Installation Instructions for UL 864

30-3001-1008
NetController II Rev A

Mounting
Screw

Andover Continuum
Power Supply Connector

Third-Party I/O Bus Cover


Power Supply Connector Connector

Mounting
Screw Mounting
Screw

See the “Ethernet and Comm Port


BOTTOM PANEL Connections” section later in this
document.

Cover Tab Cover Tab

Controller Installation (Model CX 9680 -S)


To install the controller, follow these steps: 3. Connect the Ethernet and Communication Port con-
nections based on your requirements. (See the “Ethernet and
1. Mount the controller on a standard DIN rail or to a panel Comm Port Connections” section of this document.)
using screws. (See the “Mounting Instructions” and 4. Connect the power supply connector of the controller to an
“Physical Dimensions” sections of this document.) Andover Continuum power supply or third-party UL Listed UL
Warning: Do not apply power to the controller until all 1481 power limited power supply. Access the PC board and
connections are secured. Read the “Wiring Rules” connect the battery. (See the “DC Power and Battery Backup
Connections” section.)
section of this document before performing the
next steps. 5. Apply power to the controller and I/O modules.
2. Connect the I/O modules by simply plugging the modules 6. Configure the controller using the controller’s embedded Web-
together or using a cable assembly to bridge the modules Server pages and CyberStation. For more information, refer to
together. (See the “Connecting I/O Modules” section of the “Related Documentation” section at the end of this docu-
this document.) ment.

© 2010 Schneider Electric, all rights reserved.


Mounting Instructions

DIN RAIL 4
2 3

5
PANEL

Physical Dimensions

222.3 mm
8.75”

152.4 mm
6.00”

63.5 mm
2.50”
Wiring Rules
These modules are intended for installation Inspecting the Ground
within the UL Listed enclosure 3P-UL-ENCL. Be sure to have your grounds inspected before you begin the installation
process.
Check your grounds as follows:
For reliable operation, follow these wiring guidelines:
Inspect the building power distribution panel for earth-ground termina-
• Never lay wires across the surface of a printed circuit board.
tion. If the ground termination is any of the following, it is not adequate
• Use shielded wire.
and must be corrected:
• Terminate the shield of the wires at one end of the run
• Does not exist
only — preferably at the end where your I/O module is located.
• Is connected to a corroded or galvinized pipe
• When stripping wire, be careful not to drop small pieces of wire
• Is connected using a small gauge wire (less than 14 AWG).
inside the cabinet.
• Don’t run your wiring in the same conduit with
Be sure your Andover Continuum cabinet is connected to the ground
AC power.
with a copper conductor that terminates at the distribution panel. For
• Don’t run your wiring in the same conduit with your
more information, see the “Related Documentation” section at the end
output wiring.
of this document.
Grounding the Controller
To insure proper operation of the controller, it must be connected to Caution: Earth ground ( ) must be connected to avoid
a good earth ground. The connection must be made as close to the module damage.
module as possible.

DC Power and Battery Backup Connection

Andover Continuum Power Supply * Power Supply Battery Backup


Battery Backup Connection
PS 120/240 AC 85-U, AC 50-U
and PS -48 DC 50-U
Continuum
CX9680-S I/O I/O
Power Supply

NOTE: For more information on Andover


Continuum Power Supplies, see the “Input
Power” section of the Specifications topic. BAT BAT
(+) ( )

24VDC
Battery
Supply
Third-Party UL 1481 Power Supply
( ) ( )

(+) (+)

2-Conductor 12VDC, 7AH 12VDC, 7AH


Shielded Power Cable Battery Battery
Third-Party from Power Supply
DC Power Supply * The battery backup and battery
2-Conductor CX9680-S 2-Conductor Shielded
data cable from
backup connection were not evaluated
Shielded
Power Cable CX9680-S by UL for UL 864.

