NG7 en (New)

The document describes a 24kV gas insulated switchgear system. It provides details on the system's technical specifications, including voltage and current ratings, insulation levels, mechanical life, protection degrees, and SF6 gas pressure parameters. It also describes the system's structure, including interior components like the busbar insulator, load switch, and earthing switch.

Uploaded by

Alaim Alves
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views

NG7 en (New)

The document describes a 24kV gas insulated switchgear system. It provides details on the system's technical specifications, including voltage and current ratings, insulation levels, mechanical life, protection degrees, and SF6 gas pressure parameters. It also describes the system's structure, including interior components like the busbar insulator, load switch, and earthing switch.

Uploaded by

Alaim Alves
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

T&D

Power Transmission & Distribution

NG7 Cubicle Gas Insulated Switchgear (C-GIS)

en.chintelectric.com
C-GIS

NG7 Cubicle Gas Insulated Switchgear(C-GIS)


1. General
1.1 Ratings: system voltage 24kV, the rated current up to 630A, AC50Hz.
1.2 Application: applicable for power receiving and distribution and for control, protection and
measurement of circuit.
1.3 Standard:
● IEC 62271-200: 2003

● IEC 62271-100: 2001

● IEC 62271-102: 2002

● IEC 60694: 1996

2. Type Designation
N G 7 - □ (□) / T □-□

Rated short time withstand current (kA)


Rated current (A)
Spring operating mechanism
Model type
Rated voltage (12/24kV)
Design code
Cubicle Gas Insulated Switchgear
Corporate code

3. Working Condition
CCF
3.1 Ambient temperature: -40℃~+45℃(average temperature ≤35℃)
3.2 Altitude: ≤3000m
3.3 Humidity: Daily average ≤95%, daily average water vapor pressure ≤2.2KPa
Monthly average ≤90%, monthly average water vapor pressure ≤1.8KPa
3.4 The electromagnetic interference value in the second system will not exceed 1.6kV.
※ Note: Customized products are available.

P1.
C-GIS

4. Main Technical Parameter


Item Unit LBS unit FSC unit VCB unit
Rated voltage kV 12/24
Rated frequency Hz 50/60
Rated current of main bus bar A 630, 1250
Rated current A 630 125 630, 1250
1min power frequency Phase to earth, Between phases kV 42/65
Rated withstand voltage Between open contacts kV 48/79
insulation Lightning impulse Phase to earth, Between phases kV 75/125
level withstand voltage Between open contacts kV 85/145
1min Power frequency voltage of Secondary /control loop kV 2
Rated short circuit breaking current kA/Times 31.5 20/30
Rated transfer current A 1750/1400
Rated short-time Main loop 3s kA 20 20/31.5
withstand Earthing switch 2s kA 20 20/25
current Earthing connecting loop 2s kA 17.4 17.4/21.7
Rated withstand Main loop, load switch kA 50 50/63
current(peak) Earthing switch kA 43.5 43.5/54.5
Rated short-circuit closing current(peak) kA 50 80 50/63
Load switch rated active load breaking current A 630
Rated load switch loop breaking current A 630
5% rated active load switch load breaking current A 31.5
Load switch rated cable charging breaking current A 10/25
Load switch rated active load breaking frequency Times 100/200
Cable and circuit charging breaking frequency when earth fault A/Times 20/10 (12kV),31.5/10(24kV)
Earth fault current breaking A/Times 5/10(12kV),10/10(24kV)
Rated single back to back capacitor unit breaking current A 400
Rated capacitor unit closing inrush current kA 20(50Hz)
Rated SF6 Design and rated charged level Mpa 0.04
gas pressure Lowest function level Mpa 0.02
(20℃) Release of pressure Mpa 0.14
Mechanical Load switch/ Earthing switch Times 5000/2000 5000/2000
life Circuit breaker/Disconnect Times 10000/20000
Protect Enclose case IP67
degree Shell of switchgear IP4X
SF6 gas leakage rate ≤1‰

P2.
C-GIS

5. Technical Specification
Manual operation (Local) and
electric operation (Remote)
are both available.

Note:
Modular design and flexible expansion
Silicone rubber coupling Sealed system without
is used in the installation
to simplify the site work. environmental impact
Compact structure
High safety
Environment protection

6. Structure
6.1 The Interior Structure of Sealing Cubicle

Busbar insulator
It can be flexibly expanded by
using bus connector

Load switch
It is used in opening, closing
and earthing phenomenon.

