Solar Enquiry Permanand
Solar Enquiry Permanand
6 Maximum Peak MDI (From Feb-23 to Jan 24) KW 638.4 432 24.51
7 Annual Average Power Drawn KWH 262.9 159.1 7.3
8 Annual Energy Consumption (Feb-23 to Jan-24) Lac KWH 22.9 13.8 0.64
20 Design Voltage & Frequency Variation % ±10% (Voltage) & ±5% (Freq) ±10% (Voltage) & ±5% (Freq) ±10% (Voltage) & ±5% (Freq)
21 Area Available (Excluding Parking Area) Sq Feet 15,000 10,000 12000 To be evaluate
Vender
Sr. No. Description UOM Requirement Vender Confirmation Vender Confirmation Remarks
Confirmation
A Total Solar PV Plant Capacity kWp Maximum capacity as per available area 220 130 45
4 MMS Column Post with Anchor Fasteners - VTS yes yes yes
9 MMS height from Floor m 1.2m/1.4m/2m (May Vary during DDE) yes yes yes
Vender
Sr. No. Description UOM Requirement Vender Confirmation Vender Confirmation Remarks
Confirmation
3 AC Rating@ PF 1 @ 50 0C kW VTS
4 Nos of Inverters for Installation with stand and Canopy Nos. VTS
10 Inverter Output Voltage Volt 415 +/- 10% yes yes yes
Vender
Sr. No. Description UOM Requirement Vender Confirmation Vender Confirmation Remarks
Confirmation
F ACDB
G DCDB
1. Min 4 SQMM
2. Losses Less than 1.0 %
1 DC Cable (String) & Accessories Sq mm yes yes yes
3. Compatible MC4 Connector
4. To be laid in DWC Conduit
1. Losses Less than 2.0 %
2 AC Cable (Inverter to ACDB) & Accessories Sq mm yes yes yes
2. Type - FRLS
4 Extention panel with MCCB at Final Connection Point - Vender to check feasibility with Existing Panel yes yes yes
DC Earthing -
1. Module to Module Earthing (Cable 2.5 Sqmm)
2. Table to Table Earthing
3. DC Grid to be Prepared
8 Earthing system with Earthing Pits shall be considered - yes yes yes
4. Min 2 Earthing Pit / As per IS Standards
AC Earthing -
1. Earthining Pit quantity for Inverter: VTS
2. Earthining Pit quantity for ACDB: VTS
10 Lightning system (Level-4 LA & Earthing system) Required yes yes yes
Vender
Sr. No. Description UOM Requirement Vender Confirmation Vender Confirmation Remarks
Confirmation
1. Inverter data
2. ACDB MFM
15 Data Logger, control & Report Set yes yes yes
3. Manin Incomer
4. Reactive power Control
1. Two Nos Liquefied CO2/ foam/ ABC type fire extinguisher shall be upright type of
capacity 10 kg.
16 Fire Extinguishers & Saferty equipment yes yes yes
2. Two no. of sand bucket on one stand
3. Rubber Mat for ACDB Floor & Extension Panel Floor
1 Complete design and engineering including Civil - Required yes yes yes
Vender
Sr. No. Description UOM Requirement Vender Confirmation Vender Confirmation Remarks
Confirmation
Vender
Sr. No. Description UOM Requirement Vender Confirmation Vender Confirmation Remarks
Confirmation
LT Connection
Plant Load
X MCCB
Vendor Scope
PV
String
Note :
1. Net-Meter (Meter, CT & PT) Shall be in vendor scope.
2. Extension Panel with MCCB shall be Vendor scope.