Comparative Analysis of Exciting Current Harmonics and Reactive Power Consumption From GIC Saturated Transformers
Comparative Analysis of Exciting Current Harmonics and Reactive Power Consumption From GIC Saturated Transformers
Abstract: Geomagnetically induced currents (GIC) can cause severe MVar consumption directly with the given GIC, which is
transformer half-cycle saturation. This paper introduces a simplified helpful for on-line GIC monitoring. The effect of the
method based on the equivalent magnetizing curve of the transformer transformer parameters on the GIC induced saturation is also
to estimate harmonic currents and MVar with only the given the GIC discussed, such as the voltage, MVA, and the normal exciting
and nameplate and core design information of the transformer. The
current.
simulation method is validated with the field results. The simulation
methods are validated with observational and field test data for
transformers experiencing half-cycle saturation. II. DESCRIPTION OF THE SIMPLIFIED APPROACH
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 318
Authorized licensed use limited to: University of Otago. Downloaded on September 24,2023 at 22:42:26 UTC from IEEE Xplore. Restrictions apply.
i(t) is equal to the applied GIC, I&. FFT is used to find 2. Three-phase, 3-legged, core form. Similar to the case of
harmonic currents from i=(t), and the MVar Q is given below three-phase, shell form, the different values of the slope kz, k3,
the second knee CZ, and the scaling factor of GIC are
Q = 3* Ul”Il (3) determined by test results.
3. Three-phase, 5-iegged, core form. Supposed that the
11is the fundamental component of i(t). positive-sequence AC flux only exists in the main legs and the
magnetic path per phase can be roughly shown in Fig.2 (a).
B. Treatment of auto transformers The DC flux flows between the side leg and the main leg as
shown in Fig.2 (b). Here S is the cross-section area of the
Auto transformers can be modeled as two-winding main leg, and that of the side leg is half of the main leg. L is
transformers as long as an effective GIC or DC current&c is the leg height. The equivalent AC and DC magnetizing curves
used for the unequal flow of GIC in the series and common are shown in Fig. 1 (a). The AC curve can be found according
windings ‘6]. to the no-load V-I curve of the transformer, and the DC curve
is obtained below.
Z* =fI&,+z#(k+l) (4) Provided that FI is the AC magnetic-motive force (MMF)
in Fig.2 (a), the first slope kw of the AC magnetizing curve is
Where Id., and I& are the GIC flowing in the series winding given below.
and the common winding, respectively. k = VH/VL-1. VH and
VL are the terminal voltages on the HV and the LV side of the F,= NIW = HIL + H2L
auto transformer. In the analysis below, only two-winding =/d*@S+,ul*y/(2S) =,Ld/S*(l.5~ (5)
transformers are discussed assuming that auto transformers
have already been represented by two-winding transformers. k== ~(NI=) = (2/3) *S/(/d) (6)
C. Simpll~ed algorithm for single-phase transformers Where Ix is the AC exciting ctu?ent, HI and Hz are the
magnetic strength of the legs, v is the AC linkage, N is the
The process of estimating harmonic currents for the single- turn number of the exciting winding. The effect of yokes is
phase transformer is straight-forward since it involves only ignored. F2 is the DC MMF in Fig.2 (b), and ~& is the DC
one common main flux path that can be represented by a non- current per phase, then the first slope of the DC magnetizing
linear inductance. The magnetizing curve VZ can be given curve kdcis shown below.
directly from the no-load voltage-current V-Z curve of the
exciting winding according to Eq. 1, either core form or shell
form. The typical magnetizing curve can be replaced by a
proxy using a piecewise linear representation as shown in
Fig. 1 (a), k, and kz are the slopes of the lines. As a rule of
thumb, ].1 is equal to 1.1* fi& at the knee of the
magnetizing curve. l=. is the RMS value of the normal
exciting current.
m
transformers is not considered below.