I/O I/O I/O I/O I/O

NOTE: Only if you use a third-party


DC power supply, input power to the I/O
modules must be supplied externally.
DC Power and Battery Backup Connection (Continued)

Third-Party Power Supply


(DC Connections)

!
Use care when attaching power
wiring to these connectors.
They are not to be used as a strain relief.
The connectors cannot withstand
AC POWER
excessive bending or flexing. 24 VAC
20 VA
50/60 HZ

L +
+ 12 to 28VDC
N -
VDC Return

DC POWER
12 - 28 VDC
10 W

Third-Party Power Supply


(AC Connections)

*Part Number EMSC-549 90

50
Warning

Note: For a list of UL -evaluated, approved transformers, see the UL 864 Infinet
Smoke Control System Design Guide, 30-3001-1006.
DC Power and Battery Backup Connection (Continued)

Internal Battery Connection


During shipment the internal battery pack has been disconnected to prevent it from draining prior to installation.

NOTE: The indicator lamps and switches are connected to the circuit board via two thin ribbon cables. When you
lift the plastic housing do not remove the cables from their connectors.

To activate the battery:


1. Locate the plastic tabs on the bottom panel of the controller. (See illustration on the first page of this document.)
2. Using your fingers, gently depress the tabs while lifting the cover. Fold the cover back to access the main circuit board.
3. Connect the battery connector into the receptacle as shown in the illustration below.

Ribbon Cable
Connectors

_
Receptacle . +

Battery

Connecting the I/O Modules *All I/O Modules are Power Limited

Plugging Modules Together • FTT-10a (free topology transceiver technology)


The CX9680-S can directly connect to the I/O modules without using
NOTE: Prior to installing an I/O module network using the
cables through a system of built-in plugs and jacks. All I/O modules
include two complementary module connectors. Creating a system is as FTT-10a bus, read the installation documentation from
simple as physically plugging the modules together. (See the Horizontal the Echelon Corporation.
and Vertical Connection illustrations below).
Maximum Number of I/O modules
I/O Bus Connector
Continuum allows a maximum of 32 I/O modules per CX9680-S.
The I/O bus connector on the upper right side further distributes the There is also a limit based upon the capacity of the power supply
24 VDC input power and special I/O communication signals to all the feeding the modules. (60 W maximum power)
I/O modules. (See the I/O Bus Connector illustration below.)
Maximum Length of I/O Bus
Horizontal and Vertical Connections
The following are the cable length specifications:
In vertical extended systems, I/O modules may be located above or • RS-485 — 2000 ft. (610 m.)
below other modules. Connector cables bridge the I/O modules together. • FTT-10a — 8858 ft. (2700 m.) double termination
Connection between the modules is one-to-one, straight-forward wiring. 1640 (500 m.) free topology
(See the I/O Cable Wiring illustration below.)
Termination of I/O Modules
LON Interfaces
An external 120 ohm terminating resistor (part number EMSC-
The CX9680-S supports two types of Local Operating Network 546) is required at both ends of the bus for proper termination.
(LON) bus media: (See the I/O Cable Wiring illustration that follows.)
• RS-485 (ACC-LON) – Default setting
Connecting the I/O Modules (Continued)
I/O Bus Connector Pins Horizontal Connection

I/O Bus Connector


Power Supply CX9680-S I/O I/O

5
PIN Function
4
3 5 +24 VDC
2
I/O Bus 1 4 24 VDC Return
Connector
3 Shield
Power Supply CX9680-S I/O I/O
2 Comm B
1 Comm A

I/O Cable Wiring Vertical Connnection

5 5
4 4 I/O
3 3
2 2
1 1
1
Power Supply CX9680-S

I/O Cable Wiring

CX9680-S

Part Number: EMSC-546

Part Number: EMSC-546


Ethernet and Comm Port Connections *All Comm Ports are Power Limited
Bottom Panel

Ethernet COMM1 COMM2 COMM3 COMM4


ETHERNET Ethernet Cable w/
RJ-45 Connector
Port Connector Interface UL 864 Functions
Ethernet RJ-45 (Ethernet 10/100 BASE-T) Used for fire panel**
Comm1 RS-232 Not used

