s 9 221

PXC64-U

DESIGO™ PX
.
Automation stations PXC...-U .
.
.
modular model .
.
.
.
• Freely programmable modular automation stations for HVAC and building .
.
services. .
• Native BACnet automation station with communication via BACnet over .
Ethernet / IP, LON, or PTP .
.
• BTL label (meets B-AAC requirements) .
• PPC processor for high performance and reliable operation .
.
• Comprehensive management and system functions (alarm management, time .
scheduling, trends, remote management, access protection etc.) .
.
• An Integrated Web server supports generic or graphic Web operation as well
.
as transmission of alarms by e-mail or SMS .
• P-bus for connection of external PTM I/O modules with any data point mix .
.
• 64 or 128 load units per automation station .
• Integration platform for subsystems and 3rd party systems .
.
• For stand-alone applications or for use within a device or system network .
• Supports the following methods of operation: .
.
– QAX... room units
.
– Local or network-compatible operator units .
– PX-WEB (operation via Web browser, touch panel or PDA) .
.

CA1N9221en Building Technologies


23.09.2005 Building Automation
Functions

These freely programmable automation stations provide the infrastructure for the
provision and processing of system-specific and application-specific functions.
Apart from the freely programmable control functions these units comprise integrated
convenient management functions such as:
• Alarm management with alarm routing throughout the whole network. Three level
alarm management (simple, basic and enhanced) with safety control transmission
and automatic transmission monitoring
• Time schedulers
• Trend functions
• Remote management functions
• Access protection for the whole network with individually defined user profiles and
categories

Programming language These automation stations are freely programmable with the D-MAP programming
language (follows closely CEN Standard 1131). All function blocks available in libraries
are graphically linked with the plant operating programs.
.
Communication .
.
.
BACnet / IP Communication is via Ethernet with the international standard BACnet protocol. .
Both peer-to-peer communications with other automation stations and connections to .
.
the PXM20-E operator units are supported. .
.
.
BACnet / LON The devices communicate via an open LonTalk system in accordance with the inter- .
national standard BACnet protocol. Both peer-to-peer communications with other .
automation stations and connections to the PXM20 operator units are supported. .
.
.
BACnet / PTP The devices communicate via the public telephone network in accordance with the .
.
international standard BACnet protocol. .
.
.
.
Types .
.
.
Device Type .
Automation station for the Integration via PXA30-K11, PXC00-U .
.
without a P-Bus interface .
Automation station for 64 load units *) PXC64-U .
.
Automation station for 128 load units *) PXA-C128-U .
Connecting cable (to connect an operator unit PXM10 or PXM20 and PXA-C1 .
.
for Firmware download) .
.
.
*) 1 load unit = 12.5 mA (see data sheets of the I/O modules PTM1…) .

2/12

Building Technologies PXC...-U – Automation stations modular model CA1N9221en


Building Automation 23.09.2005
Compatibility
.
.
.
Extension modules network .
.
.
Module PXA30-T PXA30-N PXA30-NT PXA30-W1 PXA30-W2 .
Function .
Data sheet N9261 N9262 N9263 N9264 N9265 .
.
Interfaces .
Ethernet RJ45 X X X X .
.
Serial RS232 X X X X .
.
Network functions
.
Configuration network RJ45 X X X X .
.
BACnet / IP operation RJ45 X X X X .
BACnet / LON operation X .
.
PTP Dial-in DTS and X-Works RS232 1) X X X X .
1) .
PPP Remote configuration RS232 X X .
Remote management .
.
PTP Dial-in Desigo Insight RS232 1) X X X X .
1) .
PPP via Ethernet RJ45 X X .
.
Web-Functions .
Generic web functions X X .
.
Graphic web functions X .
Send alarms via SMS (RS232) X X .
.
Send alarms via E-Mail (RJ45) X X .
.
1) .
Per PXC or PXA30-W... , either the PTP or the PPP function is possible / configurable .
.
.
.
Extension modules for the integration of subsystems .
.
Module PXA30-K11 PXA30-RS .
Function .
Data sheet N9280 N9281 .
.
Interfaces .
.
KNX interface X .
Ethernet RJ45 X .
.
Serial RS232 X .
Seral RS485 X .
.
Network functions .
Integration of RXB X .
.
Integration of Synco X .
.
Integration of KNX 3rd party devices X .
Integration of M-Bus counters X .
.
Integration of Modbus X .
.
.
.
I/O-Modules .
.
Device Type Data sheet .
.
I/O modules with basic functions measuring, signalling, switching and controlling PTM1... 8111 bis 8171 .
.
I/O OPEN modules for pumps PTM5... 866x .
I/O OPEN modules PTM1...,PTE 978x .
.

