FACP - Operation
FACP - Operation
3.1 Overview
This section contains instructions for operating the control panel. Listed below are the topics
detailed in this section:
This manual also contains information on operating the control panel in the appendixes, listed as
follows:
• Appendix A, “Special Zone Operation”, on page 53
• Appendix B, “Intelligent Detector Functions”, on page 62
• Appendix C, “Remote Terminal Access”, on page 64
• Appendix D, “Point and System Troubles Lists”, on page 72
WARNING:
! WHEN USED FOR CO2 RELEASING APPLICATIONS, OBSERVE PROPER PRECAUTIONS AS
STATED IN NFPA 12. DO NOT ENTER THE PROTECTED SPACE UNLESS PHYSICAL
LOCKOUT AND OTHER SAFETY PROCEDURES ARE FULLY COMPLETED. DO NOT USE
SOFTWARE DISABLE FUNCTIONS IN THE PANEL AS LOCKOUT.
In Normal mode, the control panel does the following functions at regular intervals:
• Polls all SLC devices and the four NACs to check for valid replies, alarms, troubles, circuit
integrity, supervisory signals, etc.
• Checks power supply troubles and batteries at 10-second intervals
• Sends a supervisory query on the optional FDU-80 and verifies proper response
• Refreshes the LCD display and the optional FDU-80 display and updates time
• Scans for any keypad or Control Key entries
• Performs a detector automatic test operation
• Tests system memory
• Monitors for microcontroller failure
• Sends an Alarm message to the LCD display, remote annunciators, History buffer, installed
printers, and CRT-2s.
• Latches the control panel in alarm. (You can not return the control panel to normal operation
until you correct the alarm condition and reset the control panel)
• Initiates any Control-By-Event actions
• Starts timers (such as Silence Inhibit, Auto Silence)
• Activates the general alarm zone (Z00)
1. Check the Alarm message for the location and type of trouble.
2. Correct the condition causing the alarm.
3. When you finish correcting the alarm condition, press the SYSTEM RESET key to return the
control panel to normal operation (indicated by the “System Normal” message). The control
panel sends a “System Normal” message to the LCD display, History buffer and installed
printers, FDU-80 annunciators, and CRT-2s.
Latching
Type Code Purpose What it does
(Y/N)
Monitor Modules
Blank Y Indicates activation of a device with no description Lights FIRE ALARM LED and activates CBE
HEAT DETECT Y Indicates activation of a conventional heat detector Lights FIRE ALARM LED and activates CBE
MONITOR Y Indicates activation of an alarm-monitoring device Lights FIRE ALARM LED and activates CBE
PULL STATION Y Indicates activation of a manual fire-alarm-activating Lights FIRE ALARM LED and activates CBE
device, such as a pull station.
RF MON MODUL Y Indicates activation of a wireless alarm-monitoring device Lights FIRE ALARM LED and activates CBE
RF PULL STA Y Indicates activation of a wireless manual fire-alarm- Lights FIRE ALARM LED and activates CBE
activating device, such as a pull station
SMOKE CONVEN Y Indicates activation of a conventional smoke detector Lights FIRE ALARM LED and activates CBE
attached to an FZM-1
SMOKE DETECT Y Indicates activation of a conventional smoke detector Lights FIRE ALARM LED and activates CBE
attached to an FZM-1
WATERFLOW Y Indicates activation a waterflow alarm switch Lights FIRE ALARM LED and activates CBE
EVACUATE SW N Performs Drill function. Activates all silenceable outputs
Latching
Type Code Purpose What it does
(Y/N)
MAN. RELEASE Y Indicates activation of a monitor module programmed to a Lights FIRE ALARM LED and activates CBE
releasing zone to perform a releasing function.
MANREL DELAY Y Indicates activation of a monitor module programmed for Lights FIRE ALARM LED and activates CBE
a release output
SECOND SHOT N Provides second activation of releasing zone after soak Indicates ACTIVE and activates CBE
timer has expired.
CO MONITOR* Y Indicates activation of a CO conventional detector Activates CBE, does not light an indicator
at the control panel.
