Training Report On 220KV Substation PowerGrid
Training Report On 220KV Substation PowerGrid
Arunachal Pradesh
The concept in images content in this summer training report is a sincere manifest
input from Ranganadi hydro power station, Kathalguri gas-based power station,
Kopili hydro power station etc. It also supplies power to various state utilities like
2|Page
ACKNOWLEDGEMENT
3|Page
I would like to take this opportunity to express our profound gratitude
and deep regards to Sir Prashanta Kanungo, Sr. General Manager, Sir
them from time to time shall be an impetus in the journey of the life on
which I am about to embark. This project would have not been possible
4|Page
CONTENTS:
No No
STATION
2. ASSET DETAILS OF
MISA SUBSTATION
3. SLD OF MISA
SUBSTATION
5|Page
4. SWITCHYARD
EQUIPMENTS:
1. Introduction
2. Lightning Arrestor
3. CVT
4. CT
5. Wave Trap
6. Isolators
7. Transformers
8. Bus Reactors
9. Circuit Breakers
11. PLCC
5.
6|Page
RELAYS AND THEIR
6. ROLE IN PROTECTION
SCHEMES
TRANSFORMER OIL
7. TESTS
SUBSTATION
8. AUXILARY
EQUIPMENTS
1. Battery bank
3. Diesel generating
set
9. GIS
10. CONCLUSION
7|Page
1.ABOUT MISA SUBSTATION
Initially proposed to be set up at Misa (35 km from Nagaon town on NH-37) the
8|Page
from Nagaon town, the substation retains its proposed name – often creating confusion among
• Strategically positioned in the centre of the Region, Misa substation provides vital
connectivity for all major generating stations to load centres both within and outside NER.
• Located on the foothills of the Rengma Hills, the substation presents a picturesque view
to the onlookers.
HOW TO REACH
Silchar.
• Nearby Railway Stations: Hojai (34 km), Nagaon (28 km), Kampur (19 km)
Misa substation is an important element in the NE Regional Grid.In 1989,PGCIL took over
misa substation is 2*315 MVA,400/220/33 kV in the bank of single phase auto transformer
9|Page
• 220 kV Misa-Mariani Single Circuit line
10 | P a g e
2.ASSET DETAILS OF MISA SUBSTATION
11 | P a g e
3. SLD OF MISA SUBSTATION
12 | P a g e
4.SWITCHYARD EQUIPMENTS
1.INTRODUCTION:
Switchyard is a switching station which is the main link between the generating plant and the
transmission system. It can be considered as the heart of the power plant, the generated power will only
be worthy if it can be transmitted and received by the consumers. Switchyard is a junction which carries
the generated power to the destination, it plays a major part in the security of the system, it can control
the reactive power devices which plays a major role in power quality. It is mostly an assemblage of
switches, power circuits, breakers, and the auxiliary equipment which is used to collect power from the
generators at the power plant and then it will be distributed to the transmission lines at a load point.
Switchyard makes available the generated power at the plant to the people. The power generated at a
power station is transmitted via a switchyard. When there is sudden damage outside the plant switchyard
can protect the plant. A Switchyard consists of many equipment such as Current transformer (CT),
Voltage transformer (VT), Lightning arrester (LA), Power transformers, Isolators support structure,
Circuit breaker (CB), Wave traps, Earthing switch, Bus bar etc.
2. LIGHTNING ARRESTOR
13 | P a g e
The device which is used for the protection of the equipment at the substations against travelling waves,
such type of device is called lightning arrester or surge diverter. In other words, lightning arrester diverts
the abnormals high voltage to the ground without affecting the continuity of supply. It is connected
between the line and earth, i.e., in parallel with the equipment to be protected at the substation. The
device which is used for the protection of the equipment at the substations against travelling waves,
such type of device is called lightning arrester or surge diverter. In other words, lightning arrester diverts
the abnormals high voltage to the ground without affecting the continuity of supply. It is connected
between the line and earth, i.e., in parallel with the equipment to be protected at the substation.
The lightning arrester is located close to the equipment that is to be protected. They are usually
connected between phase and ground in an AC system and pole and ground in case of the DC system.
