Solar System Specs in KP
Solar System Specs in KP
1. SOLAR PANELS
> The Solar Panel shell meet the requirement set in IEC 61215:2016, IEC61730-1:2004 and IEC 61730-2:2004, IEC
61710, / international standards.
> Solar Panels with Anti-PID Certification based on IEC standard TS-62804-1 will be preferred (i.e: TUV PPP-58042).
> Outstanding conversion efficiency.
> More Power per square meter than other panels.
> Positive watt class rating/positive power tolerance (5 to 10 watt above industry average.
> Low temperature coefficient.
> PID degradation free.
> The PV module(s) shall contain mono crystalline silicon, poly crystalline, thin film, multi junction Grade-A Solar
cells.
> The PV module have an ability to Works well with high-voltage input Inverters/ charge controllers (1000 Vdc)
> The PV Panel must have clear anodized aluminum frame with Anti-reflection cover glass.
> Split cell standard technology
> Maximum bus bars.
> Special glass etching and anti-reflective coating.
> Solid Warranty, stable and well established company.
> Ammonia and salt mist corrosion resistance.
> Tier 1 solar panel producer.
> Fully automated production cycle, reducing sources of variation in production.
> Extremely low failure rate.( 6 sigma certified)
> Financial strong company.
> Multi award winning company.
> Test Standard(s) to which the module has been tested and certified.
> Each panel should have factory equipped weather proof terminal junction box having at least IP65 protection with
provision of opening for replacement of DC cables, blocking diodes and easy debugging if necessary.
> /25 years performance warranty for 80 % output power.
> Brand name(s) of PV modules
> Certified with high wind speed.
> Flash test reports from manufacturer for each panel given for sample.
> All information regarding solar panel with above mentioned featured data should be accessible and verifiable
online on the manufacturer website.
Page 1 of 10
The complete datasheet showing all the electrical parameters like input & output voltage ranges should be provided
in the technical bid. All the electrical parameters like input & output voltage ranges, and efficiency should be provided
at the time of pre-supply testing and inspection. Efficiency of inverter should be 92% and above.
• Rated output voltage of inverter / Controller shall be pure sine wave AC. Total harmonic distortion in AC output should
not exceed 2%.
• Inverter should have at least three (5) years extendable to 10 years performance warranty.
• Inverter circuit must include protection against:
> Over or Low voltages and currents beyond critical level of the inverters circuits.
> Protection against accidental short circuits & reverse polarity connections.
> Protection against lightning induced transients.
> Over load protection.
> Low RPM Protection (i.e: Frequency < 30 Hz) Motor Should Stop.
> Dry run protection.
• dV/dT Filters With Inverter (VFD):
> The use of load reactors increases the reliability, performance, and efficiency of VFD systems, extends the life
of both drives and motors, and reduces the amount of energy consumed by the motor/drive system.
> Output dV/dT or Sine Filters (between VFD and Motor) of appropriate size should be used where the motor
cable length is more than Fifty (50) Feet or as advised / recommended by the inverter manufacturer in their
Technical Documentation.
> dV/dT Filter should be enclosed in a box.
i) The DC power produced is fed to inverter for conversion into AC. In a grid interactive system AC power should be
fed to the grid at three phase 415 AC bus.
ii) Power generated from the solar system during the daytime is utilized fully by powering the critical building loads
and feeding excess power to the grid as long as grid is available. In cases, where solar power is not sufficient due to
more demand or cloud cover etc. the building loads should be served by drawing power from the grid. The inverter
should always give preference to the Solar Power and will use Grid/DG power only when the Solar Power is
insufficient to meet the load requirement.
iii) The output of the inverter must synchronize automatically its AC output to the exact AC voltage and frequency of
the grid.
iv) The offered On-Grid Inverter must be of Hybrid type has an ability to synchronize with battery bank as backup
system.