Detectors
SMOKE(ION) Y Indicates activation of an ion smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(DUCT I) Y Indicates activation of a duct ion smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(PHOTO) Y Indicates activation of a photo smoke detector Lights FIRE ALARM LED and activates CBE
RF_PHOTO Y Indicates activation of a wireless photoelectric smoke Lights FIRE ALARM LED and activates CBE
detector
SMOKE(DUCTP) Y Indicates activation of a duct photo smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(HARSH)* Y Indicates activation of a HARSH smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(LASER) Y Indicates activation of a laser smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(DUCTL) Y Indicates activation of a duct laser smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(BEAM) Y Indicates activation of a beam smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(DUCTL) Y Indicates activation of a duct laser smoke detector Lights FIRE ALARM LED and activates CBE
AIR REF Y Indicates activation of a laser air reference detector. Lights FIRE ALARM LED and activates CBE
HEAT Y Indicates activation of a 190oF intelligent thermal detector Lights FIRE ALARM LED and activates CBE
HEAT+ Y Indicates activation of a 190oF adjustable threshold Lights FIRE ALARM LED and activates CBE
intelligent thermal detector
HEAT(ANALOG) Y 135oF intelligent thermal sensor Lights FIRE ALARM LED and activates CBE
HEAT (ROR) Y 15oF per minute rate-of-rise detector Lights FIRE ALARM LED and activates CBE
SMOKE ACCLIM Y Indicates activation of detector (Acclimate Plus™, FSC- Lights FIRE ALARM LED and activates CBE
851 IntelliQuad), without freeze warning
SMOKE (ACCL+) Y Indicates activation of detector (Acclimate Plus™, FSC- Lights FIRE ALARM LED and activates CBE
851 IntelliQuad), with freeze warning
SMOKE MULTI* Y Multisensor smoke detector Lights FIRE ALARM LED and activates CBE
PHOTO/CO* Y Indicates activation of the Photo, Heat, or CO element of a Lights FIRE ALARM LED for photo and heat,
detector. no LED will light for a CO alarm. Photo and
heat will activate CBE, CO alarm activates
special function zone FC and sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
PHOTO/CO (P SUP)* Y Indicates activation of the Photo, Heat or CO element of a Lights FIRE ALARM LED for heat, no LED will
detector. light for a CO alarm, supervisory LED will
light for photo alarm, heat and photo will
activate CBE, CO alarm activates special
function zone FC and sixth CBE zone only
(sixth CBE zone programmable via VeriFire
Tools)
PHOTO/CO (C SUP)* Y Indicates activation of the Photo, Heat or CO element of a Lights FIRE ALARM LED for heat and photo
detector. alarms, will light supervisory LED for CO
alarm, photo and heat alarms will activate
CBE, CO alarm will activate sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
*FlashScan only
Table 3.1 Fire Alarm Type Codes (2 of 2)
• Sends an Alarm message to the LCD display, remote annunciators, History buffer, installed
printers, and CRT-2s.
• Latches the control panel in MN alarm. (You can not return the control panel to normal
operation until you correct the alarm condition and reset the control panel)
• Initiates any Control-By-Event actions
• Activates special zone ZFD (Not applicable for First Command applications)
• Sends an Alarm message to the proprietary receiver via the network, if applicable
• Sends an MN Supervisory message to the LCD display, remote annunciators, History buffer,
installed printers, and CRT-2s.
• Initiates any Control-By-Event actions
• Activates special zone ZFE
• Sends an MN Supervisory message to the proprietary receiver via the network, if applicable
• Sends an MN trouble message to the LCD display, remote annunciators, History buffer,
installed printers, and CRT-2s.
• Initiates any Control-By-Event actions
• Activates special zone ZFF
• Sends an MN Trouble message to the proprietary receiver via the network, if applicable
Latching
Type Code Purpose What it does
(Y/N)
Monitor Modules
ECS/MN MONITOR1 Y Indicates activation of a mass notification device Activates CBE, does not light any LEDs,
overrides existing fire event2, shuts off
silenceable outputs and all fire activated
strobes
ECS/MN SUPL1 Y Indicates activation of a mass notification device Lights SUPERVISORY LED and activates
CBE
ECS/MN SUPT N Indicates activation of a mass notification device Lights SUPERVISORY LED and activates
CBE
ECS/MN TROUBLE N Indicates trouble on a mass notification device Monitors mass notification devices. Will
MON1 generate a trouble condition for both open
and short conditions.
1
This Type Code is not compatible with First Command applications.
Table 3.2 Mass Notification Type Codes
NOTE: If a fire alarm exists when a trouble exists, the SYSTEM TROUBLE LED lights, but the Alarm
message appears in the LCD display.
NOTE: Pressing the SIGNAL SILENCE key when only troubles exist, gives the same result as
pressing the ACKNOWLEDGE/SCROLL DISPLAY key. The SIGNALS SILENCED LED does not light unless
an alarm exists in the system.
2. The control panel sends an Acknowledge message to the remote annunciators, history buffer,
installed printers, and CRT-2s.
Status banner Time and date of Acknowledge
ACKNOWLEDGE
03:15P 041508 Tue
3. Check the trouble message for the location and type of trouble.
TROUBL MONITOR MODULE ADDRESS M021 Z00 OPEN CIRCUIT 08:10A 042108 2M021
TROUBL MONITOR MODULE ADDRESS M022 Z00 OPEN CIRCUIT 08:12A 042108 2M022
4. Correct the condition causing the trouble. If the trouble clears, the control panel sends a Clear
Trouble message to the History buffer and installed printers FDU-80 annunciators, and
CRT-2s.