In an AC system, separate arrester is provided for each phase. There are many types of lightning arrester
14 | P a g e
CVT Capacitive Voltage Transformer is a step down transformer just like potential transformer which
converts high voltage in to low voltage. Capacitor Voltage Transformers convert transmission class
voltages to standardized low and easily measurable values, which are used for metering, protection and
control of the high voltage system. Normally in high voltage system, the line voltage or current cannot
be measured. Therefore, instrument transformer such as Potential transformer and current transformers
are generally used. At that same time in EHV lines (Extra high voltage lines) the cost of a potential
transformer is high because of its insulation. In order to reduce the cost of the insulation the capacitive
voltage transformers are used instead of standard voltage transformer. The Capacitive voltage
transformer (CVT) is also called capacitive potential transformer. Capacitive voltage transformers
(CVTs) are used on higher voltage levels, starting from 72.5 kV and upwards.
CVT is working under principle of potential divider. It consists of two capacitors to form a potential
divider, line reactor and a step down transformer. Here line reactor is used to compensate the capacitor’s
phase shift. The value of inductances is adjustable. The inductance compensates the voltage drops
occurs in the transformer because of the reduction of the current from the potential divider. But, in
actual practice, the compensation is not possible because of the inductance losses.
15 | P a g e
4.CURRENT TRANSFORMER
Current transformers (CT) are used in High Voltage (HV) and Medium Voltage (MV) installations to
give an image of electrical current to protection relays and units and metering equipment and they are
designed to provide a current in its secondary proportional to the current flowing in its primary. CT are
connected in series and protection devices and metering equipments are connected to the secondary of
or indoors, in GIS substations (Gas Insulated Substation) MV CT are usually installed indoors, in MV
Switchgears.
• “On line” (straight-through) CT – bar primary type and wound primary type.
“Ring type” CT is constructed of an iron toroid, which forms the core of the transformer, and is wound
with secondary turns. The doughnut fits over the primary conductor, which constitutes one primary
turn. Ring type CT are commonly used in cables, busbars and transformers bushings.
Usually HV CT use oil or gas (SF6) as insulation medium and MV CT use synthetic resins.
CT may have one or more cores; typical applications of these cores are:
16 | P a g e
Cores 2 and 3 – protection.
The use of more than one core for protection is justified when the installation has two protections
5.WAVETRAP
Wave trap is used to create a high impedance to the carrier wave high-frequency communication
150kHz to 800kHz frequency to send all the communication. These high-frequency damages the power
system components which are designed to operate 50 or 60 Hz. Wave traps are also called line traps.
It consists of an inductor coil which is connected in series with the high voltage power system.
17 | P a g e
Wave trap circuit diagram
• Main Coil
• Tuning Device
• Protective Device
18 | P a g e
6.ISOLATORS
The isolator is a mechanical switch which isolates a part of the circuit from the system as
when required. Electrical isolators separate a part of the system from rest for safe
There are different types of isolators available depending upon system requirement such as
Depending upon the position in the power system, the isolators can be categorized as
1. Bus side isolator – the isolator is directly connected with main bus
2. Line side isolator – the isolator is situated at line side of any feeder
3. Transfer bus side isolator – the isolator is directly connected with transfer bus.
Earthing Switches:
Earthing switches are mounted on the base of line side isolator. Earthing switches are usually
vertically broken switches. Earthing arms (contact arm of earthing switch) usually are aligned
horizontally at off condition during switching on the operation, these earthing arms rotate and move
to vertical position and make contact with earth female contacts fitted at the top of the post insulator
stack of the isolator at its outgoing side. The earthing arms are so interlocked with the main isolator
moving contacts that it can be closed only when the primary contacts of the isolator are in open
19 | P a g e
position. Similarly, the main isolator contacts can be closed only when the earthing arms are in
open position.
As no arc quenching technique is provided in isolator it must be operated when there is no chance
current flowing through the circuit. No live circuit should be closed or open by isolator operation.
A complete live closed circuit must not be opened by isolator operation, and also a live circuit must
not be closed and completed by isolator operation to avoid huge arcing in between isolator contacts.