v) Inverter should continuously monitor the condition of the grid and in the event of grid failure; the inverter
automatically switches to off-grid supply within 20-50 milliseconds and synchronize with battery bank and fulfil
shortcoming from battery bank as PV-Battery hybrid system. The solar system is resynchronized with the grid
within two minutes after the restoration of grid or DG set.
vi) Grid voltage should also be continuously monitored and in the event of voltage going below a pre-set value and
above a pre-set value, the solar system should be disconnected from the grid within the set time. Both over voltage
and under voltage relays should have adjustable voltage (50% to 130%) and time settings (0 to 5 seconds).
vii) Metal Oxide Varistors ( MOVs) should also be provided on DC and AC side of the inverter.
Page 2 of 10
viii) The inverter control unit should be so designed so as to operate the PV system near its maximum Power Point
(MPP), the operating point where the combined values of the current and voltage of the solar modules result in a
maximum power output.
ix) The inverter should be a true sine way inverter for a grid interactive PV system.
x) The degree of protection of the outdoor inverter panel should be at least IP-55.
xi) Typical technical features of the suggested inverters must mention as per following sequence.
Continuous output power rating (1.1 times for 60seconds)
Nominal AC output voltage and frequency
Accuracy of AC voltage control ±1%
Accuracy of frequency control ±0.5%
Grid Frequency Control range +/- 3 Hz
Maximum Input DC Voltage range
MPPT Range DC
Ambient temperature -10 deg C to 55 deg C
Humidity 95 % non- condensing
Protection of Enclosure IP-55 (minimum)
Grid Voltage tolerance -20 % and + 15 %
Power factor control 0.95 inductive to 0.95 capacitive
No-load losses < 1% of rated power
Inverter efficiency (minimum) 95%
TUV certified, Warranty 5 years.
Liquid crystal display should at least be provided on the inverters front panel or on separate data
logging/display device to display following
a. DC Input Voltage
b. DC Input current
c. AC Power output(kW)
d. Current time and date
e. Time active
f. Time disabled
g. Time Idle
h. Temperatures (C)
i. Converter status
Following should also be displayed like Protective function limits, Over voltage, AC under voltage, Over
frequency, under frequency, ground fault, PV starting voltage, PV stopping voltage, over voltage delay, under
voltage delay over frequency, ground fault delay, PV starting delay, PV stopping delay.)
Page 3 of 10
4. Cable and DC Wiring for Water Pumping system:
> The AC / DC cables should be made of 99.9% copper strands and Flexible.
> The DC cable must have double insulation suitable for 1000 VDC transmission.
> DC circuit breakers (not fuse) of at least 800V and suitable ampere rating must be installed between PV modules
and PV pump controller in order to avoid short circuiting.
> AC Circuit Breaker of suitable rating must be installed between Pump Controller and Motor.
> DC Breaker, AC Breaker and Inverter / Controller should be placed in an enclosure of IP55 standard.
> Cables shall be clearly labelled with essential electrical parameters including manufacturer name, Voltage Range,
standards etc.
> All wiring shall be aesthetically neat and clean, over all wiring/connection losses shall not exceed 1% of the total
rated output power.
> All connections/ socket outlet among array, controller, inverters, batteries, and pumping set etc must be made in
junction boxes of adequate protection level.
> All wires/cables should be in standard flexible UV-Resistant conduits for outdoor installation and HDPE pipes (3
feet deep) for underground wiring and PVC ducts for indoor installation.
The auto Tracker should also have manual control mode to adjust the tracking angle manually. Structure Material
Should be Hot Dipped Galvanized Steel (Minimum 80 Microns).
All nuts, bolts, washers and other fasteners for mounting structure shall be made of minimum A2 grade stainless steel.
Foundation and other details will be separately provided. 06 years Comprehensive Free Replacement, Repair and
maintenance Warranty (Free of Cost) should be provided for all the components of auto Tracker (including Batteries).
