The document provides details on generator sizing for a hospital project. It includes a customer name, project name, consultant comments and responses. Generator capacity, fresh air requirements, material lists and sizing reports are discussed.

Uploaded by

salahuddin.engg
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views

Gen Cal

The document provides details on generator sizing for a hospital project. It includes a customer name, project name, consultant comments and responses. Generator capacity, fresh air requirements, material lists and sizing reports are discussed.

Uploaded by

salahuddin.engg
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

Customer Name: MIRAS INTERNATION INVESTMENT

Project Name : Olayan Hospital

# Consultant Comments Cummins Reply


1 Cummins last agreed proposal with the contractor, consultant and user in the meeting dated 30 November 2022 is for total Gen-Sets rated power 4088kVA
/ 3270KW ESP achieved by the following proposal:-
•Qty: 1 X C2000D6 with rated power "2500kVA / 2000KW ESP", Derated site net output at site conditions 50⁰C & 635mASL is 2,411.25kVA / 1,929kW ESP.
Generator capacity submitted is not matching with
•Qty: 1 X C1250D6 with rated power "1588kVA / 1270KW ESP", Derated site net output at site conditions 50⁰C & 635mASL is 1,527kVA / 1,222kW ESP.
project contract documents.
The total Project Gen-Sets derated site net output Power is 3,151 KW / 3,938.25 kVA, the total loads are 2202 KW hence the Gen-Sets will be running @
70%.

2 Submit Sizing report at derating calculation 50C shown Attaching the last updated sizing report and Gen-Sets deration reports for the proposed Gen-Sets @ 50⁰C & 635mASL
genset net power as per engine derating -engine gross

power(KW) -fan power- ………. etc.


3 Cummins required air flow are as follows:-
Fresh air inlet required for the generator (CFM) In
•The C1250D6 cooling system air flow is 34.6 m3/sec (73,313.3 CFM) @ maximum cooling air flow static restriction 12.7 mmH2O with required combustion
coordination with the Mechanical Department to avoid
air flow rate is 110.4 m3/min (3,898.8 CFM).
any overheating or in efficient operation for the
•The C2000D6 cooling system air flow is 38.2 m3/sec (80,941.3 CFM) @ maximum cooling air flow static restriction 12.7 mmH2O with required combustion
generator.
air flow rate is 174 m3/min (6,144.8 CFM
4 Material list with brand and country of origin to be Attached.
submitted.

# Cummins Public
Date: 04 December 2022.
Subject: Deration Calculation Sheet.
Project: LTAC Rehabilitation Hospital.

“C2000 D6” Standby Power Genset

GENSET NET POWER AS PER ENGINE DERATION:


Engine: QSK60-G6

Engine Standby Power = 2180 KWm


Deration at 50 ⁰C and 635 mASL = 6 %
Engine Fan Power = 44 KWm
Alternator Efficiency = 96.2 %
Genset Net Power = {(Engine kW Deration%) – Fan Power} x Alt.Efficiency

Genset Net S Power = {(2180 x 0.945) – 44} x 0.962 = 1929 KWe


GENSET NET POWER AS PER ALTERNATOR DERATION

Alternator: PI734F

Power output at 400V: 2084 KW


Deration at 50 ⁰C & 635 mASL altitude: 6 %
Total power Output after Deration: 2084 x 0.94 = 1958.96 KWe

Total Genset Net Power After Deration @ 50 ⁰C and 635 mASL is = 1929 KWe ESP

Baher Adel Elbarbary


Application Engineer – Technical Specialist
Cummins Saudi Arabia Limited, (Riyadh Branch)
Loads Summary Report
Project - LTAC Rehabilitation Hospital
Comments -
Project Requirements

Frequency, Hz : 60.0 Generators Running in Parallel : 2

Duty : Standby Site Altitude, ft(m) : 2001(610)

Voltage : 220/380, Series Wye Site Temperature, °C : 50

Phase : 3 Max. Altr Temp Rise, °C : 150

Fuel : Diesel Project Voltage Distortion Limit, % :

Emissions : No Preference

Loads Summary List


*Note: Detailed Loads and Step Report available below

Running Starting Peak Dip Limits, % VTHD%


Step No. Load Name Quantity
kW kVA kW kVA kW kVA Vdip Fdip Limit

Step01 LOAD A (LIFE 1 86.08 107.6 86.08 107.6 None None 30.0 10.0 0.0
SAFETY) - H-DPBL-LS
FEEDER 2

Step01 LOAD B (CRITICAL ) - 1 41.52 51.9 41.52 51.9 None None 30.0 10.0 0.0
H-SGBL-NL5/EL5
FEEDER 3

Step Summary 64.0 80.0 64.0 80.0 None None 30.0 10.0 0.0

Step02 LOAD E - H-SGBL- 1 1134.96 1418.7 1134.96 1418.7 None None 30.0 10.0 0.0
NL3/EL3

Step Summary 567.0 709.0 567.0 709.0 None None 30.0 10.0 0.0

Step03 LOAD F - H-SGBL- 1 939.6 1174.5 1174.5 1468.12 None None 30.0 10.0 0.0
NL1/EL1

