Umg96rm-M DB en
Umg96rm-M DB en
Power Analyser
UMG 96RM-M
Data sheet
02/2019
Dok.-Nr. 2.040.178.0
DEVICE VIEWS
UMG 96RM-M
□ 91,5
104
□ 91,5
97
All dimensions in mm
UMG 96RM-M
General
Net weight (with attached connectors) 300g
Packaging weight (including accessories) 625g
Device dimensions ca. l = 42mm, w = 97mm, h = 100mm
Service life of the backlight 40,000 hours (50% of initial brightness)
Outputs
2 digital outputs, semi-conductor relay, not short circuit protected.
Switching voltage max. 33V AC, 60V DC
Switching current max. 50mAeff AC/DC
Reaction time 10/12 periods + 10ms *
Pulse output (energy pulses) max. 50Hz
Voltage metering
Three-phase, 4-wire systems with nominal voltages 277V/480V (+-10%)
up to
Three-phase, 3-wire systems, unearthed, IT 480V (+-10%)
with nominal voltages up to
Overvoltage category 300V CAT III
Rated surge voltage 4kV
Metering range L-N 01) .. 300 Vrms
(max. overvoltage 520 Vrms )
Metering range L-L 01) .. 520Vrms
(max. overvoltage 900Vrms )
Resolution 0.01V
Crest factor 2.45 (relative to the metering range)
Impedance 3MΩ/phase
Power consumption approx. 0.1 VA
Sampling rate 21.33 kHz (50 Hz), 25.6 kHz (60 Hz) per measuring
channel
Mains frequency 45 Hz .. 65 Hz
- Resolution 0.01 Hz
1)
The UMG 96RM-M can only detect measurements when a voltage L1-N greater than 20V eff
(4-wire measurement) at voltage input V1 or a voltage L1-L2 greater than 34V eff
(3-wire measurement) is applied.
Serial interface
M-Bus 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 baud
M-Bus device load max. 20 mA
Stripping length 7mm
1)
Referred to amplitude. * The display returns to 0 W when the
2)
Referred to phase and amplitude. maximum total energy values are reached.
3
) Referred to mains frequency.
4)
Referred to root mean square value.
5)
Accuracy class 0.5/ 0.5S with ../5 A transformer.
Accuracy class 1 with ../1 A transformer.