SGC 421data Sheet
SGC 421data Sheet
Main features
Monitoring engine safety, electrical load, site battery backup • Monitors telecom site battery backup level and shelter
voltage and shelter temperature (to reduce fuel consumption). temperature to reduce engine running and fuel consumption
at telecom tower sites
Configure parameters from a PC using DEIF’s configuration
• Controls start relay, fuel relay, alarm horn and more as
software (Microsoft Windows based). Connect to the PC through
digital outputs
the controller’s USB Type-B port.
In addition, the SGC 421 controller also includes an integrated • Event log for 100 events with real time clock (RTC) stamps
electronic governing function. and engine running hours information
Digital outputs
Environment • 5 x 1 A high-side drivers configurable for pre-heat, horn
and more
• Vibration: 2G in X,Y and Z axes, in compliance with IEC
• 2 x 5 A high-side drivers configurable for start relay, stop
60068-2-6
solenoid, fuel relay, contactors and more
• Shock: 15 g for 11 ms, in compliance with IEC 60068-2-27
• CE approved:
Mains/genset voltage measurement
- Comply to the EU Low Voltage Directive: EN 61010-1 Safety
requirements for electrical equipment for measurement, • 32 to 300 V AC RMS @ 5 to 75 Hz for phase-to neutral
control, and laboratory use - Part 1: General requirements
- Comply to the EU EMC directive EN 61000-6-2, 4 Load current measurement
• TÜV • 0 to 5 A AC RMS for current transformer (CT) secondary
• UL
E-governor module interface
• 1 A, 2-phase output for rotary actuators
• 2.5 ± 2 V input for target speed bias
• 2.5 V for zero bias
Dimensions
• External dimensions: 207 mm x 160 mm x 38.5 mm
• Mounting panel cut: 189 mm x 143 mm
Front of controller:
Rear of controller:
.
Technical specifications
Terminals
Terminals
Connector type Pitch Male (on controller) SM part no. Female (mating part) SM part no. Quantity
Power supply
Category Specification
1 (Ground)
Controller terminals
2 (Battery or DC+)
Resolution 0.1 V
Category Specifications
54 (Neutral)
55 (L3)
Controller terminals
56 (L2)
57 (L1)
Frequency range 5 to 75 Hz
For single genset applications, it is mandatory to connect the genset phase and neutral cables to the genset controller's
phase L1 and neutral terminals.
Category Specifications
Burden 0.25 VA
Category Specifications
Burden 0.25 VA
Follow the recommended phase sequence while connecting the current transformer (CT).
Mains voltage and frequency measurement
Category Specifications
50 (Neutral)
51 (L3)
Controller terminals
52 (L2)
53 (L1)
Frequency range 5 to 75 Hz
For single phase applications, it is mandatory to connect the mains phase and neutral cables to the genset controller's
phase L1 and neutral terminals.
Digital inputs
Category Specifications
Controller terminals 33, 34, 35, 36, 37, 38, 39, 40, 41
Number of inputs 9
Category Specifications
11 (LOP)
12 (Fuel)
Controller terminals 13 (Temperature)
14 (Aux 1)
15 (Aux 2)
Number of inputs 5
Range 10 to 1000 Ω
Open circuit detection Above 5.5 kΩ
21 (Aux3)
Controller terminal
23 (Aux4)
0 to 5 V DC
Range
4 to 20 mA
For genset paralleling application, configure input Aux4 on terminal 23 to accept a 0 to 5 V DC speed bias signal generated by a
LSM (Load Sharing Module).
Category Specifications
Number of inputs 2
Type Differential
Range ±60 V
Resolution 0.1 V
Category Specifications
Controller terminal 22
The Magnetic pick-up (MPU) is an inductive sensor fitted on the engine flywheel for the engine speed sensing. The output of the
MPU is a sine-wave signal.
Digital outputs
Category Specifications
Controller terminals 3, 4, 5, 6, 7, 8, 9
Number of outputs 7
5 A (3 and 4)
Maximum current rating
1 A (5, 6, 7, 8, 9)
Start relay, Fuel relay, Close genset contactor, close mains
Software configurable options contactor, Stop solenoid and many more (see Controller
overview, Configurable parameters for more details).
• Do not connect the Starter motor relay and the Stop solenoid directly to the controller's output terminals. It is
recommended to connect terminals 3 and 4 to Start and Stop.
• Genset and mains contactor latching relays should be compiled against 4 kVA surge as per IEC-61000-4-5 standard.
Actuator outputs
Category Specifications
Max. current 1A
The actuator outputs are used only for the Rotary actuator, if installed. The Rotary actuator is a 4-wire actuator that is used for
creating an electronic governing application in case of a mechanical fuel system engine. In diesel engines, the Rotary actuator's
shaft output gets mechanically connected to the stop lever or the throttle lever of an in-line or rotary fuel injection pump. In case of
petrol or natural gas engines, the Rotary actuator's shaft output gets connected to the throttle/charge control valve.
It is recommended to follow the connection details of the Rotary actuator connector and SGC 421.
D+ CHG ALT
Category Specifications
Controller terminal 10
0 to VBATT
Voltage range
VBATT = 8 to 30 V DC
The charge fail is a combined input and output terminal. When the genset starts, the terminal provides controlled power output to
excite the charging alternator. After the excitation is successfully done, the controller reads the charging alternator's output voltage
for monitoring its health. The action for charge fail is configurable.
Category Specifications
Controller terminal 16
Range ±2 V
Resolution 0.1 V
The sensor common point (SCP) terminal 16 of the controller should be directly connected to an electrically sound point on
the engine body. This point on the engine body should serve as a common reference point for all analogue sensors such
as those for measuring lube oil pressure, engine temperature and fuel level. The electrical cable used for the connection
should not be shared with any other electrical connection. Such a wiring practice is strongly recommended to ensure that
there is negligible potential difference, if any, between the engine body and the controller's SCP terminal, and, predictable
and accurate analogue sensor measurements are always available in a wide variety of field conditions.
Communication ports
Category Specifications
Half Duplex
Max. Baud Rate 115200
Data connection 2-wire
RS-485 Serial Port Termination resistor of 120 Ω is provided between output
terminals A and B
Common-mode operating range
Maximum distance of line is 1200 m
30 (GND)
Controller terminals 31 (A)
32 (B)
26 RESERVED RESERVED
27 RESERVED RESERVED
N/A
28 RESERVED RESERVED
29 RESERVED RESERVED
61 RESERVED RESERVED