Firmware Update Procedure
Firmware Update Procedure
Note – Some USB to RS232 serial port devices can cause a failure during the firmware transfer process,
which results in the panel failing to restart. Even if the panel is in this state, the process below can be used
to attempt to load the file into the panel.
It is recommended that a direct RS232 computer port is used, as these are proven reliable and robust
Page 1 of 4 Issue 01
FIRMWARE UPDATE PROCEDURE
Check COM port setting is correct for the serial port used for the panel connection.
Page 2 of 4 Issue 01
FIRMWARE UPDATE PROCEDURE
This completes the update process. For networked systems, ensure all panels are updated with the same
firmware version to ensure reliable and robust operation.
*Note* The EN54 compatible firmware version is for panels WITHOUT a write enable switch fitted.
Upgrading Syncro panels that have an Issue 06 Display board is NOT recommended, as this may result in
watchdog faults.
!! Loop Explorer Version 6 MUST be used for V6.xx Firmware control panels!!
Page 3 of 4 Issue 01
FIRMWARE UPDATE PROCEDURE
2 AUTOLEARN Procedure
Warning: The Autolearn procedure will erase ALL previous panel configuration information. Ensure that you
have a copy of the site configuration before attempting this process.