The document discusses Elastimold fused elbows which are molded fuse products that provide full-range current-limiting fusing and 15/25 kV hotstick-operable, loadbreak elbow switching to improve distribution system reliability without adding separate switchgear. The elbows have EPDM molded rubber construction, fuse ratings from 3-80 amps, and have been tested per applicable IEEE, ANSI and industry standards.

Uploaded by

Juan Montenegro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views10 pages

Molded Fuse Products

The document discusses Elastimold fused elbows which are molded fuse products that provide full-range current-limiting fusing and 15/25 kV hotstick-operable, loadbreak elbow switching to improve distribution system reliability without adding separate switchgear. The elbows have EPDM molded rubber construction, fuse ratings from 3-80 amps, and have been tested per applicable IEEE, ANSI and industry standards.

Uploaded by

Juan Montenegro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Elastimold® Cable Accessories

Molded Fuse Products


Fused Elbows
The fastest, most cost-effective way to improve a distribution
system’s reliability
Probe
Upper Elbow
Half Replace existing 200 A tap elbows with Elastimold® Fused Elbows to protect
light-duty underground distribution systems, including sub-loops, radial taps, junctions,
transformers and other equipment.
Probe Lug
Elastimold® Fused Elbows provide full-range current-limiting fusing with 50 kA interrupting
capability. They are rated for 5 kV ungrounded to 28 kV grounded Wye. Plus they provide
15/25 kV hotstick-operable, loadbreak elbow switching.
Fuse

Crimp Lug

Hose Clamp Lower Elbow


Half

Combined Full-Range Current-Limiting Fusing 15/25 kV Hotstick-Operable, Loadbreak Elbow Switching Quickly improve the distribution
system’s reliability without the expense of adding a separate piece of switchgear or replacing existing sectionalizing cabinets.

High Fault Close Rating Current-limiting fuses improve the fault close rating of the elbow (10 kA) to that of the fuse, thereby reducing the risk
of component damage or personnel injury.

EPDM Molded Rubber Deadfront Construction Elbows are fully sealed and submersible, and they insulate, shield and eliminate exposed live parts.

Two-Piece Housing Enables easy fuse replacement.

Application Information Ratings


• Construction: Submersible, non-venting, deadfront,
corrosion resistant System Voltage Class (kV) 15 25* 25/28*

• Ambient Temperature Range: -30°C to 65°C Nominal Fuse Voltage (kV) 8.3 15.5 17.2
Rated Maximum Fuse Voltage (kV) 8.8/10 15.5 17.2
Frequency (Hz) 50/60 50/60 50/60
Certified Tests
BIL Impulse Withstand (kV) 95 125 140
Elastimold® Fused Elbows have been designed and tested per One-Minute AC Withstand (kV) 34 40 45
applicable portions of IEEE, ANSI and other industry standards,
Fifteen-Minute DC Withstand (kV) 53 78 78
including:
Corona Extinction (kV) 11 19 21.5
ANSI C37.40 Standard for Current-Limiting Fuse Service Conditions
Symmetrical Interrupting Capability (Amp) 50,000 50,000 50,000
ANSI C37.41 Standard for Current-Limiting Fuse Design and Testing
Current Rating (Amp) 3–80 6–20 3–45
ANSI C37.47 Standard for Current-Limiting Fuse Ratings
* The 15.5 kV L-G rated fuse requires 75% grounded load to be applied on a 25 kV system.
and Specifications The 17.2 kV L-G rated fuse requires at least 75% grounded load to be applied on a 28 kV system.
IEEE 386 Standard for Separable Connectors Fuses are only suitable for the system voltage class shown if the recovery voltage across the fuse
will not exceed its rated maximum voltage. For three-phase applications, this generally requires that
protected transformers be gndY–gndY and have at least 50% grounded load. Fuse replacement requires
the elbow to be de-energized.

