T - Quan - Project - VC0-Report
T - Quan - Project - VC0-Report
Author
Project: demo vsip
Variant: New simulation variant
PVsyst V7.1.1
Simulation date:
22/09/23 14:30
with v7.1.1
Project summary
Geographical Site Situation Project settings
Tả Quan Latitude 20.91 °N Albedo 0.20
Vietnam Longitude 106.69 °E
Altitude 6m
Time zone UTC+7
Meteo data
Tả Quan
Meteonorm 7.3 (1993-2000), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 2002 units Nb. of units 9.4 units
Pnom total 1101 kWp Pnom total 940 kWac
Pnom ratio 1.171
Results summary
Produced Energy 708.7 MWh/year Specific production 644 kWh/kWp/year Perf. Ratio PR 47.36 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 8
Loss diagram 9
Special graphs 10
PVsyst V7.1.1
Simulation date:
22/09/23 14:30
with v7.1.1
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Array Characteristics
PV module Inverter
Manufacturer JA Solar Manufacturer Huawei Technologies
Model JAP72-S09-340-SC Model SUN2000-100KTL-M1-480Vac
(Custom parameters definition) (Original PVsyst database)
Unit Nom. Power 550 Wp Unit Nom. Power 100 kWac
Number of PV modules 1786 units Number of inverters 8.4 units
Nominal (STC) 982 kWp Total power 840 kWac
Array #1 - PV Array
Orientation #1
Tilt/Azimuth 6/90 °
Number of PV modules 216 units Number of inverters 10 * MPPT 10% 1 units
Nominal (STC) 119 kWp Total power 100 kWac
Modules 12 Strings x 18 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 66.1 kWp Max. power (=>40°C) 110 kWac
U mpp 612 V Pnom ratio (DC:AC) 1.19
I mpp 108 A
Array #2 - Sub-array #2
Orientation #1
Tilt/Azimuth 6/90 °
Number of PV modules 216 units Number of inverters 10 * MPPT 10% 1 units
Nominal (STC) 119 kWp Total power 100 kWac
Modules 12 Strings x 18 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 66.1 kWp Max. power (=>40°C) 110 kWac
U mpp 612 V Pnom ratio (DC:AC) 1.19
I mpp 108 A
Array #4 - Sub-array #4
Orientation #1
Tilt/Azimuth 6/90 °
Number of PV modules 16 units Number of inverters 1 * MPPT 10% 0.1 units
Nominal (STC) 8.80 kWp Total power 10.0 kWac
Modules 1 String x 16 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 4898 Wp Max. power (=>40°C) 110 kWac
U mpp 544 V Pnom ratio (DC:AC) 0.88
I mpp 9.0 A
PVsyst V7.1.1
Simulation date:
22/09/23 14:30
with v7.1.1
PV Array Characteristics
Array #5 - Sub-array #5
Orientation #2
Tilt/Azimuth 6/-90 °
Number of PV modules 16 units Number of inverters 1 * MPPT 10% 0.1 units
Nominal (STC) 8.80 kWp Total power 10.0 kWac
Modules 1 String x 16 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 4898 Wp Max. power (=>40°C) 110 kWac
U mpp 544 V Pnom ratio (DC:AC) 0.88
I mpp 9.0 A
Array #6 - Sub-array #6
Orientation #2
Tilt/Azimuth 6/-90 °
Number of PV modules 216 units Number of inverters 10 * MPPT 10% 1 units
Nominal (STC) 119 kWp Total power 100 kWac
Modules 12 Strings x 18 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 66.1 kWp Max. power (=>40°C) 110 kWac
U mpp 612 V Pnom ratio (DC:AC) 1.19
I mpp 108 A
Array #7 - Sub-array #7
Orientation #2
Tilt/Azimuth 6/-90 °
Number of PV modules 234 units Number of inverters 10 * MPPT 10% 1 units
Nominal (STC) 129 kWp Total power 100 kWac
Modules 13 Strings x 18 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 71.6 kWp Max. power (=>40°C) 110 kWac
