectively divides the 10V input signal by two.
The proper switch settings for various modes of operation are listed on the front for the
module.
Note: Setting the reference resistor enable switch to ‘ON’ and setting the range to
‘10V’ is invalid.
38 Schneider Electric
UI-8-10
Each input includes a low-pass filter after the pull-up formed by a series resistor and a
parallel capacitor. The resistor is utilized for over-voltage protection in limiting current to
two protection diodes (not shown). It is possible to have more than one input share a
single return wire. Keep in mind that the current through each input is approximately
0.3mA, so voltage drops occur with long runs of small gauge wire.
These switch modules are commonly called “DIP Switches” and require a small object
such as the tip of a pen or a small screwdriver to operate them. Each switch position acts
as a “slide switch”. Pressing the raised slide marker to the side marked “on” closes or
enables the switch. To open or disable the switch position, press the slide marker over to
the “off” side.
The UI-8-10-10V module allows you to choose from two input voltage ranges. Selection
is accomplished by using a switch arrangement that is similar to the operation of the pull-
up resistor switches. This small 8-position switch module is located to the right of the pull-
up selector switch and is accessible from the front of the module when the door is
opened.
The Voltage Range switches allow you to select a range (0-5 V) or (0-10 V) for each
input.
The 0-5V range allows connections to signals that do not exceed 5.00V.
The 0-10V range allows connection to signals up to 10.00V. In this mode the circuit
actually uses the same input measuring circuit as the 0-5V range, however, it divides the
voltage present by two thereby limiting the internal circuitry to 0-5V. When you read a 0-
10V input the actual reading will be 0-5V. You must adjust your readings for the higher
range via formula. This is accomplished by applying a conversion factor to the reading.
When creating a 10V InfinityInput, set the Conversion to ElecValue * 2.
When using the 10V mode be sure to set the Reference resistor switch to Off.
Note: Setting the Reference Resistor enable switch to ‘ON’ and setting the Range
to ‘10V’ is invalid. Switching to 10V inputs dramatically lowers the impedance of
the input to 4.4 KΩ.
40 Schneider Electric
UI-8-10
Supervisory Inputs
UI-8 inputs may be connected as supervisory inputs. The following drawings depict the
three types of supervisory inputs that exist—three normally closed and three normally
open types.
NC Series
With this type of input wiring, a resistor is placed in series with the input being monitored.
When the input contact presents a short circuit (normal closed position) the input is
assumed in a normal closed state, the circuit presents a reading of 10 K Ωs at the input.
When the input contact is opened, the circuit opens and an infinite resistance is
measured. If the wires to the input contact are cut it also appears as an “input contact
open” condition. In this case there would be an input contact open without a valid card
swipe or valid keypad entry resulting in an “input contact violation”. Shorting the input
causes a zero Ω resistance, which also results in an input contact violation.
ElecType: Supervised
Resistor Type: NCSeries
When the input contact is opened the switch opens and the value of the parallel resistor
is measured. If the wires to the input contact are cut it appears as an infinite resistance.
Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance
(open) should result in an error condition.
ElecType: Supervised
Resistor Type: NCSerPar
42 Schneider Electric
UI-8-10
NO Series Parallel
With this type of input wiring, two external resistors are added to the input, one in series
and the other in parallel. When the input contact switch is open (normal position) the
input contact is assumed to be closed. The circuit reads the value of the parallel resistor.
When the input contact is opened the switch closes and a reading results that is
composed of both resistances in parallel that works out to be half the value of one of
them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance.
Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance
(open) should result in an error condition.
ElecType: Supervised
Resistor Type: NOSeriPar
Some switches have built-in resistors that facilitate Series Parallel connections as shown
below:
10 KΩ
RET
Wiring is similar to a normal input contact switch input, however, the motion sensor
requires an external power supply of 12 VDC or 24 VDC (UL listed under APHV). The
maximum length wire you should use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire)
or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire).
44 Schneider Electric
UI-8-10
Measuring Temperature
UI-8-10 inputs can be configured to sense temperature by configuring one of the
module’s inputs appropriately. This is done by setting the Electrical Type to either ACC
Temp (DEG F) or ACC Temp (DEG C). Connect a resistive thermistor sensor to that
input terminal. The following is a schematic representation of the connection:
IN x
Thermistor
RET
One lead connects to a numbered input terminal, the other to a return terminal.
To use the input for temperature sensing, the pull-up reference resistor must be
connected into the circuit, therefore, the reference resistor switch for this input must
be placed in the “on” position and the Range switch must be in the 5V position.
When the input point is configured as a temperature input, the controller utilizes a look-up
table to convert from a voltage reading to a temperature reading in degrees Fahrenheit or
Celsius.
Caution
Never apply voltage to a thermistor—doing so alters the thermistor’s accuracy and
reliability. In fact, it’s a good idea to replace any thermistor that has had any sort of
voltage applied to it.
To keep thermistor errors to a minimum, limit the length of wire runs to the maximum for
the gauge wire you select.
The following two pages include three tables that indicate the maximum length runs for
wires of various gauges to keep errors within certain temperature limits when using
thermistor elements.
Gauge 1/2 °F (.28 °C) Error 1/4 °F (.14 °C) Error 1/10 °F (.06 °C) Error
Gauge 1/2 °F (.28 °C) Error 1/4 °F (.14 °C) Error 1/10 °F (.06 °C) Error
46 Schneider Electric
UI-8-10
Measuring DC Voltages
The UI-8-10 inputs may be configured to sense DC voltage by connecting the input
terminals to a DC voltage source within the range of the module’s input specifications.
The following is a schematic representation of the connection:
+ IN x
V
-
RET
The plus lead connects to the numbered input terminal, the other to a return terminal.
When interfacing to a voltage output sensor, specific information on the transducer may
be required. The pull-up resistor of the input circuit will affect the output of the transducer.
ElecType: Voltage
Reference Resistor OFF
Voltage Dividers
There are instances when it is necessary to interface to a voltage source that is higher
than the input range of the module. In these cases a voltage divider is necessary.
The circuit shown above is a simple two-resistor voltage divider connected to one of the
UI-8-10 module’s inputs. The input circuitry of the module can measure a maximum of
either 5 Volts or 10 Volts (UI-8-10-10V only). Therefore, the voltage measured across the
reference resistor must not exceed this maximum.
In this case, be sure to switch the pull-up resistor out of the circuit.
48 Schneider Electric
UI-8-10
Assuming you know the maximum voltage reading you are trying to measure (Vsource),
perform the following steps to determine the resistance values necessary to condition the
input for the module. If you have the UI-8-10-10V model, set the Range switch to 5V.
1. First, determine the current that will flow through the divider. Pick a value that your
source can supply. Let’s say 20 mA. This value will be represented by the variable
Itotal in the following equations.
2. Determine the total resistance value required of the entire divider (R1 + R2) to create
20mA given the source voltage by solving the following:
Rtotal = Vsource
Itotal
Rtotal = 30 V
.02 A
Rtotal = 1500 Ω
The current is constant through the two resistors. Knowing this and the fact that our input
can’t exceed 5V can determine the value of the resistor labeled R2.
3. Determine the value of R2 by solving the following:
R2 = Vinput
Itotal
R2 = 5 V
.02 A
R2 = 250 Ω
IN x
Contact
Closure
RET
Note: When configuring a Digital point, there is a “Polarity” attribute. If this attribute is
enabled, readings are reversed: “On” will occur when the contact is open, and “Off”
occurs when the contact is closed.
ElecType: Digital
Reference Resistor ON
50 Schneider Electric
UI-8-10
When using an input as a counter, you must take into account the frequency of the input
signal being counted. Universal inputs do not allow for very high speed contact counting.
This module allows counting up to a maximum of 4 Hz or 4 contact closures per second.
ElecType: Counter
Reference Resistor ON
Status/Control Panel
Status Indicators
The UI-8-10 module includes a complete indicator status panel on the front of the
module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate there is a problem with the module.
This panel also includes two operator switches that perform the following:
52 Schneider Electric
DI-6-AC
DI-6-AC, DI-6-AC-HV
Digital AC Input Modules
The DI-6-AC, Andover Continuum’s digital AC input module, has six digital (“wet”) AC
inputs for cost-effective ON-OFF status indication of fan motor starters, solenoid valves,
control relays, or external power supplies, and similar applications that require a quick
and easy way to detect voltage. The DI-6-AC monitors the absence or presence of AC
voltage levels directly, with no interposing relays needed.
The DI-6-AC can monitor voltages from 20–132V. A DI-6-AC-HV model is also available
for sensing higher voltages (90–250V). Both models can also accept DC voltages. All
inputs are optically coupled with 2500V isolation on each input for noise-free operation.
FEATURES
• Independently Mounted
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 20-26V.
Power Consumption: 0.7 Watt (29 mA) @ 24VDC (max.); normally provided by Andover
Continuum power supply module.
Overload Protection: 0.5 A resettable fuse with transient voltage suppressor (TVS) and
reverse polarity protection.
INPUTS
Number of Inputs: 6 digital AC voltage inputs
Input Protection: 2500V isolation on each input.
Each input has a 270V MOV.
Input Connections: Two-piece, 13-position removable terminal block
DI-6-AC DI-6-AC-HV
Input Range: 20–132 Vrms 90–250 Vrms
Input Current: 5 mA max. 2 mA max.
DI-6-AC DI-6-AC-HV
AC Voltage “ON” Threshold: 16 Vrms 75 Vrms
(Above this voltage is considered “ON”)
EUROPEAN STANDARDS
European Multi-Purpose Control–Electronic
Type 1B–Micro Disconnect
54 Schneider Electric
DI-6-AC
I/O Connections
The actual input connections are located on a thirteen-position removable screw terminal
connector located at the bottom of the module.
The inputs are labeled IN1, IN2, IN3, and so forth. Each pair of terminals corresponds to
one input. With both AC and DC signals there is no polarity to observe during connection.
The connector allows for an Earth ground connection, eight inputs and four signal
returns.
The diagram screen printed on the module indicates where each input number is located
on the terminal block. These connections are also listed below.
Connection Description
Earth Ground
1. IN 1
2. IN 1
3. IN 2
4. IN 2
5. IN 3
6. IN 3
7. IN 4
8. IN 4
9. IN 5
10. IN 5
11. IN 6
12. IN 6
Input Circuitry
The following is a simplified schematic of both the DI-6-AC and the DI-6-AC-HV Digital
Input module:
AC
15K OptoCoupler
IN x
AC to DC
Converter II
275V
MOV
10V
RET 15K
DI-6-AC
AC
100K OptoCoupler
IN x
AC to DC
Converter II
275V
MOV
40V
RET 100K
DI-6-AC-HV
The main difference between the two is the DI-6-AC-HV circuit includes a front end that
supports the higher voltages.
56 Schneider Electric
DI-6-AC
Sensing AC or DC Digital Inputs
Digital input points are designed to provide an ON or OFF reading of a signal. Normally
you would associate an AC or DC voltage input with a value measurement, however, the
DI-6 modules include a voltage level trigger that senses the presence of a range of
voltages and converts those readings to ON and OFF indications.