Fuse
In order to secure the wire while the
current passing, the switch-fuse will
be turned off via interlocking process
to trip closing.

Earthing switch
It is used for double connection
and to ensure security.

The interior structure of sealing cubicle

P3.
C-GIS

6.2 Front of Sealing Cabinet

Installation point of
pressure meter Spring operating mechanism
Installation point of Major operating shaft is divided into earthing
pressure meter shaft and Closing shaft.

Fuse component
Three fuse vessels arranged in oppose-triangle
position, and connect tripping half shaft by
Fuse component blurted link.

Gas filling point of switchgear


SF6 gas is filled in switchgear via self-seal valve.

Outgoing feeder insulator


Connected power grid circuit via cable.

Front of sealing cabinet

6.3 Load switch/Earthing switch

Stationary contact Stationary contact Stationary contact

Moving contact
Moving contact
Earthing switch Earthing switch Earthing switch
Moving contact

Closing situation Opening situation Earthing situation

6.4 Spare Parts

Pressure indicator Operating grip

P4.
C-GIS

7. Connection Mode
7.1 Between switchgears
There are some connection modes to enhance the sensitivity of design schemes as below:
● Extensible mode
● Inextensible mode
● Standard bushing mode
7.2 With the cables

Connection example

C C M CPT F F V

Busbar connector Cable connection

8. Protection Function
With the cables
Transformer protection
Fuse protection in F units:
In the Load switch-fuse combination units, if the fuse blow out, the load switch will trip-free and cut
off the connection to transformer.
In the form below, it shows the choice of the over current to the corresponding capability of the
transformer in F unit.
Relay protection devices can be used in over current and earthing fault.

Transformer Fuse Rated Fuse Rated Transformer Fuse Rated Fuse Rated
Capacity current A current A Capacity current A current A
(kVA) (10kV) (24kV) (kVA) (10kV) (24kV)
50 10 6.3 315 31.5 16
75 10 6.3 400 40 20
100 16 10 500 50 25
128 16 10 630 63 31.5
160 16 10 800 80 40
200 20 10 1000 100 50
250 25 16 1250 125 63

P5.
C-GIS

9. Single Functional Unit Schemes


Scheme Type Function Standard Configuration Choice
Using three point load switch , □ Three position load switch □ Load switch electrical mechanism □ Key lock
connect and break the □ Electrical indicator □ Open and close button(electrical) □ Load switch auxiliary contacts
C connection of lay in and lay □ Manometer of SF6 □ Short current and earthing fault indicator □ Earthing switch auxiliary contacts
unit out cables and the bus bar, □ Load switch spring operating mechanism □ Surge Arrester or double cables
can make 3 phases of the □ Interlock □ Secondary cabinet
LBS
cable earthing at the same time,
□ 630A busbar, earthing busbar □ Lengthen or having bussing is non-must
and have the ability to control
□ Operating handle □ Terminal enclose terminal(for the terminal box)
the lay in and lay outl.
□ CT or VT
W×D×H/h (Cables installation height) 350×840×1450(1800)/500(850)
□ Three position load switch □ Load switch electrical machanism □ Load switch auxiliary contacts
Having a same load switch
□ Electrical indicator □ Open and close button(electrical) □ Earthing switch auxiliary contacts
with the lay in and lay out
□ Manometer of SF6 □ Short curient and earthing failure indicator □ Fall off windings
F panel , and combine with the
□ Load switch spring actuating mechanism □ Surge Arrester or two way cables □ Relays Protection
fuse breaker to a unit, can be
unit □ Fail safe interlock □ Secondary chamber
installed with over current
FSC □ 630Abusbar,earthing busbar □ Lengthen or having bussing is non-must
protect device. Applying for
the control and protection □ Operating handle □ Terminal enclose terminal(for the terminal box)
of the transformer. □ Cut out indicate of fuse breaker □ CT or PT
□ Fuse breaker connected with earthing switch □ Key lock
W×D×H/h (Cables installation height) 350×840×1450(1800)/500(850)
Having a VCB which □ VCB □ Circuit breaker button □ Disconnector on-off & Earthing
installed in series with a □ Triple position disconnector, earthing switch □ Short curient and earthing failure indicator switch auxiliary contacts
3 point disconnector , □ Manometer of SF6 □ Surge Arrester or two way cables □ Relays Protection
V1 the circuit breaker is □ Circuit breaker, disconnector, mechanical □ Secondary chamber
unit beside the busbar while interlock and location indicator □ Lengthen or having bussing is non-must
VCB the disconnector is beside □ Electrify indicator □ Terminal enclose (for the terminal box)
the lay in and lay out □ 630A bus bar, Earthing bus. □ Current transformer
cables, and can install □ Disconnector operating handle □ Key lock
relay protection device.
□ VCB charging handle □ Circuit condition contactor
W×D×H/h (Cables installation height) 420×840×1450(1800)/500(850)
□ VCB □ Circuit breaker breaking button □ Disconnector on-off & Earthing
Having a VCB in-line with □ Triple position disconnector, earthing switch □ Short circuit & earthing fault indicator switch auxiliary contacts
a triple way disconnector, □ Manometer of SF6 □ Surge Arrester or two way cables □ Relay protection
V2 VCB is beside the in & out □ Circuit breaker, disconnector, mechanical □ Secondary chamber
unit cables, the disconnector interlock and location indicator □ Lengthen or having bussing is non-must
VCB is beside the bus where □ Electrify indicator □ Terminal enclose
the relay protection can □ 630A bus bar, Earthing bus □ Current transformer
be installed. □ Disconnector handle □ Key lock
□ VCB charging handle □ Circuit breaker condition contant
W×D×H/h (Cables installation height) 420×840×1450(1800)/500(850)
□ 630A bus □ Surge Arrester or two way cables
D □ Electrify indicator □ Secondary chamber
Inlet cables connected
unit □ Lengthen or having bussing is non-must
directly to the bus, with
□ Terminal enclose
Cable non-corrosive steel
incoming protect shell. Applied in
without connection of lay in and
out cables.
switch