RS-485 (3-pin) Supervised Used for field controllers


Service Port cable (Wireless Adapter or Not used
RoamIO2)
Comm2 Service Port cable (Wireless Adapter or Not used
Service Port RS-485 4-pin connector
RoamIO2)
RS-485 (4-pin) Supervised Used for field controllers

Comm3 RS-232 Non-Supervised Used for FSCS***

(Optional) Modem (RJ-11) Not used Wireless Adapter or RoamIO2


Comm4 RS-422 (L-Bus) or Not used (COMM1 and COMM2)

RS-485 (5-pin) Not used

COMM 4*
RS-422 Connector
1 5
8 1 COMM 3*
COMM 1 & 3*
RJ-11 Modem Connector
RS-232 Connectors
(Optional)
RX+ (IN+)
TXD
DSR RX- (IN-)
RD Shield
Ground
TIP
RTS
DCD TX+ (OUT+)
RING
CTS
DTR TX- (OUT-)

COMM 4*
COMM 2* 1 4 RS-485 Connector
1 3 (Jumpers convert
COMM 1* RS-485 Connector
RS-422 to RS-485)
RS-485 Connector

+
+ +
Shield
-
Shield
Shield
Earth Ground
+
** The ethernet port is non-supervised. The cable connected to the hub from this port must be in conduit and no greater -
than 20 ft. * The Ethernet connector has been
***The RS-232 port is non-supervised. The cable connected to the FSCS from this port must be in conduit and no
greater than 20 feet.
evaluated by UL for UL294/UL1076.
All other communication connectors
have been evaluated by UL for
“supplemental use.”
Configuring the CX9680-S
(NOTE: Check with your system administrator for assistance.) 6. Log on using the default Andover Continuum user name and
1. Disable the DHCP Services on your PC. password.
2. Disconnect your computer from the network and set your IP 7. Enter relevant configuration parameters on the WebServer
address to 169.254.1.2 and your subnet mask to 255.255.0.0. Configuration web pages.
3. Using a CAT5 cable (straight-through or crossover), connect 8. After entering the parameters, click the Commit Changes/Restart
the PC Ethernet port to the NetController II Ethernet port. Controller button on the WebServer page. (Restore the PC, and
connect the CX9680-S to the network when it reboots.)
4. Run your web browser, then go to URL: http://169.254.1.1 to
display the Andover Continuum Embedded WebServer page in the
NetController II. For more information, please see the “Related Documentation” section
at the end of this document.
5. Select Controller Configuration from the WebServer page.

Specifications
Dimensions
8.75” W x 6.00” L x 2.5” H (222.3 x 152.4 x 63.5 mm) Infinet Bus Length (Maximum Line Impedance)
4,000 ft (1,220m) standard for Infinet using approved shielded, twisted
Weight pair, low capacitance cable. 120 ohm terminating resistor (part number
1.5 lbs. (0.68 kg) EMSC-546) required at both ends. InfiLink module allows extensions to
longer distances.
Enclosure Type
UL open class, flammability rating of UL94-5V, IP 10 I/O Bus
ACC-LON communications. Choice of bus media, RS-485 or
Mounting FTT-10A.
DIN rail or wall mount using attached fasteners. Andover
Continuum UL Listed enclosure model 3P-UL-ENCL is available RS-485 Bus
for UL 294 and UL 1076. Comm. Speed: 39K baud
Bus Length: 2,000 ft. (610m)
Operating Environment Bus Media: Shielded, twisted pair cable. 120 ohm terminating resistor
Temperature: 32o to 122o F (0o to 50o C) (part number EMSC-546) required at both ends of the
Humidity: 10 to 90% RH, non-condensing ACC-LON network (when modules are
mounted remotely).
Input Power FTT-10A Bus
Andover Continuum Power Supply: Comm Speed: 78K baud
Bus Length: Up to 8858 ft. (2700m) — bus topology
• PS 120/240 AC 65U-S Up to 1640 ft. (500m) — free topology. Repeater required
for longer distances.
Third Party Power Supply: Bus Media: Refer to Echelon FTT-10A free topology documentation
• 12–28VDC @ 10W
• 24VAC @ 20VA, 50/60 Hz. Connections
Power: 5-position plug-in connector on left side of module for
Internal Battery direct connection to Continuum power supply module.
NiMH, 3.6 VDC, 800 mAh 3-position connector on left side of module for connection to a
third-party power supply module.
Real Time Clock I/O Bus: 5-position plug-in connector on right side of module for
Battery-backed by UPS and internal battery. direct connection of up to 32 I/O modules.
Ethernet: RJ-45 connector for 10/100 Ethernet.
Comm. Error Checking Printer: RJ-45
International Standard CRC 16. Modem: RJ-11 Connector