If all troubles clear and no supervisory signals or fire alarms exist, the control panel does the fol-
lowing:
• Returns to Normal operation (indicated by the “System Normal” message)
• Sends a “System Normal” message to the LCD display, History buffer and installed printers,
FDU-80 annunciators, and CRT-2s
• Restores troubles automatically - even if troubles are not acknowledged
If multiple trouble conditions exist in the system, the LCD and optional CRT-2 and FDU-80s auto-
matically step through each trouble every 3 seconds in the following order:
1. Alarms, in order of address
2. Supervisory, in order of address
3. Troubles, in order of address
Press the ACKNOWLEDGE/SCROLL DISPLAY key and the display stops on the current trouble event
for 1 minute, then begins to automatically step through remaining troubles. To manually step
through remaining troubles, press the ACKNOWLEDGE/SCROLL DISPLAY key.
Refer to Appendix D, “Point and System Troubles Lists”, on page 72 for explanations of troubles
that appear on the display.
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALS SILENCED LED is
lighted), a Security alarm will resound the panel sounder.
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALS SILENCED LED is
lighted), a Security alarm will resound the panel sounder.
1. Press the ACKNOWLEDGE/SCROLL display key to silence the panel sounder and switch the
SECURITY LED from flashing to steady—regardless of the number of troubles, alarms,
supervisory, and security signals. The control panel sends a Security message to the remote
annunciators, history buffer, installed printers, and CRT-2s.
2. Correct the condition that activated the Security point.
3. When you finish correcting the Security condition, press the SYSTEM RESET key to return the
control panel to normal operation (indicated by the “System Normal” message). The control
panel sends a “System Normal” message to the LCD display, remote annunciators, history
buffer, installed printers, and CRT-2s.
Monitor Modules
Latching
Type Code Purpose What it does
(Y/N)
AREA MONITOR Y Monitors area surveillance equipment, such Lights SECURITY LED, activates CBE
as motion detectors
SECURITY Y Monitors security switches for tampering Lights SECURITY LED, activates CBE
SYS MONITOR Y Monitors critical equipment for security Lights SECURITY LED, activates CBE
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALS SILENCED LED is
lighted), a Supervisory alarm will resound the panel sounder.
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALS SILENCED LED is
lighted), a Supervisory alarm will resound the panel sounder.
1. Press the ACKNOWLEDGE/SCROLL DISPLAY key to silence the panel sounder and switch the
SUPERVISORY LED from flashing to steady—regardless of the number of troubles, alarms, and
supervisory signals. The control panel sends a Supervisory message to the remote
annunciators, history buffer, installed printers, and CRT-2s.
2. Correct the condition that activated the supervisory point.
3. When you finish correcting the latching supervisory condition, press the SYSTEM RESET key to
return the control panel to normal operation (indicated by the “System Normal” message). The
control panel sends a “System Normal” message to the LCD display, remote annunciators,
history buffer, installed printers, and CRT-2s.
If Non-latching Type Code Displays
Some Supervisory Type Codes do not latch the control panel. (Refer to Table 3.4 for a list of these
type codes). The control panel automatically returns to normal operation, when you correct the con-
dition that activates the supervisory point. If the control panel indicates a non-latching supervisory
point, take the following action:
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALS SILENCED LED is
lighted), a Supervisory alarm will resound the panel sounder.
1. Press the ACKNOWLEDGE/SCROLL DISPLAY key to silence the panel sounder and switch the
SUPERVISORY LED from flashing to steady—regardless of the number of troubles, alarms, and
supervisory signals. The control panel sends a Supervisory message to the remote
annunciators, history buffer, installed printers, and CRT-2s.
2. Correct the condition that activated the supervisory point.
3. The control panel automatically returns to normal operation (indicated by the “System
Normal” message) and the control panel sends a “System Normal” message to the LCD
display, remote annunciators, history buffer, installed printers, and CRT-2s.
Monitor Modules
Latching
Type Code Purpose What it does
(Y/N)
WATERFLOW S Y Indicates supervisory condition for activated waterflow switch Lights SUPERVISORY LED and activates CBE
RF SUPERVSRY N Monitors a radio frequency device Lights SUPERVISORY LED and activates CBE
LATCH SUPERV Y Indicates latching supervisory condition Lights SUPERVISORY LED and activates CBE
TRACK SUPERV N Indicates tracking supervisory condition Lights SUPERVISORY LED and activates CBE
SPRINKLR SYS Y Indicates activation of sprinkler system Lights SUPERVISORY LED and activates CBE
TAMPER Y Indicates activation of tamper switch Lights SUPERVISORY LED and activates CBE
Detectors
SUP.T(DUCTI) N Ion detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.L(DUCTI) Y Ion detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUPT(DUCTL) N Laser detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUPL(DUCTL) Y Laser detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.T(DUCTP) N Photo detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.L(DUCTP) Y Photo detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUPT(PHOTO) N Photo detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.L(PHOTO) Y Photo detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.T(ION) N Ion detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.L(ION) Y Ion detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.L(LASER) Y Laser detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
SUP.T(LASER) N Laser detector that indicates supervisory (non-alarm) condition Lights SUPERVISORY LED and activates CBE
PHOTO/CO (C SUP)* Y Indicates activation of the Photo, Heat or CO element of a Activation of the Heat or Photo elements will
detector. light an indicator at the control panel.