A70 w w w. tnb.c a
Elastimold® Cable Accessories

Molded Fuse Products


Fused Elbows
Electrical Characteristics of Elastimold® EFX-E Elbow Fuses

Current Maximum Continuous Peak Arc Total l2t Maximum


System Voltage Nominal Fuse Rated Max. Current (2) (6)
Rating Cat. No. Minimum Melt l2t (A2-Sec)
Class (kV) Voltage Rating (kV) Voltage (kV)
(A) 25ºC 40ºC 65ºC (kV) (A2-Sec) (3) (4)
3 EFX083003-E 4.3 4.2 3.9 30 100 350
6 EFX083006-E 9.5 9.0 8.5 32 620 2,7
8 EFX083008-E 11.5 11.0 10.5 28 800 4
10 EFX083010-E 14.0 13.5 13.0 28 800 4
12 EFX083012-E 19.0 18.5 17.5 26 920 8
18 EFX083018-E 10.0 21.0 20 19.0 26 1,31 9,5
15 8.3 20 EFX083020-E 26.0 25 24.0 26 1,62 11
25 EFX083025-E 34.0 33.0 31.0 26 3,66 22
30 EFX083030-E 37.5 36.5 34.5 26 5,25 30
40 EFX083040-E 43.0 42.0 40.0 26 8,7 50
45 EFX083045-E 49.0 47.0 45.0 26 12,8 70
65 EFX083065-E 70.0 68.0 64.5 23 34 200
8.8
80 EFX083080-E 80.0 77.5 73.5 22 51,2 280
6 EFX155006-E 8.5 8.0 7.7 52 620 3
8 EFX155008-E 10.5 10.0 9.5 40 800 4,3
10 EFX155010-E 13.0 12.5 12.0 40 800 4,3
25 15.5 15.5
12 EFX155012-E 16.0 15.5 15.0 38 920 8
18 EFX155018-E 20.0 19.5 18.5 38 1,62 13
20 EFX155020-E 23.5 22.5 21.5 38 2,2 16,5
3 EFX172003-E 4.3 4.2 3.9 51 100 510
6 EFX172006-E 9.5 9.0 8.5 54 620 3,25
8 EFX172008-E 11.5 11.0 10.5 46 800 4,6
10 EFX172010-E 14.0 13.5 13.0 46 800 4,6
12 EFX172012-E 18.0 17.5 16.5 43 920 8,5
25/28 17.2 18 EFX172018-E 17.2 20.0 19.5 18.5 45 1,31 10
20 EFX172020-E 24.0 23.0 22.0 45 1,62 12,5
25 EFX172025-E 31.5 30.5 29.0 45 3,66 27,5
30 EFX172030-E 35.5 34.5 32.5 45 5,25 37,5
40 EFX172040-E 41.0 40.0 38.0 45 8,7 62,5
45 EFX172045-E 46.0 45.0 42.5 45 12,8 87,5
1. Designs have a 50,000 A RMS Symmetrical Rating (except 3 A, 17.2 kV — which was tested at 44 kA maximum).
2. Fuses have a Rated Maximum Application Temperature (RMAT) of 65º C. RMAT is the maximum temperature of the air, in contact with the elbow housing,
at which fuses have been shown to be suitable for use.
3. Tabulated Maximum Total I2t values are for currents of 50,000 A at the nominal voltage of the fuse. Values for 8.3kV fuses at 10kV are approximately 30% higher.
Values for 17.2 kV fuses at 15.5 kV are approximately 20% lower.
4. Maximum total I2t values are reduced for currents below 50,000A. For example, at 10,000A, maximum total I2t values are approximately 15% less than the published values.
5. Peak arc voltages listed are for 50,000A currents at the rated maximum voltage listed. Reduced currents and voltages will reduce the peak arc voltage. For more information, contact your T&B Regional Sales Office.
6. Maximum continuous currents at ambient temperatures other than those listed may be determined by derating the fuses by 0.2% per degree C over 25ºC. For example:
At 40ºC the derating would be 15 x 0.2 = 3%, making the maximum continuous current of a 17.2kV, 25A fuse 31.5 x 0.97 = 30.5 A.
7. Time-current characteristic curves are published at 25ºC. Reduction in the long time melting current of the fuses (approximately one hour and longer) due to higher ambient
temperatures is the same as described above for “maximum continuous currents.”

