System No. C-AJ-2371: F Rating - 3 HR T Rating - 2 HR and 3 HR (See Item 3)

The document provides details on a firestop system rated for up to 3 hours. It can be used with nonmetallic pipes up to 6 inches in diameter installed through concrete floors or walls. The system includes wrapping the pipe with intumescent material and securing a metal collar around the wrap with fasteners.

Uploaded by

darwish.hilti
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
148 views

System No. C-AJ-2371: F Rating - 3 HR T Rating - 2 HR and 3 HR (See Item 3)

The document provides details on a firestop system rated for up to 3 hours. It can be used with nonmetallic pipes up to 6 inches in diameter installed through concrete floors or walls. The system includes wrapping the pipe with intumescent material and securing a metal collar around the wrap with fasteners.

Uploaded by

darwish.hilti
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

CAJ 2371

System No. C-AJ-2371


F Rating - 3 Hr
T Rating - 2 Hr and 3 Hr (See Item 3)

A A

3C

3B

3A SECTION A-A

1. Floor or Wall Assembly — Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) (1600-2400 kg/m3) concrete. Wall may also be
constructed of any UL Classified Concrete Blocks*. Max diameter of opening is 7 in. (178 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants — One nonmetallic pipe to be installed concentrically or eccentrically within the firestop system. Annular space between pipe
and periphery of opening to be as shown in the table below. The following types and sizes of nonmetallic pipes may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid or cellular core PVC for use in closed (process or
supply) or vented (drain, waste or vent) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 6 in. (152 mm) diam (or smaller) SDR13.5 CPVC for use in closed (process or supply)
piping systems.
C. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 solid or cellular core ABS for use in closed
(process or supply) or vented (drain, waste or vent) piping systems.
D. Flame Retardant Polypropylene (FRPP) Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed (process or
supply) or vented (drain, waste or vent) piping system.

Nom. Diam. of Min./Max. Annular Number of Steel


T Rating (Hr.)
Pipe,in.(mm) Space,in. (mm) Bands
1-1/2 (38) 0 - 1/4 (6) 1 2
2 (51) 0 - 1/4 (6) 1 2
3 (76) 0 - 1/2 (13) 1 2
4 (102) 0 - 1/2 (13) 1 2
6 (152) 0 - 3/8 (10) 2 3

S IFI
Reproduced by HILTI, Inc. Courtesy of AS
CL

ED

Underwriters Laboratories, Inc.


November 18, 2006
Page: 1 of 3
CAJ 2371
System No. C-AJ-2371
F Rating - 3 Hr
T Rating - 2 Hr and 3 Hr (See Item 3)
3. Firestop System — The firestop system shall consist of the following:
A. Fill, Void or Cavity Material* — Wrap Strip - Layers of intumescent wrap strip are continuously wrapped around the pipe with end held in
place with masking or aluminum tape. Wrap strip butted tightly against bottom surface of floor or both surfaces of wall. Size of wrap strip and
number of layers for a given size penetrant are shown in the table below.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP648-E W25/1" or CP48-E W45/1-3/4" Firestop Wrap Strip
Nom. Pipe Size in. Nom. Wrap Strip
Product Designation Number of Layers
(mm) Width in. (mm)
CP 648-E W25/1" 3 (76) 2 1 (25)
CP 648-E W45/1-3/4" 3 (76) 1 1-3/4 (44)
CP 648-E W25/1" 4 (102) 3 1 (25)
CP 648-E W45/1-3/4" 4 (102) 2 1-3/4 (44)
CP 648-E W45/1-3/4" 6 (152) 3 1-3/4 (44)

A1. Fill, Void or Cavity Material* — Wrap Strip — (As an alternate to the wrap strip in Item 3A) - One layer of intumescent wrap strip is
continuously wrapped around the pipe with ends butted and held in place with integrated tape. Wrap strip butted tightly against bottom
surface of floor or both wall surfaces. Size of wrap strip for a given size penetrant is shown in the table below.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP648-S-1.5" US, CP648-S-2" US, CP648-S-3" US, CP648-S-4" US
or CP648-S-6" US Wrap Strip

Nom. Wrap Strip Nom. Wrap Strip Nom. Wrap Strip


Product Designation Pipe Size in. (mm)
Length in. (mm) Thick in. (mm) Width in. (mm)
CP648-S-1.5" US 1-1/2 (38) 6.5 (165) 0.18 (0.4) 1 (25)
CP648-S-2" US 2 (51) 8 (203) 0.18 (0.4) 1 (25)
CP648-S-3" US 3 (76) 11.5 (292) 0.18 (0.4) 1-3/4 (44)
CP648-S-4" US 4 (102) 15.1 (383) 0.36 1-3/4 (44)
CP648-S-6" US 6 (152) 22.4 (620) 0.53 (1.4) 1-3/4 (44)

B. Steel Collar — Steel collar fabricated from coils of precut min 0.016 in. (1.6 mm) thick (No. 28 gauge) galv steel available from fill material
manufacturer. Collar shall be nom 1 in. (25 mm)(for 1 in.(25 mm) wide wrap strip) or 1-/34 in. (44 mm)( for 1-3/4 in. (44 mm) wide wrap
strip) deep with 1 in. (25 mm) wide by 2 in. (52 mm) long anchor tabs on 1-3/4 in. (44 mm) centers for securement to the underside of floor
or both surfaces of wall. The opposite side incorporates retainer tabs, 1/2 in. (13 mm) wide by 3/16 in. (4.8 mm) long, prebent toward the
pipe surface. Collar shall be tightly wrapped over the wrap strip, overlapping min. 1 in (25 mm) at seam. A nom 1/2 in. (13 mm) wide
stainless steel hose clamp shall be secured to the collar at its mid-height. Optional securement of the collar may be accomplished with two
sheet metal screws screwed though the overlapping portion of the collar. The length of the sheet metal screws shall not exceed the
thickness of the wrap strip. Every other anchor tab or with 3 equal angle tabs of collar secured to concrete slab at with 1/4 in. (6 mm) diam
by 1-3/4 in. (44 mm) long steel expansion type masonry fasteners, 1/4 in.(6 mm) diam by 1-1/2 in. (44 mm) long steel concrete screws or
0.145 in. (3.8mm)diam by 1-1/4 in. (32 mm) long powder actuated fasteners utilizing a 1-7/16 (37 mm) diam by 1/16 in. (1.6 mm) thick
steel washer. As alternates to the anchors specified above, Hilti 1/4 in. (6 mm) diam by 1-1/4 in.(32 mm) long KWIK-CON II+ concrete
screw anchor, Hilti 1/4 in.(6 mm) diam by 1-3/4 in. (44 mm) long KWIK-BOLT 3 steel expansion anchor or Hilti X-DNI 27 P8 S15 powder
actuated floor pin with integral nom 9/16 in. diam washer may be used. In floor assemblies, one collar to be used at the bottom of the
concrete floor only. In wall assemblies, a collar is used on both surfaces.
C. Fill, Void or Cavity Materials* (Optional) — Sealant -Min 1/4 in. (6 mm) thickness of fill material applied within the annulus, flush with
bottom surface of floor or both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant

S IFI
Reproduced by HILTI, Inc. Courtesy of AS
CL

ED

Underwriters Laboratories, Inc.


November 18, 2006
Page: 2 of 3