That is why isolators must be open after circuit breaker is open, and these must be closed before
circuit breaker is closed. The isolator can be operated by hand locally as well as by motorized
mechanism from a remote position. Motorized operation arrangement costs more compared to hand
operation; hence decision must be taken before choosing an isolator for the system whether hand
operated or motor operated economically optimum for the system. For voltages up to 145 KV
system hand operated isolators are used whereas for higher voltage systems like 245 KV or 420 KV
7.TRANSFORMERS:
POWER TRANSFORMER:
A power transformer is used primarily to couple electrical energy from a power supply line to a circuit
system, or to one or more components of the system. A power transformer used with solid state circuits
is called a rectifier transformer. A power transformer's rating is given in terms of the secondary's
20 | P a g e
Fig No: 7 Parts of a Power Transformer
A transformer is made of several different parts that function in their own different ways to enhance the
overall functioning of a transformer. These include core, windings, insulating materials, transformer
oil, tap changer, conservator, breather, cooling tubes, Buchholz Relay and explosion vent. The core,
windings, insulating materials and transformer oil are seen in almost every transformer, while the other
• Core:
The core of the transformer is used to support the windings. It is made of soft iron to reduce eddy current
loss and Hysteresis loss, and provides low reluctance path to the flow of magnetic flux. The diameter
of a transformer’s core is directly proportional to copper loss and inversely proportional to iron loss.
21 | P a g e
• Windings:
Windings consist of several copper coil turns bundled together, each bundle connected to form a
complete winding. Windings can be based either on the input-output supply or on the voltage range.
Windings that are based on supply are classified into primary and secondary windings, meaning the
windings to which the input and output voltage is applied respectively. On the other hand, windings
based on voltage range can be classified into high voltage and low voltage windings.
• Insulating materials:
Insulating materials like papers and card boards are used to isolate primary and secondary windings
from each other as well as the transformer core. These windings are made of copper due to high
conductivity and ductility. High conductivity minimizes the amount of copper needed and minimizes
losses. Moreover, high ductility results in easy bending of conductors into tight winding around the core
• Transformer Oil:
The transformer oil insulates as well as cools the core and coil assembly. The core and windings of the
transformer must be completely immersed in the oil that normally contains hydrocarbon mineral oils.
• Conservator:
The conservator is an airtight metallic cylindrical drum fitted above the transformer that conserves the
transformer oil. It is vented at the top and is filled only half with the oil to allow expansion and
contraction during temperature variations. However the main tank of the transformer with which the
22 | P a g e
• Breather:
The breather is a cylindrical container filled with silica gel, which is used to keep the air that enters the
tank moisture-free. This is because the insulating oil when reacts with moisture can affect the insulation
and cause internal faults, which is why it is a must to keep the air free from moisture. In the breather,
when the air passes through the silica gel, the moisture contents are absorbed by the silica crystals.
• Tap changer:
To balance voltage variations within the transformer, tap changers are used. There are two types of tap
changers – on load and off load. In on load tap changers, tapping can be changed without isolating
transformer from the supply, while in off load, the transformer needs to be disconnected from the
supply.
• Cooling tubes:
As the name suggests, cooling tubes are used to cool the transformer oil. The circulation of oil within
the transformer may be natural or forced. In the case of natural circulation, when the oil temperature
rises, the hot oil naturally moves to the top and cold oil moves down, while in case of forced circulation,
• Buchholz Relay:
Placed over the connecting pipe that runs from the main tank to conservator tank the Buchholz Relay
senses the faults occurring within the transformer. It operates by the gases emitted due to decomposition
of transformer oil during internal faults. Thus, this device is used to sense and in turn protect the
• Explosion vent:
The boiling hot oil from the transformer is expelled during internal faults through the explosion vent to
avoid explosion of the transformer. This is generally placed above the level of the conservatory tank.
23 | P a g e
Understanding all these parts of a transformer will help you understand transformers and their functions
much better. With a wide variety of transformers available, you need to know which transformer type
is the most suitable for you. However, for any kind of transformer purchase, you can get in touch with
Miracle Electronics who manufactures the best-in-class power transformers in India since over the past
20 years and has been successfully supplying its products to over 20 countries across the globe.
AUTO-TRANSFORMER:
The autotransformer is a special type of power transformer. It consists of a single, continuous winding
that is tapped on one side to provide either a step-up or a step-down function. This is different from a
conventional two-winding transformer, which has the primary and secondary completely isolated from
each other, but magnetically linked by a common core. The autotransformer's windings are both
rated two-winding transformer. It also has better regulation (smaller voltage drops), and greater
efficiency. Furthermore, it can be used to obtain the neutral wire of a three-wire 240/120-volt service,
just like the secondary of a two0winding transformer. The autotransformer is considered unsafe for use
on ordinary distribution circuits. This is because the high-voltage primary circuits are connected directly
24 | P a g e
8.BUS REACTORS:
A bus reactor is an air core inductor, or oil filled inductor, connected between two buses or two sections
of the same bus to limit the voltage transients on either bus. It is installed in a bus to maintain system
voltage when the load of the bus changes. It adds Inductance to the system to offset the Capacitance of
the line.