w w w. tnb.c a
A71
Elastimold® Cable Accessories

Molded Fuse Products


Fused Elbows
Recommended Elastimold® EFX-E Elbow Fuse at 40ºC Ambient Temperature

Recommended Fuse Current Ratings (Amperes)


Fuse Voltage 8.3 kV 15.5 kV (17.2 kV)
1-Phase Transformer 1-Phase Voltage Rating (kV), Phase to Ground
Transformer 2.4 4.16 4.8 7.2 7.62 12 14.4 16
kVA
A B A B A B A B A B A B A B A B
10 — 6 — 6a — 3 — 3 — 3 — 6a — 6a — (3a)
15 — 10 — 6 — 6a — 3 — 3 — 6a — 6a — (3a)
25 12 20 — 8 — 8 — 6 — 6 — 6a — 6a — -3
37.5 20 25 — 12 — 12 — 8 — 6 — 6 — 6a — (6a)
50 25 40 18 20 12 20 10 12 — 10 — 6 — 6 — (6a)
75 45 65 20 30 20 25 12 20 12 18 — 10 — 8 — -8
100 65 80 30 45 25 40 18 25 18 25 12 18 10 12 — -10
167 — — 65 80 45 65 25 45 25 45 18 -25 18 20 -12 -20
250 — — 80 — 80 — 45 65 45 65 -25 -45 20 -30 -20 -30
333 — — — — — — 65 — 80 — -40 — -30 -45 -25 -45
500 — — — — — — — — — — — — -45 — -45 —

Recommended Elastimold® EFX-E Elbow Fuse at 40ºC Ambient Temperature

Recommended Fuse Current Ratings (Amperes)


Fuse Voltage 8.3 kV 15.5 kV (17.2 kV)

1-Phase Transformer 1-Phase Voltage Rating (kV), Phase to Ground


Transformer 2.4 4.16 4.8 7.2–7.96 8.32 12.47 13.2–14.4 20.8 22.9–24.9
kVA
A B A B A B A B A B A B A B A B A B
15 — 6 — 3 — 3 — 3a — 3a — 6a — 6a — 6a — (3a)
22.5 — 8 — 6a — 6a — 3 — 3 — 6a — 6a — 6a — (3a)
30 10 12 — 6 — 6 — 6a — 3 — 6a — 6a — 6a — (3a)
45 12 20 — 10 — 8 — 6 — 6a — 6a — 6a — 6a — (3a)
75 20 30 12 20 — 12 — 8 — 8 — 6 — 6 — 6a — -3
100 30 45 18 25 18 20 — 12 — 10 — 8 — 8 — 6a — (6a)
112.5 40 65 20 25 18 25 — 12 — 12 — 8 — 8 — 6 — (6a)
150 45 80 25 40 20 30 18 20 12 20 10 12 10 12 — 6 — -6
200 65 80 40 65 30 45 20 25 18 25 12 18 12 18 8 10 — -8
225 80 — 45 65 40 65 20 30 20 25 12 20 12 18 8 10 — -10
300 — — 65 80 45 80 30 45 25 40 18 25 18 25 12 18 — -12
500 — — — — 80 — 65 80 45 80 30 45 30 45 18 -25 -18 -25
750 — — — — — — 80 — 80 — 45 65 45 — -25 -45 -25 -40
1 — — — — — — — — — — 80 — — — -40 — -40 —
1. Column A = 140–200% of transformer rating and Column B = 200–300% of transformer rating.
2. Ratings in parenthesis are 17.2 kV fuses.
3. 8.3 kV, 3–45 A fuses and 15.5 kV, 6–20A fuses are used in the small (size 1) elbow housing; 8.3 kV, 65–80 A fuses and 17.2 kV, 3–45 A fuses are used in the large (size 3) elbow fuse housing.
4. Recommended fuses meet inrush criteria of 12 times transformer full-load current for 0.1 second and 25 times transformer full-load current for 0.01 second.
Fuses also meet cold-load pickup criteria of 6 times transformer full-load current for 1 second and 3 times transformer full-load current for 10 seconds.

a. Fuse allows greater than 300% of transformer rating.