AC Polarity DC
Signal IN x Independent Signal IN x
DI-6-AC DI-6-AC-HV
AC Voltage “ON” Threshold: 16 Vrms 75 Vrms
(Above this voltage is considered “ON”)
Note: When configuring a Digital point, there is a ‘Polarity’ attribute. If this attribute is
enabled, readings are reversed: ‘ON’ will occur when the input is at the normal OFF
threshold. OFF occurs at the normal ON threshold.
When configuring either type of input, select:
ElecType: Digital
Status/Control Panel
Status Indicators
The DI-6-AC module includes a complete indicator status panel on the front of the
module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate there is a problem with the module.
58 Schneider Electric
DI-6-AC
This panel also includes two operator switches that perform the following:
DI-8
Digital Input Module
The DI-8, Andover Continuum’s digital input module, is used for cost-effective sensing of
multiple dry digital inputs in applications such as equipment status monitoring or alarm
point monitoring. The DI-8 has eight digital inputs⎯each can be software configured to
accept a digital (contact closure or 0–5 volt input) or counter signal. Counter frequency is
10Hz on all eight inputs. In addition, high speed counting up to 10KHz max. is available
(via a DIP switch) on Channels 1 and 2 for high-speed metering and industrial
applications.
40V transient suppressors on all eight inputs protect against high voltage short duration
transients events. The DI-8 is designed to accept dry contact inputs or 0-5 volts and can
withstand up to 24 VAC/DC continuous voltage on four channels.
FEATURES
60 Schneider Electric
DI-8
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 10-28V. 24V for UL864 and UL294
installations.
Power Consumption: 0.8 Watt (33 mA) @ 24VDC (max.); normally provided by Andover
Continuum power supply module.
Overload Protection: 0.5 A resettable fuse with transient voltage suppressor (TVS) and
reverse polarity protection.
INPUTS
Number of Inputs: 8 digital inputs
Input Types: Digital or Counter, software selectable
Input Protection: 24V AC/DC applied to 4 channels max.
(40V transient protection on each input)
Input Impedance: 10 KΩ pull-up resistor referenced to +5V
Input Connections: Two-piece, 13-position removable terminal block
Digital:
Input Type: Contact closure or 0–5V input
Pulse Width: 50 ms minimum
Current: 0.5 mA
Counter:
Input Type: Contact closure or 0–5V input
I/O Connections
The actual input connections are located on a thirteen-position removable screw terminal
connector located at the bottom of the module.
The inputs are labeled IN1, IN2, IN3, and so forth. Each pair of inputs is followed by its
return connection labeled RET.
The connector allows for an Earth ground connection, eight inputs and four signal
returns.
The diagram screen printed on the module indicates where each input number is located
on the terminal block. These connections are also listed below.
Connection Description
Earth Ground
1. IN 1
2. IN 2
3. RETURN
4. IN 3
5. IN 4
6. RETURN
7. IN 5
8. IN 6
9. RETURN
10. IN 7
11. IN 8
12. RETURN
62 Schneider Electric
DI-8
Slide marker
moves left and right
1 2
O N
These switch modules are commonly called “DIP Switches” and require a small object
such as the tip of a pen or a small screwdriver to operate them. Each switch position acts
as a “slide switch”. Pressing the raised slide marker to the left disables high speed
counting. To enable high speed counting, move the slide marker over to the right side.
Input Circuitry
5V
10K
5V
IN x R
II
C
RET
Channels 1 and 2 can be configured to allow high speed counting. The switches on the
front of the module substitute different value components for the low pass filter formed by
the combination of R and C. These values support higher frequency inputs.
64 Schneider Electric
DI-8
Digital logic IN x IN x
Signal
Contact
Closure
RET RET
A digital input is considered “ON” whenever the input senses a digital ‘low’ or a contact
closure. Similarly, an OFF condition is sensed with a logic ‘high’ or an open contact.
Note: When configuring a Digital point, there is a ‘Polarity’ attribute. If this attribute is
enabled, readings are reversed.
ElecType: Digital
When using an input as a counter, you must take into account the frequency of the input
signal being counted. Inputs 3–8 do not allow for very high speed contact counting.
These channels allow counting up to a maximum of 10 Hz or 10 contact closures or
digital pulses per second.
In high-speed mode, channels 1 and 2 can be configured (via front panel switch) to count
to a maximum of 10 kHz or 10,000 contact closures or digital pulses per second.
ElecType: Counter
66 Schneider Electric
DI-8
Status/Control Panel
Status Indicators
The DI-8 module includes a complete indicator status panel on the front of the module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate there is a problem with the module.
This panel also includes two operator switches that perform the following:
68 Schneider Electric
MI-6
MI-6
MilliAmp Input Module
The MI-6, Andover Continuum’s milliamp input module, allows for a direct connection of a
2-wire, loop powered, 0–20mA or 4–20mA sensor to any of the module’s six inputs. The
need for an external resistor and an external power supply are eliminated. The MI-6
module is a perfect match for temperature transmitters, humidity and pressure
transducers, gas monitors, and other industry-standard sensors with either a 0–20mA or
4–20mA output. The six inputs on the MI-6 module have a 0–20mA range and 10 bit A/D
conversion.
FEATURES
• 0–20mA Range
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 20-26V. 24V for UL864 installations.
Power Consumption: 3.8 Watts (158 mA) @ 24VDC (max.); normally provided
by Andover Continuum power supply module (including up
to 20mA sensor power for each input).
70 Schneider Electric
MI-6
I/O Connections
The actual input connections are located on a thirteen-position removable screw terminal
connector located at the bottom of the module.
The inputs are labeled IN1, IN2, IN3, and so forth. Each input occupies a pair of
terminals, resulting in a sequence of IN1+, IN1-, IN2+, IN2-, and so on. For any given
input, observe the polarity for that input, + connects to the Supply terminal of the input.
The minus terminal connects to the Signal input.
The diagram below indicates where each input number is located in the terminal block.
Connection Description
Earth Ground
1. IN 1 +
2. IN 1 -
3. IN 2 +
4. IN 2 -
5. IN 3 +
6. IN 3 -
7. IN 4 +
8. IN 4 -
9. IN 5 +
10. IN 5 -
11. IN 6 +
12. IN 6 -
Input Circuitry
24V
300mA
Resettable
Fuse
5V
100mA
Resettable
Fuse R
To
Analog/Digital
Converter
249Ω C
All six input pairs include their own automatically resettable fuses. These devices are
designed to open when sensing an over-current. They reset when the current supplied is
within range.
Note: In some extreme instances, the fuses may require that you remove power to
the module temporarily to reset their state.
72 Schneider Electric
MI-6
Sensing Current
Supply
24V
Loop-Powered INx
Sensor
Signal
ElecType: ACC_InputCurrent
Status/Control Panel
Status Indicators
The MI-6 module includes a complete indicator status panel on the front of the module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
74 Schneider Electric
MI-6
This panel also includes two operator switches that perform the following:
DM-20
Digital Input/Output Module
The DM-20, Andover Continuum’s Digital Input and Output module, provides high
density, versatile I/O for many control applications. When coupled with the optional DIO-
20 Expansion Board, the DM-20 allows you to mix and match up to 20 digital inputs and
outputs. Using standard off-the-shelf digital I/O blocks, the DIO-20 allows the system to
meet a wide range of applications, including ON-OFF or pulse-width modulation (PWM)
control of equipment and for switching inductive loads up to 240 VAC. The DM-20
provides 24 VDC power to the DIO-20 via a separate cable assembly.
When used without the DIO-20 Expansion Board, the DM-20 can control any combination
of inputs and outputs, up to a total of 20 per module.
FEATURES
76 Schneider Electric
DM-20
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 20-26V. 24V for UL864 and UL294
installations.
Power Consumption: 0.5 Watts (20 mA) @ 24VDC (max.); provided by Andover
Continuum power supply module.
Up to 9 Watts (375 mA) @ 24VDC when the DIO-20 is
powered from the DM-20 .
External Power Connector: Three-position removable connector
Outputs:
Output Type: w/DIO-20 w/o DIO-20
5 VDC logic voltage. Open- collector Output
Range depends on output transistor with series
module selected. 330 Ω 1/8 W resistor;
5 VDC (max.), 15 mA
Output Resolution: 0.1 sec. For Pulse Width Modulation (PWM) control
I/O Connections
The actual I/O connections are located on a 25-position DB25-type female connector
located at the bottom of the module. A separate three-conductor removable screw
connector provides 24 VDC power to external devices.
The inputs are labeled I/O1, I/O2, I/O3, and so forth. Each input/output occupies a single
position of the connector. Five signal ground pins are supplied as well.
The diagram below indicates where each input number is located on the module.
3-Pin Connector
Connection Description
Earth Ground
1 + 24VDC @ .36 Amps
2 24 V Return
25-Pin D Connector
Connection Description
1. I/O 1
2. I/O 2
3. I/O 3
4. I/O 4
5. I/O 5
6. I/O 6
7. I/O 7
8. I/O 8
9. I/O 9
10. I/O 10
11. I/O 11
12. I/O 12
13. I/O 13
14. I/O 14
15. I/O 15
16. I/O 16
17. I/O 17
18. I/O 18
19. I/O 19
20. I/O 20
21. Ground
22. Ground
23. Ground
24. Ground
25. Ground
78 Schneider Electric
DM-20
Input/Output Circuitry
+5V
330
I/O x
II
24V
500mA
Resettable
Fuse
Note: In some extreme instances, the fuses may require that you remove power to
the module temporarily to reset their state.
Note: Make sure that external devices are attached to the DM-20 before powering
the unit.
DIO-20 Interface
The DIO-20 Expansion Module provides a connection for up to 20* solid state input or
output modules for the I/O channels of the DM-20. It includes individually fused sockets
for modules from manufacturers such as Opto 22, Grayhill, Gordos, Crydom and Potter &
Brumfield. You can mix input and output modules on the DIO-20 as needed.
The connection between the DM-20 and the DIO-20 consists of a 25-pin ribbon cable to
supply data between the modules and a two-conductor power cable.
Data connection between the two is accomplished via a 25-pin male-male DB25 cable:
DM-20
DM-20 to DIO-20
Data Connection
DIO-20
*The actual number of modules supported depends on type and power used. Refer to the power requirements
on page 86.
.
80 Schneider Electric
DM-20
The Power connection between the DIO-20 and the DM-20 is via a two-conductor cable
assembly as shown:
DM-20
D CONNECTOR
G G G G G
I/O I/O I/O I/O I/O I/O I/O N N N N N
14 15 16 17 18 19 20 D D D D D
+ -
1 2
I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O
1 2 3 4 5 6 7 8 9 10 11 12 13 DM-20 to DIO-20
DC Power Connection
+24 V Return
+24 VDC
DIO-20
10K
GROUND GROUND
As a digital output, the DM-20 has an open collector output with a 330 Ω series resistor.
Connect digital devices and LED indicators as shown below:
5V +5V
10K
LED
Indicator
Digital logic I/O x I/O x
Input
GROUND GROUND
ElecType: Digital
* The actual number of modules supported depends on type and power used. Refer to the power requirements
on the following page.
