Project Report

The document contains a detailed lighting design project including a table of contents listing sections on contacts, descriptions, luminaire information, lighting plans and calculations for multiple rooms and light scenes.

Uploaded by

Anuj Kumar
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 57

Date 27-03-2024

Project

Created with DIALux


Project

Preface

Notes on planning:

The energy consumption quantities do not take into account light


scenes and their dimming levels.
Project

Table of Contents

Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Images . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 .............................

Product data sheets


EAE - BLM 016A 40OD00 1K8 303020 (1x LED) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 ..............................
Rayon Lighting - CONTINUO-38w-4000k (1x CONTINUO-38w-4000k) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
12
Rayon Lighting - RAY- SD-DL REC- 160- IP44-20W (1x RAY- SD-DL REC- 160- IP44- . . . . . . . . . . . . . . . . . . . . .............................
13
20W)

Site 1

Building 1
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
.............................

Site 1 - Building 1

Storey 1
Room list / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 .............................

Site 1 - Building 1 - Storey 1

Room 1
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 .............................
Working plane (Room 1) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . 29
.............................
Calculation surface 5 / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 .............................

Site 1 - Building 1 - Storey 1

Room 2
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
.............................
Project

Table of Contents

Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 .............................


Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
37 .............................
Working plane (Room 2) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . 39. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Calculation surface 7 / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40.............................

Site 1 - Building 1 - Storey 1

Room 3
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
43
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46 .............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47 .............................
Surface result object 1 (Floor/ceiling) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . .
49 ............................
(adaptive)
Surface result object 1 (Floor/ceiling) / Light scene 1 / Luminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 .............................
Calculation surface 4 / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51.............................

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
.............................
Project

Contacts

EE Engg
Anuj Kumar

AnujPC Punk

T 9540329210

5
Project

Description

EE Engg
Anuj Kumar

AnujPC Punk

T 9540329210

6
Project

Images

Project

Project

Project

7
Project

Images

Project

Project

Project

8
Project

Images

Project

Project

Project

9
Project

Luminaire list

Φtotal Ptotal Luminous efficacy


95180 lm 821.0 W 115.9 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

30 EAE 3209276 BLM 016A 40OD00 1K8 303020 15.9 W 1831 lm 115.1 lm/W

4 Rayon CONTINU CONTINUO-38w-4000k 38.0 W 4100 lm 107.9 lm/W


Lighting O-38W-
4000K

10 Rayon RAY- SD- RAY- SD-DL REC- 160- IP44-20W 19.2 W 2385 lm 124.4 lm/W
Lighting DL REC-
160- IP44-
20W

10
Project

Product data sheet

EAE - BLM 016A 40OD00 1K8 303020

Article No. 3209276

P 15.9 W

ΦLamp 1831 lm

ΦLuminaire 1831 lm

η 100.01 %

Luminous efficacy 115.1 lm/W Polar LDC

CCT 3854 K

CRI 80

BLOOM, with its minimally adorned design, housing displaying a


clean-cut finish, glare-free homogenous light dispersion via its opal
diffuser is ideal for the illumination of offices, hospitals, schools and
retail spaces.

11
Project

Product data sheet

Rayon Lighting - CONTINUO-38w-4000k

Article No. CONTINUO-38W-


4000K

P 38.0 W

ΦLamp 4100 lm

ΦLuminaire 4100 lm

η 100.00 %
Polar LDC
Luminous efficacy 107.9 lm/W

CCT 4000 K

CRI 80

CONTINUO represents the modern generation in linear lighting.


It combines two elements: Structure and Core.
The quick & easy connection design, allowing the designer to create
many shapes such as continous linear or rectangles and so on..

12
Project

Product data sheet

Rayon Lighting - RAY- SD-DL REC- 160- IP44-20W

Article No. RAY- SD-DL REC- 160-


IP44-20W

P 19.2 W

ΦLuminaire 2385 lm

Luminous efficacy 124.4 lm/W

CCT 3000 K
Polar LDC
CRI 80

LED Recessed Downlight for indoor use. High performance effective,


designed to meet the most varied demands of lighting in an
important
variety of atmospheres.

