Operating Manual
Operating Manual
The software and hardware described in this document is furnished under a license
and may be used or disclosed only in accordance with the terms of such license.
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Please inquire about the terms of warranty from your nearest ABB representative.
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Warnings..........................................................................................15
Operator overview............................................................................17
Identify the IED.................................................................................17
Overview...........................................................................................21
Keypad.............................................................................................22
Key activated screens......................................................................23
The Help screen..........................................................................23
The Reset screen........................................................................24
LCD..................................................................................................24
Small............................................................................................24
Medium........................................................................................24
LED...................................................................................................25
Introduction..................................................................................25
Status indication LEDs................................................................25
Indication LEDs...........................................................................25
Local HMI setup ...............................................................................26
How to navigate................................................................................26
Read............................................................................................26
Change .......................................................................................26
Control.........................................................................................27
Overview...........................................................................................29
Menu-tree for RET670.................................................................29
Overview...........................................................................................31
1
Operator's manual
Table of contents
View events......................................................................................37
Overview......................................................................................37
Identify a disturbance.......................................................................39
View disturbance record details........................................................39
View general information.............................................................39
View disturbance indications.......................................................39
View event recordings.................................................................39
View trip values...........................................................................40
Trigger a disturbance report manually..............................................40
2
Operator's manual
Table of contents
General settings...............................................................................43
Power system..............................................................................43
Overview................................................................................43
Identifiers................................................................................43
Primary values........................................................................43
Communication............................................................................43
Overview................................................................................43
Remote communication..........................................................43
SPA, LON and IEC 60870–5–103 settings.............................44
Station communication...........................................................45
Ethernet configuration............................................................46
Analog and I/O modules..............................................................47
Overview................................................................................47
Analog modules......................................................................47
I/O modules............................................................................48
HMI..............................................................................................48
Overview................................................................................48
LEDs.......................................................................................48
Screen ...................................................................................48
Functions................................................................................49
Change lock ..........................................................................49
Differential protection...................................................................49
Overview................................................................................49
Transformer differential protection, two winding
T2WPDIF................................................................................49
Transformer differential protection, three winding
T3WPDIF................................................................................49
Control.........................................................................................50
Apparatus control...................................................................50
Control commands.................................................................51
Synchrocheck and energizing check SESRSYN ...................52
Monitoring....................................................................................52
Overview................................................................................52
Service values CVMMXN.......................................................52
Current phasors CMMXU.......................................................53
Voltage phasors VMMXU/VNMMXU......................................53
Current sequence components CMSQI ................................53
Voltage sequence components VMSQI ................................53
Disturbance report DRPRDRE...............................................54
Generic measured value MVGGIO........................................54
Event function ........................................................................54
Logical signal status report BINSTATREP.............................55
IEC 60870–5–103 ..................................................................55
Metering.......................................................................................55
3
Operator's manual
Table of contents
Overview................................................................................55
Pulse counter logic PCGGIO..................................................55
Function for energy calculation and demand handling
ETPMMTR .............................................................................55
Setting group N.................................................................................56
Overview......................................................................................56
Differential protection...................................................................56
Overview................................................................................56
Transformer differential protection, two winding
T2WPDIF ...............................................................................56
Transformer differential protection, three winding
T3WPDIF ...............................................................................56
Restricted earth fault protection REFPDIF ............................56
High impedance differential protection HZPDIF ....................57
Impedance protection..................................................................57
Overview................................................................................57
Full-scheme distance protection, mho characteristic
ZMHPDIS ..............................................................................57
Distance protection zones, quadrilateral characteristics
ZMQPDIS, ZMQAPDIS..........................................................57
Distance protection zones, quadrilateral characteristics
for series compensated lines ZMCPDIS, ZMCAPDIS............58
Distance protection zone, quadrilateral characteristic,
separate settings ZMRPDIS, ZMRAPDIS..............................58
Fullscheme distance protection, quadrilateral for earth
faults ZMMPDIS, ZMMAPDIS ...............................................58
Faulty phase identification with load enchroachment
FMPSPDIS ............................................................................58
Phase selection, quadrilateral characteristic with fixed
angle FDPSPDIS....................................................................59
Phase selection, quadrilateral characteristic with
settable angle FRPSPDIS......................................................59
Phase preference logic PPLPHIZ ..........................................59
Directional impedance quadrilateral ZDRDIR .......................59
Directional impedance element for mho characteristics
ZDMRDIR ..............................................................................59
Directional impedance quadrilateral, including series
compensation ZDSRDIR .......................................................59
Additional distance protection directional function for
earth faults ZDARDIR ............................................................60
Mho impedance supervision logic ZSMGAPC.......................60