A72 w w w. tnb.c a
Elastimold® Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
The following diagram shows how to construct a catalogue number for Fuse Housings and Full-Range Current-Limiting Fuses.

Indicates field that must be filled in to complete order. 168FLR1 274FLR1 168FLR3 A = 8-7⁄8 in. (225 mm)
274FLR3 A = 9-1⁄4 in. (235 mm)
8-7⁄8 in. 9-1⁄4 in.
(225 mm) (235 mm)
F L R Ø A

Fuse Test Port


Conductor Size 6-1⁄4 in.
A Two Direct Test Ports (159 mm) 6-1⁄4 in.
180 6 – (159 mm)
Blank Two Capacitive Test Points
190 – 4

Nominal Fuse 200 4 – 10-1⁄2 in.


Voltage Rating Housing (270 mm)
210 – 2
168 8.3 kV 1 Small 220 2 1 10-5⁄8 in.
3 Large** (270 mm) 10-5⁄8 in.
274 15.5 kV 230 1 1/0 (270 mm)
274 17.2 kV 240 1/0 2/0
Cable Insulation
Diameter (in.) 250 2/0 3/0

A 0.575 in.–0.740 in. 15–19 mm 260 3/0 4/0

B 0.635 in.–0.905 in. 16–23 mm 270 4/0 – 10-5⁄8 in.


(270 mm)
C 0.805 in.–1.060 in. 20–27 mm
1. All dimensions rounded up to the nearest eighth inch.
D 0.890 in.–1.220 in. 25–31 mm 2. Also available with direct test port.
3. Dimensions with Direct Test Port units are 10-1⁄4 in. (260 mm) or 10-5⁄8 in. (270 mm).
4. 168FLR3 uses a large housing with a 15 kV, 200 A elbow interface.
* Small Housing is used with 8.3kV (3–45A) and 15.5kV (6–20A) rated fuses.
** Large Housing is used with 8.3kV (65A and 80A) and 17.2kV (3–45A) rated fuses.

Indicates field that must be filled in to complete order.


E F X E
8.3 kV (3–45 A)/15.5 kV (6–20 A) Fuse
9-1/4 in.
(235 mm)

Amperage Rating
2-1/4 in.
(54 mm) Voltage Rating 003 8.3/17.2 kV 3A
083 8.3 kV 006 8.3/15.5/17.2 kV 6A
155 15.5 kV 008 8.3/15.5/17.2 kV 8A

8.3 kV (65–80 A)/17.2 kV (3–45 A) Fuse 172 17.2 kV 010 8.3/15.5/17.2 kV 10 A


012 8.3/15.5/17.2 kV 12 A
018 8.3/15.5/17.2 kV 18 A
020 8.3/15.5/17.2 kV 20 A
2-1/4 in.
(54 mm) 025 8.3/17.2 kV 25 A
030 8.3/17.2 kV 30 A
040 8.3/17.2 kV 40 A
13-1/2 in.
(343 mm) 045 8.3/17.2 kV 45 A
065 8.3 kV 65 A
080 8.3 kV 80 A
All dimensions rounded up to the nearest eighth inch.