82 Schneider Electric
DM-20
When power is lost to the module, all outputs turn off. This also occurs when the module
has lost communication with the NetController for more than 255 seconds.
When power is finally restored, the module can immediately restore the last state of the
outputs or be delayed so that the NetController can update the state before energizing
them. This option is called Output Restore Time and its value can be set through a
Numeric.
If the Output Restore Time numeric is not defined, the output will restore immediately
upon return of I/O power.
NOTE: Pulsed values are "saved" and will occur in their entirety after delay.
The DM-20 includes the ability to directly power a DIO-20 module. DIO-20 modules
support a combination of up to 20 input and output modules. The following details the
power requirements of each combination. This information is presented to determine the
power supply requirements for the board.
• Input modules consume a maximum current in their ON state of 23mA. The DM-
20 can only supply enough power for 14 input modules.
• Output modules consume a maximum current in their ON state of 16mA.
• The DIO-20 itself without any modules installed draws 20mA.
The DM-20 provides a total of 360mA for the DIO-20. Using the numbers supplied above
you can calculate how many modules are allowed.
Examples:
Up to 14 input modules: (14 x 23mA) + 20mA = 342mA
A total of 14 input modules exhausts (with only 18mA remaining) the current capability of the DM-20.
Up to 20 output modules:(20 x 16mA) + 20mA = 340mA
A total of 20 output modules consumes only 340mA from the DM-20.
Status/Control Panel
Status Indicators
The DM-20 module includes a complete indicator status panel on the front of the module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
84 Schneider Electric
DM-20
This panel also includes two operator switches that perform the following:
AO-4-8, AO-4-8-O
Analog Output Modules
The AO-4-8, Andover Continuum’s analog output module, has four analog outputs with
eight-bit resolution, which can be configured as either voltage (0-10 VDC) or current (0-
20 mA) outputs. The AO-4-8 is the perfect choice for valves, dampers, variable speed
drives, and similar equipment that demand high control accuracy.
An AO-4-8-O model with full override capabilities is also available. Each output contains
a three-position manual override switch and override potentiometer. In addition, the AO-
4-8-O provides software override feedback to the Plain English programming language
for each output.
FEATURES
• 4 Analog Outputs
• 8 bit Resolution
• 0–10V Voltage Outputs
• 0–20mA Current Outputs
AO-4-8-O Only:
• Override Toggle Switches and
Potentiometers
• Override Detection
86 Schneider Electric
AO-4-8
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 20-26V. 24V for UL864 installations.
Power Consumption: 3.8 Watts (158 mA) @ 24VDC (max.); normally provided
by Andover Continuum power supply module.
OUTPUTS
AO-4-8: 4 analog outputs; 8 bit resolution
AO-4-8-O: 4 analog outputs with overrides; 8 bit resolution
Output Protection: 1/8 pico fuse per channel (40V TVS on each output⎯AO-4-
8-O model only)
Output Connections: Two-piece, 13-position removable terminal block
Current:
Range: 0–20 mA
Resolution: 0.1 mA
Accuracy: ±0.2 mA
Load Resistance: 650Ω (max.)
I/O Connections
The actual output connections are located on a thirteen-position removable screw
terminal connector located at the bottom of the module.
The outputs are labeled OUT1 I, OUT1 V, OUT1 GND, and so forth. Each output
presents two ways of connecting, resulting in a current output between OUT1 I and OUT1
GND, and a voltage output between OUT1 V and OUT1 GND.
The connector allows for an Earth ground connection, eight inputs and four signal
returns.
The diagram screen printed on the module indicates where each input number is located
on the terminal block. These connections are also listed below.
Connection Description
Earth Ground
1. OUT1 I
2. OUT1 V
3. OUT1 GND
4. OUT2 I
5. OUT2 V
6. OUT2 GND
7. OUT3 I
8. OUT3 V
9. OUT3 GND
10. OUT4 I
11. OUT4 V
12. OUT4 GND
88 Schneider Electric
AO-4-8
Output Circuitry
24V
125mA
Pico
OUTx V Fuse
Digital to Analog
Converter
24V
125mA
Pico
OUTx I Fuse
Voltage to Current
Converter
GND
Override Controls
The AO-4-8-O model includes an output override switch and manual variable
control for each output.
MANUAL
OFF
AUTO
ADJUST
The following describes the actions associated with each position of the override
controls:
OFF The output is set to zero volts, zero mA. Programs and the
setting on the ADJUST potentiometer have no effect on the
output Device when the switch is in this position.
ADJUST This is a variable control that allows you to manually adjust the
output of the analog signal when the override switch is in the
MANUAL position. Insert the tip of a small screwdriver to use this
control. Turning to the right (clockwise) increases the output.
Turning left (counterclockwise) decreases the output.
90 Schneider Electric
AO-4-8
Voltage Output
The voltage output is a ground-referenced signal with a range of 0–10 VDC. The
maximum output current is 5 mA (2,000 s minimum resistance). Ensure that the device
being connected is either floating or at the same ground potential as the controller.
Connect the device across the following terminals:
OUTx I
OUTx V
Device
Load ≥ 2KΩ
Resistance
GND
NOTE: The load resistance (of the external device) must be greater than or equal to 2KΩ.
ElecType: Voltage
Current Output
The current output is a current-sourcing, ground referenced circuit. This output can
source 0 - 20 mA with a maximum load impedance of 650 s.
Connect the device across the following terminals:
OUTx I
Device
Load
Resistance OUTx V
≤ 650Ω
GND
NOTE: The load resistance (of the external device) must be less than or equal
to 650 Ω.
ElecType: Current
92 Schneider Electric
AO-4-8
Status/Control Panel
Status Indicators
The AO-4-8 module includes a complete indicator status panel on the front of the module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
This panel also includes two operator switches that perform the following:
94 Schneider Electric
DO-4-R
DO-4-R, DO-4-R-O
Digital Output Module
The DO-4-R, Andover Continuum’s digital output module, has four Form C relay outputs,
rated at 5 Amps @240 VAC. These versatile outputs make the DO-4-R an excellent
choice for switching motor starters and other inductive loads up to 240 VAC, with either
two position (on/off) or Pulse-Width Modulation (PWM) control. The PWM feature permits
the modulation of valves and dampers to 0.1 second resolution. Two adjacent Form C
relay outputs can be combined in software to provide a Tri-state output, for bi-directional
control of valves and dampers and other end devices. Metal oxide varistors and 5000V
isolation on each output ensure reliable noise-free operation.
A DO-4-R-O model with full override capabilities is also available. Each output has a local
hand-off-auto switch, which enables service personnel to override the output. The switch
also provides override feedback of output values for use in troubleshooting or test
conditions. A local indicator light for each output displays relay status. Another LED
provides override status.
FEATURES
• 4 Form C Relay Outputs
• 240 VAC @ 5A Contact Rating
• Independently Mounted
• Output Status LEDs
• 10–28 V Power Supply Range
DO-4-R-O Only:
• Override Toggle Switches
• Override Detection
SPECIFICATIONS
ELECTRICAL
Power Supply Range: (DO-4-R, DO-4-R-O): Input Voltage Range: 10-28V. 24V for
UL864 and UL294 installations.
Power Consumption: 2.8 Watts (116 mA) @ 24 VDC (max.); normally provided
by Andover Continuum power supply module.
OUTPUTS
DO-4-R: 4 Form C relay outputs
DO-4-R-O: 4 Form C relay outputs with overrides
Output Resolution: 0.1 sec. For Pulse Width Modulation (PWM) control
DO-4-R-O
Output Overrides: 3-position manual override switch on each output, with
software feedback.
LED override status indicator
DO-4-R-O
Override Feedback: Override detection and feedback provided for each output.
EUROPEAN STANDARDS
European Multi-Purpose Control–Electronic
Type 1B–Micro Disconnect
96 Schneider Electric
DO-4-R
I/O Connections
The actual output connections are located on a thirteen-position removable screw
terminal connector located at the bottom of the module.
The outputs are labeled OUT 1 NC, OUT 1 NO, OUT 1 COM, and so forth. Each output
presents a single pole double throw set of contacts. OUT 1 NC is the normally closed
side of the contact. OUT 1 NO is the normally open contact. OUT 1 COM is the common
connection that represents the armature of the relay switch.
The diagram below indicates where each output number is located in the terminal block.
Connection Description
Earth Ground
1. OUT 1 NC
2. OUT 1 NO
3. OUT 1 COM
4. OUT 2 NC
5. OUT 2 NO
6. OUT 2 COM
7. OUT 3 NC
8. OUT 3 NO
9. OUT 3 COM
10. OUT 4 NC
11. OUT 4 NO
12. OUT 4 COM
Output Circuitry
OUT x NC
OUT x NO
OUT x COM
These output contacts operate as a standard relay. When the output is set to an “ON”
state, the normally open contacts (OUTx NO) close and the normally closed contacts
(OUTx NC) open.
To use the Form C output in your system, configure an output point with an Electrical
Type of Digital.
If an open, short or grounded condition exists either on the cable out to the switched
device or the cable running back to the UI-8, an audio and visual alarm would be
triggered at the central receiving station when the output was turned on.
For 24 VDC Loads use relay: Potter & Brumfield (TYCO) KUP5D15 *
For 24 VAC loads use relay: Potter & Brumfield (TYCO) KUP5A15 *
*These relays are UL recognized components
98 Schneider Electric
DO-4-R
Override Controls
The DO-4-R-O model includes an output override switch for each output.
ON
OFF
AUTO
The output of the module can be directed from program control to manual
control. The output can be disabled completely as well.
The following describes the actions associated with each position of the override
controls:
ON The output relay is energized to an “ON” state manually by
setting the switch to ON. Programs have no effect on the output
when the switch is in this position.
OFF The output relay is de-energized to an ‘OFF’ state manually by
setting the switch to OFF. Programs have no effect on the output
when the switch is in this position.
AUTO The action of the output relay is determined as a direct result of
program control.
When power is lost to the module or it loses contact with the NetController for more than
255 seconds, all outputs turn off. When power is finally restored, the module can
immediately restore the last state of the outputs or be delayed so that the NetController
can update the state before energizing them. This option is called Output Restore Time
and its value can be set through a Numeric.
If the Output Restore Time numeric is not defined, the output will restore immediately
upon return of I/O power.
Tri-State Output
Although the module contains four separate form C relays, adjacent pairs of these can be
combined at any one time to form a standard Tri-state output:
OUT1 and OUT2
OUT3 and OUT4
Configure the output point of the first point (OUT1 or OUT3) with an Electrical Type of
Tri-state.
Caution: Do not attempt to use OUT2 and OUT3 as a tri-state pair. An error
message may result. Configure tri-state outputs as OUT1-OUT2 or OUT3-OUT4.
