0% found this document useful (0 votes)
30 views

Rheonics SRV Manual

The document provides instructions for installing and operating an SRV sensor measurement system. It details connecting the sensor to transmitter electronics, powering the transmitter, and connecting outputs including 4-20mA and Modbus RTU. It also describes handling and cleaning the sensor.

Uploaded by

Tuan Anh Nguyen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views

Rheonics SRV Manual

The document provides instructions for installing and operating an SRV sensor measurement system. It details connecting the sensor to transmitter electronics, powering the transmitter, and connecting outputs including 4-20mA and Modbus RTU. It also describes handling and cleaning the sensor.

Uploaded by

Tuan Anh Nguyen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

SRV20171127 SRV Installation and Operating Instructions

Contents
1 What’s in the box ............................................................................................................................ 2
2 Preparing the system ...................................................................................................................... 2
3 Connecting and disconnecting wires to the terminal blocks on SME electronics .......................... 3
4 Connecting sensor to transmitter electronics ................................................................................ 5
5 Powering the Transmitter ............................................................................................................... 6
6 Connecting 4-20 mA outputs .......................................................................................................... 7
7 Connecting Modbus RTU (RS-485) outputs .................................................................................... 8
7.1 General.................................................................................................................................... 8
7.2 Wiring ...................................................................................................................................... 8
7.3 Configuration .......................................................................................................................... 9
7.4 Input Registers ........................................................................................................................ 9
7.5 Data-Types ............................................................................................................................ 10
8 Operating the system.................................................................................................................... 11
8.1 Viscosity measurement ......................................................................................................... 12
9 Handling the Sensor ...................................................................................................................... 13
9.1 Cleaning the sensor............................................................................................................... 13
10 Notes/Errata: ............................................................................................................................ 15
SRV Installation and Operating Instructions

1 What’s in the box


The following items are delivered with the SRV system:

• Sensor cable
• Electronic transmitter, SME
• SRV sensor
• USB stick with software tool installer
• Cable glands (optional)

2 Preparing the system


The sensor measurement system consists of two components:

• SRV Sensor
• SME Transmitter (Electronics unit)

The transmitter is shipped fully assembled. Gain access to the connections by unscrewing the cover
and removing the display (if ordered with display) by pulling it out. The SME electronics module is now
accessible for connecting the sensor, power, and communication cables.

Page 2 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions

3 Connecting and disconnecting wires to the terminal blocks on


SME electronics
The wires are generally color coded, the ends should be crimped with 8mm diameter crimps. This
connection is valid for sensor cable, power cable, Modbus cable, 4-20 mA cables.

To connect the wires, insert the crimped end in the correct port on the terminal block till it clicks firmly
in place and cannot be pulled out when tugging on the wires (do not tug on the wires with a lot of
force as that may damage the terminal block).

Page 3 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions

To disconnect the sensor wires, press the white tab for that specific port with a small flat screw driver
as shown in picture below where the user is removing wire connected to port 1.

While pressing on the white part, pull out the cable connection with the other hand as shown in the
picture below.

Page 4 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions

4 Connecting sensor to transmitter electronics


The sensor is connected to the transmitter electronics by a sensor cable. Follow the color code table
below to connect the correct wires from the sensor cable to the sensor connection terminal strip on
the transmitter. The leads are delivered with crimped ends; cable can be shortened if needed, but
sleeves should be crimped on the stripped ends.

Page 5 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions

Wire Color Sensor connection terminal #


Red 8
Blue 7
Pink (Rose) 6
Grey 5
Yello 4
Green 3
Brown 2
White 1
---not connected--- 0

5 Powering the Transmitter


Connect a 24V DC supply to the power input terminals on the transmitter.

Power input terminals are labeled with 24 V DC + and – GND.

It is important to avoid ground loops in the setup / plant where the SMET is used. Ground loops can
lead to excessive currents on the ground / return wire of the SMETs 24V power supply which can
damage the unit.

To prevent this, we strongly recommend that the SMET is powered by a separate 24V power supply
with galvanic separation. Otherwise, the SMET might be permanently damaged.

