0% found this document useful (0 votes)
312 views4 pages

Terasaki AGR-31B ACB Test Report

This document provides a test report for a Terasaki Tempower AGR-31B circuit breaker. The report details nameplate information, electrical tests including insulation resistance and contact resistance tests, an inspection and functional check, used test equipment, comments noting a full service was performed, and photos of the circuit breaker.

Uploaded by

bilal ahsan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
312 views4 pages

Terasaki AGR-31B ACB Test Report

This document provides a test report for a Terasaki Tempower AGR-31B circuit breaker. The report details nameplate information, electrical tests including insulation resistance and contact resistance tests, an inspection and functional check, used test equipment, comments noting a full service was performed, and photos of the circuit breaker.

Uploaded by

bilal ahsan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

LV ACB

TERASAKI TEM2POWER AGR-31B

SIGMA POWER SERVICES PTY LTD


www.sigmapowerservices.com.au
[email protected]
T: +61 89 2777 228 | M: +61 428 666 274
TERASAKI TEMPOWER 2 Page 1 of

AGR-31B
TEST REPORT

Customer Rio Tinto Job No. SPS-851096


Location Marandoo Work Order 110604284
Substation SUB2101 Primary Crushing Date 03/04/2024
Switchboard SUB2101.MCC1 Panel Incomer

1. NAMEPLATE DETAILS

NAMEPLATE INFORMATION

Make: Terasaki Rated Voltage: 1000V Tripping Voltage: 110 Vdc Closing Voltage: 110 Vdc

Tempower ✘ Spring Solenoid Hydraulic


Model: Nominal Current: 2500 A Mechanism:
AGR-31B S/Pole

Serial Short Circuit Live Tank Dead Tank ✘ Indoor


12104-276 85 kA Format:
No: Current:
Outdoor
Asset Insulating Oil ✘ Air SF6
N/A Short Circuit Time: 1 Sec
No: Medium: Vacuum

2. ELECTRICAL TESTS

INSULATION RESISTANCE TEST IN BREAKER OPEN POSITION

Connection +VE Connection -VE Test Voltage Duration Resistance (Ω) Remarks

RED red 500 V 60 sec > 1T Pass

WHITE white 500 V 60 sec > 1T Pass

BLUE blue 500 V 60 sec > 1T Pass


INSULATION RESISTANCE TEST IN BREAKER CLOSE POSITION

RED WHITE 500 V 60 sec > 1T Pass

WHITE BLUE 500 V 60 sec > 1T Pass

BLUE RED 500 V 60 sec > 1T Pass


Note: Insulation Resistance Test in OPEN Breaker Position to check insulation integrity of insulation.
Insulation Resistance Test in CLOSE Breaker Position with Earth,

CONTACT RESISTANCE TEST

Connection +VE Connection -VE Current Inj. Resistance (Ω) Remarks

RED red 100 A 10.2 µ Pass

WHITE white 100 A 7.8 µ Pass

BLUE blue 100 A 7.2 µ Pass

Tested by: Bilal Ahsan Reviewed By: Usman Ali


TERASAKI TEMPOWER 2 Page 2 of

AGR-31B
TEST REPORT

3. INSPECTION / FUNCTIONAL CHECK

FUNCTION / OPERATION TESTS

Earthed support structure and mechanism N/A Interlocks functional N/A

Manual open close operation available ✘ Arc chutes removed and contacts checked N/A

Operation of the manual spring charge/discharge ✘ Operational nameplate in position ✘

Visual inspection completed ✘ Structural or paint damage No

Mechanism checked and lubricated N/A Racking mechanism tested and working N/A

4. TEST EQUIPMENT

Test Equipment Used

Equipment Number Equipment Description Calibration Due Date

ANU-1 Terasaki OCR Checker 23/10/2024

5. COMMENTS

COMMENTS:

Full service has was performed. Circuit breaker has been cleaned and all contacts including slide points greased. All test results are
satisfactory and Circuit breaker is healthy.

Tested by: Bilal Ahsan Reviewed By: Usman Ali


TERASAKI TEMPOWER 2 Page 3 of

AGR-31B
TEST REPORT

6. VISUAL INSPECTION

Terasaki ACB – Front View AGR-31B Relay

Terasaki ACB – Nameplate Information Terasaki ACB – Back View

Tested by: Bilal Ahsan Reviewed By: Usman Ali