Activation of the CO element will light the
SUPERVISORY LED. Activates CBE.
PHOTO/CO (P SUP)* Y Indicates activation of the Photo, Heat or CO element of a Activation of the Heat element will light an
detector. indicator at the control panel.
Activation of the CO element will not light
and indicator at the control panel.
Activation of the Photo element will light the
SUPERVISORY LED. Activates CBE.
*FlashScan only
NOTE: For detailed information on Pre-Alarm applications, refer to the NFS2-640 Programming
Manual.
• Alert – a non-latching condition that causes a Pre-Alarm when a detector reaches the
programmed Pre-Alarm level.
• Action – a latching condition that causes a Pre-Alarm when a detector reaches the programmed
Pre-Alarm level.
Responding to a Pre-Alarm Warning
The Pre-Alarm screen display is the same for both alert and action conditions. Following is a sam-
ple screen for a Pre-Alarm message.
An Alert Pre-Alarm automatically restores to normal when the detector sensitivity, programmable
to one of nine settings, drops below the programmed Alert level. Zone F09 automatically clears
when no Pre-Alarm conditions exist.
An Action Pre-Alarm latches until you reset the system - even if the detector sensitivity drops
below the Action level. Zone F09 activates - but Zone Z00 (general alarm) and the trouble and
alarm relays do not activate. The fifth zone programmed, not the first four, in the detector’s CBE
activates. A subsequent alarm condition for this detector clears the Action indication from the LCD
display.
Interpreting Pre-Alarm Type Codes
The Type Code that displays in the Pre-Alarm warning indicates the function of the point that initi-
ates the Pre-Alarm warning. Refer to the Detectors section of Table 3.1 for the Type Codes that can
appear in a Pre-Alarm warning, and for descriptions of those Type Codes.
CAUTION:
! DISABLING A ZONE DISABLES ALL INPUT AND OUTPUT DEVICES ASSOCIATED WITH THE
ZONE.
When one or more points are disabled, the control panel does the following:
• Holds all disabled output points in the off-state
• Flashes the SYSTEM TROUBLE LED
• Lights the POINT DISABLED LED
• Sends a Disabled Point message to the LCD display, History buffer and installed printers,
FDU-80 annunciators, and CRT-2s
• Displays a message for each disabled point
Monitor Modules
Latching
Type Code Purpose What it does
(Y/N)
ACCESS MONTR N Used for monitoring building access Activates CBE
ACK SWITCH N Performs Acknowledge function Silences panel sounder, gives an
Acknowledge message on the panel LCD
ALLCALL PAGE N Activates all speaker circuits for paging Activates speakers
DRILL SWITCH N Performs Drill function Activates silenceable outputs
FIRE CONTROL N Used for air handler shutdown, intended to override Activates CBE, does NOT light an
normal operating automatic functions indicator at the control panel
NON-FIRE N Used for energy management or other non-fire Activates CBE, does NOT light an
situations. Does not affect operation of the control panel indicator at the control panel
PAS INHIBIT N Inhibits Positive Alarm Sequence Inhibits Positive Alarm Sequence
RESET SWITCH N Performs Reset function Resets control panel
SIL SWITCH N Performs Signal Silence function Turns off all activated silenceable outputs
TELE PAGE N Performs function of Page Button on FFT-7 Allows remote paging to a fire area
ABORT SWITCH N Indicates Active at the panel Aborts activation of a releasing zone
• Sends a CO Alarm message to the LCD display, remote annunciators, History buffer, installed
printers, and CRT-2s.
• Latches the control panel in CO alarm. (You can not return the control panel to normal
operation until you correct the CO alarm condition and reset the control panel)
• Initiates any Control-By-Event actions—activiates ZFC.
1. Check the Alarm message for the location and type of trouble.
2. Correct the condition causing the CO alarm.
3. When you finish correcting the CO alarm condition, press the SYSTEM RESET key to return the
control panel to normal operation (indicated by the “System Normal” message). The control
panel sends a “System Normal” message to the LCD display, History buffer and installed
printers, FDU-80 annunciators, and CRT-2s.
Latching
Type Code Purpose What it does
(Y/N)
Monitor Modules
CO Monitor* Y Indicates activation of a CO conventional detector Activates CBE, does not light an indicator
at the control panel.
Detectors
PHOTO/CO* Y Indicates activation of the Photo, Heat, or CO element of a Lights FIRE ALARM LED for photo and heat,
detector. no LED will light for a CO alarm. Photo and
heat will activate CBE, CO alarm activates
special function zone FC and sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
PHOTO/CO (P SUP)* Y Indicates activation of the Photo, Heat or CO element of a Lights FIRE ALARM LED for heat, no LED will
detector. light for a CO alarm, supervisory LED will
light for photo alarm, heat and photo will
activate CBE, CO alarm activates special
function zone FC and sixth CBE zone only
(sixth CBE zone programmable via VeriFire
Tools)
Latching
Type Code Purpose What it does
(Y/N)
PHOTO/CO (C SUP)* Y Indicates activation of the Photo, Heat or CO element of a Lights FIRE ALARM LED for heat and photo
detector. alarms, will light supervisory LED for CO
alarm, photo and heat alarms will activate
CBE, CO alarm will activate sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
4. When the trouble condition is corrected, the panel will return to normal operation (indicated by
the “System Normal” message).