Page 6 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions

6 Connecting 4-20 mA outputs


Rheonics transmitter 4/20mA connection, self-powered

V+
V-
B+
A- 24V

VM+
V-
Wiring Option (A)
V-
4/20mA input
CH1 +
CH2
CH3
R 4.36
--
Wiring Option (B)
4/20mA input
+

R 4.36
-

Load impedance: 0 to 720 Ohms


Output range: 4-20mA, (3.5mA error)
Galvanic isolation: none

Wiring Option (A)


• Connect positive terminal of current input module to desired channel terminal of SME device
• Connective negative terminal of current input module to negative power supply terminal used
for SME device

Wiring Option (B)


• Connect positive terminal of current input module to desired channel terminal of SME device
• Connective negative terminal of current input module to V- terminal of SME device

Notes
• The 4/20mA outputs are not galvanically isolated. It is not recommended to route the 4/20mA
to off-site locations if the corresponding 4/20mA input does not provide galvanic isolation.

Page 7 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions

7 Connecting Modbus RTU (RS-485) outputs


7.1 General
All SME devices implement a MODBUS RTU compliant RTU slave. The default configuration of the
MODBUS RTU slave is 38400 and ODD parity. Connection is by RS485-2W where the interface is not
electrical isolated.

7.2 Wiring
Wiring is RS485-2W. The device does not have internal biasing resistors and termination resistors and
proper setup of the RS485 network has to be ensured.

Termination: Termination should be only at the end and beginning of the bus to avoid reflections.
Requirements on termination differ not only on the baud-rate used but also on the slew-rate of device
internal drivers. As a general rule, if there are devices on the RS485 bus that allow fast transmission
speeds, and cable lengths exceed a few meters, then termination is required.

Biasing: Biasing of the RS485 BUS is required. If biasing is omitted, communication may work
unreliably or not at all. See figure below for Pull-Up/Pull-Down resistors.

Connections: Connection stubs on the RS485 bus should be kept to the minimum.

Common: RS485 does allow common mode voltages of +12V / -7V. It is therefore recommended to
use a common wire to ensure common mode voltage is within safe limits for all receivers. In case of
problems it might be necessary to introduce RS485 isolators into the network. The common terminal
for the SME device is the 0V terminal (GND) for the power supply.

Rheonics transmitter RS485 MODBUS

V+
V-
B+
+5V
A- 24V

Bus < 1000m

MODBUS
master

Stub < 20m


GND
MODBUS DO NOT CONNECT
slave GND
EARTH TO GND for
marine applications

Page 8 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions
7.3 Configuration
The SME device allows the configuration of the Modbus address using the RCP software. Please refer
to the RCP manual for instructions.

Factory default settings of Modbus parameters:

address=0 or 1

baudrate=38400

parity=odd

The system is capable of supporting:

• parity settings of odd, even and none


• baudrates of 9600, 19200 and 38400

7.4 Input Registers


The table uses PDU addressing; addresses start at zero. Depending on the PLC used it might be
required to add 1 to the addresses in the table below

Table 1: Modbus input registers.

Address (Dec) Length of registers Type Description

Parameter 1
40 2 Float Parameter 1 value as float
42 1 Int16 Parameter 1 value scaled by 100 as
signed integer
43 1 Uint16 Parameter 1 status (See datatypes)
Parameter 2
48 2 Float Parameter 2 value as float
50 1 Int16 Parameter 2 value scaled by 100 as
signed integer
51 1 Uint16 Parameter 2 status (See datatypes)
Parameter 3
58 2 Float Parameter 3 value as float
60 1 Int16 Parameter 3 value scaled by 100 as
signed integer
61 1 Uint16 Parameter 3 status (See datatypes)
Parameter 4
64 2 Float Parameter 4 value as float
66 1 Int16 Parameter 4 value scaled by 100 as
signed integer
67 1 Uint16 Parameter 4 status (See datatypes)
Parameter 5
72 2 Float Parameter 5 value as float
74 1 Int16 Parameter 5 value scaled by 100 as
signed integer

Page 9 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions
75 1 Uint16 Parameter 5 status (See datatypes)
Parameter 6
80 2 Float Parameter 6 value as float
82 1 Int16 Parameter 6 value scaled by 100 as
signed integer
83 1 Uint16 Parameter 6 status (See datatypes)
Parameter 7
88 2 Float Parameter 7 value as float
90 1 Int16 Parameter 7 value scaled by 100 as
signed integer
91 1 Uint16 Parameter 7 status (See datatypes)
Parameter 8
96 2 Float Parameter 8 value as float
98 1 Int16 Parameter 8 value scaled by 100 as
signed integer
99 1 Uint16 Parameter 8 status (See datatypes)

7.5 Data-Types
Float: IEEE754 floating point. This data type spans two registers which should be read together.
Depending on the endianness of the host it might be necessary to swap high/low byte and/or the
respective registers.