Line reactors:
A line reactor is placed in line at the point of use or just after a transformer to maintain a stable amperage
to the user. When a line is disconnected from the system, the line reactor is also disconnected from the
system. Line reactors are often used to compensate line capacitance, mitigate voltage transients due to
switching, and to limit fault currents, especially in case of underground transmission lines. A bus reactor
and a line reactor are interchangeable as long as they are rated for the same voltage which is dependent
Shunt reactors:
Shunt reactors are used in power systems to counteract the effect of the line parasitic capacitance,
thereby stabilizing the system voltage within acceptable limits. For short lines, we can basically ignore
the impact of capacitive current from a voltage regulation point of view, but medium and long lines can
have voltages at their receiving end much higher than the sending end, thus creating issues such as over-
fluxing of power transformers and over stressing of line insulators. Under light-load conditions, the line
produces more VARs, resulting in receiving end voltage being higher than sending end voltage. In order
to consume the excess VARs when system is lightly loaded, an inductor is added to the system.
25 | P a g e
Controlled shunt reactors:
A controlled shunt reactor (CSR) is a variable inductance, smoothly regulated by magnetic biasing of
ferromagnetic elements of magnetic circuit. The magnetic system of a CSR single phase consists of two
cores. Each core is equipped with control and power windings. In case of regulated DC voltage source
connection to the control windings, biasing flow is increasing and directed to different sides in the
adjacent cores. This resulted in saturation of CSR cores at relevant half-period of the current. Core
saturation is resulted in initiation and increase of the current in the power winding due to non-linear
characteristics of the magnetic core. Change in biasing current value leads to the power winding current
change, due to which a stepless variation of voltage levels in CSR connection point as well as the value
Series reactors:
Series reactors are used as current limiting reactors to increase the impedance of a system. They are
also used for neutral earthing. Such reactors are also used to limit the starting currents of synchronous
electric motors and to compensate reactive power in order to improve the transmission capacity of
power lines.
9.CIRCUIT BREAKER
A circuit breaker is a switching device that interrupts the abnormal or fault current. It is a mechanical
device that disturbs the flow of high magnitude (fault) current and in additions performs the function of
a switch. The circuit breaker is mainly designed for closing or opening of an electrical circuit, thus
26 | P a g e
WORKING PRINCIPLE OF CIRCUIT BREAKER
Circuit breaker essentially consists of fixed and moving contacts. These contacts are touching each
other and carrying the current under normal conditions when the circuit is closed. When the circuit
breaker is closed, the current carrying contacts, called the electrodes, engaged each other under the
pressure of a spring.
During the normal operating condition, the arms of the circuit breaker can be opened or closed for
a switching and maintenance of the system. To open the circuit breaker, only a pressure is required
to be applied to a trigger.
Whenever a fault occurs on any part of the system, the trip coil of the breaker gets energized and
the moving contacts are getting apart from each other by some mechanism, thus opening the circuit.
Air Circuit Breaker (ACB) is an electrical device used to provide Overcurrent and short-circuit
protection for electric circuits over 800 Amps to 10K Amps. These are usually used in low voltage
applications below 450V. We can find these systems in Distribution Panels (below 450V). Here in this
27 | P a g e
An air circuit breaker is a circuit operation breaker that operates in the air as an arc extinguishing
medium, at a given atmospheric pressure. There are several types of air circuit breakers and switching
gears available in the market today that are durable, high-performing, easy to install and maintain. The
The external parts of ACB mainly include the ON & OFF button, an indicator for the position of the
main contact, an indicator for the mechanism of energy storage, LED indicators, RST button, controller,
rated nameplate, handle for energy storage, displays, shake, fault trip rest button, rocker repository, etc.
The internal parts of ACB mainly include supporting structure with steel sheet, the current transformer
used to protect the trip unit, pole group insulating box, horizontal terminals, arcing chamber, trip unit
for protection, terminal box, closing springs, CB opening & closing control, plates to move arcing and
A breaker which used vacuum as an arc extinction medium is called a vacuum circuit breaker. In this
circuit breaker, the fixed and moving contact is enclosed in a permanently sealed vacuum interrupter.