Step Summary 470.0 587.0 587.0 734.0 None None 30.0 10.0 0.0

Project
Running Max Starting Cumulative Step Cumulative Peak
VTHD%
Project Summary
kW kVA kW kVA kW kVA kW kVA Limit

1101.1 1376.3 587.2 734.1 1218.5 1523.2 0.0 0.0 0.0

*Note: Detailed Loads and Step Report available below

Notes: -
• The proposed Gen-Set models for LTAC Rehabilitation Hospital project are (Qty: 1 X C2000D6 with rated power
"2500kVA / 2000KW ESP" + Qty: 1 X C1250D6 with rated power "1588kVA / 1270KW ESP");
► "C2000D6" Gen-Set 400V 60Hz powered by engine "QSK60-G6" & alternator "Pl734F" winding 13 derated net out
power at Riyadh site conditions (635 mASL & 50°C) is 1,929kW / 2,411.25 kVA (Standby Rating).
► "C1250D6" Gen-Set 400V 60Hz powered by engine "KTA50-G3" & alternator "PI734B" winding 13 derated net out
power at Riyadh site conditions (635 mASL & 50°C) is 1,222kW / 1,527kVA (Standby Rating).
► Therefore, Total Project Gen-Sets Net Output Power: 3,151 KW / 3,938.25 kVA

► The Project Total Running Power: 2,202 KW.


► Each Gen-Set will run at 70% rated capacity.

Loads and Steps Detail Report 13-Nov-2022 Page 1


Loads and Steps Detail Report
Project - LTAC Rehabilitation Hospital
Comments -
Project Requirements

Frequency, Hz : 60.0 Generators Running in Parallel : 2

Duty : Standby Site Altitude, ft(m) : 2001(610)

Voltage : 220/380, Series Wye Site Temperature, °C : 50

Phase : 3 Max. Altr Temp Rise, °C : 150

Fuel : Diesel Project Voltage Distortion Limit, % :

Emissions : No Preference

Calculated Individual Generator Set Load Running and Peak Requirements

Running kW : 1101.1 Max. Step kW : 587.2 In Step 3 Cumulative Step kW : 1218.5

Running kVA : 1376.3 Max. Step kVA : 734.1 In Step 3 Cumulative Step kVA : 1523.2

Running PF : 0.8 Peak kW : None Cumulative Peak kW : None

Running NLL kVA : None Peak kVA : None Cumulative Peak kVA : None
Alternator kW : 1101.08

Step1

Calculated Individual Generator Set Step Load Requirements

Running kW : 64.0 Starting kW : 64.0 Cumulative Step kW : 64.0

Running kVA : 80.0 Starting kVA : 80.0 Cumulative Step kVA : 80.0

Running Amps : 243.0 Starting Non-linear kVA : 0.0

Running Non-linear kVA : 0.0

Alternator kW : 63.8

Voltage Distortion Limit for : 0


step

LOAD A (LIFE SAFETY) - H-DPBL-LS FEEDER 2 Three Phase Quantity : 1 In this Step

Category : User Defined

Running kW : 86.08 Starting kW : 86.08 Peak kW : None

Running kVA : 107.6 Starting kVA : 107.6 Peak kVA : None

Running PF : 0.8 Starting PF : 0.8 Cyclic : No

Running Amps : 155.49 Max. % Voltage Dip : 30.0 Max. % Frequency Dip : 10.0

Alternator kW : 86.08 Voltage : 400

LOAD B (CRITICAL ) - H-SGBL-NL5/EL5 FEEDER 3 Three Phase Quantity : 1 In this Step