Connect the two outputs together as follows (example shows OUT1 and OUT2):
OUT 1 NC
OUT 1 NO
+ ON
OUT 1 COM
Common
OUT 2 NC
OFF
OUT 2 NO
ON
OUT 2 COM
Status/Control Panel
Status Indicators
All DO-4 models include a complete indicator status panel on the front of the module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
OVERRIDE This red indicator illuminates whenever any of the override switches is in
a position other than AUTO. (operates on -O models only)
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
This panel also includes two operator switches that perform the following:
DO-6-TR
Triac Output Module
The DO-6-TR, Andover Continuum’s triac output module, has six Form A triac-based
outputs, rated at 0.5 Amps @ 24 VAC, for cost-effective on/off or pulse-width modulation
(PWM) control of lighting, heat, and fan units. The PWM feature permits the modulation
of valves and dampers to 0.1 second resolution. Adjacent outputs can also be configured
in pairs to provide up to three Form K, Tri-state outputs for bi-directional control of
dampers and valves.
Metal Oxide Varistors (MOVs), Snubbers and Optocouplers on the DO-6-TR provide
2500 V isolation on each output, ensure noise-free operation, and, in most cases,
eliminate the need to install MOVs in the field.
FEATURES
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 20-26V. 24V for UL864 installations.
Power Consumption: 1.1 Watts (45 mA) @ 24 VDC (max.); normally provided
by Andover Continuum power supply module.
OUTPUTS
Output Type: 6 Form A optically isolated triac outputs (can be configured
up to 3 Form K Tri-State outputs)
Output Accuracy: 0.1 sec. for Pulse Width Modulation (PWM) control
I/O Connections
The actual output connections are located on a thirteen-position removable screw
terminal connector located at the bottom of the module.
The outputs are grouped in pairs of two connector terminals per channel. Each output
presents a normally open single pole set of contacts.
The diagram below indicates where each output number is located in the terminal block.
Connection Description
Earth Ground
1. OUT 1
2. OUT 1
3. OUT 2
4. OUT 2
5. OUT 3
6. OUT 3
7. OUT 4
8. OUT 4
9. OUT 5
10. OUT 5
11. OUT 6
12. OUT 6
Output Circuitry
OUT x
OUT x
These output contacts operate as a solid state relay. When the output is set to an “ON”
state, the contacts close allowing current to flow between the output terminals.
To use the Form A output in your system, configure an output point with an Electrical
Type of Digital.
When power is lost to the module or it loses contact with the NetController for more than
255 seconds, all outputs turn off. When power is finally restored, the module can
immediately restore the last state of the outputs or be delayed so the NetController can
update the state before energizing them. This option is called Output Restore Time and
its value can be set through a Numeric.
If the Output Restore Time numeric is not defined, the output will restore immediately
upon return of I/O power.
AC vs. DC
The first limitation is that they cannot be used with DC loads. A Triac switches AC only.
Tri-State Output
Although the module contains six separate form A relays, adjacent pairs of these can be
combined at any one time to form a standard Tri-state output:
OUT1 and OUT2
OUT3 and OUT4
OUT5 and OUT6
Configure the output point of the first point (OUT1, OUT3 or OUT5) with an Electrical
Type of Tri-state.
Caution: Do not attempt to use OUT2 and OUT3 or OUT4 and OUT5 as a tri-state pair.
An error message may result. Configure tri-state outputs as OUT1-OUT2, OUT3-OUT4 or
OUT5-OUT6.
Connect two outputs together to form a tristate output as follows (pair OUT1 and OUT2 is
shown):
OUT 1
+ ON
OUT 1
Common
OUT 2
OUT 2
ON
Status/Control Panel
Status Indicators
The DO-6-TR module includes a complete indicator status panel on the front of the
module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
This panel also includes two operator switches that perform the following:
LO-2, LO-2-O
Lighting Control Module
The LO-2, Andover Continuum’s lighting control module, can control 2 high voltage
lighting circuits, using externally mounted GE RR7 or RR9 lighting relays, rated for 277
VAC and 20 Amps (347 VAC option for Canada). The RR9 relay provides status
feedback of the relay position, using a built-in pilot contact. The RR7 relay provides
control of the circuit with no feedback. An on-board status LED for each output is
provided when RR9 relays are used, as well as pilot light voltage for wall switches that
have status indication. External 28 VAC is required to power the GE relays. This same
transformer can power the LO-2 when the module is located remotely.
An LO-2-O model, with on-board momentary override toggle switches, is also available.
FEATURES
• 2 Lighting Outputs
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 20-26V.
Power Consumption: 0.4 Watts (16 mA) @ 24 VDC (max.); provided by
Andover Continuum power supply module. Consumes no
DC power when external AC power is present.
External AC Power: 28 VAC powers both the module and lighting relays; can
also power the LO-2 module when mounted remotely.
External Transformer Size: 40 VA transformer provides power for up to 5 LO-2
modules (10 GE relays and associated devices).
Overload Protection: DC: 0.5 A resettable fuse with transient voltage suppressor
(TVS) and reverse polarity protection.
AC: 0.5 A resettable fuse with MOV.
INPUTS/OUTPUTS
Inputs: 2 Class II Low Voltage override inputs, providing direct
control of lighting relays
Input Protection: Transient voltage suppressors (TVS) with reverse polarity
protection
Outputs:
The diagram below indicates where each output number is located in the terminal block.
Connection Description
Earth Ground
1. GND for 24–30V Ext. Power
2. 24–30V External VAC
3. OUT 1 RED
4. OUT 1 BLK
5. OUT 1 YEL
6. OUT 1 WHT
7. OUT 2 RED
8. OUT 2 BLK
9. OUT 2 YEL
10. OUT 2 WHT
11. 24 VAC RECT
Electrical Description
The outputs of the LO-2 module are digital in nature (ON or OFF) yet are designed
specifically to control lighting. The two outputs are electrically connected (via cable) to an
external bracket where two GE-style lighting relays (RR-7 or RR-9) have been mounted.
Both outputs can be controlled via program or be activated manually through override
switches (LO-2-O only) on the front panel. An external momentary switch (a push button,
motion detector or other occupancy sensor) can be wired to control each of the relays as
well.
The GE relays mechanically latch in the ON position when energized. The relay remains
ON until set to OFF from the program or any external override controls. RR-9 relays also
provide operational status information (ON or OFF) that can be read via Plain English
commands. The OUTPUT indicators on the front panel illuminate if the RR-9 relay output
is ON.
Override Controls
The LO-2-O model includes a built-in output override switch for each output.
ON
OFF
The operation of the relays can be operated from program control or manual control
using the front panel mounted override switches or externally wired controls.
The following describes the actions associated with each position of the override controls:
Lighting Control
The LO-2 can be coupled with Andover Continuum’s programmable input modules to
provide flexible lighting control strategies such as:
These programs can be easily modified to fit the exact needs of your project.
Electrical Installation
External Power
The GE relays are powered by an external 28 VAC source. The LO-2 module has been
designed to utilize this external power source as its own module supply source as well. It
is not necessary to power the module in this way. However, if the LO-2 is located
remotely from your main power source, you may want to power the module locally
thereby eliminating the two extra wires necessary to bring power to the module from the
Andover Continuum power supply. It also lessens the load requirements on that supply.
28 VAC
Transformer
PWR
24-30 VAC
GND
Relays
The GE relays are mounted externally and are connected to the LO-2 via a connecting
cable. This cable terminates in a five-pin Molex-style connector that mates easily with
one of the two headers provided at the bottom of the module as shown below:
The connector is keyed so that it locks into place after insertion. The connector on the left
is output relay #1 and the one on the right is output relay #2. External relays are attached
to the provided cable by matching the colors to those attached to the relay.
The following indicates the connections for each pin of the relay connector:
1 2 3 4 5 1 2 3 4 5
OFF ON
RED
BLK
OVERRIDE
YEL
WHT
Momentary Switch
OFF ON
RED
BLK
Indicator OVERRIDE
YEL
WHT
RED
BLK
OVERRIDE
YEL
OFF ON
RED
BLK
OVERRIDE
YEL
WHT
RED (ON)
RED
BLK
BLK
(OFF)
YEL
WHT
WHT
(COM)
BLU 28 VAC
(POWER) RECT.
Status/Control Panel
Status Indicators
The LO-2 module includes a complete indicator status panel on the front of the module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
This panel also includes two operator switches that perform the following:
DIO-20
Input/Output Expansion Module
The DIO 20 provides a connection for up to 20 solid state input or output modules for the
Andover Continuum DM-20 Digital I/O module. The DIO 20 module can be mounted via a
DIN Rail or directly to a panel. The DIO 20 includes individually fused sockets for up to 20
solid state input/output modules from manufacturers such as Opto 22, Grayhill, Gordos,
Crydom and Potter & Brumfield.
FEATURES
SPECIFICATIONS
ELECTRICAL
Power Supply Range: 24 VDC
Power Consumption: All input modules installed: 12.7 Watts (529 mA) max;
provided by an external power supply module.
All output modules installed: 8.5 Watts (354 mA) max;
provided by an external power supply module.
DIO-20 board alone: 20mA
Input Module max current: 23mA
Output Module max current: 16mA
External Power Connector: Two-position terminal block
Outputs:
Output Type: Output ratings depend on input
module(s) selected.
* These manufacturers and model numbers represent devices that should be compatible. Their physical
and electrical specifications appear to meet those of our product. However, this list does not constitute
an endorsement of the product nor does it imply that the specifications listed are accurate. Ratings listed
are nominal. Refer to manufacturer’s data sheets for limitations.
DIO-20 Installation
The DIO-20 (which includes the DIO 20 printed circuit board, three plastic PCB mounting
brackets, and three plastic DIN rail mounting brackets) can be mounted to either a DIN
Rail or directly to a bulkhead. The following are additional items required for installing the
DIO-20:
1. Slide an end clamp into position on the DIN Rail. Tighten the holding screws.
End Clamp
DIN Rail
PCB
Mounting
Bracket
DIN Rail
Mounting
Bracket
2. Slide a DIN Rail Mounting Bracket under the PCB mounting bracket until flush on
the back side.
There are four #6-sized holes (0.156” (4mm)) provided at the corners and one in the
center for mounting using stand-offs directly to a flat surface. The following illustrates the
mounting dimensions of the module.
2.05”(52)
4.3”
3.88 “ (98) (108)
16.1 “ (409)
25-pin D Cable
from DO80-LED
or DM-20 Module
25-Pin D Connector
1 I/O 1 13 I/O 13
2 I/O 2 14 I/O 14
3 I/O 3 15 I/O 15
4 I/O 4 16 I/O 16
5 I/O 5 17 I/O 17
6 I/O 6 18 I/O 18
7 I/O 7 19 I/O 19
8 I/O 8 20 I/O 20
9 I/O 9 21 Ground
10 I/O 10 22 Ground
11 I/O 11 23 Ground
12 I/O 12 24 Ground
25 Ground
1 I/O 1 21 I/O 11
2 I/O 1 22 I/O 11
3 I/O 2 23 I/O 12
4 I/O 2 24 I/O 12
5 I/O 3 25 I/O 13
6 I/O 3 26 I/O 13
7 I/O 4 27 I/O 14
8 I/O 4 28 I/O 14
9 I/O 5 29 I/O 15
10 I/O 5 30 I/O 15
11 I/O 6 31 I/O 16
12 I/O 6 32 I/O 16
13 I/O 7 33 I/O 17
14 I/O 7 34 I/O 17
15 I/O 8 35 I/O 18
16 I/O 8 36 I/O 18
17 I/O 9 37 I/O 19
18 I/O 9 38 I/O 19
19 I/O 10 39 I/O 20
20 I/O 10 40 I/O 20
The AC-1 provides a Wiegand card input for Wiegand and Proximity type cards, reading
up to 64 bits per card. Reader power is switch-selectable between 5 volts and 12 Volts to
meet most card reader power requirements.
