Distribution System (Part 1)
Distribution System (Part 1)
Chapter 4
Distribution
System
1
Course Outcome
2
CONTENTS
• Introduction
• Subtransmission and Distribution
• Subtransmission System
• Distribution System
• Distribution Substation
• Primary Distribution Circuit
• Secondary System
3
Introduction
4
Introduction
6
Subtransmission and Distribution
7
Subtransmission and Distribution
8
Nominal Voltage Levels in Transmission and
Distribution Systems
• Three phase, 50 Hz systems are universally used for
generation, transmission and distribution of electrical power.
• The voltage are step up at generating station for purpose of
long distance high power transmission.
• The voltage are step down in receiving substations for
subtransmission.
• The voltage are further step down in distribution substations
and finally near load points for final utilization
• Thus, the entire power system network has several AC voltage
levels obtained by means of power transformer located in
substations and distribution systems voltage levels are
standardized.
9
Nominal Voltage Levels in Transmission and
Distribution Systems
References Values of Nominal Voltage Levels and Nominal System Voltages
Nominal Voltage of 3-phase, 400 kV EHV Transmission
AC Systems at 50Hz, 220 kV HV
phase to phase kV, rms 132 kV HV
66 kV HV
220 kV HV Subtransmission
132 kV HV
66 KV HV
33 kV MV Distribution
22 kV MV Primary Circuits and
15 kV MV Direct Feeders To Large
11 kV MV
Consumers
6.6 kV MV
3.3 kV MV
3-Phase,AC, 50 Hz phase to phase, 415 V LV Distribution
and Secondaries and
1-phase, AC 50 HZ phase to neutral 240 V LV Service to consumers
10
Nominal Voltage Levels in Transmission and
Distribution Systems
Voltage levels:
(1) Generator voltage (6.6kV to 22 kV, 3phase AC, 50 HC
(2) Main transmission voltage (400kV or 220kV)
Transformers / Feeders
(3) Subtransmission voltage ( 220kV/132 kV/66kV/33kV)
(A)Step-up transformer in generating station
(4) Primary distribution voltage
(B)Step-down transformer in receiving
(33kV/22kV/15kV/11kV/6.6kV/3.3kV
substation
(5) , (6) Secondary distribution voltage (415V, 3phase, 240,
(C)Step-down transformer in distribution
1phase)
substation
(D)Small distribution transformer in
distribution system 11
(E)H.T. Feeder to industry
Main Intake Substation
12
Main Distribution Substation
13
Distribution Substation
14
Subtransmission System
15
The Distribution
System
• EHV/HV/MV/LV
Network Arrangements
Generator
Transformer
Circuit Breaker
Disconnector
Feeder
Fuse
LV Customer
16
The Distribution System
17
The Distribution System
18
The Distribution System
19
Distribution Substation
• Distribution Substations
• Distribution substation (DS) have a step down power
transformers, a few incoming HV subtransmission line
and several outgoing MV overhead lines or underground
cables.
• DS have several equipment from switching, protection,
metering, voltage control, communication, power factor
corrector and so on.
• DS’s are located in the load area and the outgoing
overhead lines or underground cables from DS feed the
primary side of distribution transformer and therefore
called primary distribution circuit.
20
Distribution Transformer
21
Distribution Transformer
22
Distribution Transformer
• Principles Components
• The principles components of a transformer are:
a) A magnetic core
The core is constructed of sheet steel laminations –
the laminations are insulated to keep the iron losses
low.
24
Distribution Transformer
• Principles Components
• The principles components of a transformer are (cont.):
b) The windings
The windings are wound on round formers. The secondary
windings are first inserted onto the core. The primary
windings are then inserted over the secondary windings.
The two windings are kept apart by insulator
25
Distribution Transformer
• Principles Components
• The principles components of a transformer are (cont.):
c) The casing or tank
i. Mineral (or liquid) filled transformer
A steel tan is used for housing the transformer. The
completed assembly is placed in the tank and bolted into
position. The tank is then filled with mineral oil. Fins (or
radiators) at the side of the tank improves the cooling of the
transformer.
Mineral oil-filled
Transformer(Hermetically
sealed type)
26
Distribution Transformer
• Principles Components
• The principles components of a transformer are (cont.):
c) The casing or tank
ii. Cast resin transformer
Each winding of cast resin transformer is impregnated with
synthetic resin before assembly. The cast resin transformer
must be placed in a room or in a closure. The enclosure can
be made of wire mesh or sheet steel.
