Conductor Test Report: Sample Details

The document reports on test results for a 1000mm copper conductor bar sample. Resistance, resistivity, and conductivity were measured at ambient temperature, 20C, and 75C according to IEC-60851-5:2008. Conductivity was found to be 99.482% which meets the declared specifications.

Uploaded by

txr qc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
225 views1 page

Conductor Test Report: Sample Details

The document reports on test results for a 1000mm copper conductor bar sample. Resistance, resistivity, and conductivity were measured at ambient temperature, 20C, and 75C according to IEC-60851-5:2008. Conductivity was found to be 99.482% which meets the declared specifications.

Uploaded by

txr qc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

QSF-QC-07

Conductor Test Report Ver:01, Rev:00

PO No 1239 Sample No: 1


Check Date 04.09.2021 Tested By: Adex Engineering Ltd.
Supplier: Ripon Enterprise

Sample Details:
Length 1000 mm Conductor Size 120 X 3 mm
Insulation Thickness (mm) N/A Temperature 27 °C
Conductor Type Rectangular Copper Bar

Test Data: The following test were conducted as per IEC-60851-5:2008 standard.
Parameter At Ambient Temperature At 20 °C At 75 °C
Resistance
49.5 48.138255 58.83768
(μΩ)
Resistivity
0.00001782 1.73298E-05 2.11816E-05
(Ω-mm )
Conductivity
99.482
%

Insulation Breakdown Voltage (KV) Leakage Current (mA)


N/A N/A

Summary:
Parameter Decleared Measured
Conductor Size (mm) 120.00 X 3.00 #### X 3.0
Covered Conductor Size (mm) N/A X N/A N/A X N/A
Insulation Thickness (mm) N/A N/A
Resistivity at 20°C (Ω-mm) N/A 1.73298E-05
Conductivity (%) 99 99.48
Insulation Breakdown Voltage (KV) N/A N/A

Observations: Conductivity of this sample copper sheet is good.

_____________________________
Testted By:
MD. Islam Hossain
Engineer (QA &QC)
Adex Engineering Ltd.