The document provides instructions for installing swage grounding connectors. It lists the necessary tools and fittings for different connector sizes. It then provides 5 steps for cleaning and preparing the cable, assembling the connector on the cable, compressing the connector with the proper tooling, checking the connection with gauges, and inspecting the compression.

Uploaded by

Ganesh Duraisamy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views

Swage - Grounding Installation Instructions

The document provides instructions for installing swage grounding connectors. It lists the necessary tools and fittings for different connector sizes. It then provides 5 steps for cleaning and preparing the cable, assembling the connector on the cable, compressing the connector with the proper tooling, checking the connection with gauges, and inspecting the compression.

Uploaded by

Ganesh Duraisamy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Installation Instructions

INS-ACA081

Swage Grounding Installation Instructions


NOTE: VISUALLY INSPECT ALL TOOLS, ACCESSORIES AND FITTINGS PRIOR TO BEGINNING THE INSTALLATION
PROCEDURE. INSPECT CONDUCTOR ACCESSORIES AND ENSURE THAT THE FITTING IS NOT OBSTRUCTED. ENSURE YOU
HAVE THE CORRECT TOOLS; SEE TABLE 1.

Table 1
FITTING OD (INCHES) DIE SIZE HEAD FILLER DIE PRESS
1.00 45TD16 45THA20 — 45TPU
1.25 45TD20 45THA20 — 45TPU
1.50 45TD24 45THA36 B11336-15 45TPU
1.75 45TD28 45THA36 B11336-15 45TPU
1.88 45TD30 45THA36 B11336-15 45TPU
2.00 45TD32 45THA36 — 45TPU
2.25 45TD36 45THA36 — 45TPU
2.75 65TD44L 65THA200L — 65TPU-L

INSTRUCTIONS
1. Clean and prepare the cable end.
Using a brass or stainless steel wire brush, brush and thoroughly clean the conductor to be used with the Swage grounding connector.

2. Assemble the cable connector fitting with the cable.


Insert the cleaned end of the conductor into the barrel of the grounding fitting to be used. Using the sight/weep hole, ensure that the
conductor is at the bottom of the cavity and mark the insertion depth on the conductor with a permanent ink marker.

continued

www.AFLglobal.com or 800-890-8878 © 2016, AFL, all rights reserved. Revision 1, 2.19.18


Specifications are subject to change without notice.
207
Installation Instructions
INS-ACA081

Swage Grounding Installation Instructions (cont.)


3. Make the Swage compression.
With the tooling assembled, insert the grounding connector in the tool. Align the raised Swage mark (line) on the connector with the
raised portion of the teeth of the dies (contact surface) and the end of the connector. Insert the cable in to the grounding connector to
the ink mark on the conductor and compress to 10,000 PSI.
INSTRUCTIONS

continued

www.AFLglobal.com or 800-890-8878 © 2016, AFL, all rights reserved. Revision 1, 2.19.18


Specifications are subject to change without notice.
208
Installation Instructions
INS-ACA081

Swage Grounding Installation Instructions (cont.)


4. Make the proper Swage connection.
Use appropriate go/no-go gauge and measure the crimped area for fit. If the gauge fits compressed area, compression is complete.
If the gauge does not fit the compressed area, check hydraulic pump for correct pressure and fluid level. Re-squeeze to ensure full
compression and re-check.

INSTRUCTIONS
5. Properly inspect the Swage compression.
Verify complete compression was achieved by using the “Swage Gauge.” See Fig. 5a. Place the –GO/NO-GO– gauge over Swage
compression area to ensure the gauge fits over the full compression area. Confirm that the accessory touches the deepest point
of gauge. See Fig. 5b and 5c. If the “Swage Gauge” does not slide over compressed area, then re-swage the fitting and re-inspect
using the –GO/NO-GO– gauge ensuring they touch the compression mark.

Fig. 5a Fig. 5b

Repeat steps 1-5 for each Grounding Fitting.