Pole slip protection PSPPPAM ..............................................60
Power swing detection ZMRPSB ..........................................60
Power swing logic ZMRPSL ..................................................60
Current protection........................................................................60
4
Operator's manual
Table of contents
Overview................................................................................60
Breaker failure protection CCRBRF ......................................61
Broken conductor check BRCPTOC .....................................61
Capacitor bank protection CBPGAPC....................................61
Directional over-power protection GOPPDOP ......................61
Directional under-power protection GUPPDUP .....................61
Instantaneous phase overcurrent protection PHPIOC ..........61
Instantaneous residual overcurrent protection EFPIOC ........62
Negativ sequence time overcurrent protection for
machines NS2PTOC..............................................................62
Four step directional negative phase sequence
overcurrent protection NS4PTOC..........................................62
Four step phase overcurrent protection OC4PTOC ..............62
Pole discordance protection CCRPLD...................................62
Four step residual overcurrent protection EF4PTOC ............62
Sensitive directional residual over current and power
protection SDEPSDE ............................................................63
Thermal overload protection, one time constant LPTTR .......63
Thermal overload protection, two time constants
TRPTTR ................................................................................63
Voltage protection........................................................................63
Overview................................................................................63
Loss of voltage check LOVPTUV ..........................................63
Overexcitation protection OEXPVPH ....................................64
Two step overvoltage protection OV2PTOV .........................64
Two step residual overvoltage protection ROV2PTOV .........64
Two step undervoltage protection UV2PTUV ........................64
Voltage differential protection VDCPTOV .............................64
Frequency protection...................................................................64
Overview................................................................................64
Overfrequency protection SAPTOF .......................................65
Rate-of-change frequency protection SAPFRC ....................65
Underfrequency protection SAPTUF .....................................65
Multipurpose protection...............................................................65
Overview................................................................................65
General current and voltage protection CVGAPC..................65
Scheme communication..............................................................66
Overview................................................................................66
Current reversal and weak-end infeed logic for residual
overcurrent protection ECRWPSCH .....................................66
Scheme communication logic for residual overcurrent
protection ECPSCH ...............................................................66
Secondary system supervision....................................................66
Overview................................................................................66
5
Operator's manual
Table of contents
Overview...........................................................................................73
IED test mode...................................................................................74
View binary input values...................................................................74
Overview......................................................................................74
Binary Input Module BIM........................................................74
Signal matrix for binary input SMBI........................................75
View binary output values.................................................................75
Overview......................................................................................75
Binary Output Module BOM...................................................75
Signal matrix for binary outputs SMBO..................................75
Function test modes.........................................................................75
Overview......................................................................................75
6
Operator's manual
Table of contents
7
Operator's manual
Table of contents
8
Operator's manual
Table of contents
Overview...........................................................................................99
Read measured values and check apparatus status...................99
Locating and using the single line diagram.................................99
9
Operator's manual
Table of contents
Overview.........................................................................................107
Principle of operation......................................................................107
LogOn or logOff..............................................................................109
Authorization handling in the IED...................................................109
Internet Protocol ports security guideline.......................................110
10
Operator's manual
1MRK 504 114-UEN D Section 1
Introduction
This chapter is an introduction to the operator’s manual, its purpose and usage.
Decommissioning
Commissioning
Maintenance
Engineering
Operation
Installing
Engineering manual
Installation and
Commissioning manual
Operator’s manual
Application manual
Technical reference
manual
IEC09000744-1-en.vsd
IEC09000744 V1 EN
11
Operator's manual
Section 1 1MRK 504 114-UEN D
Introduction
The Engineering Manual (EM) contains instructions on how to engineer the IEDs
using the different tools in PCM600. The manual provides instructions on how to
set up a PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and DNP3.
Use the operator’s manual for instruction on how to perform common tasks during
normal service.
• The chapter “Safety information” presents warnings and notices, which the
user should pay attention to.
• The chapter “Overview” describes operations an operator may perform on a
daily basis or when the need arises.
• The chapter “Understand the local human-machine interface” describes how
to use the human-machine interface.
• The chapter “Understand the HMI tree” describes the different menu trees.
• The chapter “Read measured values” describes how to locate and identify
available measurement data.
• The chapter “Event list” describes the location and nature of recorded events.
• The chapter “Handle disturbances” describes how to retrieve disturbance
information and reset alarms.
• The chapter “Read and change settings” describes how to locate, and change
settings and parameters.
• The chapter “Diagnose IED status” describes the location and use of available
diagnostic tools.
• The chapter “Test the IED” describes the tests applicable to the IED.
• The chapter “Control and supervise the bay” describes how to use the Single
Line Diagram to open and close primary apparatuses.
12
Operator's manual
1MRK 504 114-UEN D Section 1
Introduction
This manual does not contain any instructions for commissioning or testing.
The operator’s manual addresses the operator, who operates the IED on a daily basis.
The operator must be trained in and have a basic knowledge of how to operate
protection equipment. The manual contains terms and expressions commonly used
to describe this kind of equipment.
13
Operator's manual
Section 1 1MRK 504 114-UEN D
Introduction
14
Operator's manual
1MRK 504 114-UEN D Section 2
Safety information
This chapter lists warnings and cautions that must be followed when handling the
IED.
15
Operator's manual
16
1MRK 504 114-UEN D Section 3
Overview
The operator can document disturbances so that their causes can be analyzed and
evaluated for future reference. For example, the fault currents and voltages at the
time of the fault can be documented. The operator can also retrieve data about
protected objects, providing further information for fault analysis. This implies
viewing the mean value of current, voltage, power and frequency or primary and
secondary measured phasors. The operator can check the IED status at any time.
In some cases the operator may need to change the way the IED operates. This
might include changing the active setting group or a parameter value. This must
always be done strictly according to applicable regulations because un-authorized
changes may lead to severe damage of the protected object especially if a fault is
not properly disconnected.
To identify the IED, open the diagnostics menu. The identity of the IED along with
other data is found under:
17
Operator's manual
Section 3 1MRK 504 114-UEN D
Overview
IEC10000336-1-en.vsd
IED10000336 V1 EN
Both IEDProdType and ProductDef are visible in the PCM600 tool, under Properties:
18
Operator's manual
1MRK 504 114-UEN D Section 3
Overview
IEC10000337-1-en.vsd
IEC10000337 V1 EN
SerialNo
OrderingNo Are production identifiers
ProductionDate
19
Operator's manual
20
1MRK 504 114-UEN D Section 4
Understand the IED local human-machine interface
This chapter describes the display, its keys (buttons) and LEDs that make up the
local HMI on the IED. How the keys are used to navigate the HMI, how to
interpret the graphic information on the LCD and, what the LEDs indicate is
explained in the sections that follow.
The human machine interface is used to monitor and to some extent control the
way the IED operates. The configuration designer can add functions that alert to
events requiring the attention of the operator.
IEC08000098 V1 EN
21
Operator's manual
Section 4 1MRK 504 114-UEN D
Understand the IED local human-machine interface
IEC08000084 V1 EN
The keypad is used to monitor and operate the IED. The keypad has the same look
and feel in all IEDs. LCD screens and other details may differ but the way the keys
function is identical.