7. BATTERIES:
> The battery should be maintenance free, Deep Cycle, Tubular, OPzV Type. (AGM, GEL, LI ion)
> The battery must ensure safe and reliable operation in the whole range of ambient temperatures from -5° C to +
50° C.
> The maximum permissible self-discharge rate should not be more than 5 percent of rated capacity per month at
25° C.
Page 4 of 10
> Cycle life of the battery minimum 3000 @ DOD 80 %.
> Battery should have maximum discharge rate.
> The battery shall have a certificate of compliances, issued by a recognized laboratory.
> The Batteries should have minimum 5 to 10 years.
> The battery shall meet the requirements and recommendations given in IEC 60896 21/22.
8. LED LIGHTS:
> Solar Based LEDs/Light fixtures shall conform to the latest IEC/ISO internationally recognized standards.
> LEDs/Light fixtures should not be Chip-on-board (COB) single chip type due to their poor heat dissipation.
> LEDs/Light fixtures shall be modular type with proper heat sinks.
> Solar based lights (LED fixtures etc) should provide at least 100 Lumen/watt.
> LEDs/Light fixtures should be designed to deliver at least 10 years of service.
> Complete lightening unit shall be weather proof (Protection Class IP65).
> The output from the LEDs/Light fixtures should be constant throughout the duty cycle.
> The LED lights should have minimum 10,000 duty hours.
15. Water Pump
Internationally certified. Pump should be supplied having standard ISO-9906 Grade-1 specifications. The pump must
be submersible, made of stainless steel. The characteristic curves (Original from Manufacturer) showing the efficiency
at duty point and performance of the pump should be provided in the technical proposal and also at the time of pre-
supply testing. The quoted pump should be tested for its performance and certified as per ISO-9906 Grade-1 standard.
The pump should be suitable for installation and operation in tube wells/dug wells/open well with clear water
discharge. Pump shall comprise off bowl assembly and non-return valve as integral part of pump’s parts. Pump and
motor shall rigidly couple through NEMA standard coupling. The stage casings of pumps should be connected as per
NEMA/ANSI/AWWA /ASTM/BSS standard. Each stage casing must have replaceable wear ring. The impellers shall be
secured to the pump shaft with tapered conical sleeves pressed into the taper bore of impeller or impeller secured
through chrome plated stainless steel hexagonal sleeves. Suction casing must be between pump and motor with
suction strainer as protection of pump against coarse impurities of the liquid handled.
Note: Bronze submersible pump of equivalent standards can also be provided with prior approval.
Specification for main components of the Pumps:
S.NO Components Specifications
Casing/Diffuser The Casing/Diffuser should be in fabricated stainless steel AISI
1
304.
2 Impellers stainless steel AISI 304
3 Driving Shaft Stainless steel 304/420
4 Sleeves Stainless steel AISI 329/ 304
5 Gaskets Rubber Gaskets
6 Bearings AISI 329 stainless steel
7 Coupling & Screen + Cable Stainless steel AISI 316/319/304/420
Guard
Non-Return Valve / As per British standard specifications (BSS), Minimum
8
Sluice Valve 16 bar pressure sustaining design
9 Pressure Gauge As per British standard specifications (BSS), having PSI or Bar
scale
10 Clamps Steel – Pressed
11 Pump Efficiency
Minimum efficiency of the pump should be 70% ensured at
duty point. (Duty Point of the Pump should always be selected
to the right of Pump Peak efficiency Point)
Page 5 of 10
16. Water Motor
Internationally certified .The winding material should be 99.99% copper. The motor should have wet type, water cool
rewind-able/repairable stator. The motor should have non-disposable/non-hermetically sealed winding. The
insulation class of the winding material should be mentioned. For each model quoted, all the technical parameters
such as rated voltage, power factor, efficiency, full load ampere, speed and other similar parameters should be
provided at the time of pre-supply testing. The testing report with all basic parameters should also be provided at the
time of pre-supply testing.
