E T-90series Reva
E T-90series Reva
(1) Kind of input (2) Kind of outer case and its dimensions
● AC TRANSDUCER
● SENSOR TRANSDUCER
Dimensions (mm)
Mark Material of outer case
Length × Width × Height
82 Fire-retardant ABS resin 120× 56×130
83 Fire-retardant ABS resin 120×110×130
● SIGNAL TRANSDUCER
Dimensions (mm)
Mark Material of outer case
Length × Width × Height
82 Fire-retardant ABS resin 120× 56×130
83 Fire-retardant ABS resin 120×110×130
§ BOX TRANSDUCER §
COMMON STANDARD SPECIFICATION
Item Specification
Tolerance % against output span. See [Specifications]
Influence of temperature 23±20℃ tolerance %
No display: 1/2 of tolerance % at 45-65Hz
Influence of frequency
Rated Hz display: 1/2 of tolerance at ±5% of rating
Characteristics In conformity with the classifications of JIS C 1111-1989 in tolerance
Time it takes to fall within ±1% of the final steady-state value
Response time
when applied a stepped input. ≦1 sec.
Output ripple ≦1% P-P against output span
External adjustment of output ±5% adjustable
Auxiliary supply AC110V or AC220V ±15% (50/60Hz)
2 times of rated voltage (10 sec.), 1.2 times (Continuity)
Over voltage
Auxiliary supply of isolator: 1.5 times 10sec.
40 times of rated current (1 sec.), 20 times (4 sec.) 10 times (16 sec.), 1, 2 times
Over current
(Continuity), (Signal transducer: 10 times 5 sec.)
Item Specification
Frequency 1. Voltage/current transducer
► General frequency
(1) Frequency fixation (Fixed Hz ±10% Tolerance %)
variation
Frequency Tolerance Response time (±1%) Ripple (P-P)
40Hz-2kHz, ≦1 sec.
25Hz-2kHz ±0.5% 30Hz-39kHz, ≦1.5 sec.
25Hz-29kHz, ≦2 sec. ≦1%
2.1kHz-10kHz ≦1 sec.
±1%
20Hz-24Hz ≦2 sec.
(2) Frequency variation (tolerance % within the range)
Rated Hz Frequency Tolerance Response time (±1%) Ripple (P-P)
50/60Hz 35Hz-80Hz ±0.5% ≦1.5 sec.
≦1%
25Hz-200Hz ±1% ≦2 sec.
► Special frequency
2. Electric power transducer (only WTT-83 is manufacturable)
variation
(1) Frequency fixation (Fixed Hz ±10% Tolerance %)
Frequency Tolerance Response time (±1%) Ripple (P-P)
40Hz-2kHz, ≦1 sec.
30Hz-2kHz ±0.5%
30Hz-39kHz, ≦1.5 sec.
≦1%
2.1kHz-10kHz ≦1 sec.
±1%
20Hz-29Hz ≦2 sec.
Rated Hz (2) Frequency variation (tolerance % within the range)
50/60Hz Frequency Tolerance Response time (±1%) Ripple (P-P)
25Hz-100Hz ≦2 sec.
Consult us for the case 30Hz-90Hz ≦1.5 sec.
of CVVF. 40Hz-120Hz ±1% ≦1%
200Hz-600Hz ≦1 sec.
500Hz-1.5kHz
§ BOX TRANSDUCER §
COMMON STANDARD SPECIFICATION
Item Specification
Voltage/current/transducer
Response time (±1%) Frequency Ripple (P-P) Tolerance
≦0.1 sec. ≦5%
50/60Hz ±0.5%
≦0.2 sec. ≦3%
Electric power transducer (3 phase 3 wire type)
Response time (±1%) Frequency Ripple (P-P) Tolerance
≦1%
(Input sensitivity 120-80%)
Response time
≦2%
≦0.1 sec. 50/60Hz
(Input sensitivity 79-60%)
≦5%
±0.5%
(Input sensitivity 59-50%)
≦1%
(Input sensitivity 120-70%)
≦0.2 sec. 50/60Hz
≦2%
(Input sensitivity 69-50%)
IEC standard
Have a consultation with us for rating plate indication items, tolerance and line impulse and
conformity
so on.
(Pub. 688-1)
ANSI (SWC)
Please specify if any test by ANSI C37.90a-1974 is necessary.
test
Terminal cover Polycarbonate
Other Subject to consultation
§ BOX TRANSDUCER §
SMALL SIZED AC TRANSDUCER CONSTANT VOLTAGE/CURRENT TYPE 90 SERIES
■ FEATURES
●Heavy current oriented size reduction ●With a terminal cover as standard equipment.
●Withstand voltage AC2000V 50/60Hz for 1 min. ●Auxiliary supply DC100/110V (88-143V) is also
between input, output, auxiliary supply and earth. manufacturable.
●Impulse withstand voltage between electric circuit ●Supports both DIN rail mounting and wall
and earth 5kV 1.2/50µs positive/negative polarity 3 mounting.
times each.
●As a constant voltage/current output type, it is
possible to transmit an output directly to a distant
place.
■ COMMON SPECIFICATIONS
Item Specification
Tolerance % against output span
Influence of temperature 23±10℃ tolerance %
Influence of output load 1/2 of tolerance % based on the center value of rated output load
No display: 1/2 of tolerance % at 45-65Hz
Influence of frequency
Rated Hz display: 1/2 of tolerance % at rating ±5%
Characteristics In conformity with JIS C1111-1989
Response time Time it takes to fall within ±1% of the final steady-state value ≦1 sec.
Output ripple ≦1%P-P against output span
External adjustment of output ±5% adjustable
Confines output to about 1.5 times of rating and protects output side equipments when an
Output limiter circuit
excessive input is applied.