The type of enclosure will depend on the environment in
which the transformer is insulated. The enclosure must be
bonded to the main earthing bar of the electrical system.
27
Distribution Transformer
• Terminal Marking
• The terminal marking of the windings of a transformer
are marked as follows:
a) High voltage winding – marked with capital letters e.g. A, R
b) Low voltage winding – marked with small letters, e.g. a, r
c) Tertiary winding – marked with the number 3 and followed
by a capital letter e.g. 3A, 3R
28
Distribution Transformer
• Terminal Marking
• For a 3 phase transformer with three winding, the
markings could be:
a) High voltage winding – 1st phase: A1 & A2
2nd phase: B1 & B2
3rd phase: C1 & C2
b) Low voltage winding – 1st phase: a1 & a2
2nd phase: b1 & b2
3rd phase: c1 & c2
c) Tertiary winding – 1st phase: 3A1 & 3A2
2nd phase: 3B1 & 3B2
3rd phase: 3C1 & 3C2
29
Distribution Transformer
• Polarity
• The polarity ( or direction) of the induced emf of the
secondary winding depends on the relative position of the
two windings.
(a) Subtractive polarity (b) Additive polarity
30
Distribution Transformer
31
Distribution Transformer
33
Distribution Transformer
• Tap changers
• A tap changer is a device that provides the means for changing
the voltage ration of the windings.
• It is used to compensate for variations of the primary supply
voltage, hereby maintaining the secondary voltage within the
statutory limit
• Types of tap changers:-
1) On load tap changers
On load tap changer can be operated without switching off
the electricity supply. On load tap changers re used mainly
on transformers with larger capacities where the daily and
short periods of voltage adjustments are necessary.
34
Distribution Transformer
35
Distribution Transformer
• Tap changers
• Example
• The taps designation is specified a (6-2.5)%(2+4)
• It means that
– 6 taps in addition to nominal, or a total of 7 possible
tap setting
– Each tap will adjust the voltage 2.5% per step
– 2 taps above nominal, 4 taps below nominal
– The taps allow for voltage setting at +5%, +2.5%,
nominal, -2.5%,-5%,-7.5% and -10%
36
Distribution Transformer
• Transformer Impedance
• The transformer impedance is the vector sum of the
resistance and reactance ZTR = RTR + XTR
• The actual ohmic impedance values
1 %resistance VL,Transformer
2
RTR
100 VATransformer
X TR
1 % V 2
reactance L ,Transformer
100 VATransformer
37
Distribution Transformer
• Transformer Impedance
• If the transformer impedance is Z and given the X/R ratio,
then the actual ohmic impedance values can be found by
using
1 % Z VL,Transformer
2
RTR x cos
100 VATransformer
1 % Z VL,Transformer
2
X TR x sin
100 VATransformer
38
Distribution Transformer
• Transformer Impedance
Example 4.1
• A 75 KVA, 480-208Y/120 V, three phase transformer has
a winding resistance of 3% and leakage reactance of
4.22%. Determine the ohmic impedances referred to the
low voltage side.
• Solution:
1 3%208
2
RTR 0.0173
100 75kVA
1 4.22%208
2
X TR 0.0243
100 75kVA
39
Primary Distribution Circuit
40
Network Configurations
41
Network Configurations
• Mesh Network
• The interconnecting circuits of the mesh arrangement can
provide increased security of the supplies to individual
substations, and this arrangement is therefore frequently
used in HV systems.
• This arrangement requires more substation
equipment overall, for example switchgear and
electrical connections, it is usually more
efficient in terms of total circuit cost.
• The system arrangement is easier to extend and
has a higher utilization of circuits when fully
developed than a ring system.
42
Network Configurations
• Mesh Network
• A mesh network system consists of a number of inter-
connected ring system.
• Advantages of mesh network are:
– More than one alternate route of supply
– Very flexible in load transfer
– No interruption of power supply if faulty
equipment/section is isolated quickly
43
Network Configurations
• Interconnected Network
• By interconnecting and operating a number of infeed
substations in parallel.
• Subject to satisfactory network circuit
loadings such as arrangement can accept
the loss of one infeed interruption of
supplies within the network.
Note: Voltage levels and reactive power flows throughout the
network may be a problem on extended interconnected systems,
and parallel operation of the infeed points can result in reverse
power flows through the infeed transformers under outage
conditions on the higher-voltage system.