U mpp 612 V Pnom ratio (DC:AC) 1.29
I mpp 117 A
Array #8 - Sub-array #8
Orientation #2
Tilt/Azimuth 6/-90 °
Number of PV modules 108 units Number of inverters 5 * MPPT 10% 0.5 units
Nominal (STC) 59.4 kWp Total power 50.0 kWac
Modules 6 Strings x 18 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 33.1 kWp Max. power (=>40°C) 110 kWac
U mpp 612 V Pnom ratio (DC:AC) 1.19
I mpp 54 A
Array #9 - Sub-array #9
Orientation #2
Tilt/Azimuth 6/-90 °
Number of PV modules 48 units Number of inverters 3 * MPPT 10% 0.3 units
Nominal (STC) 26.40 kWp Total power 30.0 kWac
Modules 3 Strings x 16 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 14.69 kWp Max. power (=>40°C) 110 kWac
U mpp 544 V Pnom ratio (DC:AC) 0.88
I mpp 27 A
PVsyst V7.1.1
Simulation date:
22/09/23 14:30
with v7.1.1
PV Array Characteristics
Array #10 - Sub-array #10
Orientation #2
Tilt/Azimuth 6/-90 °
Number of PV modules 216 units Number of inverters 10 * MPPT 10% 1 units
Nominal (STC) 119 kWp Total power 100 kWac
Modules 12 Strings x 18 In series
At operating cond. (50°C) Operating voltage 200-1000 V
Pmpp 66.1 kWp Max. power (=>40°C) 110 kWac
U mpp 612 V Pnom ratio (DC:AC) 1.19
I mpp 108 A
PVsyst V7.1.1
Simulation date:
22/09/23 14:30
with v7.1.1
PV Array Characteristics
Array #3 - Sub-array #3
Orientation #1
Tilt/Azimuth 6/90 °
PV module Inverter
Manufacturer JA Solar Manufacturer Huawei Technologies
Model JAP72-S09-340-SC Model SUN2000-100KTL-M1-400Vac
(Custom parameters definition) (Original PVsyst database)
Unit Nom. Power 550 Wp Unit Nom. Power 100 kWac
Number of PV modules 216 units Number of inverters 10 * MPPT 10% 1 units
Nominal (STC) 119 kWp Total power 100 kWac
Modules 12 Strings x 18 In series Operating voltage 200-1000 V
At operating cond. (50°C) Max. power (=>30°C) 110 kWac
Pmpp 66.1 kWp Pnom ratio (DC:AC) 1.19
U mpp 612 V
I mpp 108 A
Array losses
Array Soiling Losses Thermal Loss factor LID - Light Induced Degradation
Loss Fraction 3.0 % Module temperature according to irradiance Loss Fraction 2.0 %
Uc (const) 20.0 W/m²K
Uv (wind) 0.0 W/m²K/m/s
DC wiring losses
Global wiring resistance 4.5 mΩ
Loss Fraction 0.7 % at STC
PVsyst V7.1.1
Simulation date:
22/09/23 14:30
with v7.1.1
DC wiring losses
Array #9 - Sub-array #9 Array #10 - Sub-array #10
Global array res. 339 mΩ Global array res. 95 mΩ
Loss Fraction 1.5 % at STC Loss Fraction 1.5 % at STC
Array #11 - Sub-array #11 Array #12 - Sub-array #12
Global array res. 95 mΩ Global array res. 95 mΩ
Loss Fraction 1.5 % at STC Loss Fraction 1.5 % at STC
Array #13 - Sub-array #13 Array #14 - Sub-array #14
Global array res. 573 mΩ Global array res. 509 mΩ
Loss Fraction 1.5 % at STC Loss Fraction 1.5 % at STC
System losses
Unavailability of the system
Time fraction 3.0 %
10.9 days,
3 periods
PVsyst V7.1.1
Simulation date:
22/09/23 14:30
with v7.1.1
Main results
System Production
Produced Energy 708.7 MWh/year Specific production 644 kWh/kWp/year
Performance Ratio PR 47.36 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.1.1
Simulation date:
22/09/23 14:30
with v7.1.1
Loss diagram
1364 kWh/m² Global horizontal irradiation
PVsyst V7.1.1
Simulation date:
22/09/23 14:30
with v7.1.1
Special graphs
Daily Input/Output diagram