13
Project

Building 1
Luminaire list

Φtotal Ptotal Luminous efficacy


95180 lm 821.0 W 115.9 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

30 EAE 3209276 BLM 016A 40OD00 1K8 303020 15.9 W 1831 lm 115.1 lm/W

4 Rayon CONTINU CONTINUO-38w-4000k 38.0 W 4100 lm 107.9 lm/W


Lighting O-38W-
4000K

10 Rayon RAY- SD- RAY- SD-DL REC- 160- IP44-20W 19.2 W 2385 lm 124.4 lm/W
Lighting DL REC-
160- IP44-
20W

14
Project

Building 1 · Storey 1 (Light scene 1)


Room list

15
Project

Building 1 · Storey 1 (Light scene 1)


Room list

Room 1

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


238.5 W 34.17 m² 6.98 W/m² = 1.34 W/m²/100 lx (Room) 523 lx
7.63 W/m² = 1.46 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

15 EAE 3209276 BLM 016A 40OD00 1K8 303020 15.9 W 1831 lm

Room 2

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


238.5 W 33.82 m² 7.05 W/m² = 1.33 W/m²/100 lx (Room) 529 lx
7.76 W/m² = 1.46 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

15 EAE 3209276 BLM 016A 40OD00 1K8 303020 15.9 W 1831 lm

Room 3

Ptotal ARoom Lighting power density


344.0 W 36.85 m² 9.34 W/m² (Room)

pcs. Manufacturer Article No. Article name P ΦLuminaire

4 Rayon CONTINU CONTINUO-38w-4000k 38.0 W 4100 lm


Lighting O-38W-
4000K

10 Rayon RAY- SD- RAY- SD-DL REC- 160- IP44-20W 19.2 W 2385 lm
Lighting DL REC-
160- IP44-
20W

16
Project

Building 1 · Storey 1
Luminaire list

Φtotal Ptotal Luminous efficacy


95180 lm 821.0 W 115.9 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

30 EAE 3209276 BLM 016A 40OD00 1K8 303020 15.9 W 1831 lm 115.1 lm/W

4 Rayon CONTINU CONTINUO-38w-4000k 38.0 W 4100 lm 107.9 lm/W


Lighting O-38W-
4000K

10 Rayon RAY- SD- RAY- SD-DL REC- 160- IP44-20W 19.2 W 2385 lm 124.4 lm/W
Lighting DL REC-
160- IP44-
20W

17
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

18
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target) (Target)

Working plane (Room 1) 523 lx 317 lx 639 lx 1.65 2.02 WP1


Perpendicular illuminance (adaptive) (≥ 500 lx) (≤ 1.67)
Height: 0.800 m, Wall zone: 0.126 m

Working plane (Room 2) 529 lx 305 lx 655 lx 1.73 2.15 WP2


Perpendicular illuminance (adaptive) (≥ 500 lx) (≤ 1.67)
Height: 0.800 m, Wall zone: 0.135 m

Surface result objects

Properties ∅ min max Ē/Emin Emax/Emin Index

Surface result object 1 (Floor/ceiling) 413 lx 50.0 lx 661 lx 8.26 13.2 RS1
Perpendicular illuminance (adaptive)
Height: 0.000 m

Surface result object 1 (Floor/ceiling) 26.3 cd/m² 3.19 cd/m² 42.1 cd/m² 8.24 13.2 RS1
Luminance
Height: 0.000 m

Calculation surfaces

Properties Ē Emin Emax Ē/Emin Emax/Emin Index

Calculation surface 4 406 lx 50.7 lx 636 lx 8.01 12.5 CG1


Perpendicular illuminance
Height: 0.000 m

Calculation surface 5 382 lx 250 lx 508 lx 1.53 2.03 CG2


Perpendicular illuminance
Height: 0.000 m

Calculation surface 7 383 lx 197 lx 496 lx 1.94 2.52 CG3


Perpendicular illuminance
Height: 0.000 m

19
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

Calculation points

Properties Calculated Index

Calculation point 1 445 lx CP1


Horizontal illuminance
Height: 0.283 m

Calculation point 2 523 lx CP2


Horizontal illuminance
Height: 0.000 m

20
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Ground area 34.17 m² Clearance height 2.600 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.126 m