w w w. tnb.c a
A73
Elastimold® Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Application Information Ratings
Construction: Submersible, non-venting, deadfront, corrosion resistant
System Voltage Class (kV) 5 15 25/28* 35
Ambient Temperature Range:
Rated Maximum Fuse Voltage (kV) 5.5 8.3/10** 15.5/17.2** 23
• -30°C to 65°C for 6–50 A fuses;
Frequency (Hz) 50/60 50/60 50/60 50/60
• -30°C to 40°C for >50 A fuses.
BIL Impulse Withstand (kV) 60 95 125/140 150
One-Minute AC Withstand (kV) 34 34 40–45 50
Certified Tests
Fifteen-Minute DC Withstand (kV) 53 53 78 103
Elastimold® Molded Current-Limiting Fuses have been designed and Corona Extinction (kV) 11 11 19/21.5 26
tested per applicable portions of IEEE, ANSI, NEMA and other industry Symmetrical Interrupting Capability (A) 50 50 50 50
standards, including: Current Rating (A) 80–180 10–115 10–100 10–50
ANSI C37.40 Standard for Current-Limiting Fuse * 15.5 kV L-G rated fuses require 75 % grounded load to be applied on a 25 kV system.
** 17.2 kV L-G rated fuses require at least 75 % grounded load to be applied on a 28 kV system.
Service Conditions
ANSI C37.41 Standard for Current-Limiting Fuse Fuse replacement requires the MCLF to be de-energized.
Fuses are only suitable for the system voltage class shown if the recovery voltage across the fuse will not
Design and Testing exceed its rated maximum voltage. For three-phase applications, this generally requires that protected
transformers be gndY-gndY and have at least 50 % grounded load.
ANSI C37.47 Standard for Current-Limiting Fuse
Ratings and Specifications
ANSI/IEEE 386 Standard for Separable Connectors and
Bushing Interfaces

Interchangeable Replaceable Molded Rubber


Molded Rubber Current-Limiting Fuse
End Fittings

Assembled Fuse Unit

Assembled Fuse Unit with Optional


Wall-Mounting Bracket

A74 w w w. tnb.c a
Elastimold® Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Electrical Characteristics of Encapsulated Fuses Used in MCLF
Maximum
Fuse Rated Continuous Maximum Total
Nominal Fuse Current Peak Arc Minimum
Maximum Current l2t
Voltage Rating Rating Catalogue Total l2t Melt l2t
Voltage (2) (6) (A2–Sec)
(kV) (A) Number (kV) (5) (A2–Sec)
(kV) (3) (4)
25°C 40°C
80 M05CLF080 86 84 22,100 110,000
100 M05CLF100 108 105 56,700 280,000
5.5 125 M05CLF125 5.5 137 133 15 109,200 530,000
150 M05CLF150 159 154 176,000 860,000
180 M05CLF180 185 180 259,000 1,270,000
10 M15CLF010 14 13 28 800,000 4,000
20 M15CLF020 23 22 1,620 11,000
30 M15CLF030 10.0 35 33 5,250 30,000
26
40 M15CLF040 43 41 8,700 50,000
8.3 50 M15CLF050 51 47 12,800 70,000
65 M15CLF065 73 71 25,200 100,000
80 M15CLF080 87 84 47,000 185,000
8.3 25
100 M15CLF100 106 103 78,300 330,000
115 M15CLF115 120 116 115,150 480,000
10 M25CLF010 14 13 46 800,000 3,700
20 M25CLF020 23 22 1,620 10,000
30 M25CLF030 17.2 35 33 5,250 30,000
45
40 M25CLF040 43 41 8,700 50,000
15.5
50 M25CLF050 47 45 12,800 70,000
65 M25CLF065 68 66 25,200 110,000
80 M25CLF080 15.5 88 84 40 54,400 255,000
100 M25CLF100 100 100 80,000 380,000
10 M35CLF010 14 13 61 800,000 4,800
20 M35CLF020 23 22 1,620 13,000
23.0 30 M35CLF030 23.0 35 33 5,250 38,000
60
40 M35CLF040 41 40 8,700 61,000
50 M35CLF050 47 46 12,800 82,000
1. Designs have a 50,000 A all U/CERMSs Symmetrical Rating.
2. 10–50 A fuses have a Rated Maximum Application Temperature of 65°C, and 65–180 A fuses have a Rated Maximum Application Temperature of 40°C.
(RMAT is the maximum temperature of the air in contact with the MCLF housing at which the fuses have been shown suitable for use.)
3. Tabulated Maximum Total I2t values are for currents of 50,000 A at the nominal voltage of the fuse. Fuses that have a Rated Maximum Voltage higher than their Nominal Voltage Rating will
have a higher I2t let-through when applied at voltages up to these higher values. For example, Maximum Total I2t values are increased by approximately 30% when 8.3 kV fuses are applied at
10kV and approximately 25% when 15.5kV fuses are used at 17.2 kV.
4. Maximum total l2t values are reduced for currents below 50,000 A. For example, at 10,000 A, l2t values are approximately 15% less than the published values.
5. Peak arc voltages quoted are for 50,000A currents at the rated maximum voltage listed. Reduced currents and voltages will reduce the peak arc voltage. Consult the factory for further information.
6. Maximum continuous currents at higher ambient temperatures may be determined by derating the fuses by 0.2% per degree C over 25° C.
For example: At 40°C, the derating would be 15 x 0.2 = 3%, making the maximum continuous current of a 20 A fuse 23.0 x 0.97 = 22 A.

