Method Statement For Press Leak Test
Method Statement For Press Leak Test
METHOD STATEMENT
FOR
PRESSURE LEAK TEST
CONTENTS
I. SCOPE
II. REFFERENCE
V.ATTACHMENT
Doc. No.
1. SCOPE
2. REFERENCE
3.1 The PIPING SECTION CHIEF shall have responsibility and authority for direction
and control of the pressure leak test including all necessary provisions to perform
the activities.
3.2 The PIPING ENGINEER shall perform the pressure leak test activities and shall
provide all required inspection and control required for execution of pressure leak
test.
3.3 Prior to pressure test, the QC ENGINEER shall perform the inspection with
respect to the completeness of work, markings, calibrations adjustment,
protection from damage, or other characteristics as required verifying the quality
and conformances of the item to specified requirements (under the presence of
Owner).
3.4 Pressure test shall be performed by the PIPING ENGINEER under the presence
of QC ENGINEER and/or Owner.
3.5 Item to be checked shall be documented on the piping pressure test report by the
QC ENGINEER and approved by the QC SECTION CHIEF.
4.1.2 All testing shall be conducted by the Piping Engineer and shall be
witnessed by the QC Engineer and OWNER.
Doc. No.
4.1.3 Prior to pressure test, the Piping Engineer shall prepare the pressure
test package including Piping Pressure Test Report, Line & ISO
Drawing, marked up P & ID drawings to show the boundaries of the
test and filling.
4.1.4 The following items shall be shown in the "Pressure Test Package".
4.1.5 Valves intended for use in test boundary isolation shall be researched
by Piping Engineer that the valve are capable of withstanding the
pressure loads applied, likewise, all equipment within the test segment
shall be determined as being capable of withstanding the test.
4.1.7 Additional supports shall be temporarily installed if the system has not
been designed to support the weight of the test media.
4.1.8 Any expansion joints in the system shall be restrained or they shall be
isolated from the system during the test.
4.1.9 When pressure testing a system, the test pressure shall not exceed
maximum test pressure for any component in the system.
4.1.10 All components in the system that should not be subjected to pressure
test, such as pumps, tanks, heat exchangers, and instruments such as
control valve, relief valve, rupture discs, rotameter, pressure gauge,
gauge glasses, and filler elements shall be isolated from the test.
4.1.11 Two indicating pressure gauges shall be used for all process piping.
4.1.12 For the other piping except process piping may be used one indicating
pressure gauge.
4.1.13 The gauges shall have a reading range of 1 1/2 to maximum of 4 times
the test pressure.
Doc. No.
4.1.16 When performing pneumatic testing, Tape barrier shall be erected and
access to the area shall be restricted. Safety representative of each
area shall be control (restricted access) the restricted area. And also
safety valve is required for all high pressure testing (above 1.73
kg/cm²).
4.1.17 All welding inspection records for field welds, field modification welds,
and pressure boundary attachment welds shall be verified to exist and
be completed by QC Engineer.
4.1.19 The punching items found out during preliminary walk down shall be
cleared prior to the notification of pressure test to OWNER.
4.1.20 All open Non-Conformance Reports shall have been identified and
completed except those that are not pressure test restraints.
4.1.21 All joints shall be exposed and cleared of insulation and wrapping for
easy inspection.
4.1.22 Touch-up or primer one coating may be applied to shop and field
welds or damaged area prior to pressure testing, except where it may
mask a defect.
4.1.23 Before the start of the test, the Piping Engineer shall verify that tags
("DANGER" Tag) are attached on the all valves and components
within the boundaries of the test. He shall also verify that the test area
has been secured for the safety of personnel.
4.1.25 For low temperature service, it's requested to use air or nitrogen
without moisture content at the test pressure.
4.1.26 Except for the location to be inspected, the thermal insulation work
and painting work shall be performed upon completion of the pressure
leak tests and overall air-tightness tests.
4.2.7 To detect and pinpoint leaks, soap solution shall be applied until leaks
shall be seen as evolving bubbles or froth.
4.2.8 Soap solution shall be applied only with an apparatus, which will flow
the solution over the surface without leaving bubbles caused by
application.
4.2.9 Sponges or brushes shall not be used for the application of soap
solution.
4.2.11 Test equipment shall be removed and the system sealed sufficiently
with valves or blind flanges to prevent entry of foreign material into the
system.
4.3.1 Air vent shall be opened to allow the elimination of air from the system
during the water fill.
4.3.2 The system shall be gradually filled, venting air from high points.
4.3.4 A gradual and slow filling, combined with the removal of air from the
system, is required to eliminate the danger of water hammer.
4.3.5 The test pressure shall be applied gradually with a suitable hydraulic
pump in increments of 1/3 or less of the test pressure.
4.3.6 The test pressure shall not be applied until the system and the
pressurizing medium are at approximately the same temperature.
4.3.7 From 15 to 20 minutes shall be allowed after filling the system for
temperature equalization.
4.3.9 Thereafter, the test pressure shall be hold for as long as required to
allow examination by the QC Engineer and OWNER of all joints,
connections and regions and high stress such as around openings and
thicknesses transition sections.
4.3.11 Action shall be taken to properly vent the system during drainage after
hydrostatic test to prevent a vacuum in the test line.
11. Each hydrant and monitor shall be opened and closed under
water pressure with pumps running.
12. Monitors shall be checked carefully to see that they are properly
located to provide effective water spray and streams for the
equipment to be protected.
14. Fixed water spray systems for outside protection shall be tested
for rates of flow per nozzle, total rates, nozzle coverage patterns
and water run-down film character.
15. Flow rates per nozzle shall not vary more than ± 15% of the
calculated rate, and the total rate of each system shall not be
less than the required rate.
16. This test shall include the operation of all devices and
instruments that make up the system.
17. The installer shall correct nozzle locations and modify piping as
necessary.
After the pressure test and leak test, flushing or air blowing shall be conducted
for the tested system to assure the removal of dirt’s, debris and obstructions.
Details shall be subject to the field instructions by the OWNER and Line Table.
5. ATTACHMENT
The status and result of control according to this procedure shall be documented by use
of the following forms.