3/12

Building Technologies PXC...-U – Automation stations modular model CA1N9221en


Building Automation 23.09.2005
.
Operation There are various options for operation of the PXC…U automation stations: .
• QAX... room unit connected to the PPS2 interface. A maximum of five room units .
.
QAX… (not QAX5…) can be connected. Details on the PPS2 communication are .
described in the DESIGO Technical principles manual (chapter "I/O blocks", section .
.
"PPS2 addressing"). .
• Local PXM10 operator unit, either plugged into the automation station or connected .
.
via PXA-C1 cable
.
• Network-compatible PXM20 operator unit (BACnet / LON) .
for operation of the local automation station or an automation station in a network, .
.
either plugged into the automation station, or connected via PXA-C1 cable .
• Network-compatible PXM20-E operator unit (BACnet / IP) .
.
for operation of the local automation station or an automation station in a network, .
either plugged into the automation station, or connected to the Ethernet network or .
.
an Ethernet switch.
.
• PX-WEB: The PXA30-W… extension module is used to activate the Web server, .
allowing operation with a Web browser, a touch panel or a PDA. .
.
The transfer of alarms via SMS or e-mail can be configured in the automation .
station. .

Technology

The data between the automation station and the I/O modules are exchanged via the 3-
core P-bus.. Each module on the same P-bus is provided with its own address between
1 and 255. The addresses are set with address plugs.

The automation stations provide the connected I/O modules with a DC 23 V supply.

The automation station load by I/O modules is expressed by the number of load units of
12.5 mA each (details of the calculation of the total load see the I/O module range
document CM2N8100).

4/12

Building Technologies PXC...-U – Automation stations modular model CA1N9221en


Building Automation 23.09.2005
Design

6
7
8 00255a

4
1
5

1 Plug-in unit
2 Front cover .
(a PXM... operator unit can be fitted instead of the front cover) .

3 Battery
4/5 Extension modules
6 Device socket
7 Plug-in connection for automation station for device supply and bus
electronics
8 Housing with pcb for device supply
9 Plug-in terminal blocks with reversible support bar (here used for wall
mounting)

00256 A
LED indicators
Service pin

COM1 COM2

RUN STA INFO TX SERVICE TX SERVICE

5/12

Building Technologies PXC...-U – Automation stations modular model CA1N9221en


Building Automation 23.09.2005
Concerned LED Color Status Function
Automation station RUN Green Continuously off No supply
Continuously on Supply OK, firmware OK
Red Continuously on RESET key pressed
STATUS Red Continuously off Normal operation
Continuously on Hardware fault detected during self-test or
automation station in "coma" operating state
Quick flashes No validly licensed firmware
INFO Red Freely programmable
.
Data traffic LON bus TX COM1 Yellow Flashing Data traffic on LON bus .
COM2 Yellow Inactive .
.
SERVICE Red Continuously off LON node is configured .
COM1 Flashing LON node is not configured .
Flashing acc. to wink Physical identification of automation station .
.
command pattern *) after receiving wink command .
Continuously on LON chip defect or service key was pressed .
.
again .
COM2 Red Inactive .
.
Data traffic Ethernet / IP TX COM1 Yellow Inactive .
.
(PXA30-N..., PXA30-W...) COM2 Yellow Flashing Sends Ethernet data .
SERVICE .
.
COM1 Red Inactive .
COM2 Red Continuously off Ethernet OK .
.
Flashing slowly IP address not configured
.
Continuously on No link pulse .
.
*) Wink command rhythm pattern:
21s 00408

5 Hz 5 Hz

2s 1s 2s 1s

Mounting instructions

The modular automation stations are particularly suitable for control panel front
mounting as well as flush-panel and wall mounting.
For control panel front mounting the device socket is held in place by clamps at all four
corners (no tools required for mounting). The upper housing is fixed to the device .
.
socket with two screws. .
For flush panel mounting the plug-in terminal blocks can be repositioned whilst at the
same time reversing the support bars to enable front access. The support bars absorb
the screw force and also provide the means of fixing the device to the wall.
.
Instead of the front cover a PXM... operator unit can be fitted on the modular auto- .
mation station. .
.
Note For PXM20-E mounting (ethernet cable) see the mounting instructions delivered with .
.
the operator unit! .
.
STOP Note! • Insert the PXA30… extension module fully into its socket (to a depth of 1.5 mm), .
.
using slight force. Then check that the plug is safely snapped on to ensure safe .
and smooth functioning. .
.
• Do not touch the connector pins (electrostatic discharge) .