21
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 523 lx ≥ 500 lx WP1

Ē/E min 1.65 ≤ 1.67 WP1

Lighting power density 7.63 W/m² –

1.46 W/m²/100 lx –

Energy estimation(2) Consumption [371.95 - 590.29] kWh/a max. 1200 kWh/a

Room Lighting power density 6.98 W/m² –

1.34 W/m²/100 lx –

(1) Based on a rectangular space of 5.852 m x 5.900 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

15 EAE 3209276 BLM 016A 40OD00 1K8 303020 – 15.9 W 1831 lm 115.1 lm/W

22
Project

Building 1 · Storey 1 · Room 1


Luminaire layout plan

23
Project

Building 1 · Storey 1 · Room 1


Luminaire layout plan

Manufacturer EAE P 15.9 W

Article No. 3209276 ΦLuminaire 1831 lm

Article name BLM 016A 40OD00


1K8 303020

Fitting 1x LED

15 x EAE AYDINLATMA A.Ş. BLM 016A 40OD00 1K8 303020

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.590 m / 0.975 m /
2.600 m 0.590 m 4.877 m 2.600 m 1

X-direction 5 pcs., Centre - 1.770 m 4.877 m 2.600 m 2


centre, 1.180 m
2.950 m 4.877 m 2.600 m 3
Y-direction 3 pcs., Centre -
centre, 1.951 m 4.130 m 4.877 m 2.600 m 4

Arrangement A1 5.310 m 4.877 m 2.600 m 5

0.590 m 2.926 m 2.600 m 6

1.770 m 2.926 m 2.600 m 7

2.950 m 2.926 m 2.600 m 8

4.130 m 2.926 m 2.600 m 9

5.310 m 2.926 m 2.600 m 10

0.590 m 0.975 m 2.600 m 11

1.770 m 0.975 m 2.600 m 12

2.950 m 0.975 m 2.600 m 13

24
Project

Building 1 · Storey 1 · Room 1


Luminaire layout plan

X Y Mounting Luminaire
height

4.130 m 0.975 m 2.600 m 14

5.310 m 0.975 m 2.600 m 15

25
Project

Building 1 · Storey 1 · Room 1


Luminaire list

Φtotal Ptotal Luminous efficacy


27465 lm 238.5 W 115.2 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

15 EAE 3209276 BLM 016A 40OD00 1K8 303020 15.9 W 1831 lm 115.1 lm/W

26
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Calculation objects

27
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target) (Target)

Working plane (Room 1) 523 lx 317 lx 639 lx 1.65 2.02 WP1


Perpendicular illuminance (adaptive) (≥ 500 lx) (≤ 1.67)
Height: 0.800 m, Wall zone: 0.126 m

Calculation surfaces

Properties Ē Emin Emax Ē/Emin Emax/Emin Index

Calculation surface 5 382 lx 250 lx 508 lx 1.53 2.03 CG2


Perpendicular illuminance
Height: 0.000 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

28
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Working plane (Room 1)

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target) (Target)

Working plane (Room 1) 523 lx 317 lx 639 lx 1.65 2.02 WP1


Perpendicular illuminance (adaptive) (≥ 500 lx) (≤ 1.67)
Height: 0.800 m, Wall zone: 0.126 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

29
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Calculation surface 5

Properties Ē Emin Emax Ē/Emin Emax/Emin Index

Calculation surface 5 382 lx 250 lx 508 lx 1.53 2.03 CG2


Perpendicular illuminance
Height: 0.000 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

30
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Summary

Ground area 33.82 m² Clearance height 2.600 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.600 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.135 m

