Netcontroller II For Ul864 Installation Instructions - en
Netcontroller II For Ul864 Installation Instructions - en
30-3001-1008
NetController II Rev A
Mounting
Screw
Andover Continuum
Power Supply Connector
Mounting
Screw Mounting
Screw
DIN RAIL 4
2 3
5
PANEL
Physical Dimensions
222.3 mm
8.75”
152.4 mm
6.00”
63.5 mm
2.50”
Wiring Rules
These modules are intended for installation Inspecting the Ground
within the UL Listed enclosure 3P-UL-ENCL. Be sure to have your grounds inspected before you begin the installation
process.
Check your grounds as follows:
For reliable operation, follow these wiring guidelines:
Inspect the building power distribution panel for earth-ground termina-
• Never lay wires across the surface of a printed circuit board.
tion. If the ground termination is any of the following, it is not adequate
• Use shielded wire.
and must be corrected:
• Terminate the shield of the wires at one end of the run
• Does not exist
only — preferably at the end where your I/O module is located.
• Is connected to a corroded or galvinized pipe
• When stripping wire, be careful not to drop small pieces of wire
• Is connected using a small gauge wire (less than 14 AWG).
inside the cabinet.
• Don’t run your wiring in the same conduit with
Be sure your Andover Continuum cabinet is connected to the ground
AC power.
with a copper conductor that terminates at the distribution panel. For
• Don’t run your wiring in the same conduit with your
more information, see the “Related Documentation” section at the end
output wiring.
of this document.
Grounding the Controller
To insure proper operation of the controller, it must be connected to Caution: Earth ground ( ) must be connected to avoid
a good earth ground. The connection must be made as close to the module damage.
module as possible.
24VDC
Battery
Supply
Third-Party UL 1481 Power Supply
( ) ( )
(+) (+)
!
Use care when attaching power
wiring to these connectors.
They are not to be used as a strain relief.
The connectors cannot withstand
AC POWER
excessive bending or flexing. 24 VAC
20 VA
50/60 HZ
L +
+ 12 to 28VDC
N -
VDC Return
DC POWER
12 - 28 VDC
10 W
50
Warning
Note: For a list of UL -evaluated, approved transformers, see the UL 864 Infinet
Smoke Control System Design Guide, 30-3001-1006.
DC Power and Battery Backup Connection (Continued)
NOTE: The indicator lamps and switches are connected to the circuit board via two thin ribbon cables. When you
lift the plastic housing do not remove the cables from their connectors.
Ribbon Cable
Connectors
_
Receptacle . +
Battery
Connecting the I/O Modules *All I/O Modules are Power Limited
5
PIN Function
4
3 5 +24 VDC
2
I/O Bus 1 4 24 VDC Return
Connector
3 Shield
Power Supply CX9680-S I/O I/O
2 Comm B
1 Comm A
5 5
4 4 I/O
3 3
2 2
1 1
1
Power Supply CX9680-S
CX9680-S
COMM 4*
RS-422 Connector
1 5
8 1 COMM 3*
COMM 1 & 3*
RJ-11 Modem Connector
RS-232 Connectors
(Optional)
RX+ (IN+)
TXD
DSR RX- (IN-)
RD Shield
Ground
TIP
RTS
DCD TX+ (OUT+)
RING
CTS
DTR TX- (OUT-)
COMM 4*
COMM 2* 1 4 RS-485 Connector
1 3 (Jumpers convert
COMM 1* RS-485 Connector
RS-422 to RS-485)
RS-485 Connector
+
+ +
Shield
-
Shield
Shield
Earth Ground
+
** The ethernet port is non-supervised. The cable connected to the hub from this port must be in conduit and no greater -
than 20 ft. * The Ethernet connector has been
***The RS-232 port is non-supervised. The cable connected to the FSCS from this port must be in conduit and no
greater than 20 feet.
evaluated by UL for UL294/UL1076.
All other communication connectors
have been evaluated by UL for
“supplemental use.”