w w w. tnb.c a
A75
Elastimold® Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Recommended MCLF at 40°C Ambient Temperature
Recommended Fuse Current Ratings (Amperes)
Fuse Voltage (5.5 kV) 8.3 kV 15.5 kV 23 kV
Transformer 1-Phase Voltage Rating (kV), Phase to Ground
1-Phase
Transformer kVA 2.4 4.16 4.8 7.2 7.62 12 14.4 16 34.5
A B A B A B A B A B A B A B A B A B
10 — 10a — 10a — 10a — 10a — 10a — 10a — 10a — 10a — 10a
15 — 10 — 10a — 10a — 10a — 10a — 10a — 10a — 10a — 10a
25 — 20 — 10 — 10 — 10a — 10a — 10a — 10a — 10a — 10a
37.5 20 30 — 20 — 20 — 10 — 10 — 10a — 10a — 10a — 10a
50 30 40 20 30 — 20 — 10 — 10 — 10a — 10a — 10a — 10a
75 50 65 30 40 20 30 — 20 — 20 — 10 — 10 — 10 — 10a
100 65 -80 40 50 30 50 20 30 20 30 — 20 — 10 — 10 — 10
167 -100 -150 65 -80 50 65 30 50 30 50 20 30 20 30 — 20 — 20
250 -150 — (100) -125 -80 -100 50 65 50 65 30 50 30 40 20 30 20 30
333 -180 — -125 -180 -100 -150 65 100 65 100 50 65 30 50 30 50 20 40
500 — — -180 — -150 — 115 — 115 — 65 100 65 80 50 — 40 —
750 — — — — — — — — — — 100 — 80 100 — — — —
1 — — — — — — — — — — — — 100 — — — — —

Recommended MCLF at 40°C Ambient Temperature

Recommended Fuse Current Ratings (Amperes)