31
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 529 lx ≥ 500 lx WP2

Ē/E min 1.73 ≤ 1.67 WP2

Lighting power density 7.76 W/m² –

1.46 W/m²/100 lx –

Energy estimation(2) Consumption [371.95 - 590.29] kWh/a max. 1200 kWh/a

Room Lighting power density 7.05 W/m² –

1.33 W/m²/100 lx –

(1) Based on a rectangular space of 5.852 m x 5.795 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

15 EAE 3209276 BLM 016A 40OD00 1K8 303020 – 15.9 W 1831 lm 115.1 lm/W

32
Project

Building 1 · Storey 1 · Room 2


Luminaire layout plan

33
Project

Building 1 · Storey 1 · Room 2


Luminaire layout plan

Manufacturer EAE P 15.9 W

Article No. 3209276 ΦLuminaire 1831 lm

Article name BLM 016A 40OD00


1K8 303020

Fitting 1x LED

15 x EAE AYDINLATMA A.Ş. BLM 016A 40OD00 1K8 303020

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.580 m / 0.975 m /
2.600 m 0.580 m 4.877 m 2.600 m 1

X-direction 5 pcs., Centre - 1.739 m 4.877 m 2.600 m 2


centre, 1.159 m
2.898 m 4.877 m 2.600 m 3
Y-direction 3 pcs., Centre -
centre, 1.951 m 4.057 m 4.877 m 2.600 m 4

Arrangement A1 5.216 m 4.877 m 2.600 m 5

2.898 m 2.926 m 2.600 m 6

0.580 m 2.926 m 2.600 m 7

1.739 m 2.926 m 2.600 m 8

4.057 m 2.926 m 2.600 m 9

5.216 m 2.926 m 2.600 m 10

0.580 m 0.975 m 2.600 m 11

1.739 m 0.975 m 2.600 m 12

2.898 m 0.975 m 2.600 m 13

34
Project

Building 1 · Storey 1 · Room 2


Luminaire layout plan

X Y Mounting Luminaire
height

4.057 m 0.975 m 2.600 m 14

5.216 m 0.975 m 2.600 m 15

35
Project

Building 1 · Storey 1 · Room 2


Luminaire list

Φtotal Ptotal Luminous efficacy


27465 lm 238.5 W 115.2 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

15 EAE 3209276 BLM 016A 40OD00 1K8 303020 15.9 W 1831 lm 115.1 lm/W

36
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Calculation objects

37
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target) (Target)

Working plane (Room 2) 529 lx 305 lx 655 lx 1.73 2.15 WP2


Perpendicular illuminance (adaptive) (≥ 500 lx) (≤ 1.67)
Height: 0.800 m, Wall zone: 0.135 m

Calculation surfaces

Properties Ē Emin Emax Ē/Emin Emax/Emin Index

Calculation surface 7 383 lx 197 lx 496 lx 1.94 2.52 CG3


Perpendicular illuminance
Height: 0.000 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

38
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Working plane (Room 2)

Properties Ē Emin Emax Ē/Emin Emax/Emin Index


(Target) (Target)

Working plane (Room 2) 529 lx 305 lx 655 lx 1.73 2.15 WP2


Perpendicular illuminance (adaptive) (≥ 500 lx) (≤ 1.67)
Height: 0.800 m, Wall zone: 0.135 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

39
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Calculation surface 7

Properties Ē Emin Emax Ē/Emin Emax/Emin Index

Calculation surface 7 383 lx 197 lx 496 lx 1.94 2.52 CG3


Perpendicular illuminance
Height: 0.000 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

40
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Summary

Ground area 36.85 m²

Reflection factors Ceiling: 70.0 %,


Walls: 50.0 %,
Floor: 20.0 % Clearance height 2.600 m

Maintenance factor 0.80 (fixed) Mounting height 2.000 m – 2.610 m

41
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Energy estimation(2) Consumption [536.16 - 850.91] kWh/a max. 1300 kWh/a