Category : User Defined

Running kW : 41.52 Starting kW : 41.52 Peak kW : None

Running kVA : 51.9 Starting kVA : 51.9 Peak kVA : None

Running PF : 0.8 Starting PF : 0.8 Cyclic : No

Loads and Steps Detail Report 13-Nov-2022 Page 2


Running Amps : 75.0 Max. % Voltage Dip : 30.0 Max. % Frequency Dip : 10.0

Alternator kW : 41.52 Voltage : 400

Step2

Calculated Individual Generator Set Step Load Requirements

Running kW : 567.0 Starting kW : 567.0 Cumulative Step kW : 631.0

Running kVA : 709.0 Starting kVA : 709.0 Cumulative Step kVA : 789.0

Running Amps : 2158.0 Starting Non-linear kVA : 0.0

Running Non-linear kVA : 0.0

Alternator kW : 567.48

Voltage Distortion Limit for : 0


step

LOAD E - H-SGBL-NL3/EL3 Three Phase Quantity : 1 In this Step

Category : User Defined

Running kW : 1134.96 Starting kW : 1134.96 Peak kW : None

Running kVA : 1418.7 Starting kVA : 1418.7 Peak kVA : None

Running PF : 0.8 Starting PF : 0.8 Cyclic : No

Running Amps : 2050.14 Max. % Voltage Dip : 30.0 Max. % Frequency Dip : 10.0

Alternator kW : 1134.96 Voltage : 400

Step3

Calculated Individual Generator Set Step Load Requirements

Running kW : 470.0 Starting kW : 587.0 Cumulative Step kW : 1219.0

Running kVA : 587.0 Starting kVA : 734.0 Cumulative Step kVA : 1523.0

Running Amps : 1787.0 Starting Non-linear kVA : 0.0

Running Non-linear kVA : 0.0

Alternator kW : 469.8

Voltage Distortion Limit for : 0


step

LOAD F - H-SGBL-NL1/EL1 Three Phase Quantity : 1 In this Step

Category : User Defined

Running kW : 939.6 Starting kW : 1174.5 Peak kW : None

Running kVA : 1174.5 Starting kVA : 1468.12 Peak kVA : None

Running PF : 0.8 Starting PF : 0.8 Cyclic : No

Running Amps : 1697.25 Max. % Voltage Dip : 30.0 Max. % Frequency Dip : 10.0

Alternator kW : 939.6 Voltage : 400

Loads and Steps Detail Report 13-Nov-2022 Page 3


Cummins Saudi Arabia LLC Ref: PD-MAZ-12-06-22

1. BILL OF QUANTITIES

2. COMPLIANCE STATEMENT

3. GENERATOR DATA SHEETS

4. PRODUCT CERTIFICATES

5. PREVOIUS APPROVALS

6. REFERENCES LIST
Origin and Plant Specification

BOP- C1250D6 (Open Type) -1270KW, 1588 KVA Standby:

Item Description Qty.

1 CPG Diesel Engine Generator model (C1250D6) rated @ ISO Conditions: 1

1588 KVA/1270 KW STANDBY POWER

1400 KVA/1120 KW PRIME POWER at 400/230 V, 3phase, 4 wire, 0.8 Power factor, 60
Hz & 1800rpm

Each Generator Set Will Include:

Engine – Cummins 1

Jacket Water Heater. 1

Alternator – Stamford (Cummins). 1

Basic Base frame with integral Anti-Vibration Mountings and Lifting Points 1

Alternator (400/230 V, 60Hz. 1800rpm) 1

Alternator Heater. 1

Battery Charger 1

Set mounted Power Command 3.3 Control Panel 1

Skid Mounted Radiator Suitable for 50C Ambient Temperature 1

Lead Acid Batteries w/tray, & cables. 1

Startup & Commissioning 1

Transportation to site 1

Exhaust Silencer with Flexible 1

This Genset with Cummins UK Origin


Item Description Qty.

1 CPG Diesel Engine Generator model (C2000D6) rated @ ISO Conditions: 1

2500 KVA/2000 KW STANDBY POWER

2281 KVA/1825 KW PRIME POWER at 400/230 V, 3phase, 4 wire, 0.8 Power factor, 60
Hz & 1800rpm

Each Generator Set Will Include:

Engine – Cummins 1

Jacket Water Heater. 1

Alternator – Stamford (Cummins). 1

Basic Base frame with integral Anti-Vibration Mountings and Lifting Points 1

Alternator (400/230 V, 60Hz. 1800rpm) 1

Alternator Heater. 1

Battery Charger 1

Set mounted Power Command 3.3 Control Panel 1

Skid Mounted Radiator Suitable for 50C Ambient Temperature 1

Lead Acid Batteries w/tray, & cables. 1

Startup & Commissioning 1

Transportation to site 1

Exhaust Silencer with Flexible 1

This Genset with Cummins UK Origin


Origin and Plant Specification

BOP- C1250D6 (Open Type) -1270KW, 1588 KVA Standby:

Item Description Qty. Origin

1 CPG Diesel Engine Generator model (C1250D6) rated @ ISO 1 Complete Genset Model
Conditions: C1500D6 / Cummins UK

1588 KVA/1270 KW STANDBY POWER

1400 KVA/1120 KW PRIME POWER at 400/230 V, 3phase, 4


wire, 0.8 Power factor, 60 Hz & 1800rpm

Each Generator Set Will Include:

Engine – Cummins 1 Cummins India

Alternator – Stamford (Cummins). 1 Stamford Europe/India/

Depends on availability

Battery Charger 1 Cummins Europe/India


/USA

Depends on availability

Set mounted Power Command 3.3 Control Panel 1 Cummins Singapore/ USA

Lead Acid Batteries w/tray, & cables. 1 Part of the Genset

This Genset with Cummins UK Origin


BOP- C2000D6 (Open Type) -2000 KW, 2500 KVA Standby:

Item Description Qty. Origin

1 CPG Diesel Engine Generator model (C2000D6) rated @ ISO 1 Complete Genset Model
Conditions: C1500D6 / Cummins UK

2500 KVA/2000 KW STANDBY POWER

2281 KVA/1825 KW PRIME POWER at 400/230 V, 3phase, 4


wire, 0.8 Power factor, 60 Hz & 1800rpm

Each Generator Set Will Include:

Engine – Cummins 1 Cummins UK

Alternator – Stamford (Cummins). 1 Stamford Europe/India

Depends on availability

Battery Charger 1 Cummins Europe/India


/USA

Depends on availability

Set mounted Power Command 3.3 Control Panel 1 Cummins Singapore/ USA

Lead Acid Batteries w/tray, & cables. 1 Part of the Genset

This Genset with Cummins UK Origin