5. The control panel sends a “System Normal” message to the LCD display, History buffer and
installed printers, FDU-80 annunciators, and CRT-2s.
Table 3.8 Control Module and NAC Circuit Trouble Type Codes (1 of 2)
Table 3.8 Control Module and NAC Circuit Trouble Type Codes (2 of 2)
2. The control panel sends an Acknowledge message to the History buffer and installed printers,
FDU-80 annunciators, and CRT-2s. Check the trouble message for the location and type of
trouble.
3. Correct the condition causing the trouble.
4. When the trouble condition is corrected, the panel will return to normal operation (indicated by
the “System Normal” message).
5. The control panel sends a “System Normal” message to the LCD display, History buffer and
installed printers, FDU-80 annunciators, and CRT-2s.
The LCD display shows the current selections for System Functions, which includes the three sys-
tem timers.
Sample LCD display of a System Function screen with system timer selections:
Silence Inhibit Timer set to 180 seconds
Auto Silence Timer set to 600 seconds
Alarm Verification Timer set to 30 seconds
SIL INH=180 AUTO=600 VERIFY=30 USA TIME
TERM=N AC-DLY=Y LocT BLINK=01 ST=4 ACS=N
NOTE: In firmware version 18.x (or higher), silenceable outputs activated from a WATERFLOW
type code activation can be silenced if the silenceable waterflow option is enabled via VeriFire
Tools.
4.1 Introduction
This section contains instructions and sample screens to show how to access all Read Status func-
tions and menus. For information on Read Status using a CRT-2 refer to “Remote Terminal Access”
on page 64.
NOTE: If a fire alarm or trouble occurs while you are in Read Status, the control panel
automatically exits Read Status operation and displays the new fire alarm or trouble.
For example, the block to the left shows how to display the “Read Point” screen:
2. From the “Entry” screen, press the 2 key. The control panel displays the “Read Status Options”
screen as shown below:.
READ POINT=0 HIST=2 ALARM HIST=4 <ENTER>
PRNT POINT=1 HIST=3 ALARM HIST=5 <ENTER>
NOTE: If attempting to read a point that is not installed, the control panel displays “Not Installed”.
During all Read Status operations (except print operations) the control panel starts a 2-minute timer
each time you press a key. If the control panel does not detect a key press for 2 minutes, the control
panel exits Read Status and returns to the “System Normal” display.
In Read Status, you can also do the following:
• Press the ESC key to delete the previous entry.
• Press the SYSTEM RESET key to abort Read Status.
4.4.1 How to View Read Status of Devices, Zones, & System Settings
Overview
Read Point options 0, 2, and 4 in the Read Status Screen let you display and view information for
devices and zones programmed into the control panel, as well as view system and annunciator set-
tings. This section provides instructions and sample displays so you can view Read Status.
Topics covered in this section:
ZONE=Z,AA,E DETECTOR=*,LDAAA,E
MODULE=#,LMAA,E OUTPUT CKT=8,AA,E
• To view a detector, press DETECTOR , SLC number, detector SLC address, ENTER.
• To view a zone, press , zone number, ENTER.
• To view a monitor or control/relay module, press MODULE , SLC number, module SLC
address, ENTER.
• To view a NAC, press OUTPUT , two-digit address, (for example 01 for B01, etc.), ENTER.
When you select a device or a zone, the control panel displays information for the device or zone,
but does not send this information to the serial ports or the History buffer.
How to View Read Status for a Detector
From the “Read Status” screen, press 0, then press the ENTER
key. You can now view Read Status for a detector as follows:
SLC number followed by three press DETECTOR, enter the SLC number followed by the three
digit address
digit address, then press the ENTER key. For example, to read
next device the status of detector 1D002: press DETECTOR, enter the SLC
number (1), enter address 002, then press the ENTER key. The
previous device control panel now displays information about the detector, as
shown in Figure 4.1.
NOTE: Refer to “Detector Sensitivity Settings” in the NFS2-640 Programming Manual for more
information on the Pre-Alarm and Alarm Sensitivity settings
• Device Status The status of the module: control/relay module [On (device active) OFF (device
not active] or monitor module (Normal, Alarm, or Test).
• Type Code The software Type Code that identifies the type of module. (Refer to “Point
Programming” in the NFS2-640 Programming Manual.)
• CBE list Only the first zone in the device’s CBE list will be displayed.
• Device SLC Address The SLC address of the module.
• Switch Inhibit (control/relay module only) Displays whether the remote ON/OFF capability
of the device is inhibited. (I=on; *=off).