6/12

Building Technologies PXC...-U – Automation stations modular model CA1N9221en


Building Automation 23.09.2005
Commissioning

In order to prevent equipment damage and/or personal injuries always follow local
safety regulations and the required safety standards.
.
STOP Caution! Electronic parts may be damaged if the upper housing is inserted or .
.
disconnected with the supply voltage switched on (hot plugging). .

Loading plant operating Download the plant operating program to the automation station with the PX Design
program tool in the DESIGO TOOLSET, direct via the RJ45 connector or the LON bus.

Setting parameters and Use the PX Design tool in the DESIGO TOOLSET for setting the control parameters
configurations and the configuration data. Data visible in the network can also be changed with the
.
PXM… operator unit. .

Wiring test It is possible to test field devices and the wiring as soon as the power supply is
connected, without first downloading the plant operating program.
.
The test is carried out with a PXM20 or PXM20-E operator unit. .

Network connection The network addresses are configured with the DESIGO TOOLSET. In order to provide
a unique identification in the LON network press the service pin with a sharp implement
(COM1 on the front, see page 4) or send a wink command to the relevant automation
station (service LED flashes).

Service functions Three service buttons are provide under the front cover:
.
A Connected to If this key is pressed during a restart (Power- .
00257
Force LON-Bus fail) the current D-MAP program is deleted .
from the FLASH. .
Firmware .
A B RESET Download The automation station waits a short while for .
the signal to activate the FWLoader and then .
starts the automation station.. .
Connected to If this key is pressed for >5 s, the automation .
.
Ethernet / IP station waits for a firmware download via .
Ethernet. .
B Pressing this button during a restart forces a .
cold start. .
Force .
Cold Start .
RESET Forces a restart .
.

Maintenance

Battery life Lithium batteries usually have a life span of at least four years. The automation station
automatically sends a system event in order to indicate a low charge.
After the "Battery low" event there are several months of remaining life span.

Battery change To change the battery, remove the front cover. As long as the supply voltage is .
.
connected, the battery may be removed for unlimited time. .

STOP Caution! To prevent hardware damage by electrostatic discharge (ESD), a wrist strap with earth
cable must be used during the battery change.

7/12

Building Technologies PXC...-U – Automation stations modular model CA1N9221en


Building Automation 23.09.2005
Disposal

The unit contains electric and electronic components and must not be disposed of with
domestic waste. Lithium battery, printed circuit board and housing must be disposed of
separately
The local and actual regulations must be observed.

Technical data

General device data Operating voltage AC 24 V ± 20 %


Safety extra-low voltage SELV
Protective extra-low voltage PELV HD 384
Frequency 50/60 Hz
Current consumption 4A
Power consumption PXC64-U 45 VA
PXA-C128-U 95 VA
Internal fuse Thermic, automatic reset
.
Operating data Processor MOTOROLA Power PC 32 Bit .
Memory space FLASH 16 MByte
SDRAM 32 MByte
SRAM 2 MByte
Data backup in case of power failure
Applications, parameter (FLASH) > 10 years
Run-time data (battery) > 4 years (battery)

.
Ethernet interface Interface type 100BaseTX, IEEE 802.3 compatible .
(extension modules Bit rate 10 / 100 Mbit/s, auto-sensing .
.
PXA30.N, PXA30.W…) Protocol BACnet over UDP/IP .
Connection RJ45 socket, screened .
Wiring Cable type Standard CAT5 .
.
UTP (Unshielded Twisted Pair) .
or STP (Shielded Twisted Pair) .
.
Cable length Max. 100m .
LON bus interface Network TP/FT-10
Baud rate 78 kBit/s
Protocol BACnet .
Interface chip Echelon Processor TMPN3150B1AF .
Wiring Cable type 2-core, twisted pair, unscreened
Cable length Max. 450 m in free topology
Max. 900 m in serial topology
.
Serial interface Interface type RS232 .
Baud rate / Data bits / Stop bit 57 600 bps / 8 / 1 .
.
Parity / Flow control None / None .
Wiring Cable type 9-core standard screened cable .
.
Cable length Max. 3m .
P-bus interface Polling cycle at I/O modules 0.3 s
Transmission speed 62.5 kBaud
Signal level DC +23 V and 0/–5 V
Wiring Cross-section Min. 3 x 0.75 mm2
Cable length Max. 50 m
.
Cable length (special requirements) Max. 200 m .