The motor shall be manufactured in compliance with National Electrical Manufacturer Association (NEMA) standards.
The motor shall be three-phase submersible and shall be capable of operating at rated voltage of 380 Volts at 50 Hz.
The motor should be capable of operating with variable
speed through V/F control. Winding of the motor shall of rewind able type with class - IC40 insulation and IP68
protection. The synchronous speed should be 2850-2950 RPM. Motor shall be capable of operating in well water
with temperature normally start from 40C. Motor should be designed for continuous operation. Motor must be
filled with water without any chemical additives hazards to health for cooling. The motor must be properly
protected against the entry of well water sand etc by double mechanical seal one is rotating and other stationary
and must be made of Silicon carbide/ Tungsten carbide and must be protected with sand protection guards. All
supports shall be high grade cast iron and stator outer side jacket body should be in stainless steel in AISI 304.
The excessive pressure due to heating up of the filled water must be compensated by a pressure equalizing
rubber diaphragm in the lower part of the motor. The axial thrust of the pump shall be countered by oscillating
sliding block type thrust bearing. The thrust bearing of the motor should be able to bear a download thrust force
from the water pump and the upward thrust force produced while starting the water pump. Motor shall be
capable of maximum of 20 starts in an hour. Motor efficiency should not be less than 75% at Motor Rated
Voltage.
Page 6 of 10
Technical specification of rewind-able wet stators, three phase squirrel cage water filled submersible motor.
Page 7 of 10
The column pipe shall be supplied in interchangeable section having an approximate length of 10 feet column
pipe shall be flanged perpendicular to the axis of pipe.
HDPE Pipe of 1 or 0.75 Inch diameter conforming to ASTM F-2160 Standard without Joints to be
installed/included along with and equal to Column pipe for confirming Water Level testing purpose.
FEATURES:
• Manufacturer’s pipes should meet international standards like BSEN 10255 & ASTMA 53.
• Dimensional accuracy circularity and plan end cut should be observed,
• Weld strength of pipe and mechanical properties or raw material should be tested as per manufacturing
standards.
• Pipes should be NDT tested (Non-destructive - Eddy current)
• Pipes should be hydrostatically pressure as per manufacturing standard.
• Pipes should be gone through straightening process to remove bendiness.
For Cleaning of solar Panels, Plastic pressure pipe should be provided of suitable length to reach the furthest /
last Solar Panel.
Every Water Supply Scheme should have a non-removable name plate fitted at inverter box having essential
information and bearing the name of supplier and client.
The equipment must be internationally certified. DC motor brushless, Built inside a cast stainless steel housing. High power
rare earth (neodymium) permanent magnets to provide high torque for maximum performance. Driven by a PWM signal
from the controller. The PWM signal ensures a soft start and infinite speed control of the motor. Only non-corrodible
materials are used, motor windings are cast in resin to provide a very long life, even in difficult conditions.
Control equipment must:
Control equipment includes monitoring, power conversion, MPPT (Maximum PowerPoint Tracking) sensors,
Software base commission, Mobile Software, Storage data option, frequency control and other equipment
related to the solar pumping system.
The W-LED solar lightning system should be designed to operate from dusk to dawn (more than 14 hours)
The Light source should be white type.
Page 8 of 10
Color LED used in the system should be in the range of 5500 K to 6500 K (Cool White)
LED emits ultra violet light is not permitted.
The light output source should be constant.
Luminous flux should be 4000 lumens with permissible allowance of 10 %.
The outdoor housing or luminaries should be all weather proof.
Heat sink temperature should not increase more than 20 degree centigrade above ambient temperature.
The charge controller must ensure safe and reliable operation in the whole range of ambient temperature from -
20 to +50 degree centigrade.
The make, model number and country of origin should be mentioned.
The performance warranty should cover at least 3 years for replacement upon defect/ malfunctioning.
25. The authorized dealer must attach List of clients/customers to whom the
equipment delivered.
Page 9 of 10