IEC05000153 V1 EN
Table 1 describes the HMI keys that are used to operate the IED.
22
Operator's manual
1MRK 504 114-UEN D Section 4
Understand the IED local human-machine interface
Press to open two sub menus: Key operation and IED information.
IEC05000103 V1 EN
Press to open the main menu and to move to the default screen.
IEC05000105 V1 EN
Press to start the editing mode and confirm setting changes, when in editing mode.
IEC05000108 V1 EN
Press to navigate forward between screens and move right in editing mode.
IEC05000109 V1 EN
Press to navigate backwards between screens and move left in editing mode.
IEC05000110 V1 EN
Press to move up in the single line diagram and in the menu tree.
IEC05000111 V1 EN
Press to move down in the single line diagram and in the menu tree.
IEC05000112 V1 EN
The help screen is activated by pressing the Help key on the front panel of the IED.
It includes the submenu listed below:
• General operation
The General Operation submenu provides information about the IED keypad.
23
Operator's manual
Section 4 1MRK 504 114-UEN D
Understand the IED local human-machine interface
The I and O keys are used to open (OFF) and close (ON) breakers and
disconnectors when using the Single Line Diagram (SLD) in direct control situations.
The reset screen is activated by the Reset key on the front panel of the IED or via
the main menu. The reset screen includes the submenus listed below:
• Reset LEDs
• Reset lockout
• Reset counters
• Reset temperature functions
The Reset LEDs submenu consists of two lower level menus which are the “Start
and trip LEDs” and “All indication LEDs” submenus. To reset a counter, the actual
counter must first be selected. The submenus and their structures are discussed in
the “Reset” chapter of this document.
The small sized HMI is available for 1/2, 3/4 and 1/1 x 19” case. The LCD on the
small HMI measures 32 x 90 mm and displays 7 lines with up to 40 characters per
line. The first line displays the product name and the last line displays date and
time. The remaining 5 lines are dynamic. This LCD has no graphic display potential.
The following case sizes can be equipped with the medium size LCD:
• 1/2 x 19”
• 3/4 x 19”
• 1/1 x 19”
This is a fully graphical monochrome LCD which measures 120 x 90 mm. It has 28
lines with up to 40 characters per line. To display the single line diagram, this LCD
is required.
24
Operator's manual
1MRK 504 114-UEN D Section 4
Understand the IED local human-machine interface
The three LEDs above the LCD provide information as shown in the table below.
Green:
Steady In service
Flashing Internal failure
Dark No power supply
Yellow:
Steady Dist. rep. triggered
Flashing Terminal in test mode
Red:
Steady Trip command issued
The LED indication module comprising 15 LEDs is standard in 670 series. Its main
purpose is to present an immediate visual information for protection indications or
alarm signals.
Alarm indication LEDs and hardware associated LEDs are located on the right
hand side of the front panel. Alarm LEDs are located on the right of the LCD
screen and show steady or flashing light.
Alarm LEDs can be configured in PCM600 and depend on the binary logic.
Therefore they can not be configured on the local HMI.
• Position error
• CB spring charge alarm
• Oil temperature alarm
• Thermal overload trip
• Bucholtz trip
The RJ45 port has a yellow LED indicating that communication has been
established between the IED and a computer.
The Local/Remote key on the front panel has two LEDs indicating whether local or
remote control of the IED is active.
The contrast and other settings of the LCD can be adjusted from the local HMI
menu tree. The contrast and other factory settings for the local HMI can be
adjusted as follows:
Settings/General settings/HMI/Screen
To read values and access information about the objects being monitored the
operator must navigate the menu tree using the arrow keys. The active submenu or
value is highlighted.
Navigation is as follows:
26
Operator's manual
1MRK 504 114-UEN D Section 4
Understand the IED local human-machine interface
The HMI offers the operator the opportunity to exercise direct local control over
breakers and other apparatuses in the bay using the graphic display and designated
keys on the front panel of the IED.
By pressing the L/R key until the uppermost of the two LEDs next to the key lights
up, local operator control can be exercised from the HMI.
An apparatus is selected using the up and down arrow keys. The active apparatus is
highlighted in the display.
27
Operator's manual
28
1MRK 504 114-UEN D Section 5
Understand the HMI tree
This chapter describes the structure of the HMI. The main menu includes
submenus such as Measurements, Events, Disturbance Report, Settings,
Diagnostics, Test and Reset. These branch out into a typical tree structure.
• Control
• Measurements
• Events
• Disturbance records
• Settings
• Diagnostics
• Test
• Reset
• Authorization
• Language
29
Operator's manual
Section 5 1MRK 504 114-UEN D
Understand the HMI tree
30
Operator's manual
1MRK 504 114-UEN D Section 6
Read measured values
This chapter describes measurement categories and how to locate them using the
HMI. Each measurement category has a section of its own that includes a general
description of the type of quantity being measured and the path in the local HMI to
the measurement.
1. Analog primary values are the quantities measured on the primary side of the
current and voltage transformers (CTs and VTs).
2. Analog secondary values are the quantities measured on the secondary side of
the current and voltage transformers. These are the quantities measured on the
Transformer module (TRM) inputs.
3. Analog mean values are the quantities measured at the inputs of the
milliampere module (MIM).
4. Under Monitoring a number of submenus are available. These include Service
values, Current phasors, Voltage phasors, Current sequence components and
Voltage sequence components.
5. Metering displays the pulse counter and energy calculation and demand
handling functions. The measurements available for pulse counter show pulse
counter status data.
31
Operator's manual
Section 6 1MRK 504 114-UEN D
Read measured values
The analog primary values are analog quantities measured on the primary side of
the TRM and reflect the actual current or voltage on the primary side of the VTs
and CTs. The ratio is adjusted under settings and also depends on the rating of the
TRM. 24 primary values and phase angles are displayed in this view.