8/12

Building Technologies PXC...-U – Automation stations modular model CA1N9221en


Building Automation 23.09.2005
Interface, room units Interface type PPS2
Supply class 4
PPS2 baud rate 4.8 kBit/s
Wiring Cable type 4-core, twisted pair, unscreened
Capacitance per unit length Max. 56 nF/km
Single cable length Max. 125 m where A = 1.0 mm2

Connecting cable PXM10 or PXM20 / DESIGO TOOLSET Max. 3 m

Plug-in screw terminal Power supply and signals Stranded of solid conductors,
0.25 … 2.5 mm2 or 2 x 1.5 mm2
LON bus Stranded or solid conductors,
2 x 1.0 mm2

Housing protection standard Protection standard to EN 60529 IP 30


Protection class Isolation protection class II
Ambient conditions Operation Class 3K5 to IEC 721
Temperature 0 ... 50 °C
Humidity < 85 % rh
Transport Class 2K3 to IEC 721
Temperature – 25 ... 65 °C
Humidity < 95 % rh

Industry standards Meets all requirements for B-AAC BACnet Implementation Conformance .
.
Statement (PICS) .
Product safety
Automatic electronic controls for
household and similar use EN 60730-1
Special requirements for energy controllers EN 60730-2-11
Electromagnetic compatibility
Interference immunity EN 50082-2
Emitted interference EN 50081-1
Meets requirements for CE marking:
Electromagnetic compatibility 89/336/EEC
Low Voltage Directive 73/23/EEC

Dimensions See “Dimensions”


Weight Without / with packaging 0.96 / 1016 kg

9/12

Building Technologies PXC...-U – Automation stations modular model CA1N9221en


Building Automation 23.09.2005
Connection terminals
00341
PXC64-U
C1 G
1
C2 G0
8
C3 PD

C4 2 PU

S PC
9
S CP+
4
CLA CP–
10
CLB

MMI/TOOL

G/G0 Supply voltage AC 24 V/PELV


PD P-bus Synchronisation cable
PU Data transmission line, bi-directional
PC Reference voltage DC 23 V (against G0)
CP+/CP– PPS2 bus (for QAX... room operator units) .
CLA/CLB LON bus (inactive, if a PXA30-N... or PXA30-W... extension module .
.
for Ethernet is plugged in)
HMI/TOOL RJ45 socket on front cover
(for PXM10 / PXM20 operator unit or DESIGO TOOLSET)

PXA-C128-U The PXA-C128-U includes a second P-bus:


• Terminals P-bus 1 PD1, PU1 and PC1
• Terminals P-bus 2 PD2, PU2 and PC2
.
PXC00-U The automation station PXC00-U does not have an active P-Bus interface .

Tool socket Standard RJ45 tool socket for LON devices.

12 345 678

1 LON, Data A (CLA) *) 5 Unoccupied


2 LON, Data B (CLB) *) 6 Unoccupied
3206Z01

3 G0, GND 7 COM1/TxD


4 G/Plus 8 COM1/RxD

.
*) The LON pins are inactive, if a PXA30-N... or PXA30-W... extension module for .
Ethernet is plugged in, and in the automation station PXC00-U) .

Connection diagrams

Connection of field devices: see mounting and installation manual for I/O modules and
P-bus (CM2M8102).

10/12

Building Technologies PXC...-U – Automation stations modular model CA1N9221en


Building Automation 23.09.2005
Dimensions

Front mounting

17
55
00232 K

min. 40 mm
22.5
.
.
.

24
max R2 .
.

0
+1
.

25
PXM...

138
+1 .
138
137

150

0
.
.
.
min. 80 mm

15 27 109
min. 100 mm
136
210
For PXM20-E only *)

*) This hole is required for the Ethernet cable .


.
when an operator unit PXM20-E is moun- .
ted on top of the automation station. .

Wall mounting
17

55
min. 40 mm

00233 K
.
.
.
.
18 40,7

.
14,5
PXM...

.
137

150

81

.
.
.
.
22,7

.
5,2 .
min. 80 mm

15 27
.
109 124,5 min. 100 mm
.
136 .
210

11/12

Building Technologies PXC...-U – Automation stations modular model CA1N9221en


Building Automation 23.09.2005
12/12 © 2005 Siemens Schweiz AG Änderungen vorbehalten