The AC-1 provides two 5 Amp, Form C relays⎯one for the door lock and a second for
local alarm annunciation. Each output has an integral hand-off-auto switch for manual
operation, and software feedback of the switch position.
Up to three supervised alarm inputs can be used for door status contacts, request-to-exit
devices, a cabinet tamper switch, and any other two-state or three-state (on/off/trouble)
alarm device.
Keypad Control
The AC-1 supports Wiegand output keypads. To simplify installation and reduce wiring
costs, the keypad data comes into the module via the reader data lines.
FEATURES
• 1 Card Reader Input
• +5 V or +12 V reader power (switch
selectable)
• 1 Card Reader LED control output
• Up to 3 Supervised Inputs
• 2 FormC Relay Outputs rated
24 VAC/DC @ 5A
• Override Toggle Switches
w/Override Detection and Feedback
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 20-26V. 24V UL294 installations.
Power Consumption: 2.6 Watts + (15 Volts) * (Reader Current) max. @ 24 VDC;
normally provided by Andover Continuum power supply module.
Overload Protection: 0.5 A resettable fuse with transient voltage suppressor
(TVS) and reverse polarity protection
INPUTS/OUTPUTS
Inputs
Card Readers: 1
Card Reader Type: Wiegand and Proximity readers *
Maximum Number
of bits/Card: 64
Card Reader Power: +5 V or +12 V (switch selectable)
Switch Setting Output Voltage Output Current
+5 V +5.20 V ±0.05V 120 mA (max.)
+12 V +12.0 V ±5% 180 mA (max.)
Wiring Distance:
Card Reader to AC-1: 500 ft. max. using 18-gauge wire
200 ft. max. using 22-gauge wire
* The following reader and keypad models are the only approved for use in UL 294 Access Control
applications:
Essex KTP-163-SN keypad; HID Epic 32985 reader; Indala ASR-500 reader.
I/O Connections
The actual I/O connections are located on a sixteen-position removable screw terminal
connector located at the bottom of the module. Wires should enter from either the top or
bottom wiring troughs, and outputs should come from the right side of the rack, inputs
from the left (by convention).
The diagram below indicates where each output number is located in the terminal block.
Connection Description
Earth Ground
1. Reader +V
2. Reader GND
3. Reader DATA (Wiegand I)
4. Reader CLK (Wiegand 0)
5. Reader LED
6. Sup Input Aux
7. Sup Input Door
8. Sup Input REX
9. Sup Input RETURN
10. Door NC
11. Door NO
12. Door COM
13. OUT2 NC
14. OUT2 NO
15. OUT2 COM
Caution: Make sure the Reader Power switch is set properly. Setting the switch to
12 V for a 5 V reader may damage the unit.
READER
POWER
+ 5V, 120mA
+ 12V, 180mA
Degrade Mode
If network communications are interrupted, as a fail-safe mode, the AC-1 will revert to a
programmable degraded mode of operation. System operation during degrade mode
provides uninterrupted card access using site codes, cards formats, and other degrade
mode parameters stored in non-volatile EEPROM in each AC-1 module.
Degrade mode parameters are configured from the “Access Validation” section of the
door editor’s “Entry Reader” tab. For dual reader doors, configurable degrade mode
parameters are available from the “Access Validation” section of the door editor’s “Exit
Reader” tab.
Two of the site codes entered on the “Card Formats” tab of the door editor (out
of four supported by the door during normal operation). The site codes
supported are Site1 and Site2.
One card type (determined below)
In NetController version 1.4 and forward, when more than one card type is selected at the
door, the following procedure determines which one of the card types the AC-1 stores for
degrade mode operation:
1. Open the door editor and de-select all card types except the one that you want
the AC-1 to store for degrade mode operation.
2. Save the door settings by clicking “Apply”.
3. Select the other card types that will be allowed at the door in normal operation.
4. Save the door settings again by clicking “Apply” or “OK” to save and close the
door editor.
WARNING: The AC-1 is not recommended for use with inverted door output
installations. For inverted door output installations, use the AC-1A or AC-
1 Plus modules.
Connecting a Reader/Keypad
Reader/Keypad Inputs
The AC-1 includes a full interface to a single Wiegand access card reader. The modules
were designed to allow integral reader/keypad units to be connected directly. Separate
keypads that have similar interfaces (Wiegand) can be connected in parallel with a reader
through the use of the Keypad Interface Module as shown on the following page.
The Wiegand reader and/or reader/keypad unit is connected to the AC-1 module as
shown below:
+V 5V
12 V
GND
+V
GND
Wiegand DATA / I
DATA I
Reader
or DATA 0
Reader with Keypad LED
CLK / 0
LED
Note: The KIM is not approved for use with UL 294 Access Control Systems.
AC-1
+V
GND
+V
GND
Wiegand Reader
LED
or
Reader with Keypad DATA 1
or Keypad only CLK 0
LED
DATA / I
CLK / 0 P1
DATA / I DATA / I
P2
CLK / 0 CLK / 0
DATA / I
CLK / 0
DATA 1
CLK 0
Wiegand Reader LED
or
GND
Reader with Keypad
or Keypad only +V
Door
Supervised Input
Door
Switch
Door
AC-1 Exit IOU Strike
Supervised
Input Resistor
Configuration
(Corresponds to
type of supervised
input on AC-1
Exit Reader Reader Entry IOU)
1-Door
NOTE: As the door switch connects only to the Entry IOU, the door switch operation at
the Exit IOU is not supported in degrade mode.
NOTE: The resistor configuration on the AC-1 Exit IOU matches the resistor configuration
of the supervised input type. (Examples: NC Series, NC Series Parallel, or NO Series
Parallel.) Connect only the resistor across the input, not any other wire connections.
NC Series
With this type of input wiring, a resistor is placed in series with the input being monitored.
When the input contact presents a short circuit (normal closed position) the input is
assumed in a normal closed state, the circuit presents a reading of 10 K Ωs at the input.
When the input contact is opened, the circuit opens and an infinite resistance is
measured. If the wires to the input contact are cut it also appears as an “Input Contact
Open” condition. In this case there would be an input contact open without a valid card
swipe or valid keypad entry resulting in an “Input Contact Violation”. Shorting the input
causes a zero Ω resistance, which also results in an input contact violation.
ElecType: Supervised
Resistor Type: NCSeries
When the input contact is opened the switch opens and the value of the parallel resistor
is measured. If the wires to the input contact are cut it appears as an infinite resistance.
Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance
(open) should result in an error condition.
ElecType: Supervised
Resistor Type: NCSerPar
NO Series Parallel
With this type of input wiring, two external resistors are added to the input, one in series
and the other in parallel. When the input contact switch is open (normal position), the
input contact is assumed to be closed. The circuit reads the value of the parallel resistor.
When the input contact is opened, the switch closes and a reading results that is
composed of both resistances in parallel that works out to be half the value of one of
them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance.
Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance
(open) should result in an error condition.
ElecType: Supervised
Resistor Type: NOSeriPar
Some switches have built-in resistors that facilitate Series Parallel connections as shown
below:
Switch with AUX
Built-In Resistor or
DOOR
or
REX
10 KΩ
RET
Wiring is similar to a normal door switch input; however, the motion sensor requires an
external power supply of 12 VDC or 24 VDC (UL listed under APHV). The maximum
length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of
#22 gauge wire (60 m of 0.35 mm2 wire).
The following shows a typical motion detector circuit:
No AUX
Motion or
Detected DOOR
or
REX
Normally Open 10 KΩ
PIR Motion
Detector
RET
Motion AUX
Detected or
DOOR
or
REX
Normally Open 10 KΩ
PIR Motion
Detector
RET
Connecting Outputs
The AC-1 module includes two Form C single-pole double-throw relay outputs. The
following is a simplified schematic of each output channel:
OUT x NC
OUT x NO
OUT x COM
Note: When configuring a Digital point, there is a “Polarity” attribute. If this attribute is
enabled, the operation of the outputs are reversed.
Override Controls
The AC-1 module includes an output override switch for each output.
ON
OFF
AUTO
The output of the module can be directed from program control or manual control. The
output can be disabled completely as well.
The following describes the actions associated with each position of the override controls:
This configuration shows a normally de-energized lock (when secured) in a fail secure
mode. If power loss occurs, the lock closes. Always be sure to use “panic” hardware that
allows emergency exit from the secured area.
The following represents a typical door output installation when the dual reader door
circuit is controlling a fail-secure lock:
Status/Control Panel
Status Indicators
The AC-1 module includes a complete indicator status panel on the front of the module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
OVERRIDE This red indicator illuminates whenever any of the override switches is in
a position other than AUTO.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
+5V, +12V These green indicators illuminate when either voltage is selected as the
reader power source.
This panel also includes two operator switches that perform the following:
AC-1A
Access Control Module
The AC-1A, Access Control Module, provides full I/O for an access controlled door or
portal in one compact module. The AC-1A can be remotely located at a door reader for
localized control and reduced wiring costs; or several AC-1A modules can be grouped
together and DIN rail-mounted for centralized control.
The AC-1A provides a Wiegand card input for Wiegand and Proximity type cards, reading
up to 64 bits per card. Reader power (5 volts) is provided to meet most card reader
power requirements.
The AC-1A includes two 5 Amp, Form C relays⎯one for the door lock and a second for
local alarm annunciation. Each output has an integral hand-off-auto switch for manual
operation, and software feedback of the switch position.
Up to three supervised alarm inputs can be used for door status contacts, request-to-exit
devices, a cabinet tamper switch, and any other two-state or three-state (on/off/trouble)
alarm device.
Keypad Control
The AC-1A supports Wiegand output keypads. To simplify installation and reduce wiring
costs, the AC-1A has a second set of connections.
FEATURES
• 1 Card Reader Input*
• 1 Keypad Input*
* Only one of these two devices can be active
at any given moment.
• +5 V reader power
• 1 Card Reader LED control output
• Up to 3 Supervised Inputs
• 2 FormC Relay Outputs rated
24 VAC/DC @ 5A
• Override Toggle Switches
w/Override Detection and Feedback
• 10–28 V Power Supply Range
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 10-28V. 24V for UL864 and UL294
installations.
Power Consumption: 2.0 Watts + (Input Voltage) * (Reader Current) max. @ 24 VDC;
normally provided by Andover Continuum power supply module.
Overload Protection: 0.5 A resettable fuse with transient voltage suppressor
(TVS) and reverse polarity protection
INPUTS/OUTPUTS
Inputs
Card Readers: 1*
Keypads: 1*
Card Reader Type: Wiegand and Proximity readers
Maximum Number
of bits/Card: 64
Wiring Distance:
To Card Reader: 500 ft. max. using 18-gauge wire
200 ft. max. using 22-gauge wire
Alarm Inputs: Up to 3 supervised inputs. Single or double resistor
supervision, series or parallel.
* Only one of these two devices can be active at any given moment.