Analog secondary values shows secondary CT currents and VT voltages. These are
the actual current and voltage values at the TRM inputs.
For analog values received from Merging Units, no analog secondary values are
shown.
32
Operator's manual
1MRK 504 114-UEN D Section 6
Read measured values
Measurements from the Milliampere Input Module (MIM) are found in this part of
the measurements menu. Data from either the hard wired mA module or Signal
Matrix Tool mA modules are shown here.
Main menu/Measurement/Monitoring/ServiceValues(MMXN)/CVMMXN:x
Displays up to three instances of CVMMXN with measured values for S, P, Q, PF,
U, I, ILead, ILag and F.
Main menu/Measurement/Monitoring/CurrentPhasors(MMXU)/CMMXU:x
All three phase currents and their phase angles are displayed here.
33
Operator's manual
Section 6 1MRK 504 114-UEN D
Read measured values
Main menu/Measurements/Monitoring/VoltagePhasors(MMXU)/Phase -
Phase/VMMXU:x
Phase to phase voltages and phase angles are displayed here.
Main menu/Measurements/Monitoring/CurrentSequenceComponents(MSQI)/
CMSQI:x
The current sequence component under monitoring displays the positive (I1),
negative (I2) and zero sequence (I0) current values for a three phase line, both
magnitude and phase angle for each component are displayed. These indicate how
well balanced a system is. In an ideal balanced system the zero sequence current
should be zero, the positive sequence current should be equal to the current of each
phase with the same phase angle (relative to GPS) as the L1 phase signal and the
negative sequence current should be zero.
Main menu/Measurements/Monitoring/VoltageSequenceComponents(MSQI)/
VMSQI:x
The Voltage sequence component displays the positive (U1), negative (U2) and
zero (U0) sequence components in the system, and includes the magnitude and
phase angle of each component.
Main menu/Measurements/Metering/PulseCounter(PCGGIO)/PCGGIO:x
The output data generated from the pulse counter function include data about the
status of the counter and counter values.
34
Operator's manual
1MRK 504 114-UEN D Section 6
Read measured values
Main menu/Measurements/Metering/ThreePhEnergMeas(MMTR)/
ETPMMTR:x
The output data generated from the energy measuring function includes active
forward/reverse energy and reactive forward/reverse energy.
35
Operator's manual
36
1MRK 504 114-UEN D Section 7
Event list
This chapter describes how to find and read the event list.
Events displays recorded events such as trips and breaker opened or closed.
Main menu/Events
Displays a list of events in chronological order and where each event has a time
stamp. The latest event is at the top of the list.
37
Operator's manual
38
1MRK 504 114-UEN D Section 8
Handle disturbances
This chapter describes disturbance detection and handling. This includes resetting
LED alarms, triggering disturbance reports and the viewing of several fault indicators.
The Indications section of a disturbance record displays the recording number and,
the time and date of the disturbance. The path in the HMI is shown below.
The Event recording section in the Disturbance report shows the recording number.
The path in the HMI is shown below.
39
Operator's manual
Section 8 1MRK 504 114-UEN D
Handle disturbances
In the Trip values section of a disturbance recording both the pre-fault and the fault
values for current, voltage and phase angle can be viewed. The recording number
and Trig time are also displayed. The path in the HMI is shown below.
Using the manual trigger generates an instant disturbance report. Use this function
to get a snapshot of the monitored line. Follow the path below and answer yes in
the Execute manual trig dialog box.
40
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
This chapter describes how to find and change settings and parameters. The chapter
is divided into two sections which match the way the two categories of settings are
divided up in the HMI. The General settings group consists of those parameters
that cause an automatic restart of the IED. The Setting group N consists of six
groups of settings with default values for all parameters. These do not require or
cause a restart once they have been changed. Time, synchronization and the
activation of setting groups are also dealt with here.
It takes a minimum of three minutes for the IED to save the new
settings, during this time the DC supply must not be turned off.
The synchronization settings are divided into categories Time synch, Time synch
BIN, Time synch SNTP, Time synch DST Begin, Time synch DST End, Time
synch time zone and Time synch IRIG-B. The settable parameters are found under
each category.
Main menu/Settings/Time/Synchronization/TIMESYNCHGEN:x/General
41
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
Main menu/Settings/Time/Synchronization/TIMESYNCHGEN:x/
IEC61850-9-2
Main menu/Settings/Time/Synchronization/SYNCHBIN:x
Binary input synchronization settings available here are the position of the of the
module, the number of the binary input and the detection mode.
Main menu/Settings/Time/Synchronization/DSTBEGIN:x
The starting point for Daylight Savings Time is set here.
Main menu/Setttings/Time/Synchronization/DSTEND:x
The end point of Daylight Savings Time is set here.
Main menu/Settings/Time/Synchronization/SYNCHIRIG-B:x
The type of input, time domain, type of encoding and time zone for IRIG-B are set
here.
Main menu/Settings/Time/Synchronization/SYNCHSNTP:x
Here the IP addresses for the Simple Network Time Protocol servers are set.
Main menu/Settings/Time/Synchronization/TIMEZONE:x
The time zone according to Coordinated Universal Time (UTC) is set here.
42
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
Parameters under General settings that are changed will cause the IED to restart.
This occurs automatically and requires no manual intervention.
Under Power system in General settings there are four parameter categories. These
are Identifiers, Primary values, three phase analog group and three phase analog
sum group.
The parameter settings for communications are found under General Settings
\Communications. Communication settings cover network interfaces, protocol,
remote communication and reception of interlocking information.
43
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
Displays settings for Remote Binary Communication (CRB) and for Remote Multi
Communication (CRM). The multi communication block can send both binary and
analog data whereas the binary can only send binary data.
Each instance of CRB has several settable parameters where the channel mode can
be set on or off, terminal numbers can be entered, synchronization can be set to
master or slave and opto power can be set high or low.