1. Three-phase, shell form. The equivalent @ curve is
represented by five straight lines, other than three lines, in
s S12 L
order to roughly describe the complicated AC and DC flux
H,
coupling in the core. As shown in Fig. 1 (b), the slope kl and
+&,:
the tirst knee Cl are determined according to the rated voltage
and the normal exciting current similar to the case of the (a) AC magnetic path (b) DC magneticpath
single-phase transformer. The slope kz, k3, and the second
knee Cz are determined by field results. Since the path of DC Fig.2 The simplified magnetic path of the three-phase, 5-
flux induced by GIC is different from the AC flux path, a Iegged, core form transformer
scaled GIC which would have the same effect as the original
GIC in the core is considered in Eq.2.
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 319
Authorized licensed use limited to: University of Otago. Downloaded on September 24,2023 at 22:42:26 UTC from IEEE Xplore. Restrictions apply.
0-7803-6674-3/00/$10.00 (C) 2000 IEEE
F,= NI&= M* @Y + /d* y/i(O.5*S) = ,WS*(3 y/) (7) Table 1 The comparison of the second harmonic current of transformers with
different core design between the simulated and measured results
k&= ~(NI~J = (1/3) *S/@Z)= kJ2 (8)
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 320
Authorized licensed use limited to: University of Otago. Downloaded on September 24,2023 at 22:42:26 UTC from IEEE Xplore. Restrictions apply.
0-7803-6674-3/00/$10.00 (C) 2000 IEEE
t~2, and t2= T14 + tJ2. GIC per phase can be obtained by the
3W
triangle area S divided by the period of T, that is,
~.
$2?0
— Single-phase GIC = S/T= (A@/2)/T (9)
b ------ Three-phase, shell form
Sm ~ /
The exciting current i(t)and its Fourier series are given
~ Three-phase, 3-legged
below.
‘El // – ~=-ph~e$,’==d
‘4(l+(t-~~).~d) t,<t<T~
i(t) = .4(1- (t-T~).~d) %<t+
(10)
GIC per phase (A) [
0’
Fig.4 The variation of the exciting current vs the input GIC per
phase
I others
In =+ f~i(t). exp(-jrcoot) d
2
(11)
[1
sin(nq f)
=GIC. exp(-jnroo $).
td
rrc&2
~
GIC per phase (A) GIC per phase (A)
(a) Single-phase (b) Three-phase, shell form
Where @ = 27dT, n = 1,2,3 Eq. 11 means that not only the
,6 35 fundamental component 11, but also all other harmonics are of
2,, good linear relationship with GIC. The magnitude of the
E
?. /
g’: harmonics falls off as l/n. In fact, since the duration td does
also vary with the increase of GIC, this results in the
.: e nonlinear relationship between the higher order harmonics
04 and GIC. Thk has been verified by field measurements ‘2].
E
z
~2 Fig.5 also shows that the even harmonics increase
0 >0203040! dramatically with the increase of GIC, different from the case
GIC per phase (A) GIC per phase (A) of the transformer over-excitation. Half-cycle saturation,
caused by the presence of GIC, will produce significant levels
(c) Three-phase, 3-Iegged, (d) Three-phase, 5-le~ed,
core form core form of even harmonics. The detection of even harmonics serves
as a reliable indicator of the presence of GIC and half-cycle
Fundarnerrtrd-frequency
saturation.
~ 4ti harmonics
------ 2“dharmonics +++++ 5ti harmonics
B. Reactive power consumption
------- 3rdharmonics eegeeo 6ti harmonics
The MVar consumption of the transformer is calculated by
Fig.5 The relationship of the exciting current hwrnonics and GIC for
using Eq.3. As shown in Fig. 7, the variation of the MVar
transformers with different core design
consumption is also linear with the increase of GIC for the
sake of the fimdamental component of the exciting current.