Outputs
Door Outputs: 2 Form C relays
Output Rating: 24 VAC/VDC @ 5 Amp
Reader LED Output: Open collector; up to 100 mA.
Output Protection: 5000 V isolation 270 V MOVs on each output
Overrides: 3-position manual override switch on each output for
manual control of relay. LED override status indicator.
I/O Connections
The actual I/O connections are located on an eighteen-position removable screw terminal
connector located at the bottom of the module. Wires should enter from either the top or
bottom wiring troughs, and outputs should come from the right side of the rack, inputs
from the left (by convention).
The diagram below indicates where each output number is located in the terminal block.
Connection Description
Earth Ground
1. Reader +5V
2. Reader GND
3. Reader DATA (Wiegand I)
4. Reader CLK (Wiegand 0)
5. Keypad DATA (Wiegand I)
6. Keypad CLK (Wiegand 0)
7. Reader LED
8. Sup Input 1 Aux
9. Sup Input 2 Door
10. Sup Input 3 REX
11. Sup Input RETURN
12. 1-Door NC
13. 1-Door NO
14. 1-Door COM
15. OUT2 NC
16. OUT2 NO
17. OUT2 COM
Degrade Mode
If network communications are interrupted, as a fail-safe mode, the AC-1A will revert to a
programmable degraded mode of operation. System operation during degrade mode
provides uninterrupted card access using site codes, cards formats, and other degrade
mode parameters stored in non-volatile EEPROM in each AC-1A module.
Degrade mode parameters are configured from the “Access Validation” section of the
door editor’s “Entry Reader” tab. For dual reader doors, configurable degrade mode
parameters are available from the “Access Validation” section of the door editor’s “Exit
Reader” tab.
Two of the site codes entered on the “Card Formats” tab of the door editor (out
of four supported by the door during normal operation). The site codes
supported are Site1 and Site2.
One card type (determined below)
Note: In the NetController version 1.4 and forward, when more than one card type is
selected at the door, the following procedure determines which one of the card types the
AC-1A stores for degrade mode operation:
1. Open the door editor and de-select all card types except the one that you want
the AC-1A to store for degrade mode operation.
2. Save the door settings by clicking “Apply”.
3. Select the other card types that will be allowed at the door in normal operation.
4. Save the door settings again by clicking “Apply” or “OK” to save and close the
door editor.
Connecting a Reader/Keypad
Reader/Keypad Inputs
The AC-1A includes a full interface to a single Wiegand access card reader and a
keypad. The modules were designed to allow Integral reader/keypad units to be
connected directly. Separate keypads that have similar interfaces (Wiegand) can be
connected through the keypad connections provided on the terminal block.
The Wiegand reader, keypad and/or reader/keypad unit is connected to the AC-1A
module as shown below:
+ 5V
GND
+V
LED
Similarly, two readers can be connected. This allows a site to slowly introduce a different
type of reader (i.e., proximity) while allowing access through the normal reader. The
connections are as shown below:
AC-1A
+ 5V
1
GND
2
+V
GND
Wiegand Reader LED
or
DATA 1
Wiegand Keypad
CLK 0
LED
7
DATA / I
3
CLK / 0
4
DATA / I
5
CLK / 0
6
DATA 1
CLK 0
Wiegand Reader LED
or
Wiegand Keypad GND
+V
Request to
AC-1A Entry IOU Exit Device
Supervised Input
REX
Door
Supervised
Input Door
Switch
Door
AC-1A Exit IOU Strike
1-Door
Note:
As the door switch connects only to the Entry IOU, the door switch operation at the
Exit IOU is not supported in degrade mode.
NC Series
With this type of input wiring, a resistor is placed in series with the input being monitored.
When the input contact presents a short circuit (normal closed position), the input is
assumed to be in a normal closed state, the circuit presents a reading of 10 K Ωs at the
input.
When the input contact is opened, the circuit opens and an infinite resistance is
measured. If the wires to the input contact are cut it also appears as an “input contact
open” condition. In this case there would be an input contact open without a valid card
swipe or valid keypad entry resulting in an “input contact violation”. Shorting the input
causes a zero Ω resistance, which also results in an input contact violation.
ElecType: Supervised
Resistor Type: NCSeries
When the input contact is opened, the switch opens and the value of the parallel resistor
is measured. If the wires to the input contact are cut it appears as an infinite resistance.
Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance
(open) should result in an error condition.
ElecType: Supervised
Resistor Type: NCSerPar
NO Series Parallel
With this type of input wiring, two external resistors are added to the input, one in series
and the other in parallel. When the input contact switch is open (normal position) the
input contact is assumed to be closed. The circuit reads the value of the parallel resistor.
When the input contact is opened the switch closes and a reading results that is
composed of both resistances in parallel that works out to be half the value of one of
them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance.
Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance
(open) should result in an error condition.
ElecType: Supervised
Resistor Type: NOSeriPar
Some switches have built-in resistors that facilitate Series Parallel connections as shown
below:
10 KΩ
RET
Wiring is similar to a normal door switch input, however, the motion sensor requires an
external power supply of 12 VDC or 24 VDC (UL listed under APHV). The maximum
length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of
#22 gauge wire (60 m of 0.35 mm2 wire).
No AUX
Motion or
Detected DOOR
or
REX
Normally Open 10 KΩ
PIR Motion
Detector
RET
Motion AUX
Detected or
DOOR
or
REX
Normally Open 10 KΩ
PIR Motion
Detector
RET
OUT x NC
OUT x NO
OUT x COM
NOTE: When configuring a Digital point, there is a ‘Polarity’ attribute. If this attribute is
enabled, the operation of the outputs are reversed.
Override Controls
The AC-1A module includes an output override switch for each output.
ON
OFF
AUTO
The output of the module can be directed from program control or manual control. The
output can be disabled completely as well.
The following describes the actions associated with each position of the override controls:
MOV
(Andover #01-2020-095)
C
Door Strike
(UL listed burglary-resistant
electric locking mechanism (CVXY))
12/24V
Power Supply
(UL listed power supply (APHV))
This configuration shows a normally de-energized lock (when secured) in a fail secure
mode. If power loss occurs, the lock closes. Always be sure to use “panic” hardware that
allows emergency exit from the secured area.
The following represents a typical door output installation when the circuit is normally
closed:
MOV
(Andover #01-2020-095)
12/24V
Power Supply
(UL listed power supply (APHV))
This configuration shows a normally de-energized lock (when secured), in a fail safe
mode. If power loss occurs, the lock opens.
The following represents a typical door output installation when the dual reader door
circuit is controlling a fail-secure lock:
Exit IOU
Entry IOU
MOV
(Andover #01-2020-095)
C
Door Strike
Fail-Secure
(UL listedDoor Lock
burglary-resistant
(Energize
electric to unlock)
locking mechanism (CVXY))
UL-listed burglary-resistant
Electric locking mechanism (CVXY)
12/24V
Power Supply
(UL listed power supply (APHV))
The following represents a typical door output installation when the dual reader door
circuit is controlling a fail-safe lock:
Exit IOU
MOV
(Andover #01-2020-095)
Entry IOU
Electromagnetic
Fail-Safe Door LockDoor Lock
(UL listed
(Energize toburglary-resistant
lock)
electric locking mechanism (CVXY))
UL-listed burglary-resistant
Electric locking mechanism (CVXY)
12/24V
Power Supply
(UL listed power supply (APHV))
Status/Control Panel
Status Indicators
The AC-1A module includes a complete indicator status panel on the front of the module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
OVERRIDE This red indicator illuminates whenever any of the override switches is in
a position other than AUTO.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
+5V This green indicator illuminates when the reader power source is
operational.
Andover Continuum I/O System Reference 165
AC-1A
This panel also includes two operator switches that perform the following:
AC-1 Plus
Access Control Module
The AC-1 Plus, Access Control Module, provides full I/O for an access controlled door or
portal in one compact module. The AC-1 Plus can be remotely located at a door reader
for localized control and reduced wiring costs; or several AC-1 Plus modules can be
grouped together and DIN rail-mounted for centralized control.
The AC-1 Plus provides a reader input connection for Wiegand/ABA/CK34 and Proximity
type cards, reading up to 64 bits per card for Wiegand cards and 255 bits per card for
ABA cards. Reader power (5 volts) is provided to meet most card reader power
requirements.
The AC-1 Plus includes two 5 Amp, Form C relays⎯one for the door lock and a second
for local alarm annunciation. Each output has an integral hand-off-auto switch for manual
operation, and software feedback of the switch position.
Up to five supervised alarm inputs can be used for door status contacts, ADA request-to-
exit devices, a cabinet tamper switch, and any other two-state or three-state
(on/off/trouble) alarm device.
Keypad Control
The AC-1Plus supports Wiegand output keypads. To simplify installation and reduce
wiring costs, the keypad data comes into the module via the reader data lines.
FEATURES
• 1 Card Reader Input*
• 1 Keypad Input*
♦ *Only one of these two devices can be
active at any given moment.
• Wiegand/ABA or CK34 formats
supported
• +5 V reader power
• 2 Card Reader LED control outputs
• Up to 5 Supervised Inputs
• 2 FormC Relay Outputs rated
24 VAC/DC @ 5A
• Override Toggle Switches
w/Override Detection and Feedback
• Supports Bond Sensor and ADA
input switches
INPUTS/OUTPUTS
Inputs
Card Readers: 1*
Keypad: 1*
* Only one of these two devices can be active at any given moment.
Card Reader Type: Wiegand, ABA or CardKey (switch selectable) **
Maximum Number 64 (Wiegand)
of bits/Card: 255 (ABA)
** The following reader and keypad models are the only approved devices for use in UL 294
Access Control applications:
Essex KTP-163-SN keypad; HID Epic 32985 Wiegand reader; Indala ASR-500 Wiegand reader.
Outputs
Door Outputs: 2 Form C relays
Output Rating: 24 VAC/VDC @ 5 Amp
Reader LED Output: (2) each, open collector; up to 100 mA.
Output Protection: 5000 V isolation 270 V MOVs on each output
Overrides: 3-position manual override switch on each output for
manual control of relay. LED override status indicator.
Override Feedback: Override detection and software feedback provided for
each output.
I/O Connections
The actual I/O connections are located on a sixteen-position removable screw terminal
connector located at the bottom of the module. Wires should enter from either the top or
bottom wiring troughs, and outputs should come from the right side of the rack, inputs
from the left (by convention).
The diagram below indicates where each output number is located in the terminal block.
Connection Description
1. Reader +5V
2. Reader GND
3. Reader DATA (Wiegand I)
4. Reader CLK (Wiegand 0)
5. Keypad DATA (Wiegand I)
6. Keypad CLK (Wiegand 0)
7. Reader LED1
8. Reader LED2
9. Earth Ground
10. IN1
11. IN2
12. RET
13. IN3
14. IN4
15. RET
16. IN5
17. OUT1 NC
18. OUT1 NO
19. OUT1 COMM
20. OUT2 NC
21. OUT2 NO
22. OUT2 COMM
The AC-1 Plus also supports ADA (Alternate Door Access) and inverted door output
installations and Bond Sensor circuitry. A bond sensor detects the actual status (locked
or unlocked) of the door.