Each instance of CRM has several settable parameters. These include those above
and others such as transmission delay and transmission current.
The menu for the rear optical LON port has five submenus for various settings
affecting LON parameters. The HMI paths to these submenus and their contents
are described below.
44
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
45
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
46
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
Under Analog modules in the General settings menu there are settings for Analog
inputs and I/O modules. Within each instance of analog input there are settings for
all 12 channels that include the name of the channel, star point of the CT circuit,
the primary and secondary values from the measuring transformers (CTs and VTs).
The channel type and ratings are shown but cannot be changed.
The settings for binary inputs and outputs even include the milliampere input
modules. A mix of up to 14 instances of BIM, BOM and IOM is possible
depending on the physical configuration of the IED. Operation ON or OFF can be
set for all of these and for the BIMs oscillation release and oscillation block
settings are available. These settings are on board level and apply to all binary
inputs or outputs on a board.
47
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
Here is where the settings for the summation block are done. The summation type,
Fourier filter reference frequency, minimum voltage for frequency measurement
and the system voltage are some of the parameters that can be set here.
The milliampere modules (MIMs) are also found in the I/O Modules folder.
Parameters possible to set here are dead band settings and various current threshold
values.
Under HMI in General settings there are submenus for LEDs, Screen, Functions,
Reference channel service values and the Change lock function. In the LED
submenu there are settings for operation, illumination times, and sequence types
for the LEDs on the IED front panel. In the Screen submenu Contrast level, Default
screen, Auto repeat and Timeout display can be set. In the Functions submenu the
Event list sorting order and Distance presentation can be set.
Settings/General settings/HMI/LEDs
Parameters such as Operation, tRstart, tMax and 15 instances of SeqTypeLED can
be set here. The SeqTypeLED offers several options for the type of illumination
sequence the LEDs should follow.
48
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
Local HMI setting parameters such as Language, Contrast level and Default menu
can be set here.
49
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
50
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
51
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
Under monitoring there are parameters for setting Service values, current phasors,
Voltage phasors, Disturbance reports and the Measured value expander block.
52
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
There are sets of settings with some categories of parameter settings per set
instance of CMSQI.
53
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
voltage is 3U0, for positive sequence voltage is U1 and for negative sequence
voltage is U2.
There are sets of settings with some categories of parameter settings per set
instance of VMSQI
54
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
Under metering there are settings for the Pulse counter function. There are some
instances of the Pulse counter function. Each instance can be switched on or off
and a number of parameters can be adjusted.
55
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
There are some default setting groups. Under general settings, parameters in these
groups can be changed to suit the needs of an application. The default settings have
been chosen according to established practice in the industry but will usually
require a certain amount of adjustment to suit the requirements of individual
applications.
The settings available for differential protection in Setting group N are not the
same as those under General settings. The main difference is that settings in the
Setting group N category can be changed on the fly without the IED requiring a
restart. A dialog box appears when attempting to make changes to setting group N.
Choose OK to proceed, or cancel to abort.
56
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
Displays available instances of REFPDIF with some settings per instance. These
are for the Current transformer ratios, operation, rated current Ibaseoperate angle
of the zero sequence directional feature and Idmin which is a percentage of Ibase
and is the current threshold in section one of the characteristic slope.
Under Impedance protection there are settings for Distance zones, Phase selection,
directional impedance, Power swing detection, and Automatic switch onto fault
protection. Each instance of a function can be switched on or off with the operation
parameter and the remaining parameter settings like rated current and voltage are
data required for the function to operate.
57
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
58
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
59
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
Under Current protection there are settings for Instantaneous phase overcurrent,
Phase overcurrent four step, Instantaneous residual overcurrent, Residual
overcurrent four step, Thermal overload with one time constant, Thermal overload
with two time constants, Pole discordance and Breaker failure. There are several
instances of each function with parameter settings for rated data, operation and
60
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
many others. The thermal overload functions have temperature threshold settings
as well as many others necessary for adapting the function to a particular application.
61
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
62
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
Displays some instances of EF4PTOC with a large number of settings per instance.
Typical settings are those for harmonic restraint, minimum fundamental frequency
current level, base settings for current and voltage and several others.
For Voltage protection there are settings for Under-voltage, Over-voltage, Residual
over-voltage and Overexcitation protection. There are three instances of parameters
in each category except in the case of Overexcitation which has two instances.
Each instance consists of a number of parameters that make it possible to switch
the function On or Off, set rated quantities or make other adjustments necessary for
the fine tuning of the function itself.
63
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
64
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
Under Multipurpose protection there are several instances of General current and
voltage parameters. This function has current and voltage inputs. The parameters
available are based on the data from these inputs. Within each instance operation
for the included functions can be set to On or Off and a large number of parameters
can be set.
65
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
Under Scheme communication there are settings for Zone scheme communication,
Zone current reversal, Local acceleration logic, EF Scheme communication and EF
Current reversal weak end infeed. In each category the function can be switched
On or Off and time delays, ratings and parameters can be set.
Under Secondary circuit supervision there are settings for Current circuit
supervision and Fuse failure. There are five instances of Current circuit supervision
with parameters for minimum operation current, rated current and operation. There
are six instances of Fuse failure supervision parameters for setting rated current,
voltage, operation mode and several other parameters.
66
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
Under Control in the Setting group N menu settings for Synchrocheck, are
available. Some instances of settings are available meaning that the settings for all
available apparatuses can be made here. The synchrocheck settings include the
selection of voltage from busses or lines and the configuration parameters for
circuit breakers.
67
Operator's manual
Section 9 1MRK 504 114-UEN D
Read and change settings
Parameters for current and voltage levels, deadbands, timers and alarm levels are
found here.
Event counter settings are found under Monitoring in the Setting Group N menu.
Under Logic there are settings for Trip logic, Trip matrix, Logic gate, Logic SR
memory and Logic timer set. Under each of these function categories there are a
number of instances, each with a parameter set.