AC100/110V +10/-15% or AC200/220V +10/-15% (50/60Hz)
Auxiliary supply
DC24V±15% or DC48V or DC110V (88-143V)
Input 2 times of rated voltage for 10 sec., 1.2 times Continuity
Overvoltage
Auxiliary supply 1.5 times of rated voltage for 10 sec., 1.2 times Continuity
40 times of rated current 1 sec, 20 times 4 sec, 10 times 16 sec,
Overcurrent
1.2 times Continuity
≧50MΩ at DC500V between input terminal, output terminal,
Insulation resistance
auxiliary supply terminal and outer case (earth)
AC2,000V (50/60Hz) for 1 min. between input terminal, output terminal,
Withstand voltage
auxiliary supply terminal and outer case (earth)
Between electric circuit and outer case (earth) 5kV 1.2/50µs
Impulse withstand voltage
positive/negative polarity 3 times each
Terminal block: Fire-retardant ABS (V-O) Mixed glass fiber in by 15%
Material of case
Box: Fire-retardant ABS (V-O) Terminal cover: Polycarbonate
Terminal screw M4
Appearance color Black (Munsell 1.5)
Operating temperature/humidity
-10 - +55℃, 30 - 85%RH
range
Storage temperature range -40 - +70℃
§ BOX TRANSDUCER §
SMALL SIZED AC TRANSDUCER CONSTANT VOLTAGE/CURRENT TYPE 90 SERIES
■ PRODUCT RANGE
Rated DC
Measuring objective Rated AC input range Frequency
output range
AC current 0.1-10A 45Hz-65Hz 0.1-10V
AC voltage 50-300V 45Hz-65Hz 0.1-20mA
250-600W
(110V, 5A)
Single ±150-±600W
50-240V 1A, 5A 50/60Hz
phase 500-1, 200W
(220V, 5A)
Active ±300-±1, 200W
power 3 phase 3 500-1, 200W
(110V, 5A)
wire or 3 ±300-±1, 200W
50-240V 1A, 5A 50/60Hz
phase 4 1, 000-2, 400W ±0.1-±10V or
(220V, 5A)
wire ±600-±2, 400W ±0.1--5mA
3 phase 3 500-1, 200W +20mA
(110V, 5A)
Reactive wire or 3 ±300-±1, 200W
50-240V 1A, 5A 50/60Hz
power phase 4 1, 000-2, 400W
(220V, 5A)
wire ±600-±2, 400W
50 or 60Hz
V-V phase angle 50-240V - ±30°-±150° by
specification
45-65Hz (45Hz-1kHz 0.1-10V
Frequency 50-240V - -
by specification) 0.1-20mA
Have a consultation with us for those not included in the table above. (Shall be dealt with by TT2-80A series)
§ BOX TRANSDUCER §
SMALL SIZED AC TRANSDUCER 90 SERIES
ATT2-91A WTT2-92A-33
(120×40×130mm/0.5kg) (120×56×130mm/0.7kg)
■ SPECIFICATIONS
AT2-91 VT2-91
(120×40×130mm/0.3kg) (120×40×130mm/0.3kg)
■ FEATURES
●Heavy current oriented size reduction
●Withstand voltage AC2000V 50/60Hz for 1 min. between input, output and earth.
●Protects output side equipments from an input side lightning surge with an electrostatic shield between primary and
secondary winding.
■ Features
●Load resistance fixed type
●Auxiliary supply not required type
●Terminal cover as a standard equipment
●Supports both DIN rail and wall mounting.
■ COMMON SPECIFICATION
See COMMON SPECIFICATION above
■ SPECIFICATION
*1 Please specify the voltage output with a load resistance 50kΩ or more.
Please specify the current output with a load resistance 5kΩ or more.
§ BOX TRANSDUCER §
SMALL SIZED SIGNAL TRANSDUCER TT2-91A
■ APPLICATION
This device amplifies various kinds of DC signals and converts them into
unified intersystem signals. Because input, output, power source and
earth are reciprocally insulated by a withstand voltage 2,000V, the
product offers full advantages in transmitting insulated signals between
power measuring systems, cutoff of noise, protecting control circuit from a
sneak current, and transmitting an output directly to a distant place.
■ FEATURES
●Withstand voltage AC2000V 50/60Hz for 1 min. between input, output,
auxiliary supply and earth. Isolator TT2-91A
●Impulse withstand voltage 5kV 1.2/50μs positive/negative polarity 3 (120×40×130mm/0.5kg)
times each between electric circuit and earth, auxiliary supply and
input/output.
●Supports both DIN rail and wall mounting.
■ SPECIFICATION
*1 Tolerance becomes ±0.5% in the case of input voltage less than 50mV, input current less than 500μA.
*2 For input 10μA, circuit voltage is 15V or less.
*3 Input voltage ranging from 10mV to 600V, input current ranging from 10μA to 100mA are manufacturable.
*4 Consult with us for voltage output up to 10V, current output up to 20mA.
*5 Rated voltage of auxiliary supply DC20―57V is DC24V or DC48V.
► Open current output: The output terminal can be used with the current output terminal open at all times.
Note that approx. 15V voltage will occur at the output terminal.
■ CONNECTION DIAGRAM
■ PURCHASE SPECIFICATION
§ BOX TRANSDUCER §
SMALL SIZED AC TRANSDUCER CONSTANT VOLTAGE/CURRENT TYPE 90 SERIES
■ DIMENSIONS (mm) See the connection diagram above for terminal arrangement
■ PURCHASE SPECIFICATION
1. Type; 4. Auxiliary supply;
5. Quantity;
2. Input (rated voltage / current / frequency);
3. Output (load resistance);
§ BOX TRANSDUCER §
SMALL SIZED AC TRANSDUCER 90 SERIES SPECIFICATION CODE