Room Lighting power density 9.34 W/m² –

(1) Based on a rectangular space of 5.900 m x 6.340 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Rayon CONTINU CONTINUO-38w-4000k – 38.0 W 4100 lm 107.9 lm/W


Lighting O-38W-
4000K

10 Rayon RAY- SD- RAY- SD-DL REC- 160- IP44-20W – 19.2 W 2385 lm 124.4 lm/W
Lighting DL REC-
160- IP44-
20W

42
Project

Building 1 · Storey 1 · Room 3


Luminaire layout plan

43
Project

Building 1 · Storey 1 · Room 3


Luminaire layout plan

Manufacturer Rayon Lighting P 38.0 W

Article No. CONTINUO-38W- ΦLuminaire 4100 lm


4000K

Article name CONTINUO-38w-


4000k

Fitting 1x CONTINUO-38w-
4000k

4 x Rayon Lighting CONTINUO-38w-4000k

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 2.176 m / 2.400 m /
2.000 m 2.176 m 3.450 m 2.000 m 11

X-direction 2 pcs., Centre - 4.149 m 3.450 m 2.000 m 12


centre, 1.973 m
2.176 m 2.400 m 2.000 m 13
Y-direction 2 pcs., Centre -
centre, 1.050 m 4.149 m 2.400 m 2.000 m 14

Arrangement A1

44
Project

Building 1 · Storey 1 · Room 3


Luminaire layout plan

Manufacturer Rayon Lighting P 19.2 W

Article No. RAY- SD-DL REC- 160- ΦLuminaire 2385 lm


IP44-20W

Article name RAY- SD-DL REC- 160-


IP44-20W

Fitting 1x RAY- SD-DL REC-


160- IP44-20W

10 x Rayon Lighting RAY- SD-DL REC- 160- IP44-20W

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.792 m / 0.983 m /
2.610 m 0.792 m 4.917 m 2.610 m 1

X-direction 4 pcs., Centre - 2.377 m 4.917 m 2.610 m 2


centre, Distances not
equal 3.962 m 4.917 m 2.610 m 3

Y-direction 3 pcs., Centre - 5.547 m 4.917 m 2.610 m 4


centre, Distances not
equal 0.792 m 2.950 m 2.610 m 5

Arrangement A2 5.547 m 2.950 m 2.610 m 6

0.792 m 0.983 m 2.610 m 7

2.377 m 0.983 m 2.610 m 8

3.962 m 0.983 m 2.610 m 9

5.547 m 0.983 m 2.610 m 10

45
Project

Building 1 · Storey 1 · Room 3


Luminaire list

Φtotal Ptotal Luminous efficacy


40250 lm 344.0 W 117.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

4 Rayon CONTINU CONTINUO-38w-4000k 38.0 W 4100 lm 107.9 lm/W


Lighting O-38W-
4000K

10 Rayon RAY- SD- RAY- SD-DL REC- 160- IP44-20W 19.2 W 2385 lm 124.4 lm/W
Lighting DL REC-
160- IP44-
20W

46
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Calculation objects

47
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Calculation objects

Surface result objects

Properties ∅ min max Ē/Emin Emax/Emin Index

Surface result object 1 (Floor/ceiling) 413 lx 50.0 lx 661 lx 8.26 13.2 RS1
Perpendicular illuminance (adaptive)
Height: 0.000 m

Surface result object 1 (Floor/ceiling) 26.3 cd/m² 3.19 cd/m² 42.1 cd/m² 8.24 13.2 RS1
Luminance
Height: 0.000 m

Calculation surfaces

Properties Ē Emin Emax Ē/Emin Emax/Emin Index

Calculation surface 4 406 lx 50.7 lx 636 lx 8.01 12.5 CG1


Perpendicular illuminance
Height: 0.000 m

Calculation points

Properties Calculated Index

Calculation point 1 445 lx CP1


Horizontal illuminance
Height: 0.283 m

Calculation point 2 523 lx CP2


Horizontal illuminance
Height: 0.000 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

48
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Surface result object 1 (Floor/ceiling)