68
Operator's manual
1MRK 504 114-UEN D Section 9
Read and change settings
Under the language part of the main menu the language options available in the
HMI are located. These vary depending on the configuration ordered.
69
Operator's manual
70
1MRK 504 114-UEN D Section 10
Diagnose IED status
This chapter describes where in the HMI tree to find the cause of an internal IED
failure and information about the IED as such.
Under general in IED status the functional readiness and status of cards and
applications can be viewed.
To identify the type of IED you are confronted with, navigate to identifiers using
the keypad. The path to identity parameters is shown below.
By following the menu path below the configuration of all hardware in the IED is
displayed as a list.
By following the menu path below the status signals of the merging units are listed.
71
Operator's manual
Section 10 1MRK 504 114-UEN D
Diagnose IED status
72
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
This chapter describes the tests that can be performed in the test section of the HMI.
The test part of the tree view in the HMI has a number of submenus for test and
viewing activities. When the IED Testmode is set to On, the functions are
deactivated and no signals are transmitted during testing. Under Function test
modes individual functions can be activated. The LED test is also activated here.
The submenus for binary inputs and outputs as well as the submenu titled Function
status are used to view data generated by the system. These categories of data are
outlined below.
1. Binary output values has two submenus. These are Binary output modules
(BOM) and SMT binary outputs. Under these the status of binary outputs and
SMT outputs is displayed.
2. Binary input values has two submenus. These are Binary input modules (BIM)
and SMT binary inputs. These screens show the state of all the inputs on the
Binary input modules (BIM). These are represented as digits but may also be a
number if the input is being used to receive pulses for power measurement.
3. Differential Protection displays a choice of differential functions available to
the operator. Function related measurements can be viewed by navigating to
the screen for each individual function.
4. Distance protection displays a choice of functions available to the operator.
Function related measurements can be viewed by navigating to the screen for
each individual function.
5. Current protection displays a choice of functions. To view data related to these
functions it is necessary to choose one from the list and navigate to the screen
for the function in question.
6. Voltage protection displays a choice of functions available to the operator.
Function related measurements can be viewed by navigating to the screen for
each of the four functions available. Data shown here is mainly trip and start
related.
7. Frequency protection includes measurements from frequency functions.
Measurements show trip, start and similar data.
8. Multipurpose protection includes measurements showing data regarding trip
signals, start signals, current and voltage values.
9. Secondary system supervision displays a choice of functions, Current circuit
supervision and Fuse failure. Current circuit measurements include fail and
alarm signals, and fuse failure measurements consist of start data.
73
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
10. Control displays the Synchrocheck, and Apparatus control functions. The
Synchrocheck functions include a number of function related measurements
such as calculated differences. Apparatus control includes up to 19 functions
each with their own set of measurement data regarding interlocking, breaker
and isolator conditions.
11. Scheme communication includes functions that display trip and other signals
used when interzone communication is deployed.
12. Logic displays a choice of functions available to the operator. These are Trip
logic, Event counter, Logic gate, Logic memory and Logic timer set each with
their own set of measurements.
13. Monitoring displays a choice of functions available to the operator. Function
related measurements can be viewed by navigating to the screen for each
individual function. One of the submenus shows the status of the LEDs on the
HMI.
14. Communication displays submenus for Remote communication and Station
communication including Receiving interlock information.
Binary input values display the state of each individual input in the Binary input
modules (BIM). These are indicated with a 1 or 0 depending on whether a signal is
present or not. Binary input modules with enhanced pulse counting capabilities can
receive pulses used for power measurement. The number of pulses received is used
to measure power.
74
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
Displays available binary input modules with several binary values per module.
Binary output values show the status of each individual output in the Binary output
module (BOM). If the signal matrix tool is used binary outputs are depicted as
virtual outputs. Note, that only modules installed in the IED are shown in the HMI.
With the IED, in test mode the different protections (except line differential
protection) can be individually released for test here. Events can be disabled or
enabled.
75
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
76
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
In the Function status section of the Test menu, data useful to the user in Test mode
can be found. The information available here is not limited to test applications
alone and provides information about the system as a whole.
The quantities and measurements for differential protections are accessed via the
HMI paths provided below. The measurement outputs shown here include various
trip and start signals. The magnitude of the differential currents are shown here.
77
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
78
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
Displays instances of ZMQPDIS for zone 1. The output quantities shown here
indicate trip and start signal status.
79
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
80
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
81
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
Viewable data under Current protection consists mainly of trip status data under the
various categories of current protection which include overcurrent protection,
thermal overload, pole discordance and variations of these.
82
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
83
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
The viewable data available under voltage protection are mainly trip related and
comprise data regarding undervoltage, overvoltage, residual overvoltage and
overexcitation.
84
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
85
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
The data generated by the multipurpose function comprises various trip and start
signals, block of second harmonic detection, various measured current values and
the angle between current and voltage.
86
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
Values for Current circuit supervision and Fuse failure supervision are found under
Secondary circuit supervision. Fail and alarm detection information is available
together with various start and current data.
There are large amounts of output data from the control functions. The main
categories of data are found under Synchrocheck, and Apparatus control.
Apparatus control has by far the largest amount of data since this includes all the
interlocking information for several different breaker arrangements.
87
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
Displays available instances of the function with an open and a close parameter for
each disconnection device. The enable open (EN_OPEN) parameter will have the
output value one if an open operation is allowed and a zero output if an open
operation is not allowed. The conditions for an open operation are if the device is
closed, intermediate or in a bad state as defined in IEC61850. The enable close
(EN_CLOSE) parameter is subject to similar conditions.
88
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
89
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
90
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
BayRes blocks the output values are all boolean and indicate the status of processes
and devices.
In the commands menu it is possible to view three sets of values. These are found
under the submenus menucascade/uicontrol.
