PXC64-U
DESIGO™ PX
.
Automation stations PXC...-U .
.
.
modular model .
.
.
.
• Freely programmable modular automation stations for HVAC and building .
.
services. .
• Native BACnet automation station with communication via BACnet over .
Ethernet / IP, LON, or PTP .
.
• BTL label (meets B-AAC requirements) .
• PPC processor for high performance and reliable operation .
.
• Comprehensive management and system functions (alarm management, time .
scheduling, trends, remote management, access protection etc.) .
.
• An Integrated Web server supports generic or graphic Web operation as well
.
as transmission of alarms by e-mail or SMS .
• P-bus for connection of external PTM I/O modules with any data point mix .
.
• 64 or 128 load units per automation station .
• Integration platform for subsystems and 3rd party systems .
.
• For stand-alone applications or for use within a device or system network .
• Supports the following methods of operation: .
.
– QAX... room units
.
– Local or network-compatible operator units .
– PX-WEB (operation via Web browser, touch panel or PDA) .
.
These freely programmable automation stations provide the infrastructure for the
provision and processing of system-specific and application-specific functions.
Apart from the freely programmable control functions these units comprise integrated
convenient management functions such as:
• Alarm management with alarm routing throughout the whole network. Three level
alarm management (simple, basic and enhanced) with safety control transmission
and automatic transmission monitoring
• Time schedulers
• Trend functions
• Remote management functions
• Access protection for the whole network with individually defined user profiles and
categories
Programming language These automation stations are freely programmable with the D-MAP programming
language (follows closely CEN Standard 1131). All function blocks available in libraries
are graphically linked with the plant operating programs.
.
Communication .
.
.
BACnet / IP Communication is via Ethernet with the international standard BACnet protocol. .
Both peer-to-peer communications with other automation stations and connections to .
.
the PXM20-E operator units are supported. .
.
.
BACnet / LON The devices communicate via an open LonTalk system in accordance with the inter- .
national standard BACnet protocol. Both peer-to-peer communications with other .
automation stations and connections to the PXM20 operator units are supported. .
.
.
BACnet / PTP The devices communicate via the public telephone network in accordance with the .
.
international standard BACnet protocol. .
.
.
.
Types .
.
.
Device Type .
Automation station for the Integration via PXA30-K11, PXC00-U .
.
without a P-Bus interface .
Automation station for 64 load units *) PXC64-U .
.
Automation station for 128 load units *) PXA-C128-U .
Connecting cable (to connect an operator unit PXM10 or PXM20 and PXA-C1 .
.
for Firmware download) .
.
.
*) 1 load unit = 12.5 mA (see data sheets of the I/O modules PTM1…) .
2/12
3/12
Technology
The data between the automation station and the I/O modules are exchanged via the 3-
core P-bus.. Each module on the same P-bus is provided with its own address between
1 and 255. The addresses are set with address plugs.
The automation stations provide the connected I/O modules with a DC 23 V supply.
The automation station load by I/O modules is expressed by the number of load units of
12.5 mA each (details of the calculation of the total load see the I/O module range
document CM2N8100).
4/12
6
7
8 00255a
4
1
5
1 Plug-in unit
2 Front cover .
(a PXM... operator unit can be fitted instead of the front cover) .
3 Battery
4/5 Extension modules
6 Device socket
7 Plug-in connection for automation station for device supply and bus
electronics
8 Housing with pcb for device supply
9 Plug-in terminal blocks with reversible support bar (here used for wall
mounting)
00256 A
LED indicators
Service pin
COM1 COM2
5/12
5 Hz 5 Hz
2s 1s 2s 1s
Mounting instructions
The modular automation stations are particularly suitable for control panel front
mounting as well as flush-panel and wall mounting.
For control panel front mounting the device socket is held in place by clamps at all four
corners (no tools required for mounting). The upper housing is fixed to the device .
.
socket with two screws. .
For flush panel mounting the plug-in terminal blocks can be repositioned whilst at the
same time reversing the support bars to enable front access. The support bars absorb
the screw force and also provide the means of fixing the device to the wall.
.
Instead of the front cover a PXM... operator unit can be fitted on the modular auto- .
mation station. .
.
Note For PXM20-E mounting (ethernet cable) see the mounting instructions delivered with .
.
the operator unit! .
.
STOP Note! • Insert the PXA30… extension module fully into its socket (to a depth of 1.5 mm), .
.
using slight force. Then check that the plug is safely snapped on to ensure safe .
and smooth functioning. .
.
• Do not touch the connector pins (electrostatic discharge) .
6/12
In order to prevent equipment damage and/or personal injuries always follow local
safety regulations and the required safety standards.
.
STOP Caution! Electronic parts may be damaged if the upper housing is inserted or .
.
disconnected with the supply voltage switched on (hot plugging). .
Loading plant operating Download the plant operating program to the automation station with the PX Design
program tool in the DESIGO TOOLSET, direct via the RJ45 connector or the LON bus.