Reader Power
The AC-1 Plus module supports 5 volt DC readers.
Degrade Mode
If network communications are interrupted, as a fail-safe mode, the AC-1 Plus will revert
to a programmable degraded mode of operation. System operation during degrade
mode provides uninterrupted card access using site codes, cards formats, and other
degrade mode parameters stored in non-volatile EEPROM (such as the settings of the
AccessLEDPattern Numeric) in each AC-1 Plus module.
Degrade mode parameters are configured from the “Access Validation” section of the
door editor’s “Entry Reader” tab. For dual reader doors, configurable degrade mode
parameters are available from the “Access Validation” section of the door editor’s “Exit
Reader” tab.
All four site codes entered on the “Card Formats” tab of the door editor
All card types selected on the “Card Formats” tab of the door editor
ADA functionality
General codes (Keypad)
Door Switch operation on both the Entry and Exit IOU of a dual-reader door
ReaderLED Description
Solid Red No door configured on this reader channel. The
system will not process any transaction coming
from this reader
Solid Green Door configured on this reader channel. System
is ready to process an access transaction (i.e.
card swipe)
Solid Red for 3 seconds Invalid Attempt
following an access transaction
Rapid Flashing following an Valid Access
access transaction
Slow Flashing following an System is waiting for information needed to
access transaction process the transaction. I.e. Transaction is
being processed (remote validation) or the
system is waiting for user entry (PIN needed
after card swipe).
NOTE1: Starting in V1.1, LED2 will turn ON whenever the door is open. This can be
used to control another indicator LED, such as a keypad LED.
NOTE2: A manual override does not affect the Reader LED for the Schneider Electric
LED pattern.
ReaderLED Description
Solid Red Door is locked
Solid Green Door is unlocked
Rapid Flashing following an Invalid attempt
access transaction
Slow Flashing following an System is waiting for information needed to process
access transaction the transaction. I.e. Transaction is being processed.
(remote validation) or the system is waiting for user
entry. (PIN needed after card swipe)
NOTE: Starting in V1.1, LED2 will turn ON whenever the door is open. This can be
used to control another indicator LED, such as a keypad LED.
NOTE1: The 12V incandescent lamp power is not provided by the AC-1plus.
NOTE2: The RED lamp is controlled by the LED1 output and the GREEN lamp is
controlled by the LED2 output.
This LED pattern was designed to be used with the Dorado Model 780 ABA
Reader/Keypad.
NOTE1: The dipswitches on the Dorado Model 780 must be set for CLOCK/DATA
operation.
NOTE2: The LED1 output on the AC-1plus is wired to the LED A input on the Dorado
Model 780, and the LED2 output is wired to the LED B input.
For example:
• A user can enter a string that a PE program uses to turn lights or fans on or off, or to
control other HVAC equipment.
• A user can enter a string indicating the user’s purpose for entering an area. The PE
program can capture this information as input to a PE program for tracking reasons
for activity in a secure area.
Before you can use the keypad for PE program input, you must create a Plain English
program that processes the string entered at the keypad and returns a value to the AC-1
Plus based on the entry. In addition, you must create the following objects in the
controller:
• An InfinityString object that stores the input from channel 7 of the AC-1 Plus and that
your PE program reads to obtain the content of the string
• An InfinityOutput object that stores a numeric value specified in the PE program and
sent to channel 4 of the AC-1 Plus (See “PE Feedback to the AC-1 Plus” later in this
section.)
You can use Continuum Explorer in CyberStation to create the InfinityString and
InfinityOutput objects in the controller.
The process for entering string input at a keypad has the following steps:
1. The user presents a valid access card and/or PIN (if a PIN is required) to the
door reader.
2. The controller for this reader accepts the user’s credentials, and the door
unlocks.
3. Within three seconds of the door unlocking, the user enters two consecutive
asterisks ( ** ) at the keypad to enter escape sequence mode.
4. The keypad LED flashes slowly to indicate that it is waiting for input.
5. The user enters a numeric string of up to 30 characters (not including the two
asterisks), and then terminates the string with the pound sign (#).
The following rules apply to using a keypad connected to the AC-1 Plus to enter string
input:
• After the door unlocks, if more than 3 seconds elapse before the user enters two
asterisks, the AC-1 Plus exits escape sequence mode. The user must begin the
process for string input again.
• If a user enters more than 30 characters (not including the first two asterisks), the
AC-1 Plus detects when the 31st digit is entered. The AC-1 Plus then replaces the
30th character with T to indicate Tamper, and sends the string to the controller (no #
is needed). Subsequent characters entered as part of the string are ignored.
• The user can enter asterisks within the string if needed. These asterisks are
converted to periods when sent to the PE program.
• If more than 4 seconds elapse between keystrokes, the AC-1 Plus exits escape
sequence mode. The user must begin the process for string input again.
• If a user presents an access card to the card reader while the AC-1 Plus is in escape
sequence mode, the AC-1 Plus exits escape sequence mode. The user must begin
the process for string input again.
After the PE program receives the string input and interprets its value, the program
assigns an appropriate value to the InfinityOutput object. One of the following values is
transmitted back to the AC-1 Plus through channel 4:
1 – Clear string.
NOTE: Clearing the string in the AC-1 Plus using the Clear String command is
recommended after each string input in escape sequence mode.
Based on the numeric value returned to the AC-1 Plus through channel 4, the AC-1 Plus
also uses the reader LEDs to indicate to the user whether or not the string input is valid
or invalid. The LED pattern to indicate valid/invalid entry is the same as the selected
access control LED pattern used to indicate valid/invalid card and PIN entry.
Connecting a Reader/Keypad
Reader/Keypad Inputs
The AC-1 Plus includes a full interface to a single Wiegand, ABA or CardKey access card
reader. The module is designed to allow Integral reader/keypad units to be connected
directly. Separate keypads that have similar interfaces can be connected in parallel with a
reader by using the auxiliary input connector as shown on the following page.
The reader and/or reader/keypad unit is connected to the AC-1 Plus module as shown
below:
5V
GND
+V
GND
Reader DATA / I
DATA I
or
Reader with Keypad DATA 0
LED
CLK / 0
LEDx
Similarly, two readers can be connected. This allows a site to slowly introduce a different
type of reader (i.e., proximity) while allowing access through the normal reader.
AC-1 Plus
1 5V
2 GND
+V
GND
Reader
LED
or
Reader with Keypad DATA 1
or Keypad only CLK 0
7 LED1
3 DATA / I
4 CLK / 0
5 DATA / I
6 CLK / 0
8 LED2
DATA 1
CLK 0
Reader LED
or
GND
Reader with Keypad
or Keypad only +V
Make sure the reader type switch is set to the CK34 position when using a CardKey
reader.
*
Alarm Supervised Input Bond
Termination
Out Out2 IN1 Sensor
Out1
Door
Strike
*
Supervised Input
Termination
IN1
Out1
* TERMINATION
Each input must be terminated using your chosen Supervised
Input resistor arrangement. It is important that BOTH AC-1 Plus
modules include termination where they share door switches
and/or Bond sensors.
NC Series
With this type of input wiring, a resistor is placed in series with the input being monitored.
When the input contact presents a short circuit (normal closed position) the input is
assumed in a normal closed state, the circuit presents a reading of 10 KΩs at the input.
When the input contact is opened, the circuit opens and an infinite resistance is
measured. If the wires to the input contact are cut it also appears as an “input contact
open” condition. In this case there would be a input contact open without a valid card
swipe or valid keypad entry resulting in an “input contact violation”. Shorting the input
causes a zero Ω resistance, which also results in an input contact violation.
ElecType: Supervised
Resistor Type: NCSeries
When the input contact is opened the switch opens and the value of the parallel resistor
is measured. If the wires to the input contact are cut it appears as an infinite resistance.
Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance
(open) should result in an error condition.
ElecType: Supervised
Resistor Type: NCSerPar
NO Series Parallel
With this type of input wiring, two external resistors are added to the input, one in series
and the other in parallel. When the input contact switch is open (normal position) the
input contact is assumed to be closed. The circuit reads the value of the parallel resistor.
When the input contact is opened the switch closes and a reading results that is
composed of both resistances in parallel that works out to be half the value of one of
them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance.
Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance
(open) should result in an error condition.
ElecType: Supervised
Resistor Type: NOSeriPar
10 KΩ
RET
Wiring is similar to a normal door switch input, however, the motion sensor requires an
external power supply of 12 VDC or 24 VDC (UL listed under APHV). The maximum
length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of
#22 gauge wire (60 m of 0.35 mm2 wire).
No AUX
Motion or
Detected DOOR
or
REX
Normally Open 10 KΩ
PIR Motion
Detector
RET
Motion AUX
Detected or
DOOR
or
REX
Normally Open 10 KΩ
PIR Motion
Detector
RET
Connecting Outputs
The AC-1 Plus module includes two Form C single-pole double-throw relay outputs. The
following is a simplified schematic of each output channel:
OUT x NC
OUT x NO
OUT x COM
Override Controls
The AC-1 Plus module includes an output override switch for each output.
ON
OFF
AUTO
The output of the module can be directed from program control or manual control. The
output can be disabled completely as well.
The following describes the actions associated with each position of the override controls:
MOV
(Andover #01-2020-095)
C
Door Strike
(UL listed burglary-resistant
electric locking mechanism (CVXY))
12/24V
Power Supply
(UL listed power supply (APHV))
This configuration shows a normally de-energized lock (when secured) in a fail secure
mode. If power loss occurs, the lock closes. Always be sure to use “panic” hardware that
allows emergency exit from the secured area.
The following represents a typical door output installation when the circuit is normally
closed:
MOV
(Andover #01-2020-095)
12/24V
Power Supply
(UL listed power supply (APHV))
This configuration shows a normally de-energized lock (when secured) in a fail safe
mode. If power loss occurs, the lock opens.
The following represents a typical door output installation when the dual reader door
circuit is controlling a fail-safe lock:
Exit IOU
Entry IOU
MOV
(Andover #01-2020-095)
C
Door Strike
Fail-Safe
(UL listed Door Lock
burglary-resistant
(Energize
electric to lock)
locking mechanism (CVXY))
UL-listed burglary-resistant
Electric locking mechanism (CVXY)
12/24V
Power Supply
(UL listed power supply (APHV))
The following represents a typical door output installation when the dual reader door
circuit is controlling a fail-secure lock:
Exit IOU
MOV
(Andover #01-2020-095)
Entry IOU
Electromagnetic
Fail-Secure Door Lock
Door Lock
(UL listed
(Energize toburglary-resistant
unlock)
electric locking mechanism
UL-listed burglary-resistant (CVXY))
Electric locking mechanism (CVXY)
12/24V
Power Supply
(UL listed power supply (APHV))
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
OVERRIDE This red indicator illuminates whenever any of the override switches is in
a position other than AUTO.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
This panel also includes two operator switches that perform the following:
VS-8-4, VS-8-4-T
Video Switcher
The VS-8-4, Andover Continuum’s video switcher module, includes eight input channels
and four high-speed, buffered, output channels. Any one of the eight input lines can be
connected to any of the four outputs. Each output has a gain of two and is capable of
driving 75 Ω, back-terminated, lines.