• IED Commands
• Function Commands
• User Defined Commands
Various IED, function and user defined command data can be viewed here.
91
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
Displays data about available instances of tap changer parameters such as tap
positions for low and high voltage and type of code conversion.
92
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
Settings/Test/Function status/Control/TransformerVoltageControl(ATCC,90)/
TR1ATCC:x
Settings/Test/Function status/Control/TransformerVoltageControl(ATCC,90)/
TR8ATCC:x
Displays parameters for current and voltage levels, deadbands, timers and alarm
levels.
Test/Function status/Monitoring/DisturbanceReport(RDRE)
Displays data about disturbance reports. The disturbance report can be switched
off, a disturbance report that has been initiated is indicated by a boolean number, as
are completed reports and cleared reports. The parameter MEM USED indicates
that more than 80% of the memory space available for disturbance report data has
been used and the need to clear the memory is pressing. The Memory USED
parameter generates an integer value showing the actual amount of memory used
by the disturbance record repository. The maximum number of incoming analog
channels is 40 and their Trig status is indicated here. The Fault number parameter
generates an integer indicating the number of faults recorded since the last clearing
of the memory.
93
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
94
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
Under the Logic function folder there is viewable data for trip logic (showing
number of poles that have tripped and trip signal information), event counter
values, Logic gate outputs, Logic SR memory output states and Logic timer set
output states are also shown here.
95
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
96
Operator's manual
1MRK 504 114-UEN D Section 11
Test the IED
97
Operator's manual
Section 11 1MRK 504 114-UEN D
Test the IED
The Test LEDs menu enables the operator to activate LEDs manually. LEDs that
do not light up are defective. Defective LEDs are also logged in Disturbance
records under Monitoring.
98
Operator's manual
1MRK 504 114-UEN D Section 12
Control and supervise the bay
This chapter describes the various control and supervision functions available in
the HMI. In particular, how the single line diagram available on the display can be
used for this purpose. It also describes the Selector switch function available under
the control menu.
The control menu in the HMI includes the Single line diagram, Single command
and Selector switch functions.
The Single Line Diagram (SLD) is used to control and supervise the bay by
allowing the operator to close and open apparatuses using keys on the front panel
of the IED. This is primarily intended as a backup for higher level control systems.
If for example MicroSCADA were to malfunction, then bay level switches and
circuit breakers can be controlled directly from the HMI.
The Single command function is used to view LON interlocking data and is only
visible if LON is configured and used in the system.
The Selector Switch function is configured in the PCM600 tool and the switch
position can be changed in the HMI. The selector switch has the same function as a
rotating switch with up to 32 positions. Each position is configured in the PCM600
to match a certain application. Each position number corresponds to the equivalent
position of a rotating switch. It is only visible if it has been configured in the PCM600.
In the single line diagram a number of measured quantities are displayed. These are
normally system voltage (U), system current (I), active power (P) and reactive
power (Q). They are displayed on the right hand side of the SLD graphic. The
quantities shown can be configured in PCM600 and may therefore not always have
the same appearance in different IEDs.
It is possible to navigate the SLD screen using the up and down keys on the IED
keypad. The apparatus under control is highlighted as the user moves from symbol
to symbol using the keypad. An apparatus is opened using the green Ored Close
key and closed using the red I key.
99
Operator's manual
Section 12 1MRK 504 114-UEN D
Control and supervise the bay
The symbols used in the Single Line Diagram (SLD) are described in the table below
Autotransformer
xx05000227.vsd
IEC05000227 V1 EN
Busbar
xx05000228.vsd
IEC05000229 V1 EN
Capacitor
xx05000231.vsd
IEC05000231 V1 EN
Circuit breaker
xx05000232.vsd
IEC05000232 V1 EN
Damping Coil
xx05000233.vsd
IEC05000233 V1 EN
Current Transformer
xx05000234.vsd
IEC05000234 V1 EN
Earth
xx05000235.vsd
IEC05000235 V1 EN
Feeder system
xx05000236.vsd
IEC05000236 V1 EN
Generator
xx05000237.vsd
IEC05000237 V1 EN
Disconnector
xx05000238.vsd
IEC05000238 V1 EN
Junction
xx05000240.vsd
IEC05000240 V1 EN
Motor
xx05000241.vsd
IEC05000241 V1 EN
Reactor
xx05000242.vsd
IEC05000242 V1 EN
100
Operator's manual
1MRK 504 114-UEN D Section 12
Control and supervise the bay
Surge arrestor
xx05000243.vsd
IEC05000243 V1 EN
Trafo 2 windings
xx05000244.vsd
IEC05000244 V1 EN
Trafo 3 windings
xx05000245.vsd
IEC05000245 V1 EN
Truck
xx05000248.vsd
IEC05000248 V1 EN
VT 2 windings
xx05000247.vsd
IEC05000247 V1 EN
These messages appear at the bottom of the SLD screen and are in the form of a
prompt asking the user to confirm an action, such as the opening of a circuit
breaker. They can also warn the user as to conditions that are a hindrance to the
intended action, such as an interlocking condition. The user may be given the
choice to override certain conditions.
101
Operator's manual
102
1MRK 504 114-UEN D Section 13
Reset
This chapter describes how to reset the IED and when this is necessary.
The circuit breaker counter is reset under Reset counter in the HMI tree.
The circuit switch counter is reset under Reset counters in the HMI tree.
The event counter is reset under Reset counters in the HMI tree.
The Pulse counter is reset under Reset counters menu in the HMI tree.
103
Operator's manual
Section 13 1MRK 504 114-UEN D
Reset
Activating Reset of LDCM counters sets the counter concerned to zero. A reset can
be performed by affirmation in the dialog box. This is done by pressing the E key
when YES is highlighted.
Resetting the counter for number of tap changer operations and the contact life
counter.
The internal event list is reset under Reset menu in HMI tree.
By activating this reset, the colored LEDs above the LCD, if they are latched, will
be reset.