Int16: Signed 16 bit integer (register)

Uint16: Unsigned 16 bit integer

Parameter status: The parameter status is a bitmask of individual status bits. As a general rule Bit 0
checking should be implemented where a set bit corresponds to an error/warning condition. In case
of a critical error the parameter value is also set to NAN (not a number – See IEE754)

Bit 0: General error – Check other bits for more detailed configuration

Bit 1: Internal configuration error – Restart. If error persists call Rheonics for support

Bit 2: Hardware error, e.g. broken temperature sensor. Call Rheonics for support and arrange RMA

Bit 3: Dependency error: a parameter is calculated from other parameters and one of the source
parameter has an error. Check all other parameters for errors.

Bit 4: Device is starting up and no results are ready.

Bit 5: Internal error – Restart. If error persists call Rheonics for support.

Bit 8: Parameter result is not stable. Check measurement conditions (flow, vibration, etc.)

Bit 15: Parameter exceeds sensor upper limit. No results available.

Bit 14: Parameter below sensor lower limit. No results available.

Page 10 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions
Bit 13: Parameter value above upper warning range. Measurements might not be accurate and sensor
performance might be reduced.

Bit 12: Parameter value below lower warning range. Measurements might not be accurate and sensor
performance might be reduced.

8 Operating the system

After installing the software and setting up the port, the system may now be started. The installation
of the Rheonics Control Panel (RCP) Software and its settings are described in the RCP manual.

THE ELECTRONIC BOX MUST BE ATTACHED TO THE COMPUTER WITH THE USB CABLE
AND POWERED UP IN ORDER FOR THE SYSTEM TO OPERATE

1. Connect the sensor to the Transmitter (instructions in section 2)


2. Connect power to Transmitter (instructions in section 3)
3. Connect the micro USB cable to the Transmitter electronics. Connect the other end to a free
USB port on the computer.
4. Now that the proper operating mode has been established, run the Rheonics Control Panel
software. The Rheonics Control Panel application is operned from the Start menu.

When the software is running, you will see a screen similar to the following:

Page 11 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions

For help about the Rheonics Control Panel (RCP) and its settings see:
Help -> RCP – Rheonics Control Panel Software manual

8.1 Viscosity measurement


The SRV measures the density-viscosity product of the fluid:

Density-Viscosity Product = ρ*η ρ = Density [g/cc]


η = Dynamic viscosity [mPa.s]

The Rheonics Control Panel allows you to enter the appropriate fluid density to obtain the dynamic
viscosity (η, in mPa.s) or kinematic viscosity (η/ρ, in cSt). By default, the electronics and software use
1 g/cc as the density. To enter the actual density of the fluid in the software, follow the instructions in
the RCP manual.

NOTE:

Electronics box can be programmed to set a constant or temperature-dependent density value. Please
check RCP manual for instructions on changing the density in the transmitter electronics.

Page 12 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions

9 Handling the Sensor

The SRV is a stable, robust sensor system that operates over a wide range of temperatures and
pressures. The sensor is made of 316L stainless steel, which resists attack by a wide variety of highly
corrosive fluids.

In order to get optimum performance from the system, some simple guidelines must be followed.

9.1 Cleaning the sensor


The SRV is based on a resonant sensing element that operates in the range of approximately 7-8 kHz.
The sensor measures viscosity in a thin layer of fluid surrounding the resonant element.

In any measurement scenario in which the sensor could become coated with tenacious fluids and
solids, it is recommended that the sensor be removed and mechanically cleaned at appropriate
intervals.

Adherent films can be removed by using appropriate solvents, ultrasonic cleaning, and/or wiping with
solvent-saturated cloth or paper. Under no circumstances should abrasives be used to clean the
resonator, as these will change the geometry and destroy its calibration.

Cleaning the sensor with solvent-saturated cloth or paper

Please note that it is difficult to get accurate measurement with plain water stationary in the SRV
measurement area. Even degassed water tends to have air dissolved in it, which eventually forms
micro bubbles on the surface of the sensor, disturbing its geometry. This is not a problem at higher
pressures, which tend to re-dissolve any gases present. Hydrocarbons, glycols, and other fluids with
low surface tension are less prone to bubble formation.

Page 13 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions
The SRV will operate in static fluids as well as flow rates in excess of 100 l/min. Flow may be in either
direction, subject to the above caution about the effects of bubbles.

Page 14 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.
SRV Installation and Operating Instructions

10 Notes/Errata:

Page 15 of 15
©Rheonics, Inc. 2013-17
Confidential to customer. Do not distribute without written permission of Rheonics, Inc.

You might also like