W×D×H/h (Cables installation height) 350×840×1450(1800)/500(850)

P6.
C-GIS

Scheme Type Function Standard Configuration Choice


□ Double positions earthing switch □ Electric mechanism of earthing switch
□ Manometer of SF6 □ Breaking and closing button
De □ Spring operation machaim of earthing switch □ Secondary chamber
Earthing lay in and out □ 630A bus □ Key lock
unit
cables connected to □ Operate handle □ Earthing switch auxiliary contacts
Cables
bus directly.
earthing

W×D×H 350×840×1450(1800)
Current transformer and □ Current transformer □ Voltage meter, current meter
voltage transformer are □ Voltage transformer □ Active energy meter, reactive energy meter
M installed to make it easy □ PT fuse box □ Surge arrestor
unit for the electrical department
Measuring to examine. Can be
combined with any other
panel for measuring.
(Gas insulation)
W×D×H 480×890×1450(1800) (12kV) 700×1100×1800 (24kV)
□ Double position load switch □ Load switch electrical mechanism
□ Manometer of SF6 □ Break and open button
With a double position
□ Load switch with spring mechanism □ Secondary chamber
I loading switch it can
□ 630A bus □ Key lock
unit connect or break main
□ Operation handle □ Load switch auxiliary contants
Bus bus on-load. Normally
section using in contact with
bus.

W×D×H 420×840×1450(1800)
□ 630A bus □ Load switch electrical mechanism
Having a triple position
□ Load switch □ Breaking and closing button
CPT load switch to close or
□ Load switch with spring mechanism □ Secondary chamber
unit open the voltage
□ Manometer of SF6 □ Lengthen or having bussing is non-must
with transformer and earthing.
□ Voltage transformer □ Terminal enclose
switch Apply for detection of
□ Exposure cables □ Load switch auxiliary contants
and the system voltage and
□ Operation handle □ Key lock
transformer provide the control
□ Surge Arrester
voltage.

W×D×H 500×890×1450(1800) (12kV) 700×1100×1800 (24kV)


□ 630A bus □ Secondary chamber
□ Voltage transformer □ Lengthen or having bussing is non-must
With a voltage transformer
APT □ Expose cables □ Terminal enclose
and connected directly to
unit □ Surge arrestor
bus. Apply for monitor
without
system voltage and
switch
provide operate power.
transformer
(gas insulation)

W×D×H 500×890×1450(1800) (12kV) 700×1100×1800 (24kV)

P7.
C-GIS

10. Multi-Functional Unit Schemes


Scheme Type Function, Standard configuration, Optional configuration, Accessories

Functional units, Standard configuration.