Fuse Voltage 8.3 kV 15.5 kV (17.2 kV) 23 Kv

1-Phase Transformer 1-Phase Voltage Rating (kV), Phase to Ground


Transformer 2.4 4.16 4.8 7.2–7.96 8.32 12.47 13.2–14.4 20.8 22.9–24.9 34.5
kVA
A B A B A B A B A B A B A B A B A B A B
15 — 10a — 10a — 10a — 10a — 10a — 10a — 10a — 10a — 10a — 10a
22.5 — 10 — 10a — 10a — 10a — 10a — 10a — 10a — 10a — 10a — 10a
30 — 10 — 10a — 10a — 10a — 10a — 10a — 10a — 10a — 10a — 10a
45 — 20 — 10 — 10 — 10a — 10a — 10a — 10a — 10a — 10a — 10a
75 30 40 — 20 — 20 — 10 — 10 — 10a — 10a — 10a — 10a — 10a
100 40 50 20 30 20 30 — 20 — 10 — 10 — 10 — 10a — 10a — 10a
112.5 40 65 20 30 20 30 — 20 — 20 — 10 — 10 — 10a — 10a — 10a
150 50 -80 30 50 30 40 20 30 — 20 — 10 — 10 — 10a — 10a — 10a
200 65 -100 40 65 40 50 20 30 20 30 — 20 — 20 — 10 — 10 — 10a
225 -80 -125 50 65 40 65 30 40 30 50 — 20 — 20 — 10 — 10 — 10a
300 -100 -150 65 -100 65 -80 40 50 30 50 20 30 20 30 — 20 10 20 — 10
500 -180 — -100 -150 -100 -125 65 -80 50 80 30 50 30 50 20 30 20 30 — 20
750 — — -180 — -125 -180 -80 -125 80 115 50 80 50 65 30 50 30 40 20 30
1,000 — — — — -180 — -125 -180 115 — 65 100 65 100 50 65 40 65 30 40
1,500 — — — — — — -180 — — — 100 — 100 — 65 100 65 80 40 —
2,000 — — — — — — — — — — — — — — 100 — 80 — 50 —
1. Column A = 140–200% of transformer rating and Column B = 200–300% of transformer rating.
2. Ratings in parentheses are 5.5kV fuses.
3. Recommended fuses meet inrush criteria of 12 times transformer full-load current for 0.1 second and 25 times transformer full-load current for 0.01 second.
Fuses also meet cold-load pickup criteria of 6 times transformer full-load current for 1 second and 3 times transformer full-load current for 10 seconds.

a. Fuse allows greater than 300% of transformer rating.

A76 w w w. tnb.c a
Elastimold® Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Model 22

19-1⁄2 in. (343 mm)


16-5⁄8 in." (422mm)
8-3⁄16 in.
(208 mm)
5-1⁄8 in.
(130 mm)

Approx. Weight 30 lb. (13.6 kg)


Model 222
23-5⁄8 in. (343 mm)

16-5⁄8 in. (422 mm)


8-3⁄16 in.
(208 mm)
5-1⁄8 in.
(130 mm)

Approx. Weight 35 lb. (15.9 kg)


4 in.
(102 mm)
Model 2222

27-5⁄8 in. (702 mm)

16-5⁄8 in. (422 mm)

9-3⁄16 in.
(233 mm)
5-1⁄8 in.
(130 mm)

4 in. 4 in. Approx. Weight 30 lb. (13.6 kg)


(102 mm) (102 mm)

Model 66

19-5⁄8 in. (498 mm)

16-5⁄8 in. (422 mm)


9/16 in.
(233 mm)
5-1⁄8 in.
(130 mm)

Approx. Weight 40 lb. (18.1 kg)


5-1⁄8 in.
(130 mm)
Model 6E2

Lifting Eye
9⁄16 in. (14 mm) x 1 in.
(25 mm) Mounting
Slots on 5-1⁄2 in.
(140 mm) Centers
18-5⁄8 in. 22-1⁄2 in.
(473 mm) (572 mm)

2-3⁄4 in.
(70 mm)

11-1⁄8 in. Approx. Weight 30 lb. (13.6 kg)


(283 mm) 6-3⁄8 in. 3⁄4 in. (19 mm)
(162 mm)

w w w. tnb.c a
A77
Elastimold® Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Model 6E6 5-1⁄8 in.
(130 mm)

Lifting Eye

9⁄16 in. (14 mm) x 1 in. (25 mm)


Mounting Slots on 22-1⁄2 in.
5-1⁄2 in. (140 mm) Centers (572 mm)

18-5⁄8 in.
(473mm)

2-3⁄4 in.
(70 mm)

11-1⁄8 in. 6-3⁄8 in.