The arc is extinct as the contacts are separated in high vacuum. It is mainly used for medium voltage
It is very simple in construction as compared to any other circuit breaker. Their construction is mainly
divided into three parts, i.e., fixed contacts, moving contact and arc shield which is placed inside the
28 | P a g e
Fig No: 13 Vacuum Circuit Breaker
The outer envelope of vacuum circuit breaker is made up of glass because the glass envelope help in
the examination of the breaker from outside after the operation. If the glass becomes milky from its
original finish of silvery mirror, then it indicates that the breaker is losing vacuum.
10.CONTROL PANEL:
A control & relay panel is designed to provide to control the associated line or transformer through
outdoor switchgear at various 11KV and 33KV zonal substations. The control & Relay panels are
complete in themselves with all main and auxiliary relays, annunciation relay, fuses, links, switches,
wiring, labels, terminal blocks, earthing terminals, base frame, foundation bolts, illumination, cable
glands etc. These panels are used for the control & monitoring of electrical equipments such as
transformers, generators and circuit breakers. Indoor Control panel for Outdoor VCB includes IDMT
Numerical relay, Master Trip Relay, Trip circuit Supervision Relay, Indications & meters etc.
29 | P a g e
SINGLE CIRCUIT PANELS:
Feeder Panels: A feeder panel scheme consists of feeder circuits for either 11KV or 33KV switchgear.
These panels are available in the form of over current & Earth fault relay having two O/C and one E/F
element. Single point annunciator is provided for generating the alarm during fault condition as well as
Transformer Panels: A transformer panel scheme consists of transformer circuits for either 11KV or
33KV switchgear. These panels are available in the form of over current & Earth fault relay having two
O/C and one E/F element for 11kV and three O/C elements for 33kV rating. Single point annunciator
is provided for generating the alarm during various types of transformer fault condition as well as
One Transformer & One Feeder Panels: A multi circuit one transformer & one feeder panel is a
combination of a transformer & a feeder circuit in a single panel built for either 11KV or 33KV
Switchgear.The transformer circuit shall be same as in single circuit transformer panel. Similarly the
Two Feeder Panels: A Multicircuit two feeder panel consists of 2 feeder circuits in a single panel. These
panels are exact replica of multi circuit one transformer & one feeder panel in that there shall be
Two transformer Panels: A Two transformer control & relay panel consists of two transformer circuits
in a single panel. These panels are exact replica of multi circuit one transformer & one feeder panel in
30 | P a g e
11.POWER-LINE CARRIER COMMUNICATION
PLCC carries data on a conductor that is also used simultaneously for AC electric power transmission.
It is also known as power-line digital subscriber line (PDSL), mains communication, power-line
technologies are needed for different application). Most PLC technologies limit themselves to one type
of wires (such as premises wiring within a single building). Typically transformers prevent propagating
the signal, which requires multiple technologies to form very large networks. Various data rates and
MISA substation has a double bas bar arrangment and also one and a half breaker bus bar arrangment.
A substation bus scheme is the arrangement of overhead bus bar and associated switching equipment
(circuit breakers and isolators) in a substation. The operational flexibility and reliability of the
substation greatly depends upon the bus scheme. The first requirement of any substation design is to
avoid a total shutdown of the substation for the purpose of maintenance, or due to fault somewhere out
on the line. A total shutdown of the substation means complete shutdown of all the lines connected to
the substation
31 | P a g e
1. Single bus bar scheme:
As the name implies, the sigle bus substation configuration consists of all circuits connected to a main
bus. A fault on the bus or between the bus and circuit breaker will result in an outage of the entire bus
or substation. Failure of a single circuit breaker will also result in an outage of the entire bus
In this arrangement one or more busses is added to the single bus substation scheme. One or more circuit
breakers may be used in this arrangement to make connections between the main and transfer bus.
When no Tie CB is present, for maintenance of a circuit breaker, the transfer bus is energized by closing
the isolator switches to the transfer bus, then the circuit breaker to be maintained is opened and isolated
32 | P a g e
When a tie circuit breaker is present, circuit breaker maintenance is achieved by closing the tie breaker.
The transfer bus is energized and the isolator nearest the transfer bus of the breaker to be maintained is
closed.
This configuration utilizes two buses and two breakers per circuit, both buses are normally energized
and any circuit can be removed for maintenance without an outage on the corresponding circuit. Failure
of one of the two buses will not interrupt a circuit because all of the circuits can be fed from the
33 | P a g e
This configuration uses two main buses, both of which are normally energized with three breakers
connected between the buses. In this bus configuration, three breakers are required for every two circuits
- hence the "one and half" name. Think of it as, to control one circuit requires one full and a half breaker.