Properties Ē Emin Emax Ē/Emin Emax/Emin Index

Surface result object 1 (Floor/ceiling) 413 lx 50.0 lx 661 lx 8.26 13.2 RS1
Perpendicular illuminance (adaptive)
Height: 0.000 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

49
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Surface result object 1 (Floor/ceiling)

Properties ∅ min max Ē/Emin Emax/Emin Index

Surface result object 1 (Floor/ceiling) 26.3 cd/m² 3.19 cd/m² 42.1 cd/m² 8.24 13.2 RS1
Luminance
Height: 0.000 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

50
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Calculation surface 4

Properties Ē Emin Emax Ē/Emin Emax/Emin Index

Calculation surface 4 406 lx 50.7 lx 636 lx 8.01 12.5 CG1


Perpendicular illuminance
Height: 0.000 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

51
Project

Glossary

A Formula symbol for a surface in the geometry

Background area The background area borders the direct ambient area according to DIN EN 12464- 1 and
reaches up to the borders of the room. In larger rooms, the background area is at least
3 m wide. It is located horizontally at floor level.

CCT (Engl. correlated colour temperature)


Body temperature of a thermal radiator which serves to describe its light colour. Unit:
Kelvin [K]. The lesser the numerical value the redder; the greater the numerical value the
bluer the light colour. The colour temperature of gas- discharge lamps and semi-
conductors are termed "correlated colour temperature" in contrast to the colour
temperature of thermal radiators.

Allocation of the light colours to the colour temperature ranges acc. to EN 12464-1:

Light colour - colour temperature [K]


warm white (ww) < 3,300 K
neutral white (nw) ≥ 3,300 – 5,300 K
daylight white (dw) > 5,300 K

Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).

Control group A group of luminaires that are dimmed and controlled together. For each lighting scene,
a control group provides its own dimming value. All luminaires within a control group
share this dimming value. The control groups with their luminaires are automatically
determined by DIALux on the basis of the created light scenes and their luminaire
groups.

CRI (Engl. colour rendering index)


Designation for the colour rendering index of a luminaire or a lamp acc. to DIN 6169:
1976 or CIE 13.3: 1995.

The general colour rendering index Ra (or CRI) is a dimensionless figure that describes
the quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colours (see DIN 6169 or CIE 1974) to a reference light source.

52
Project

Glossary

Daylight autonomy Describes what percentage of the daily working time the required illuminance is met by
daylight. The nominal illuminance is used from the room profile, unlike described in EN
17037. The calculation is not done in the centre of the room but at the placed sensor
measuring point. A room is considered sufficiently supplied with daylight if it achieves at
least 50% daylight autonomy.

Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky.

Formula symbol: D (Engl. daylight factor)


Unit: %

Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.

Energy evaluation Based on an hourly calculation procedure for daylight in indoor spaces, considering the
project geometry and any existing daylight control systems. Orientation and location of
the project are also considered. The calculation uses the specified system power of the
luminaires to determine the energy demand. A linear relationship between power and
luminous flux in the dimmed state is assumed for daylight-controlled luminaires. Times
of use and nominal illuminance are determined from the usage profiles of the spaces.
Switched-on luminaires that are explicitly excluded from control also consider the
specified times-of-use. The daylight control systems use a simplified control logic that
closes them at an outdoor horizontal illuminance of 27,500lx.

The calendar year 2022 is used as a reference only. It is not a simulation of this year. The
reference year is only used to assign the days of the week to the calculated results. The
changeover to summer time is not considered. The reference sky type used is the
average sky described in CIE 110 without direct sunlight.

The method was developed together with the Fraunhofer Institute for Building Physics
and is available for review by the Joint Working Group 1 ISO TC 274 as an extension of
the previous annual regression-based method.

Eta (η) (light output ratio)


The light output ratio describes what percentage of the luminous flux of a free radiating
lamp (or LED module) is emitted by the luminaire when installed.