(283 mm) (162 mm) 1⁄2 in.
(13 mm)
Other models are available such as 26.
Approx. Weight 30 lb. (13.6kg)

The following diagram shows how to construct a catalog number for a Molded Current-Limiting Fuse:
Indicates field that must be filled in to complete order.

M C L F

Voltage Class Mounting Brackets


5 5.0 kV Amperes
WMB Wall Mounting Bracket with Parking Stands and
Bolted Style Hold Down Straps (HDS)
15 15.0 kV 5 kV 15 kV 25 kV 35 kV
25 25.0 kV 10 — 10 10 10 WMBQ Wall Mounting Bracket with Parking Stands and
Quick Release Style Hold Down Straps (QRS)
35 35.0 kV 20 — 20 20 20 See page A79 for additional options.
See page A75 for additional options. 30 — 30 30 30
Bushings
50 — 40 40 40
22 200 A Bushing Wells both ends
65 — 50 50 50 200 A Bushing Well on one end and two 200 A
222 Bushing Wells on the other end
80 — 65 65 —
2222 Two 200 A Bushing Wells on both ends
100 80 80 80 —
66 600 A Bushings on both ends
115 100 100 100 —
6E2 600 A Elbow Connector on one end and a 600 A Bushing on
125 — 115 — — 6E6 the other end; this arrangement is not available at 35 kV
150 125 — — — See outline drawings preceding this chart for additional details.
200 150 — — —
See page A75 for additional options.

A78 w w w. tnb.c a
Elastimold® Cable Accessories

Molded Fuse Products


Full-Range Molded Current-Limiting Fuses
Mounting Options
32-3/4 in. (832 mm)

29-3/4 in. (756 mm)

5-1/2 in. 6-3/4 in.


(140 mm) (171 mm)
15 to 60˚

Approx. Weight 8 lb. (3.6 kg) 9/16 in. (14 mm) x 1 in. (25 mm)
Mounting Slots
Optional WMB Mounting Bracket with Adjustable Optional — TMA Universal Tilt Mounting
Parking Stands for Vertical Mounting and Fuse Hold-Down Strips

Optional Fuse Mountings


Option No. Description
HDS Bolted-Style Hold-Down Strap (Qty: 1 required per end fitting)
QRS Quick-Release Style Hold-Down Strap (Qty: 1 required per end fitting)
WMB Wall-Mounting Bracket with Parking Stands and Bolted-Style Hold-Down Straps
WMBQ Wall-Mounting Bracket with Parking Stands and Quick-Release Style Hold-Down Straps
SMB Support Mounting Bracket for use with Models 6E2 or 6E6 end-fitting arrangements includes Bolted-Style Hold-Down Strap
TMA-EM Tilt Mounting Adapter bolts to bottom of Wall-Mounting Bracket WMB or WMBQ to enable up to 60º angle mounting (Qty: 2 required per installation)
The option number may be added as a suffix to the MCLF catalogue number.

End Fitting Catalogue Numbers


Option No. Description System Voltage Class IEEE 386-1995 Interface Reference
EF2 200 A Bushing Well End Fitting 5, 15, 25, 35 Figure 3
EF22 Double 200 A Bushing Well End Fitting 5, 15, 25, 35 Figure 3
EF6 600 A Bushing End Fitting 5, 15, 25, 35 Figures 11 and 13
EF6E 600 A Elbow Connector End Fitting 5, 15, 25 Figure 11
EF6E is equipped with a standard through-hole spade lug (Type 03700).
Use this table only if end fittings are to be ordered and shipped separately from the fuse. See pages A77-A78 for assembled units.

Assembly/Disassembly Tool
3/8 in. (10 mm)
Sq. Drive

3/16 in. (5 mm) Hex

Other Options
Option No. Description
MCLF-ADT Hex Wrench for set screw removal and replacement when disassembling end fittings. Supplied as standard with replacement fuses.

w w w. tnb.c a
A79