Transformer USS-01

The document describes an inspection and test record for a 13.8kV transformer. It provides nameplate details, describes mechanical and electrical checks performed, and lists insulation resistance, transformer ratio, and winding resistance measurement results. The testing was okay but the physical condition and oil leakage were noted as not okay.

Uploaded by

Amr Elkady
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views

Transformer USS-01

The document describes an inspection and test record for a 13.8kV transformer. It provides nameplate details, describes mechanical and electrical checks performed, and lists insulation resistance, transformer ratio, and winding resistance measurement results. The testing was okay but the physical condition and oil leakage were noted as not okay.

Uploaded by

Amr Elkady
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

INSPECTION AND TEST RECORD

Description: Contract no.:


13.8KV Transformer USS-01 082-C01
Customer: End Client: Sheet:
Page 1 of 3
ALHARBI ROYAL COMMISSION
Site: Panel / Designation / Location #: Project no.:
Secondary infrastructure 097-c73R
ALHARBI JUBAIL Transformer-USS-01

1. INFORMATION: NAMEPLATE DETAILS

USS-01 RATING POWER 300KVA


TAG NO
TYPE ONAN PRIMARY 13800 V

% IMPEDENCE 3.75 SECONDARY 400V


RATED
60 VECTOR GROUP Dyn11
FREQUENCY
SERIAL NO. 2008S07839 NUMBER OF PHASES 3

2. MECHANICAL CHECK AND VISUAL INSPECTION.

ITEM DESCRIPTION DONE REMARKS


1 Inspect for physical damage/defects (cracks, chips, etc., of the cast resin)  NOT OK
2 Check nameplate for correctness.  OK
3 Check tightness of all bolts  NOT OK
4 Check that all groundings are securely connected, Including star point neutral.  OK
5 Check HV and LV bushing for damages.  OK
6 Check quality of paintwork,quality of weld aress and rust spots.  NOT OK
7. Check completeness of accessories.  Not OK
8. Oil Leakage.  NOT OK

3. ELECTRICAL TESTS.

ITEM DESCRIPTION DONE REMARKS


1 Insulance Resistance (PI) Test  OK
2 Turns ratio all (taps) test.  OK
3 Winding resistance measurement (all taps).  OK

3.1 INSULATION RESISTANCE:

COMPANY ECO LIMITED ARABIA


NAME AMJAD KHAN
SIGNATURE
DATE 21-04-2024
TEST EQUIPMENT USED: METREL,IR
RXMB1 Page 1 of
3
INSPECTION AND TEST RECORD
Description: Contract no.:
13.8KV Transformer USS-01 082-C01
Customer: End Client: Sheet:
Page 2 of 3
ALHARBI ROYAL COMMISSION
Site: Panel / Designation / Location #: Project no.:
Secondary infrastructure 097-c73R
ALHARBI JUBAIL Transformer-USS-01

IR value
IR value
Applied points Applied Polarization Index
1 min ( G. 10 min ( G.
between voltage (PI)
Ohms ) Ohms )

Prim to Gnd 5kv 620 995 GΩ 1.60

Prim to Sec 2.5kv 17 GΩ 30 GΩ 1.76

Sec to Gnd 1kv 18 MΩ 7.7MΩ 2.3

3.2 TRANSFORMER RATIO MEASUREMENT:

Rated Tap Measured Measured Measured


Tap Calculated
Voltage Ratio Ratio Ratio % Error
Position Ratio
HV LV (UV/un) (VW/vn) (WU/wn)

1 14490 400 62.742 62.761 62.712 62.773 0.38

2 14145 400 61.248 61.277 61.284 61.271 0.13

3 13800 400 59.754 59.802 59.95 59.811 0.17

4 13455 400 58.260 58.303 58.312 58.308 0.24

5 13110 400 56.766 56.804 56.816 56.809 0.15

3.3 WINDING RESISTANCE MEASUREMENT:

Primary Winding:
COMPANY ECO LIMITED ARABIA
NAME AMJAD KHAN
SIGNATURE
DATE 21-04-2024
TEST EQUIPMENT USED: METREL,IR
RXMB1 Page 2 of
3
INSPECTION AND TEST RECORD
Description: Contract no.:
13.8KV Transformer USS-01 082-C01
Customer: End Client: Sheet:
Page 3 of 3
ALHARBI ROYAL COMMISSION
Site: Panel / Designation / Location #: Project no.:
Secondary infrastructure 097-c73R
ALHARBI JUBAIL Transformer-USS-01

Measured Resistance
Tap no. Remarks
U-V(Ω) V-W(Ω) W-U(Ω)
1 5.142 5.11 5.162 OK
2 5.144 5.137 5.112 OK
3 (Nominal) 5.180 5.129 5.128 OK
4 5.151 5.160 5.196 OK
5 5.131 5.166 5.112 OK

Secondary Winding:
Tap no. Measured Resistance Remarks

u-n(mΩ) v-n(mΩ) w-n(mΩ) OK


3 (Nominal)
2.5 2.4 2.4

Remarks:

Testing ok but physical condition of transformer is not ok oil already leaked inside condition of LV
side bushing is also not ok check for LV side the IR value is not coming good as per standard

COMPANY ECO LIMITED ARABIA


NAME AMJAD KHAN
SIGNATURE
DATE 21-04-2024
TEST EQUIPMENT USED: METREL,IR
RXMB1 Page 3 of
3