C-GIS
2. Type Designation
N G 7 - □ (□) / T □-□
3. Working Condition
CCF
3.1 Ambient temperature: -40℃~+45℃(average temperature ≤35℃)
3.2 Altitude: ≤3000m
3.3 Humidity: Daily average ≤95%, daily average water vapor pressure ≤2.2KPa
Monthly average ≤90%, monthly average water vapor pressure ≤1.8KPa
3.4 The electromagnetic interference value in the second system will not exceed 1.6kV.
※ Note: Customized products are available.
P1.
C-GIS
P2.
C-GIS
5. Technical Specification
Manual operation (Local) and
electric operation (Remote)
are both available.
Note:
Modular design and flexible expansion
Silicone rubber coupling Sealed system without
is used in the installation
to simplify the site work. environmental impact
Compact structure
High safety
Environment protection
6. Structure
6.1 The Interior Structure of Sealing Cubicle
Busbar insulator
It can be flexibly expanded by
using bus connector
Load switch
It is used in opening, closing
and earthing phenomenon.
Fuse
In order to secure the wire while the
current passing, the switch-fuse will
be turned off via interlocking process
to trip closing.
Earthing switch
It is used for double connection
and to ensure security.
P3.
C-GIS
Installation point of
pressure meter Spring operating mechanism
Installation point of Major operating shaft is divided into earthing
pressure meter shaft and Closing shaft.
Fuse component
Three fuse vessels arranged in oppose-triangle
position, and connect tripping half shaft by
Fuse component blurted link.
Moving contact
Moving contact
Earthing switch Earthing switch Earthing switch
Moving contact
P4.
C-GIS
7. Connection Mode
7.1 Between switchgears
There are some connection modes to enhance the sensitivity of design schemes as below:
● Extensible mode
● Inextensible mode
● Standard bushing mode
7.2 With the cables
Connection example
C C M CPT F F V
8. Protection Function
With the cables
Transformer protection
Fuse protection in F units:
In the Load switch-fuse combination units, if the fuse blow out, the load switch will trip-free and cut
off the connection to transformer.
In the form below, it shows the choice of the over current to the corresponding capability of the
transformer in F unit.
Relay protection devices can be used in over current and earthing fault.
Transformer Fuse Rated Fuse Rated Transformer Fuse Rated Fuse Rated
Capacity current A current A Capacity current A current A
(kVA) (10kV) (24kV) (kVA) (10kV) (24kV)
50 10 6.3 315 31.5 16
75 10 6.3 400 40 20
100 16 10 500 50 25
128 16 10 630 63 31.5
160 16 10 800 80 40
200 20 10 1000 100 50
250 25 16 1250 125 63
P5.
C-GIS
P6.
C-GIS
W×D×H 350×840×1450(1800)
Current transformer and □ Current transformer □ Voltage meter, current meter
voltage transformer are □ Voltage transformer □ Active energy meter, reactive energy meter
M installed to make it easy □ PT fuse box □ Surge arrestor
unit for the electrical department
Measuring to examine. Can be
combined with any other
panel for measuring.
(Gas insulation)
W×D×H 480×890×1450(1800) (12kV) 700×1100×1800 (24kV)
□ Double position load switch □ Load switch electrical mechanism
□ Manometer of SF6 □ Break and open button
With a double position
□ Load switch with spring mechanism □ Secondary chamber
I loading switch it can
□ 630A bus □ Key lock
unit connect or break main
□ Operation handle □ Load switch auxiliary contants
Bus bus on-load. Normally
section using in contact with
bus.
W×D×H 420×840×1450(1800)
□ 630A bus □ Load switch electrical mechanism
Having a triple position
□ Load switch □ Breaking and closing button
CPT load switch to close or
□ Load switch with spring mechanism □ Secondary chamber
unit open the voltage
□ Manometer of SF6 □ Lengthen or having bussing is non-must
with transformer and earthing.