The middle breaker is shared by both circuits, similar to a ring bus scheme where each circuit is fed
PROTECTIVE RELAY:-
A protective relay is a device designed to trip a circuit breaker when a fault is detected. The first
protective relays were electromagnetic devices, relying on coils operating on moving parts to provide
detection of abnormal operating conditions such as over-current, over-voltage, reverse power flow,
The functions of electromechanical protection systems are now being replaced by microprocessor-based
digital protective relays, sometimes called "numeric relays". A microprocessor-based digital protection
relay can replace the functions of many discrete electromechanical instruments. These convert voltage
and currents to digital form and process the resulting measurements using a microprocessor.
Numerical Relays:-
The distinction between digital and numerical relay rests on points of fine technical detail, and is rarely
found in areas other than Protection. They can be viewed as natural developments of digital relays as a
result of advances in technology. Typically, they use a specialized digital signal processor (DSP) as the
34 | P a g e
7.TRANSFORMER OIL TESTING METHODS:
Units
Color-D1500-Used to observe darkening of the oil by comparing it to previous samples of oil from the
same transformer. Transformer oil colour is determined by means of transmitted light and given a
numerical value (0-5) based on comparison with a series of color standards. Noticeable darkening oil
Dielectric breakdown voltage-D877-Measures the voltage at which the oil fails electrically, which is
indicative of the amount of contaminant (usually moisture) in the oil. The dielectric breakdown voltage
is measured by applying a voltage between two electrodes under the oil. New oil should have a
Dissolved gas analysis (DGA)-D3612-Identifies various gas ppm levels that are present in transformer
insulating oil. Different gasses will dissolve in the oil that indicate various types of thermal and
electrical stress occurring within the transformer. An oil sample tube and syringe is used to draw, retain
and transport the oil sample in the same condition as it is inside a transformer with all fault gases
dissolved in it.-ppm
Flash point, fire point-D92-Indicates the volatility of insulating oil by measuring the minimum
temperature at which the heated oil gives of sufficient vapor to form a flammable mixture with air.-°C
Moisture (Water) Content-D1533-Measured in parts per million (ppm) using the weight of moisture
divided by the weight of oil. Moisture content in oil lowers the insulating system dielectric strength and
allows flashover that can damage a transformer. For mineral oil, a generally accepted maximum
moisture content is 35 ppm. This test does not measure the water content in the transformer paper i
35 | P a g e
8.SUBSTATION AUXILIARY EQUIPMENTS
It is used to keep the protection system in the energized form despite of any failure in the power system.
Lead acid batteries are mainly used in the substations and this type of batteries are also called floating
cells.There are basically two ranges of the battery system available in the substation i.e 220 volts and
48 volts. In every substation two sets of batteries are kept for more reliability and each set is connected
with the separate battery chargers. The capacity of the batteries are defined in terms of the Ampere
hour(Ah).
Firefighting is the act of extinguishing fires. A firefighter suppresses and extinguishes fires to
Extinguishing Agent
1. Passive fire protection (use of integral, fire-resistance rated wall and floor assemblies that are
used to form fire compartments intended to limit the spread of fire, or occupancy separations,
36 | P a g e
or firewalls, to keep fires, high temperatures and flue gases within the fire compartment of
2. . Active fire protection (manual and automatic detection and suppression of fires, as in using
and installing a fire sprinklersystem or finding the fire (fire alarm) and/or extinguishing it)
Education (ensuring that building owners and operators have copies and a working
understanding of the applicable building and fire codes, having a purpose-designed fire safety
plan and ensuring that building occupants, operators and emergency personnel know the
building, its means of Active fire protection and Passive fire protection, its weak spots and
A diesel generator is the combination of a diesel engine with an electric generator (often
Diesel generating sets are used in places without connection to the power grid, as
emergency power-supply if the grid fails, as well as for more complex applications such
There are two sources of LTAC power from SEB and from Auxiliary transformer
37 | P a g e
connected to tertiary of ICT, SEB power is not always reliable. Power supply through
the other source i.e. froni auxiliary transformer is more reliable but still there can be
interruption in case of Grid failure, ICT tripping, shut down of aux transformer or ICT
Batteries will be getting discharged. If batteries get drained, protection and control
circuit, PLCC may be rendered out of service. At night switchyard and control room
38 | P a g e
8.GIS INTRODUCTION:
A Gas-insulated substation is a station in which no live part is exposed to human touch or environmental
atmosphere, except from point of interfacing with overhead or environmental atmosphere, except from
All bus bars and other live parts of the system are enclosed in gas space enclosed in a metal enclosure.
