Component λ r (hours) Load No.

of Average Load Table 1: Basic System Data


(f/yr) point customers Connected(kW) DG
Section Village A 1000 5000
1 0.1 5
2 0.15 5 1 2 3 4 5
3 0.2 5 Village B 900 7000
4 0.25 5
5 0.15 5
Village C 700 4000
Distributor
a 0.2 2
b 0.6 2 Village D 500 2000
c 0.4 2 a b c d e
d 0.2 2
e 0.6 2 Village
A E 1200 B 6000 C D E

Figure: Radial Distribution System with Dispersed Generation


Reliability indices with DG (Enough Capacity and Full Time)

Table 2: Reliability indices with DG (capacity>24MW, can run independently)

Load point A Load point B Load point C Load point D Load point E
C λ r U λ r U λ r U λ r U λ r U
1 0.1 5 0.5 0.1 0.5 0.05 0.1 0.5 0.05 0.1 0.5 0.05 0.1 0.5 0.05
2 0.15 0.5 0.075 0.15 5 0.75 0.15 0.5 0.075 0.15 0.5 0.075 0.15 0.5 0.075
3 0.2 0.5 0.1 0.2 0.5 0.1 0.2 5 1 0.2 0.5 0.1 0.2 0.5 0.1
4 0.25 0.5 0.125 0.25 0.5 0.125 0.25 0.5 0.125 0.25 5 1.25 0.25 0.5 0.125
5 0.15 0.5 0.075 0.15 0.5 0.075 0.15 0.5 0.075 0.15 0.5 0.075 0.15 5 0.75

a 0.2 2 0.4
b 0.6 2 1.2
c 0.4 2 0.8
d 0.2 2 0.4
e 0.6 2 1.2
Total 1.05 1.21 1.275 1.45 1.59 2.3 1.25 1.7 2.125 1.05 1.86 1.95 1.45 1.59 2.3
Reliability indices with DG (full time, but partial capacity)

Table 3: Reliability indices with DG (capacity 12MW<24MW, can run full time)

Load point A Load point B Load point C Load point D Load point E
C λ r U λ r U λ r U λ r U λ r U
1 0.1 5 0.5 0.1 5 0.5 0.1 0.5 0.05 0.1 0.5 0.05 0.1 0.5 0.05
2 0.15 0.5 0.075 0.15 5 0.75 0.15 0.5 0.075 0.15 0.5 0.075 0.15 0.5 0.075
3 0.2 0.5 0.1 0.2 0.5 0.1 0.2 5 1 0.2 0.5 0.1 0.2 0.5 0.1
4 0.25 0.5 0.125 0.25 0.5 0.125 0.25 0.5 0.125 0.25 5 1.25 0.25 0.5 0.125
5 0.15 0.5 0.075 0.15 0.5 0.075 0.15 0.5 0.075 0.15 0.5 0.075 0.15 5 0.75

a 0.2 2 0.4
b 0.6 2 1.2
c 0.4 2 0.8
d 0.2 2 0.4
e 0.6 2 1.2
Total 1.05 1.21 1.275 1.45 1.9 2.75 1.25 1.7 2.125 1.05 1.86 1.95 1.45 1.59 2.3
Reliability indices with DG (full time, but partial capacity)

Table 3: Reliability indices with DG (capacity 12MW<24MW, can run full time)

Load point A Load point B Load point C Load point D Load point E
C λ r U λ r U λ r U λ r U λ r U
1 0.1 5 0.5 0.1 5 0.5 0.1 0.5 0.05 0.1 0.5 0.05 0.1 0.5 0.05
2 0.15 0.5 0.075 0.15 5 0.75 0.15 0.5 0.075 0.15 0.5 0.075 0.15 0.5 0.075
3 0.2 0.5 0.1 0.2 0.5 0.1 0.2 5 1 0.2 0.5 0.1 0.2 0.5 0.1
4 0.25 0.5 0.125 0.25 0.5 0.125 0.25 0.5 0.125 0.25 5 1.25 0.25 0.5 0.125
5 0.15 0.5 0.075 0.15 0.5 0.075 0.15 0.5 0.075 0.15 0.5 0.075 0.15 5 0.75

a 0.2 2 0.4
b 0.6 2 1.2
c 0.4 2 0.8
d 0.2 2 0.4
e 0.6 2 1.2
Total 1.05 1.21 1.275 1.45 1.9 2.75 1.25 1.7 2.125 1.05 1.86 1.95 1.45 1.59 2.3
Reliability indices with DG (Partial capacity and part of Time)

For Load C,

>>> (2.125*0.4) + (3.25*0.6) = 0.85+1.95 = 2.8

For Load D,

>>> (1.95*0.4) + (3.975*0.6) = 0.78+2.385 = 3.165

For Load E,

>>> (2.3*0.4) + (5.45*0.6) = 0.92+3.27 = 4.19

Table 4: Reliability indices with DG (capacity 12MW<24MW, can run 40% of Time)

Failur Load point A Load point B Load point C Load point D Load point E
e λ r U λ r U λ r U λ r U λ r U
Avail. 1.05 1.21 1.275 1.45 1.9 2.75 1.25 1.7 2.125 1.05 1.86 1.95 1.45 1.59 2.3
Unav. 1.05 1.21 1.275 1.45 1.9 2.75 1.25 2.6 3.25 1.05 3.79 3.975 1.45 3.76 5.45
Total 1.05 1.21 1.275 1.45 1.9 2.75 1.25 2.24 2.8 1.05 3.01 3.165 1.45 2.89 4.19