The harmonics variation in Fig.5 has the same trend as the The MVar drawn by the transformer can be easily estimated
case of the exciting current peak. It should be noted that the by using the following formula according to Fig.7.
fundamental and second harmonic currents are linear with
GIC in the calculated range for all types of core design. The Q (MVar) = kl*GIC + Q, (12)
harmonics become nonlinear with the increase of GIC if the
harmonics order is higher. This can be explained below. Here QO is the reactive power consumption from the normal
As shown in Fig.3 (a), if GIC is five times more than the exciting current and the value of GIC is in neutral. The value
peak of the normal exciting current, the normal exciting of kl is given in Table 2 for different core designs.
current can be ignored and the exciting current waveform cart
be approximately represented by a periodical triangle wave as V. CONCLUSION
shown in Fig.6. Here A is the exciting current peak, f = UT is
the fundamental frequency, k] and kz are the slopes. The To estimate harmonic currents and MVar with only the
duration of the trirtngle puke td iS equal to tz-tl, then tl= T/4 - given GIC and the nameplate information of the transformer,
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 321
Authorized licensed use limited to: University of Otago. Downloaded on September 24,2023 at 22:42:26 UTC from IEEE Xplore. Restrictions apply.
0-7803-6674-3/00/$10.00 (C) 2000 IEEE
The authors gratefully acknowledge the contributions of
—.
L _____________________
National Science Foundation (NSF) and Metatech financial
support of this work.
z
.-
.=
? k, VII. REFERENCES
H
w [1] Vernon D. Albertsou Geomagnetic disturbance causea and power
system effects, IEEE Special Panel Session Repo@ IEEE PES Summer
Meeting Jrdy 12,1989, Long Beac~ Califomi~ USA pp.3-9
t, T/4 ~2 T12 b
T [2] RL. Lesher, C.L. Wagner, W.E. Feero, SUNBURST GIC Network
Time EPRIRepo~RP-3211-01, Nov. 1993
[3] Shu LL Yilu LiL A fundamental analysis of @rnsforrner GIC
Fig.6 The approximate wavefotm of the exciting current in case of
magnetization using the finite elements approach, Proceedings of the
the transformer saturation
American Power Conference, A@ 1991, Illinois Inst. Technol, Illinois,
USA pP.1 173-1178
[4] RA Walling AH.Khaq Characteristics of transformer exciting-current
during geomagnetic disturbances, IEEE Trans. on Power Delivery, vol.
6, no. 4, 1991, pp. 1707-1714
[5] W. XW T.G. Martinic~ J.H. %wad~ Y. Mansour, Harmonics from SVC
transformer saturation with direct current offset IEEE PES Summer
3.
Meetin& 404-4 PWRD, 1993, pp. 1-7
&
3 ------ Three-phase, shell form
~= [6] D.H. Boteler, RM. Shier, T. Watanabe, RE. Hori@ Effcts of
al” +++++ Three-phase, 3-legged geomagnetically induced currents in the B.C. hydro 500 kV system,
.: ,6
0 ~ Three-phase, 5-legged IEEE Trans. on Power Delivery, vol. 4, no. 1, 1989, pp.818-823
~ ,,
[7] Ymg Kening, power engineering Press of Xi an Jiaotong Univ., 1984,
&,
pp.173
o,,o,, mss am [8] John G. Kappc- Transformer JX excitation field test& results,
GIC per phase (A) IEEE Special Panel Session Repoz IEEE PES Summer Meeting, July
12, 1989, Long Beach, California, USA pp. 14-22
Fig.7 The variation of the MVm consumption vs the input GIC [9] GeneraJ Electic Company, High-voltage direct-current converter
per phase transformer rnagnetics, EPRI EI..-434O, DC. 1985
VIII. BIOGRAPHIES
Table 2 The value of k, and kz for different core designs
Xuzhu Dong is pursuing his second Ph.D. degree in Power Systems at
Vbginia Tech. He received his BS, MS, and PHD degrees from Tsinghua
University, China, in 1993, 1998. His current research interests are power
system transient power equipment monitoring and diagnosis, Internet
applications in pewer system. H]s E-mad address is [email protected]
0-7803-6674-3/00/$10.00
0-7803-6672-7/01/$10.00
(C)(C)
2000
2001
IEEE
IEEE 322
Authorized licensed use limited to: University of Otago. Downloaded on September 24,2023 at 22:42:26 UTC from IEEE Xplore. Restrictions apply.
0-7803-6674-3/00/$10.00 (C) 2000 IEEE