• Silenceable (control/relay module only) A selection that specifies if the device can be
silenced during an alarm by pressing the signal silence key. Possible values are:
* = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by trouble
O = silenceable, does not resound
NOTE: If the “Strobe” Type ID is used with System Sensor Strobe synchronization, F, U, B, T, or
O will silence the entire circuit, “*” will silence the horn portion only.
Walk Test (control/relay module only) A selection that specifies if the device will activate
during a Walk Test.
How to View Read Status for a NAC
From the “Read Status” screen, press 0, then press the ENTER
key. You can now view Read Status for a NAC as follows:
Device address press OUTPUT, enter the device address, then press the ENTER
next device
key. For example, to read the status of NAC 0-2: press OUT-
PUT, enter 02, then press the ENTER key. The control panel
previous device now displays information for a NAC as shown in Figure 4.3.
• Device Status The status of the device: ON (device active) OFF (device not active).
• Type Code The software Type Code that identifies the type of NAC. Refer to “Appendix F -
Type Codes” in NFS2-640 Programming Manual.
• CBE List Only the first zone in the NAC’s CBE list will be displayed here.
• Device Address The address of the NAC (01-04)
• Switch Inhibit A selection for disabling the switch function for the control/relay or
transponder output circuit. (I=on; *=off).
• Silenceable A selection that specifies if the device can be silenced during an alarm by pressing
the SIGNAL SILENCE key. Possible values are:
* = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by trouble
O = silenceable, does not resound
NOTE: If the “Strobe” Type ID is used with System Sensor Strobe synchronization, F,U, B, T,
or O will silence the entire circuit, “*” will silence the horn portion only.
• Walk Test A selection that specifies if the device will activate during a Walk Test.
How to View Read Status for a Software Zone (Z01-Z99)
From the “Read Status” screen, press 0, then press the ENTER
key. You can now view Read Status for a Software Zone as fol-
Software lows: press Z, enter the zone number (01-99), then press the
Zone Number
ENTER key. For example, to read the status of Software Zone 07:
next device press Z, enter 07, then press the ENTER key. The control panel
now displays information for a Software Zone as shown below.
previous device
Zone status (ON or OFF) Custom zone label for the zone
Zone label for zones 01-99 entered in during program Change
NOTE: The zone label depends on the type of Special Zone. For example, CODING FUNCTION
CODE TYPE for F8.
NOTE: Special Function Zones FA, FB, and FC are represented in VeriFire Tools as ZF10,
ZF16, and ZF18, respectively.
To view the next three annunciator selection screens, press the (NEXT SELECTION) key.
S2 ANNUN SELECTION2: A12=* A13=* A14=*
A15=* A16=* A17=* A18=* UDACT=N
If UDACT=N, the control panel displays the Annunciator Selections 3 and 4 screen, addresses
A20-A32, as shown below:
S3 ANNUN SELECTION3: A20=* A21=* A22=*
A23=* A24=* A25=* A26=* A27=* A28=*
• SEC_RLY and SUP_RLY (0= turn on by Fire Alarm, 1= turn on by Security, 2= turn on by
Supervisory).
• BAT_SIZE (1= battery size is greater than 26 Ahr, 0= less than 26 Ahr).
• C_DRILL (custom drill N= No custom drill, Y= Yes).
• TERM_DATA (0= LCD80 Terminal using 7 bit data, 1= LCD80 Terminal using 8 bit data).
• PRT_BAND (0= 2400, 1= 4800, 2= 9600).
NOTE: Please refer to the VeriFire Tools help file for information on programming the above
screen.
An Annunciator Selection screen shows the information that will display on the ACS annunciators.
The table above contains the ACS display selections. Annunciators set to annunciator address 1 to
19 can be programmed to any one of the above selections. If t here is a UDACT or UDACT-2,
selections A-M will be sent to Annunciator addresses 20 to 32 respectively.
NOTE: An ACS selection marked with an asterisk (*) indicates no annunciator selection.
The figure above shows annunciator selections for addresses A1-A2 (addresses A3-A10, marked
with asterisks, are not selected).
• Annunciators set to annunciator address 1 (A1) display the status of detectors 1-64 on SLC 1
(ACS Selection Group H)
• Annunciators set to annunciator address 2 (A2) display the status of intelligent modules 1-64
on SLC-1 (ACS Selection Group C).
4.4.2 How to View Read Status for Event and Alarm History
Overview
The control panel maintains a History buffer of the last 800 events, each with a time and date
stamp. History events include the following:
• All alarms, troubles and operator actions, such as: Acknowledge, System Reset, Signal
Silence, Drill, and Walk Test.
• Programming entries (Program Change and Status Change, but not Read Status), along with a
number (0-9) indicating the programming submenu (for example, 0=Clear). For an example,
see Figure 4.18.
You can view events from the History buffer in two forms: by displaying all events (option 2,
HIST=2) or by displaying alarm events only (option 4, ALARM HIST=4).
NOTE: The History buffer contains 800 events total, including the alarm events that display for
Alarm history. The control panel generates Alarm history from the alarm events that exist in the
800-event History buffer.
NOTE: The NEXT SELECTION key will show the most recent event first, and then move to its
normal function of displaying the oldest events first.