□ Voltage transformer □ Terminal enclose
switch Apply for detection of
□ Exposure cables □ Load switch auxiliary contants
and the system voltage and
□ Operation handle □ Key lock
transformer provide the control
□ Surge Arrester
voltage.
P7.
C-GIS
P8.
C-GIS
P9.
C-GIS
Single
Line
Diagram
Type C C C C C D De
Left: Y Left: Y Left: Y Left: Y
Same as Same as Same as
Expansion mode
Right: Y Right: Bushing Right: Bushing Right: Y
01~04 01~04 01~04
Dimension 350×1450×840 350×1450×840 350×1450×840 350×1450×840 350×1450×840 350×1450×840 350×1450×840
(W×H×D) 350×1800×840 350×1800×840 350×1800×840 350×1800×840 350×1800×840 350×1800×840 350×1800×840
Load switch 1 1 1 1 1
CT Optional Optional Optional Optional Optional Optional
PT
HV fuse cutout
VPIS Contains Contains Contains Contains Contains Contains Contains
Surge arrester Contains Optional Contains
Remark Air insulation
P10.
C-GIS
08 09 10 11 12 13 14
M P P
P
Single
Line
Diagram
Type F F F I V1 V2 APT
Expansion mode Same as 01~04 Same as 01~04 Same as 01~04 Left: Y Right: Y Same as 01~04 Same as 01~04 Same as 01~04
Dimension 350×1450×840 350×1450×840 350×1450×840 420×1450×840 420×1450×840 420×1450×840 500×1450×890(12kV)
(W×H×D) 350×1800×840 350×1800×840 350×1800×840 420×1750×840 420×1800×840 420×1800×840 700×1800×1100(24kV)
Load switch 1 1 1 2nd station load switch 1 3rd station load switch 1 3rd station load switch 1
CT 3 included in protection relay 3 included in protection relay 3
PT 2
HV fuse cutout 3 3 3 XRNP1 3
VPIS Contains Contains Contains Contains Contains Contains
Surge arrestor Optional Optional Optional Optional Optional Contains
Remark Relay protection Relay protection Relay protection Air insulation
15 16 17 18
A A A
V
Single
Line
Diagram
P11.
C-GIS
840
1043
57
1450
500
8# channel steel
Depth 800~1000
P12.
C-GIS
Unit Module
A
C
14
φ
4-
276
B
464
9
φ
17
Front
P13.
C-GIS
A
C
14
φ
4-
276
B
464
9
φ
2-
17
Front
P14.
C-GIS
14
φ
8-
276
783
464
9
φ
2-
17
Front
1050
294 56 294 56 294
14
-φ
12
276
783
464
9
φ
3-
17
Front
1400
294 56 294 56 294 56 294
14
-φ
16
276
783
464
9
φ
4-
17
Front
P15.
C-GIS
1750
294 56 294 56 294 56 294 56 294
14
-φ
20
276
783
464
9
φ
5-
17
Front
P16.
T&D
International Business:
Attributed to our reliable quality and perfect after-sales service, CHINT T&D has been relied on and entrusted with by many of our clients around the world.
We will continue to supply best products and try hard to win more compliments through our best service.
For inquiries, further interests for products cooperation, partnership, international alliance,investment discussion with us, please contact the following representatives.
Latin America Bill Han (+86) 21 6777 7777 ext. 80911 [email protected]
North America Xufeng Jiang (+86) 21 6777 7777 ext. 80990 [email protected]
MV/HV Apparatus & Automation Division Emma Zhang (+86) 21 6777 7777 ext. 80926 [email protected]
Address:
International Business Department 2011-014EN1011
855 Wenhe Road, Songjiang District
Shanghai 201614, China The contents and data in this catalogue are for reference only. The real order
Tel: (+86) 21 6777 7777 ext. 80952 requirements and technical agreements shall prevail. The catalogue is subject
to change without further notice. The latest edition is recommended.
Fax: (+86) 21 6777 7999 CHINT reserves the right of interpretation.
Http://en.chintelectric.com