DF Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 700×840×1450(1800)/500(850)

Functional units, Standard configuration.

DV Optional configuration and accessories


are as same as relative single frame.

W×D×H/h (the installation height of cable) 770×840×1450(1800)/500(850)

Functional units, Standard configuration.


CC Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 700×840×1450(1800)/500(850)

Functional units, Standard configuration.


CCC Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 1050×840×1450(1800)/500(850)

Functional units, Standard configuration.


CF Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 700×840×1450(1800)/500(850)

P8.
C-GIS

Scheme Type Function, Standard configuration, Optional configuration, Accessories

Functional units, Standard configuration.


CCF Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 1050×840×1450(1800)/500(850)

Functional units, Standard configuration.


CFF Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 1050×840×1450(1800)/500(850)

Functional units, Standard configuration.


CCFF Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 1400×840×1450(1800)/500(850)

Functional units, Standard configuration.


CCFFF Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 1750×840×1450(1800)/500(850)

Functional units, Standard configuration.


CCV Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 1120×840×1450(1800)/500(850)

P9.
C-GIS

Scheme Type Function, Standard configuration, Optional configuration, Accessories

Functional units, Standard configuration.


CCVV Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 1540×840×1450(1800)/500(850)

Functional units, Standard configuration.


CCVVV Optional configuration and accessories
are as same as relative single frame.

W×D×H/h (the installation height of cable) 1960×840×1450(1800)/500(850)

11. Single Line Diagram


01 02 03 04 05 06 07

Single
Line
Diagram

Type C C C C C D De
Left: Y Left: Y Left: Y Left: Y
Same as Same as Same as
Expansion mode
Right: Y Right: Bushing Right: Bushing Right: Y
01~04 01~04 01~04
Dimension 350×1450×840 350×1450×840 350×1450×840 350×1450×840 350×1450×840 350×1450×840 350×1450×840
(W×H×D) 350×1800×840 350×1800×840 350×1800×840 350×1800×840 350×1800×840 350×1800×840 350×1800×840
Load switch 1 1 1 1 1
CT Optional Optional Optional Optional Optional Optional
PT
HV fuse cutout
VPIS Contains Contains Contains Contains Contains Contains Contains
Surge arrester Contains Optional Contains
Remark Air insulation

P10.
C-GIS

08 09 10 11 12 13 14

M P P

P
Single
Line
Diagram

Type F F F I V1 V2 APT
Expansion mode Same as 01~04 Same as 01~04 Same as 01~04 Left: Y Right: Y Same as 01~04 Same as 01~04 Same as 01~04
Dimension 350×1450×840 350×1450×840 350×1450×840 420×1450×840 420×1450×840 420×1450×840 500×1450×890(12kV)
(W×H×D) 350×1800×840 350×1800×840 350×1800×840 420×1750×840 420×1800×840 420×1800×840 700×1800×1100(24kV)
Load switch 1 1 1 2nd station load switch 1 3rd station load switch 1 3rd station load switch 1
CT 3 included in protection relay 3 included in protection relay 3
PT 2
HV fuse cutout 3 3 3 XRNP1 3
VPIS Contains Contains Contains Contains Contains Contains
Surge arrestor Optional Optional Optional Optional Optional Contains
Remark Relay protection Relay protection Relay protection Air insulation

15 16 17 18
A A A
V

Single
Line
Diagram

Type CPT CPT M CCF


Expansion mode Same as 01~04 Same as 01~04 Left: Y Right: Y Same as 01~04
500×1450×890 500×1450×890 500×1450×890 1050×1450×840
Dimension
500×1800×890(12kV) 500×1800×890(12kV) 700×1800×1100 1050×1800×840
(W×H×D)
700×1800×1100(24kV) 700×1800×1100(24kV)
Load switch 1 1 3
CT 2 Optional
PT 2 2 2
HV fuse cutout XRNP1 3 XRNP1 3 XRNP1 3 3
VPIS Contains Contains Contains Contains
Surge arrestor Contains Optional Optional
Remark Air insulation

P11.
C-GIS

12. Foundation Drawing of Installation


12.1 The demission diagram of the basic installation is just like the following picture.
12.2 In order to guarantee the quality of the installation of basic components, the horizontal ratio of frame
installation should meet the standard that the tolerance per meter square is less than 3mm.