Configuring the CX9680-S
(NOTE: Check with your system administrator for assistance.) 6. Log on using the default Andover Continuum user name and
1. Disable the DHCP Services on your PC. password.
2. Disconnect your computer from the network and set your IP 7. Enter relevant configuration parameters on the WebServer
address to 169.254.1.2 and your subnet mask to 255.255.0.0. Configuration web pages.
3. Using a CAT5 cable (straight-through or crossover), connect 8. After entering the parameters, click the Commit Changes/Restart
the PC Ethernet port to the NetController II Ethernet port. Controller button on the WebServer page. (Restore the PC, and
connect the CX9680-S to the network when it reboots.)
4. Run your web browser, then go to URL: http://169.254.1.1 to
display the Andover Continuum Embedded WebServer page in the
NetController II. For more information, please see the “Related Documentation” section
at the end of this document.
5. Select Controller Configuration from the WebServer page.
Specifications
Dimensions
8.75” W x 6.00” L x 2.5” H (222.3 x 152.4 x 63.5 mm) Infinet Bus Length (Maximum Line Impedance)
4,000 ft (1,220m) standard for Infinet using approved shielded, twisted
Weight pair, low capacitance cable. 120 ohm terminating resistor (part number
1.5 lbs. (0.68 kg) EMSC-546) required at both ends. InfiLink module allows extensions to
longer distances.
Enclosure Type
UL open class, flammability rating of UL94-5V, IP 10 I/O Bus
ACC-LON communications. Choice of bus media, RS-485 or
Mounting FTT-10A.
DIN rail or wall mount using attached fasteners. Andover
Continuum UL Listed enclosure model 3P-UL-ENCL is available RS-485 Bus
for UL 294 and UL 1076. Comm. Speed: 39K baud
Bus Length: 2,000 ft. (610m)
Operating Environment Bus Media: Shielded, twisted pair cable. 120 ohm terminating resistor
Temperature: 32o to 122o F (0o to 50o C) (part number EMSC-546) required at both ends of the
Humidity: 10 to 90% RH, non-condensing ACC-LON network (when modules are
mounted remotely).
Input Power FTT-10A Bus
Andover Continuum Power Supply: Comm Speed: 78K baud
Bus Length: Up to 8858 ft. (2700m) — bus topology
• PS 120/240 AC 65U-S Up to 1640 ft. (500m) — free topology. Repeater required
for longer distances.
Third Party Power Supply: Bus Media: Refer to Echelon FTT-10A free topology documentation
• 12–28VDC @ 10W
• 24VAC @ 20VA, 50/60 Hz. Connections
Power: 5-position plug-in connector on left side of module for
Internal Battery direct connection to Continuum power supply module.
NiMH, 3.6 VDC, 800 mAh 3-position connector on left side of module for connection to a
third-party power supply module.
Real Time Clock I/O Bus: 5-position plug-in connector on right side of module for
Battery-backed by UPS and internal battery. direct connection of up to 32 I/O modules.
Ethernet: RJ-45 connector for 10/100 Ethernet.
Comm. Error Checking Printer: RJ-45
International Standard CRC 16. Modem: RJ-11 Connector
Caution: The user that changes or makes modifications not expressly approved by Schneider Electric, for compliance could void the user’s au-
thority to operate the equipment.
Industry Canada
ICES-003
This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations.
UL 916 Listed product for the United States and Canada, Access Control Equipment
UL Listed product for the United States. UL 864, 9th Edition Smoke Control System
Note: Refer to the UL 864 Listed manuals (the UL 864 Infinet Smoke Control System Design Guide, 30-3001-1006, and the UL 864 BACnet Smoke
Control System Design Guide, 30-3001-1007), for specific wiring, operation, and compatability information.
Related Documentation
The following related documentation provides more information on Andover Continuum products.
These documents are neither required nor evaluated by Underwriters Laboratories (UL) for UL Listings.