Ethernet LAN Interface Status Indicator LEDs


10/100 Ethernet: Ethernet cable with RJ-45 connector. System: Power, CPU, Error
Comm1: TD, RD, DCD, DTR
Serial Comm. Interface Comm2: TD, RD
Four programmable ports, software configurable as printer, modem, Comm3/Modem: TD, RD, DCD, DTR, MODEM
wireless adapter, ROAM I/O, or third-party system. Infinet can be Comm4: TD, RD
configured on Ports 1 and 2. I/O Bus: Status
Comm1: RS-232, RS-485, Service Port Ethernet: ACT/LINK, 10/100 Mbps
Comm2: Service Port, RS-485
Comm3: RS-232, (optional) Modem (RJ-11 connector) Push Button Switches
Comm4: RS-422 (L-Bus) or RS-485 Clear Memory: RESET/Clear Memory
Reset IP Address: (On PC board) Resets Network address settings in
Serial Comm. Speed flash memory and restores all non-volatile settings to
Comm1: Baud rates up to 38.4 K for RS-232 mode. factory defaults.
Comm3: Baud rates up to 38.4 K when configured for RS-232 or
internal modem.
Regulatory Notices
Federal Communications Commission
FCC Rules and Regulations CFR 47, Part 15, Class A
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference received, including interference that may cause undesired operation.
Complies with FCC Part 68 Rules (when optional modem is installed).
FCC Registration Number: AU7NMOIBMT5656R REN Number: 0.1B

Caution: The user that changes or makes modifications not expressly approved by Schneider Electric, for compliance could void the user’s au-
thority to operate the equipment.

Industry Canada
ICES-003
This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations.

CE - Compliance to European Union (EU)


89/336/EEC - EMC Directive
This equipment complies with the rules of the Official Journal of the European Union specified in the EMC directive
89/336/EEC governing the Self Declaration of the CE Marking for the European Union.

C-Tick (Australian Communications Authority (ACA))


AS/NZS 3548
This equipment carries the C-Tick label and complies with EMC and radio communications regulations of the Australian Communications Author-
ity (ACA), governing the Australian and New Zealand (AS/NZS) communities.

WEEE - Directive of the European Union (EU)


This equipment and its packaging carry the waste of electrical and electronic equipment (WEEE) label, in compliance with European Union (EU)
Directive 2002/96/EC, governing the disposal and recycling of electrical and electronic equipment in the European community.

UL 916 Listed product for the United States and Canada, Access Control Equipment

UL Listed product for the United States. UL 864, 9th Edition Smoke Control System

Note: Refer to the UL 864 Listed manuals (the UL 864 Infinet Smoke Control System Design Guide, 30-3001-1006, and the UL 864 BACnet Smoke
Control System Design Guide, 30-3001-1007), for specific wiring, operation, and compatability information.

Related Documentation
The following related documentation provides more information on Andover Continuum products.
These documents are neither required nor evaluated by Underwriters Laboratories (UL) for UL Listings.

Document Document Number


NetController II Operation and Technical Reference Guide 30-3001-995
Network Security Configuration Guide 30-3001-996
Andover Continuum CyberStation HVAC Essentials Guide 30-3001-1000
Andover Continuum CyberStation online help
Schneider Electric
One High Street
North Andover, MA 01845
(978) 975-9600
Fax: (978) 975-9782
http://www.schneider-electric.com/buldings