NOTE: The NEXT SELECTION key will show the most recent event first, and then move to its
normal function of displaying the oldest events first.
NOTE: Before printing, make sure your control panel is connected to a compatible printer and
the printer is configured according to the manufacturer’s specifications, and that the correct baud
rate is selected at the panel.
STATUS PRINT
HISTORY PRINT
A sample printout of three events in history using the History Print option:
******************** EVENT HISTORY START****************************************
SYSTEM RESET 02:28P 042408 Thu
ALARM: SMOKE (ION) DETECTOR ADDR 1D075 Z002 02:28P 042408 1D075
ALARM: SMOKE (ION) DETECTOR ADDR 1D076 Z002 02:28P 042408 1D076
ACKNOWLEDGE 02:28P 042408 Thu
A sample printout of two alarm events in the History buffer using the Print Alarm History option.
********************ALARM HISTORY START ****************************************
ALARM: SMOKE (ION) DETECTOR ADDR 1D075 Z002 02:28P 012208 1D075
ALARM: SMOKE (ION) DETECTOR ADDR 1D076 Z002 02:28P 012208 1D076
******************* PRINT END ****************************************
4.4.4 How to View and Print Hidden Event and Alarm History
The control panel maintains a copy of the History buffer. For instance, if someone clears the His-
tory buffer using Status Change programming option 4, the control panel retains a copy of the His-
tory buffer. The copy of the preceding History buffer is called a Hidden History buffer and a copy
of the preceding Alarm History is called a Hidden Alarm History buffer.
If you attempt to view or print history and the control panel displays one of the screens shown
below you can use the options listed in the table below to view the contents of a Hidden History
buffer.
HISTORY EMPTY (ESCAPE TO ABORT)
****************************************
Options for viewing and printing Hidden History and Hidden Alarm History do not appear in the
LCD display when in Read Status. You can view and print the contents of these Hidden History
buffers using the options listed in the table below. You read and print Hidden History and Hidden
Alarm History the same way you read and print history using the options that appear on the “Read
Status” screen. The table also contains references to the sections that contain instructions for read-
ing and printing history.
To Press Refer to
A.1 Overview
This section contains information for operating the control panel as detailed in the topics listed
below:
The control panel provides ten Releasing Zones (R0-R9). These are special zones that you can use
for up to ten independent releasing operations. This section contains descriptions of each Releasing
Function option and an example of how Releasing Zone options work.
For instructions on programming Releasing Functions, refer to the NFS2-640 Programming Man-
ual.
Each Releasing Zone includes the following releasing options:
Option Description
Cross Zone Cross Zones let you program the control panel to activate a Releasing
Zone when two or more detectors or modules are alarmed. Cross Zone
selections are:
Y Two or more detectors are alarmed that are mapped to one of the ten
Releasing Zones (R0-R9)
Z Two or more detectors are alarmed that are mapped to two different
Software Zones and mapped to one of the ten Releasing Zones (R0-R9).
H At least one smoke detector mapped to one of the ten Releasing Zones
(R0-R9) is alarmed and at least one heat detector mapped to the same
Releasing Zone as the smoke detector is alarmed.
N Cross Zones not used
Delay Timer Select a 0–60 second delay before activating a zone.
Abort An Abort Switch Type Code used to abort activation of a zone.
Manual Release Allows immediate zone activation by overriding the abort function,
cross-zone function, and delay timer.
Soak Timer Automatically shuts off the releasing device after a preprogrammed period
of time. Select 0001-9999 seconds for a Soak Timer or 0000 seconds for
no Soak Timer.
A sample LCD display of a Releasing Function selected for Releasing Zone R1:
Status (On or Off) Releasing Function status banner Releasing
Zone R1
CBE list = O1 R1
CBE list = O2 R1
CBE list = 02 R1
CBE list = R1
Software
Zone Z01
Releasing
Zone ZR1
NAC
B03
Listing of each Cross Zone option and the conditions required to activate the Releasing Zone,
according to the example shown in Figure A.2.
The control panel also provides Time Control zones F5 and F6 for time and date control functions
and zone F7 for holiday functions.
or
NOTE: For instructions on programming the Time function, refer to the NFS2-640 Programming
Manual.
The LCD display shows the current selections for the Time Control function. The figure below
shows a sample LCD display of a Time Control function:
Status ON (ON time in effect)
Time Function status banner
ON TIME FUNCTION TIME CONTROL
ON=07:00 OFF=15:00 DAYS=SMTWTF*H F05
ON time for
devices that list Zone F5
F5 Day-of-week selections
OFF time for devices (H=holiday selected)
that list F5
NOTE: For instructions on programming the Holiday function, refer to the NFS2-640
Programming Manual.
The LCD display in Figure A.5 gives an example of an LCD display of a Holiday function:
Status ON (holiday function not in effect)
Holiday Function status banner
NOTE: You can turn a NON FIRE control point on and off, by listing zone F5 or F6 in the CBE list
of a control/relay module.