44
Network Configurations
• Link Arrangement
• A similar interconnection between infeed points can be
provided by the link arrangement.
• However, by opening the interconnectors as
indicated, the system can operate as radial
feeders with closure of the open points
restoring supplies if one of the infeed
substations is out of service.
45
Network Configurations
• Open Loop
• A figure shows a common option at MV and LV is the
open-loop arrangement.
• Under normal operating conditions the
network is operated as a number of radial
feeders.
• On the occurrence of a fault between the
busbar and the sectionalising open point,
once the faulted section has been isolated
the normally open disconnector can be
closed to provide back-up supplies.
46
Network Configurations
• Open Loop
• Normally the system has two or more supply sources.
• The system provides two separate route of supply to any
load.
• The disadvantages of open loop network are:
– It cost more than a radial system with the same
number of secondary sub-stations and serving the
same consumers.
– Co-ordination of the protection relays is also difficult
when compared with a radial system
– Estimation of the fault level is relatively more difficult
when compared with a radial system.
47
Network Configurations
• Radial System
• In addition, purely radial networks without the facility of
back-up interconnection, a common use, particularly for
LV rural systems.
48
Network Configurations
• Radial System
• A radial system has only one supply source and it feeds a
number of loads.
• The advantages of a radial distribution systems are:
– Simple to design – load estimation and sizing of
components is relatively easy
– Estimation of the fault level is easy
– Grading of the protection relay is easy
• The only disadvantage of radial system is that there is no
alternative route of supply to any consumer.
• A fault in a feeder will result in power outage to all
consumers after the fault location on this feeder.
49
Secondary System
50
Secondary System
• Secondary Systems
52
Voltage Drop
• Introduction
• One of the most important constraints on distribution
system design is the voltage level at the customer intake
point.
• This is particularly important for the vast majority of
customer taking supplies at low voltage with no means of
adjusting the voltage received.
• A knowledge of the voltage at different locations can
indicate the strong and weak parts of a networks.
53
Voltage Drop
• Vd phasor
• The voltage drop phasor Vd for a section of line having an
impedance Z and carrying current I is given by
Vd IZ
• In distribution system it is the arithmetic difference
between sending and receiving end voltages which is the
more useful voltage drop value.
• A close approximation to this can be obtained from the
simplified equivalent
54
Voltage Drop
• Vd phasor
• The figure has resistance R, reactance X, sending end
voltage VS and receiving end voltage Vr. . It carries
current I lagging on Vr .
• During normal load-flow conditions the angle between the
receiving and sending end voltage Vr and VS is only a few
degrees.
• For most practical cases the approximation ’ is acceptable.
Phasor Diagram
55
Voltage Drop
• Vd phasor
• The scalar relationship can be written as
VS Vr IR cos IX sin
• The voltage drop Vd in the line is given by
Vd VS Vr • IP and Iq represent
IR cos IX sin the resistive and
reactive component
I P R Iq X of load current I
56
Voltage Drop
• Vd phasor
• In single phase calculations the resistance and reactance
of the return path must be included in R and X.
• For 3-phase systems the line-line voltage drop can be
calculated from
57
Voltage Drop
Example 4.2
• Consider the three phases four wire 416 V secondary system with
balanced loads at A, B and C as shown in figure below.
Distribution
transformer
30 A 20 A 50 A
Unity p.f. Cos θB = 0.5 Cos θC = 0.9
• Determine the following: lagging lagging
a) Calculate the total voltage drop using the approximate method
b) Calculate the real power per phase for each load
c) Calculate the reactive power per phase for each load
d) Calculate the kilovolt ampere output and load power factor of the
distribution transformer 58
Voltage Drop
• Solution
a) Using the approximation voltage drop equation
Vd = I(R cos + X sin)
59
Voltage Drop
• Solution
b) The real power per phase for each load P=VI cos
the single phase voltage, 416 V
V 240 V
3
PA=240(30)(1.0)=7.2kW
PB=240(20)(0.5)=2.4kW
PC=240(50)(0.9)=10.8kW
The total real power per phase is: PA+PB+PC=20.4kW
• Solution
d) The KVA output of the distribution transformer
S=(P2+Q2)1/2
S=(20.42+9.3892)1/2=22.457 KVA/phase
Total KVA output of the distribution transformer is
3 x KVA/phase=3 x 22.457 KVA/phase = 67.37 KVA
61