A gas-insulated substation (GIS) uses a superior dielectric gas, SF6, at moderate pressure for
phase-to phase and phase-to-ground insulation. The high voltage conductors, circuit breaker
interrupters, switches, current transformers, and voltage transformers are in SF6 gas inside grounded
metal enclosures.
The atmospheric air insulation used in a conventional, air-insulated substation (AIS) requires meters
GIS can therefore be smaller than AIS by up to a factor of 10. A GIS is mostly used where space is
expensive or not available. In a GIS the active parts are protected from the deterioration from
39 | P a g e
SLD of GIS at Misa Substation:
40 | P a g e
Properties of SF6:
• It is colourless.
41 | P a g e
Critical Pressure 3.78 Mpa
Sound Velocity in SF6 136 m/s. It is 3 times less than that in air
Testing of SF6:
v Dew point – moisture content should be less. Ppm should be less than 350
42 | P a g e
v Purity – percentage of SF6 in the gas should be more than 98%. Kits are available to check the
purity
2. GIS technology enables us to divide the area of a HV switchyard by a magnitude ranging from
10 to 25.
3. Dimensional comparison at 400KV of an AIS main busbar crossing, and a GIS busbar crossing
is shown in fig(ii)
AIS Vs.
GIS:
Fig - i Fig - ii
43 | P a g e
44 | P a g e
GIS MODULES:
1. Busbar
2. Disconnector
4. Current Transformer
5. Circuit Breaker
6. Current Transformer
8. Disconnector
45 | P a g e
9. Earthing Switch
11. Bushing
12.
GIS MODULES:
§ Loose electrical and mechanical contact between conducting parts, including electrostatic
§ Fixed defects such as metallic protrusions and particles attached to solid insulator (spacer)
surfaces.
§ Contaminants which affect the quality of the SF6 gas (by-products, moisture content, erroneous
gas filling).
46 | P a g e
Partitioning of GIS:
§ As we know GIS comes in Modular manner and these Modules are connected with each other.
GIS is broadly partitioned at the joint of these modules and some time in between also.
§ During repair and Maintenance taking out of affected module mainly depends on these
partitioning further service continuities during repair and maintenance is also very much
§ Both Mechanical and Electrical segregation of GIS Module are of great importance to handle
§ - Filling valve – for filling of SF6 for each individual separated gas zone.
§ - SF6 density switch – for continuous measuring of SF6 density and provide alarm when the
density is low.
§ - Bursting disk or PRD – Burting at 11 bar. Nominal pressure of SF6 in GIS is 6.3 bar but
pressure of the gas increase when fault occurs as the temperature increases. PV=nRT. P
47 | P a g e
Advantages of GIS:
1. The earthed metal enclosure makes for a safe working environment for the attending personnel
2. Compartmentalized enclosure of the live parts makes for a very reliable system due to reduced
3. By reducing the distance between active and non-active switchgear parts, less space is required
than in the normal AIS system: this comes in handy in densely populated areas and
unfavourable terrain (minimum requirements for an AIS is about 47,000m2, while GIS with
the same power properties will require approx. 523m2). For the AIS, the highest element is
approximately 28m, whereas for GIS you have 11m at the highest point for a 400kV substation.
4. Low maintenance requirements due to expedient design and protection against external
elements.
5. Under scheduled maintenance, SF6 neither ages nor depletes. There is no need to top up the
Disadvantages:
2. Procurement and supply of SF6 gas can be a problem especially in rough terrain and off site
4. Internal faults tend to be very costly and severe when they occur. They often lead to long outage
periods. For example, the use of impure gas, as well as leakage due to ‘O’ ring failure, as well as
48 | P a g e
49 | P a g e
CONCLUSION
We have categorized the different parts of a substation and hence, studied their role, operation and
maintenance. We have also seen the various ways of protecting the costly and important devices used
in the transmission of high voltages(400kV/220kV/33kV). The 220kV uses double main cum transfer
busbar arrangement where as the 400kV uses one and a half bus bar scheme. A redundant set is always
kept to keep a continuous supply of power in case the primary set fails.
50 | P a g e
51 | P a g e