840

1043
57

1450
500

8# channel steel
Depth 800~1000

Dimension drawing of basic installation

P12.
C-GIS

Unit Module

A
C

14
φ
4-

276
B
464
9
φ

17
Front

Voltag Type C F V1 I CPT


e level
(kV) 12/24 12/24 12/24 12/24 12 24
Dimension
350 ● ●
420 ● ●
A
500 ●
700 ●
840 ● ● ● ●
B 890 ●
1100 ●
294 ● ●
364 ● ●
C
444 ●
644 ●

P13.
C-GIS

A
C

14
φ
4-

276
B
464
9
φ
2-
17
Front

Voltag Type D M De APT


e level
(kV) 12/24 12 24 12/24 12 24
Dimension
350 ●
420 ●
A 480 ●
500 ●
700 ● ●
840 ●
B 890 ● ● ●
1100 ● ●
294 ●
364 ●
C 424 ●
444 ●
644 ● ●

P14.
C-GIS

Common Box Module


700
294 56 294

14
φ
8-

276
783
464
9
φ
2-

17
Front

1050
294 56 294 56 294
14

12

276
783
464
9
φ
3-

17

Front

1400
294 56 294 56 294 56 294
14

16

276
783
464

9
φ
4-
17

Front

P15.
C-GIS

1750
294 56 294 56 294 56 294 56 294

14

20

276
783
464
9
φ
5-

17
Front

13. Ordering Information


13.1 The technical specification and scheme should be confirmed by two parties before the signature
of contract.
13.2 The single line diagram, include the type、specification and quantity of the components in
switchgear; Appoint the relay protection mode.
13.3 The schematic diagram,include rated operating current, signal and protection circuit and the
type of electrical components.
13.4 The arrangement drawing or layout of switchgear.
13.5 The list of spare parts.
13.6 The colour of the panel.
13.7 The characteristics of operation device, including operating voltage.
13.8 Foundation drawing supplied by manufacturer.
13.9 Common tools and materials for installation and examination and repair should be prepared
by customers.
13.10 The specification and type of cable and cable terminal should be supplied and purchased
by customers.
13.11 Any special requirements,please contact us.

P16.
T&D

International Business:
Attributed to our reliable quality and perfect after-sales service, CHINT T&D has been relied on and entrusted with by many of our clients around the world.
We will continue to supply best products and try hard to win more compliments through our best service.

For inquiries, further interests for products cooperation, partnership, international alliance,investment discussion with us, please contact the following representatives.

Area Representative Tel E-mail

Selina Peng (+86) 21 6777 7777 ext. 80917 [email protected]

Asia-pacific Lucy Zou (+86) 21 6777 7777 ext. 80906 [email protected]

David Liu (+86) 21 6777 7777 ext. 80963 [email protected]

Latin America Bill Han (+86) 21 6777 7777 ext. 80911 [email protected]

North America Xufeng Jiang (+86) 21 6777 7777 ext. 80990 [email protected]

Xing Peng (+86) 21 6777 7777 ext. 80910 [email protected]


Middle East
Carrie Yang (+86) 21 6777 7777 ext. 80950 [email protected]

Europe Jinhwa Yang (+86) 21 6777 7777 ext. 80981 [email protected]

Елена (+86) 21 6777 7777 ext. 80930 [email protected]


Russian-speaking
Countries Russia: 007-919-763 6527
ОлегДун [email protected]
China: (+86) 21 6777 7777 ext. 80903

Africa York Zhi (+86) 21 6777 7777 ext. 80925 [email protected]

Logan Liu (+86) 21 6777 7777 ext. 80918 [email protected]


Industrial End User Division
Tina Wu (+86) 21 6777 7777 ext. 80937 [email protected]

MV/HV Apparatus & Automation Division Emma Zhang (+86) 21 6777 7777 ext. 80926 [email protected]

General Manager Yin Zhang [email protected]

Address:
International Business Department 2011-014EN1011
855 Wenhe Road, Songjiang District
Shanghai 201614, China The contents and data in this catalogue are for reference only. The real order
Tel: (+86) 21 6777 7777 ext. 80952 requirements and technical agreements shall prevail. The catalogue is subject
to change without further notice. The latest edition is recommended.
Fax: (+86) 21 6777 7999 CHINT reserves the right of interpretation.