Setting parameters and Use the PX Design tool in the DESIGO TOOLSET for setting the control parameters
configurations and the configuration data. Data visible in the network can also be changed with the
.
PXM… operator unit. .
Wiring test It is possible to test field devices and the wiring as soon as the power supply is
connected, without first downloading the plant operating program.
.
The test is carried out with a PXM20 or PXM20-E operator unit. .
Network connection The network addresses are configured with the DESIGO TOOLSET. In order to provide
a unique identification in the LON network press the service pin with a sharp implement
(COM1 on the front, see page 4) or send a wink command to the relevant automation
station (service LED flashes).
Service functions Three service buttons are provide under the front cover:
.
A Connected to If this key is pressed during a restart (Power- .
00257
Force LON-Bus fail) the current D-MAP program is deleted .
from the FLASH. .
Firmware .
A B RESET Download The automation station waits a short while for .
the signal to activate the FWLoader and then .
starts the automation station.. .
Connected to If this key is pressed for >5 s, the automation .
.
Ethernet / IP station waits for a firmware download via .
Ethernet. .
B Pressing this button during a restart forces a .
cold start. .
Force .
Cold Start .
RESET Forces a restart .
.
Maintenance
Battery life Lithium batteries usually have a life span of at least four years. The automation station
automatically sends a system event in order to indicate a low charge.
After the "Battery low" event there are several months of remaining life span.
Battery change To change the battery, remove the front cover. As long as the supply voltage is .
.
connected, the battery may be removed for unlimited time. .
STOP Caution! To prevent hardware damage by electrostatic discharge (ESD), a wrist strap with earth
cable must be used during the battery change.
7/12
The unit contains electric and electronic components and must not be disposed of with
domestic waste. Lithium battery, printed circuit board and housing must be disposed of
separately
The local and actual regulations must be observed.
Technical data
.
Ethernet interface Interface type 100BaseTX, IEEE 802.3 compatible .
(extension modules Bit rate 10 / 100 Mbit/s, auto-sensing .
.
PXA30.N, PXA30.W…) Protocol BACnet over UDP/IP .
Connection RJ45 socket, screened .
Wiring Cable type Standard CAT5 .
.
UTP (Unshielded Twisted Pair) .
or STP (Shielded Twisted Pair) .
.
Cable length Max. 100m .
LON bus interface Network TP/FT-10
Baud rate 78 kBit/s
Protocol BACnet .
Interface chip Echelon Processor TMPN3150B1AF .
Wiring Cable type 2-core, twisted pair, unscreened
Cable length Max. 450 m in free topology
Max. 900 m in serial topology
.
Serial interface Interface type RS232 .
Baud rate / Data bits / Stop bit 57 600 bps / 8 / 1 .
.
Parity / Flow control None / None .
Wiring Cable type 9-core standard screened cable .
.
Cable length Max. 3m .
P-bus interface Polling cycle at I/O modules 0.3 s
Transmission speed 62.5 kBaud
Signal level DC +23 V and 0/–5 V
Wiring Cross-section Min. 3 x 0.75 mm2
Cable length Max. 50 m
.
Cable length (special requirements) Max. 200 m .
8/12
Plug-in screw terminal Power supply and signals Stranded of solid conductors,
0.25 … 2.5 mm2 or 2 x 1.5 mm2
LON bus Stranded or solid conductors,
2 x 1.0 mm2
Industry standards Meets all requirements for B-AAC BACnet Implementation Conformance .
.
Statement (PICS) .
Product safety
Automatic electronic controls for
household and similar use EN 60730-1
Special requirements for energy controllers EN 60730-2-11
Electromagnetic compatibility
Interference immunity EN 50082-2
Emitted interference EN 50081-1
Meets requirements for CE marking:
Electromagnetic compatibility 89/336/EEC
Low Voltage Directive 73/23/EEC
9/12
C4 2 PU
S PC
9
S CP+
4
CLA CP–
10
CLB
MMI/TOOL
12 345 678
.
*) The LON pins are inactive, if a PXA30-N... or PXA30-W... extension module for .
Ethernet is plugged in, and in the automation station PXC00-U) .
Connection diagrams
Connection of field devices: see mounting and installation manual for I/O modules and
P-bus (CM2M8102).
10/12
Front mounting
17
55
00232 K
min. 40 mm
22.5
.
.
.
24
max R2 .
.
0
+1
.
25
PXM...
138
+1 .
138
137
150
0
.
.
.
min. 80 mm
15 27 109
min. 100 mm
136
210
For PXM20-E only *)
Wall mounting
17
55
min. 40 mm
00233 K
.
.
.
.
18 40,7
.
14,5
PXM...
.
137
150
81
.
.
.
.
22,7
.
5,2 .
min. 80 mm
15 27
.
109 124,5 min. 100 mm
.
136 .
210
11/12