Unit: %

53
Project

Glossary

g1 Often also Uo (Engl. overall uniformity)


Designates the overall uniformity of the illuminance on a surface. It is the quotient from
Emin to Ē and is required, for instance, in standards for illumination of workstations.

g2 Actually it designates the "non-uniformity" of the illuminance on a surface. It is the


quotient of Emin to Emax and is generally only relevant for certifying the emergency
lighting acc. to EN 1838.

Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be determined
anywhere in space (inside or outside). The illuminance is not a product feature because it
is a recipient value. Luxometers are used for measuring.

Unit: Lux
Abbreviation: lx
Formula symbol: E

Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.

Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.

Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.

Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.

LENI (Engl. lighting energy numeric indicator)


Lighting energy numeric indicator acc. to EN 15193

Unit: kWh/(m² * a)

54
Project

Glossary

LLMF (Engl. lamp lumen maintenance factor)/acc. to CIE 97: 2005


Lamp flux maintenance factor that takes the luminous flux reduction into account of a
luminaire or an LED module in the course of the operating time. The lamp flux
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no luminous flux reduction existing).

LMF (Engl. luminaire maintenance factor)/acc. to CIE 97: 2005


Luminaire maintenance factor that takes the soiling into account of the luminaire in the
course of the operating time. The luminaire maintenance factor is specified as a decimal
digit and can have a maximum value of 1 (no soiling existing).

LSF (Engl. lamp survival factor)/acc. to CIE 97: 2005


Lamp survival factor that takes the total failure into account of a luminaire in the course
of the operating time. The lamp survival factor is specified as a decimal digit and can
have a maximum value of 1 (no failures existing within the time concerned or prompt
replacement after the failure).

Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It is
the only photometric value that the human eye can perceive.

Unit: Candela per square metre


Abbreviation: cd/m²
Formula symbol: L

Luminous efficacy Ratio of the emitted luminous flux Φ [ lm] to the absorbed electrical power P [W] Unit:
lm/W.

This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).

Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.

Unit: Lumen
Abbreviation: lm
Formula symbol: Φ

Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.

Unit: Candela
Abbreviation: cd
Formula symbol: I

55
Project

Glossary

Maintenance factor See MF

MF (Engl. maintenance factor)/acc. to CIE 97: 2005


Maintenance factor as decimal number between 0 and 1 that describes the ratio of the
new value of a photometric planning parameter (e.g. of the illuminance) to a
maintenance value after a certain time. The maintenance factor takes into account the
soiling of luminaires and rooms as well as the luminous flux reduction and the failure of
light sources.
The maintenance factor is taken into account either overall or determined in detail acc.
to CIE 97: 2005 by the formula RMF x LMF x LLMF x LSF.

P (Engl. power)
Electric power consumption

Unit: watt
Abbreviation: W

R(UG) max Measure of the psychological glare in indoor spaces.


In addition to the luminance of luminaires, the level of the R(UG) value also depends on
the observer position, the viewing direction and the ambient luminance. The calculation
is made according to the table method, see CIE 117. Among other things, EN 12464-
1: 2021 specifies maximum permissible R(UG)- values R(UGL) for various indoor workplaces.

Reflection factor The reflection factor of a surface describes how much of the striking light is reflected
back. The reflection factor is defined by the colour of the surface.

RMF (Engl. room maintenance factor)/acc. to CIE 97: 2005


Room maintenance factor that takes the soiling into account of the space encompassing
surfaces in the course of the operating time. The room maintenance factor is specified
as a decimal digit and can have a maximum value of 1 (no soiling existing).

Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.

56
Project

Glossary

UGR (max) (unified glare rating)


Measure for the psychological glare effect in interiors.
In addition to luminaire luminance, the UGR value also depends on the position of the
observer, the viewing direction and the ambient luminance. Among other things, EN
12464-1 specifies maximum permissible UGR values for various indoor workplaces.

UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).

Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN 12464
-1. The height corresponds with the height at which the visual task is executed.

Wall zone Circumferential area between working plane and walls which is not taken into account
for the calculation.

Working plane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.