Activating the Reset of indication LEDs will zero all fifteen LEDs to the right of
the LCD.
104
Operator's manual
1MRK 504 114-UEN D Section 13
Reset
Objects that are considered at risk after a trip may be prevented from reconnecting
by a lockout condition. The reset lockout facility is used to undo a lockout
condition caused by a such a trip.
The Reset temperature function under the Reset counters menu offers the following
reset possibilities. These are outlined below.
105
Operator's manual
106
1MRK 504 114-UEN D Section 14
Authorization
This chapter describes password procedures and levels of access in the system.
To safeguard the interests of our customers, both the IED and the tools that are
accessing the IED are protected, by means of authorization handling. The
authorization handling of the IED and the PCM600 is implemented at both access
points to the IED:
There are different levels (or types) of users that can access or operate different
areas of the IED and tools functionality. The pre-defined user types are given in
Table 2.
Be sure that the user logged on to the IED has the access required
when writing particular data to the IED from PCM600.
107
Operator's manual
Section 14 1MRK 504 114-UEN D
Authorization
The IED users can be created, deleted and edited only with the IED User
Management within PCM600. The user can only LogOn or LogOff on the local
HMI on the IED, there are no users, groups or functions that can be defined on
local HMI.
108
Operator's manual
1MRK 504 114-UEN D Section 14
Authorization
The Authorization menu allows the user to logOn and, logOff. The HMI path is as
follows:
Main menu/Authorization
At delivery the default user is the SuperUser. No Log on is required to operate the
IED until a user has been created with the IED User Management..
Once a user is created and downloaded to the IED, that user can perform a Log on,
introducing the password assigned in the tool.
If there is no user created, an attempt to log on will display a message box: “No
user defined!”
If one user leaves the IED without logging off, then after the timeout (set in Main
menu/Settings/General Settings/HMI/Screen/Display Timeout) elapses, the IED
returns to Guest state, when only reading is possible. The display time out is set to
60 minutes at delivery.
If there are one or more users created with the IED User Management and
downloaded into the IED, then, when a user intentionally attempts a Log on or
when the user attempts to perform an operation that is password protected, the Log
on window will appear.
The cursor is focused on the User identity field, so upon pressing the “E” key, the
user can change the user name, by browsing the list of users, with the “up” and
“down” arrows. After choosing the right user name, the user must press the “E”
key again. When it comes to password, upon pressing the “E” key, the following
character will show up: “$”. The user must scroll for every letter in the password.
After all the letters are introduced (passwords are case sensitive) choose OK and
press the “E” key again.
If everything is alright at a voluntary Log on, the local HMI returns to the
Authorization screen. If the Log on is OK, when required to change for example a
password protected setting, the local HMI returns to the actual setting folder. If the
Log on has failed, then the Log on window opens again, until either the user makes
it right or presses “Cancel”.
109
Operator's manual
Section 14 1MRK 504 114-UEN D
Authorization
The Internet Protocol ports security guide line can not suggest concrete products
for a secure system setup. This must be decided along the specific project,
requirements and existing infrastructure. The required external equipment can be
separated devices or devices that combine firewall, router and secure VPN
functionality.
To setup an Internet Protocol firewall the following table summarizes the Internet
Protocol ports used in the 670 series. The ports are listed in ascending order. The
column “Default state” defines whether a port is open or closed by default. All
ports that are closed by default are opened by configuration enabling.
The 670 series supports two Ethernet communication protocols. These protocols
are IEC61850, and DNP3/TCP. These communication protocols are enabled by
configuration. This means that the Internet Protocol port is closed and not available
if the configuration of the 670 series doesn't contain a communication line of the
protocol. If a protocol is configured the corresponding Internet Protocol port is
open all the time.
Please refer to the 670 series technical reference manual and the
corresponding protocol documentation on how to configure a
certain communication protocol for the 670 series.
• The Internet Protocol port used for file transfer (default port 21) is fixed and
cannot be changed.
• The Internet Protocol port used for IEC61850 (default port 102) is fixed and
can not be changed.
• The Internet Protocol ports used for DNP3 are configurable. The
communication protocol DNP3 could operate on UDP (default port 20 000) or
TCP (default port 20 000). It is defined in the configuration which type of
110
Operator's manual
1MRK 504 114-UEN D Section 14
Authorization
These security drawbacks are acceptable in limited local networks. For wide area
networks in particular with connection to the Internet, the 670 series Ethernet
communication must be protected against illegal access. This protection must be
handled by external devices to setup a secure virtual private network (VPN).
111
Operator's manual
112
1MRK 504 114-UEN D Section 15
Glossary
This chapter contains a glossary with terms, acronyms and abbreviations used in
ABB technical documentation.
AC Alternating current
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
ADM Analog digital conversion module, with time synchronization
AI Analog input
ANSI American National Standards Institute
AR Autoreclosing
ArgNegRes Setting parameter/ZD/
ArgDir Setting parameter/ZD/
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
AWG American Wire Gauge standard
BBP Busbar protection
BFP Breaker failure protection
BI Binary input
BIM Binary input module
BOM Binary output module
BOS Binary outputs status
BR External bistable relay
BS British Standards
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals
between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for
serial communication
CB Circuit breaker
113
Operator's manual
Section 15 1MRK 504 114-UEN D
Glossary
114
Operator's manual
1MRK 504 114-UEN D Section 15
Glossary
115
Operator's manual
Section 15 1MRK 504 114-UEN D
Glossary
116
Operator's manual
1MRK 504 114-UEN D Section 15
Glossary
117
Operator's manual
Section 15 1MRK 504 114-UEN D
Glossary
118
Operator's manual
1MRK 504 114-UEN D Section 15
Glossary
119
Operator's manual
Section 15 1MRK 504 114-UEN D
Glossary
120
Operator's manual
121
Contact us
www.abb.com/substationautomation