You can use Time Control zones F5 and F6 to program non-fire applications such as turning lights
on and off, setting a thermostat, and so on. For example, you can program zones F5 and F6 to acti-
vate outputs at one time of day and deactivate outputs at later time, on specified days of a week.
Table A.3 contains descriptions of additional Time Control applications:
Application Requirement
Control day and night sensitivity of List zone F5 or F6 in the detector CBE. This
intelligent, addressable detectors automatically sets the detector sensitivity to the
minimum setting (AL:9) during the day and
automatically returns detector sensitivity to
programmed sensitivity during the evening.
Control a specific date of year Input up to nine date in the Holiday selection screen
for Special Zone F7, then list zone F7 (Holiday) in the
CBE of a device.
The table below contains descriptions of the signals that correspond to each NAC Code Type:
NOTE: For instructions on programming the Coding function, refer to the NFS2-640
Programming Manual.
The LCD display shows the current selections for the Code Type. Figure A.6 shows a sample LCD
display of a Code Type selection of March Time:
Status Coding Function status banner
OFF CODING FUNCTION CODE TYPE
MARCH TIME F08
Coding selection Zone F08
NOTE: Presignal differs from the Alarm Verification Timer which does not require human
intervention.
• A Presignal Delay Timer (60-180 seconds) that delays activation of all outputs with a CBE that
includes Special Zone F0.
• A PAS selection, in addition to the Presignal Delay Timer, that allows a 15-second time period
for acknowledging an alarm signal from a fire detection/initiating device. If the alarm is not
acknowledged within 15 seconds, all local and remote outputs activate immediately and
automatically.
An illustration of Presignal and PAS timing.
Presignal Delay Timer (60-180)
PAS (15s)
NOTE: For instructions on programming the Presignal function, refer to the NFS2-640
Programming Manual.
The LCD display shows the current selections for the Presignal function. The figure below shows a
sample LCD display of a Presignal function selected for PAS and a Presignal Delay Timer of 60
seconds:
Status Off Presignal Function status banner
NOTE: If any monitor modules are programmed with a PAS INHIBIT Type Code and a fire alarm
occurs, zone F0 goes false and aborts the Presignal Delay Timer.
A.5.4 How to Respond to an Alarm with Presignal Delay Timer (no PAS)
If an alarm occurs with a Presignal Delay Timer (60-180 seconds), the control panel displays the
type of device and the SLC address of the device causing the alarm. If a second alarm occurs during
the Presignal Delay Timer, the control panel aborts the Presignal Delay Timer and activates all pro-
grammed outputs. A sample Alarm screen for a monitor module is shown below:
The FIRE ALARM LED flashes and the panel sounder pulses a steady tone. The control panel latches
until the alarm is corrected and you press the SYSTEM RESET key to reset the control panel. You
have the duration of the Presignal Delay Timer (60-180 seconds) to respond to the alarm before the
control panel automatically activates all outputs programmed to F0. You can take the following
actions:
• To silence the panel sounder and change the FIRE ALARM LED from flashing to steady, press
the ACKNOWLEDGE/SCROLL DISPLAY key.
• To abort the Presignal Delay Timer, press the SYSTEM RESET key.
• To manually activate all outputs programmed to F0, press the DRILL key. The Manual Evacuate
screen appears, the panel sounder pulses and the FIRE ALARM LED changes from flashing to
steady. The Manual Evacuate screen and Alarm screen display alternately at 3-second
intervals.
If the Presignal Delay Timer reaches its programmed value, without operator intervention, the con-
trol panel activates all outputs programmed to F0.
NOTE: These outputs do not delay for Presignal operations without PAS selected.
If a second alarm occurs during the Presignal Delay Timer, the control panel aborts the Presignal
Delay Timer and activates all programmed outputs.
A sample Alarm screen for a monitor module:
The FIRE ALARM LED flashes and the panel sounder pulses a steady tone. The control panel latches
until the alarm is corrected and you press the SYSTEM RESET key to reset the control panel. You
have 15 seconds to acknowledge the alarm or the control panel automatically activates all outputs
programmed to F0. If you acknowledge the alarm within 15 seconds, the control panel increases the
delay time to the full Presignal Delay Timer (60-180 seconds). You have the duration of the Presig-
nal Delay Timer to respond to the alarm before the control panel activates all outputs programmed
to F0. You can take the following actions:
• To increase the delay to the full programmed Presignal Delay Timer, press the
ACKNOWLEDGE/SCROLL DISPLAY key. The panel sounder goes silent and the FIRE ALARM LED
changes from flashing to steady.
• To abort the Presignal Delay Timer, press the SYSTEM RESET key.
• To manually activate all outputs programmed to F0, press the DRILL key. The Manual Evacuate
screen appears, the panel sounder pulses and the FIRE ALARM LED changes from flashing to
steady. The Manual Evacuate screen and Alarm screen display alternately at 3-second
intervals.
If the Presignal Delay Timer reaches its programmed value, without operator intervention, the con-
trol panel activates all outputs programmed to F0.