The VS-8-4 is an I/O module used with the Andover Continuum Product line and can be
integrated into systems requiring video security. Up to eight surveillance, cameras can be
connected to the VS-8-4 inputs. The VS-8-4 video output can then be connected directly
to a video monitor or other video display or recording device.
The VS-8-4-T version provides the capability of time/date stamping the video signal. In
addition, a title may be added to the video signal to identify the area where the camera is
being directed.
FEATURES
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 10-28V. 24V for UL294 installations.
Power Consumption: 2 Watts (83 mA) @ 24 VDC (max.); provided by Andover
Continuum power supply module.
INPUTS
Impedence: 75 Ω
Connection: BNC connector
Bandwidth (-3dB): > 75 MHz (Rload=150 Ω)
Single Channel
Crosstalk: > -60 dB @ 10 MHz.
All Channel
Crosstalk: > -50 dB @ 10 MHz.
All Channel
Off Isolution: > -55 dB @ 10 MHz.
OUTPUTS
Impedence: 75 Ω
Connection: BNC connector
Signal: 2V pk/pk
I/O Connections
The video input and output connections are located on the bottom of the module.
A quick disconnect spade lug connector allows for an Earth ground connection.
The diagram below indicates where each input and output is located on the module.
These connections are also listed below.
VIDEO OUTPUTS
Earth Ground
1 2 3 4
1 2 3 4 5 6 7 8
VIDEO INPUTS
Standard BNC connections are used for each input and output.
Programming/Use
Video Switching
The outputs of the VS-8-4 module can have up to eight input sources. These outputs are
represented as Numerics in the system. Entering a value of 1–8 selects the input source
for the particular output. Values other than 1–8 turn off the video for that output. Refer to
the programming table on the following page for specifics.
The position of the date and time for all outputs is specified as a line numbered 1 though
12. Values other than 1–12 turn off the display of the datetime.
The VS-8-4-T updates the Date and Time automatically, however, it is only accurate to
1.5 seconds per hour. You can send updated datetime readings to the unit though Plain
English.
Status/Control Panel
Status Indicators
The VS-8-4 module includes a complete indicator status panel on the front of the module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
This panel also includes two operator switches that perform the following:
VT-1
Voice Telecom Module
The VT-1, Andover Continuum’s voice-output/touch-tone input telecom module, provides
users with easy-to-use remote data entry capabilities for their Andover Continuum system
using the familiar touch-tone keypad on any standard or cellular telephone. The VT-1
provides built-in prompt messages and pre-recorded vocabulary words, which can be
used individually or combined to form phrases and sentences. In addition, custom
messages (up to 3 minutes total) can be pre-recorded to inform the user of building
conditions and/or to prompt the user for additional input.
FEATURES
SPECIFICATIONS
ELECTRICAL
Power Supply Range: Input Voltage Range: 20-26V.
Power Consumption: 1.5 Watts (63 mA) @ 24 VDC (max.); provided by
Andover Continuum power supply module.
INPUTS
To install the telephone line, open the cover of the module and plug an RJ-11 cable into
the jack located at the lower left as indicated below.
Programming/Use
Technical Description
The VT-1 module acts as an interface to the Andover Continuum system by allowing a
user to control functions via telephone. It can be configured to operate like an auto
attendant for a telephone system. As the phone line is answered, a series of voice
prompts are played indicating various options that may be selected by pressing touch
tone (DTMF) keys on the caller’s telephone. The DTMF numbers received by the module
represent a desired command or function. The module is equipped to decode the DTMF
responses and send them off to an attending controller.
The module can also be commanded to dial out and provide callback numbers to a
paging system.
User Mode
User mode is the normal operating mode of the VT-1. In this mode, the VT-1 is under the
control of a Plain English program. When a user calls into the module, messages are
played and touch-tone digits are captured.
Type of Message
PRE-RECORDED MESSAGES
Words and sentence fragments that can be
played in both User and Supervisor Mode
Approximately 80 seconds
Operation
The VT-1 includes several pre-recorded words and phrases. It is not necessary that you
record new messages. If you intend to use these pre-recorded words, there is no need to
enter Supervisor Mode.
Security
Because the VT-1 allows connection to your system via a standard telephone line, we
have included a password-based security lock to allow controlled access to its operation.
Both User and Supervisor modes have their own passwords. These passwords can be
changed at any time simply by editing a value stored in a Plain English numeric variable.
The system can easily monitor VT-1 activity. Whenever a user successfully logs into the
VT-1 (correct password entered), a status code appears in one of the module’s numeric
objects.
VT-1
Andover Continuum I/O System Reference 203
VT-1
VT-1
Supervisor Mode
The Supervisor Mode allows you to record a number of custom messages that can be
selected for playback at strategic times through your program.
At this time you are expected to press a four-digit password followed by the pound (#)
button to access the unit. The default Supervisor mode password is 1234. As indicated
earlier, this password can easily be changed.
If you enter the wrong password, the VT-1 responds with Message 2: “Invalid password.”
The unit then allows you to try again. In any case, if the module does not receive the
correct password in 30 seconds, the VT-1 disconnects the call.
Once the correct password is received, the module plays Message 3: “Press 1 to record,
2 to play or 3 to erase a message. Press star to exit.” This is referred to as the main
menu. From here you can access its supervisory functions.
Note: In this mode, the VT-1 will automatically hang up if no DTMF activity has
been received for 30 seconds.
Supervisor Functions
The messages that you can record, play and erase are stored in separate locations
denoted by their “message number”. Custom messages occupy message numbers 1-
150. Although there appears to be 150 possible custom messages, the limit is actually
the amount of time your entire message library requires. The VT-1 allows for a total of
approximately 3 minutes of custom recording time. Therefore, the total number of
messages you can record cannot exceed the 3 minute limit.
When all available message space is filled, the VT-1 will not allow subsequent recording.
The message: “Voice memory full” is played. To allow further recording, erase unused
messages.
At this point you are returned to the main menu where you can select another operation.
Pressing the star (*) button exits the mode and returns the VT-1 to the “main menu”
prompt.
Note: Recorded messages are stored in non-volatile memory within the VT-1 and are
therefore preserved (not lost) during power outages.
After the message finishes playing, you are returned to the main menu where you can
select another operation.
Pressing the star (*) button exits the mode and returns the VT-1 to the “main menu”
prompt.
At this point you are returned to the main menu where you can select another operation.
Pressing the star (*) button exits the mode and returns the VT-1 to the “main menu”
prompt.
User Mode
The User Mode is the normal operating mode of the VT-1. In this mode your Plain
English program communicates to the user through the VT-1’s pre-recorded voice
messages and receives commands from the user via telephone button entries.
At this time you are expected to press a four-digit password followed by the pound (#)
button to access the unit. The default User mode password is 4321. As indicated earlier,
this password can easily be changed.
If you enter the wrong password, the VT-1 responds with Message 2: “Invalid password.”
The unit then allows you to try again. In any case, if the module does not receive the
correct password in 30 seconds, the VT-1 disconnects the call.
Once the correct password is received, the module sends a code to the controller through
a numeric point indicating that it has been accessed by a user.
The only way to exit this mode is for your program to stop operating in the User mode
and to send the hang up command to the module. If the caller hangs up, the program
should be designed to include a method of monitoring inactivity such as a timeout.
Configuration
Your system controller communicates to the VT-1 through a series of points. The
following is a table of the points that must be defined before you can use the module.
VT State
This Numeric input indicates the current state of the VT-1. The value contained in the
numeric changes as the VT-1 operates. The various states that can be monitored are as
follows:
User Response
This String contains the values of the buttons pressed by the user in response to a
prompt. In Single Tone Mode, this value would be a single character. If the caller pressed
the 3-button, the String would contain the 3. In Multi-Tone Mode, the String contains all
the buttons pressed. If the caller pressed 234, the String contains the series of characters
234.
For example, the default password for Supervisor mode is 1234. The caller presses four
buttons to enter this series of numbers: 1-2-3-4. The numeric contains the number 1234.
If you want a three-digit password (e.g., 265), enter the number 265 into the Numeric.
The largest number you can enter into either password numeric is 65535. Passwords can
be a maximum of four digits in length. If a five-digit value is entered, the most significant
digit is discarded. (e.g., 65535 becomes 5535)
Ring Count
This Numeric determines how many rings the VT-1 will await before it answers a call. The
default is 1, however you can set it to any number up to 255.
Command
This Numeric allows you to set the mode in which you expect user responses to occur
and it allows you to hang up the line or dial out. These actions are done by entering a
code into this numeric as follows:
Code Action
8000 Dial Out
8001 Hang Up
8002 Single-Tone Mode
8003 Multi-Tone Mode
Command Summary
Single-Tone Mode is used when you want the user to press only one digit in response to
your prompt. This mode is appropriate for menu choices when you “Press 1 for
something, 2 for another…”.
Multi-Tone Mode is used for entering values. When in this mode, the VT-1 gathers
responses until the caller presses the pound (#) button. Therefore, if you are expecting
the caller to enter a temperature setpoint such as 23 degrees, the caller would press 2-3-
#. If you use this mode, be sure to inform your operator in your voice prompt of the need
to press the pound button.
Dial Out is used when you want to use the VT-1 to dial an outside number in response
from some user input. Entering this command causes the VT-1 to go “off-hook”, detect
dial tone and dial the number contained in the Dial Out Phone Number string.
Hang Up terminates a dial out operation or a user operation.
NOTE: The VT-1 cannot detect the typical pager system beeps to signify the pager
system is ready to accept the phone number. The user must know the time delay to wait
prior to sending the DIAL OUT command after the Ringing Stopped event is received.
• Including the number and the command numeric in a single Plain English line may cause
timing problems resulting in errant numbers being sent.
Play Message
This String contains the message number of a pre-recorded message for playing. Setting
this string to a valid message number starts the VT-1 playing the desired message. When
the message is finished, the VT-1 reports this fact through a code of 301 in the VT State
numeric. If the message number is an invalid one, the VT-1 reports a code 300.
You can concatenate (string-together) several messages using this string. Entering
message numbers separated by a semicolon (;) automatically concatenates the
messages within the VT-1. This is an easy way of creating sentences from the multitude
of prerecorded words and phrases found in messages 151-230.
Example:
To play the phrase “The Temperature is seventy five degrees”, the user must
concatenate pre-recorded message #’s 181,175,155, and 184 respectively. This yields
the following Plain English code:
VTPlaymessage = “181;175;155;184”
Important Note:
There is a limit to the number of characters the Play Message string can handle.
You must limit the number of characters to 30.
The example message yields a total character count of 15 (one per digit).
Status/Control Panel
Status Indicators
The VT-1 module includes a complete indicator status panel on the front of the module.
POWER This green indicator illuminates when DC power is applied through the
I/O Bus.
COMM This yellow indicator illuminates when data is transmitted from the
module to the NetController. In normal operation, data is only transmitted
when an input value changes.
This indicator will also flash periodically as the NetController checks the
I/O bus.
STATUS This red indicator is normally off. If it is always on or flashing at a fast
rate, there is a problem with the module.
This panel also includes two operator switches that perform the following: