DC Machine
DC Machine
1
Yoke (Frame) to dc in case of generators and dc to ac in
case of motors. The ends of armature coils
The stator of a dc machines consists of a
are connected to the commutator, which
frame or yoke, and poles which support the
together with the brushes rectifies the
field windings. The Frame or Yoke in
alternating e.m.f induced in the armature
addition to being a part of a magnetic circuit
coils and helps in the collection of current
serves as mechanical support for entire
Riser
assembly. Commutator segment
Insulating V-groove
Interlopes
Thread bolt
In addition to the main poles, modern direct
current machines are also provided with
interlopes with windings on them in order to
improve commutation under loaded
conditions. They are arranged midway
between the mains poles and are bolted to
the yolk
Riser
Insulating V ring
Commutator
It is mounted on the rotor of a dc machine
and it performs with help of brushes a
mechanical rectification of power: from ac
2
Pressure
Pigtail adjusting lever
B C
N S
Brush holder
A D
Spring
Brush
3
will be induced in the rotating coil and is If the machine has P poles and the armature
given by rotates at N revolutions per minute, then the
e = Blv volts frequency of the induced emf in the
armature is,
As l and v are constant for particular case, PN
f = , Hz
120
e = cons tan t B volts
Hence under the given conditions, the The above discussion clearly indicates that
change in the magnitude of induced e.m.f the e.m.f induced in the armature of a dc
with time depends upon the magnetic flux generator is of alternating nature, alternating
density distribution under the poles. It may with frequency of f hertz depending upon
be assumed neglecting harmonics it is a sine the number of poles in the machine and the
wave distribution. The direction of the speed of the armature.
induced emf in this case can be determined
by Fleming’s right hand rule as shown in However, the output voltage or the current
Figure below. Hence the conductor AB of of dc generator must be unidirectional and
the coil ABCD moves downward and CD that too of a constant value. Thus to compel
moves upward, the direction of the induced the above alternating current to flow in one
emf in the coil is along DCBA as shown in stipulated direction through the external load
Figure 4.7(a). The current in the external circuit, the dc machine is furnished with a
remains the same half a revolution of the special device called the commutator.
coil starting from its vertical position. Figure 4.9 shows that the coil ABCD
connected to a ring commutator split in two
ν
emf
TYPES OF DC GENERATORS
Figure 4.8 Right-hand rule to determine the
direction of induced emf. The field winding and the armature winding
can be interconnected in various ways to
Similarly, in the next half of the revolution,
provide a wide variety of performance
the direction of the induced emf is reversed
characteristics. This can be taken as
and hence the current flows from brush B2 to
outstanding advantages of a dc machines. A
B1 as shown in Figure 4.7(b).The magnitude
dc machine can work as an
of current in the external circuit also varies
electromechanical energy converter only
with time as per sine law; i.e. its magnitude
when its field winding is excited with direct
is not constant with time.
current, except for small dc machines
employing permanent magnets. According
4
to the method of their field excitation dc a self-excited dc machine can be sub-divided
generators are classified into the following as follows:
group:
Series Excitation
a) Separately excited and
The field winding consists of a few turns of
b) Self excited thick wire and is connected in series with the
DC machines may have one or more field armature. In other words, the series field
windings and their method of excitation, current depends on the armature current and
determines the performance characteristics in view of this; a series field may be called a
of the dc machine. current operated field.
A. Separately Excited +
Ise I
Its field winding consists of several L
Important
hundreds turns of fine wire and is connected Ia relationships
to a separate or external dc source i.e. field Series
Winding i. I a L= I se = I L
o
winding are energized from an independent Eg
ii. VL E = V + I (R + Rse )
external sources of dc current. The voltage ga L a a
d
of the external dc source has no relation with
the armature voltage, i.e. the field winding iii. Pdev = E g I a
energized from a separate supply, can be _
designed for any convenient voltage. iv. Pdel = VL I L
+ IL
Important Figure 4.13 Series excited dc machine
relationships
Ia Shunt Excitation
Shunt i. I a = I LL
The field winding consists of a large number
E gV=L VoL + I a Ra
Winding
ii.
Eg
_ a of turns of fine wire and is connected in
+ Vdc
d parallel (or in shunt) with the armature.
iii. Pdev = E g I a Therefore the voltage across the armature
_ terminals and the shunt field is the same and
iv. Pdel = VL I L it is for this reason that a shunt field may be
called voltage operated field.
Ish IL
Figure 4.12 separately excited dc machines +Important
Field relationships
B. Self Excitation Rheostat Ia V
i. I sh L= sh
When the field winding is excited by its own Rsh L
o
armature, the machines is said to be a self Eg VL
a
Shunt
excited dc machine. In these machines, the Winding ii. I a =d I sh + I L
field poles must have a residual magnetism,
so that when the armature rotates, a residual iii. _ E g = VL + I a Ra
voltage appears across the brushes. This
residual voltage should establish a current in
iv. Pdev = E g I a
the field winding so as to reinforce the
residual flux. According the connection of
the field winding with the armature winding, v. Pdel = VL I L
5
Important relationships
Figure 4.14 Shunt excited dc machine i. I a = IIshse
Remember that series field and shunt field E g − I a +(RILa + Rse ) VL
windings are characterized by low and high ii. I sh I=se
=
resistance respectively. In some application, Rsh Rsh
L
iii. I a = I sh + I L V o
Eg
a shunt excited winding may be replaced by Shunt Series
Ia
E g − I a Ra VL + I se Rse+
ii. II sh =
se
L=
Rsh o Rsh
Eg V
I a = I sh + I L d
L
Shunt Series a
Winding iii. Winding
Shunt
iv. E g = VL + I a Ra + I L Rse Series
_
v. Pdev = E g I a
_
vi. Pdel = VL I L
(a) (a)
(b)
6
Figure 4.16 compound excited dc machine (a) Generated emf, Eg= emf generated in one of
cumulative and b) differential the parallel path
On the other hand if series field opposes the Average emf generated / conductor
shunt field so that the resultant air gap flux d
= , volt
per pole is decreased, the machine is called a dt
differentially compounded dc machine as Now, flux cut / conductor in one revolution,
shown in Figure 4.16(b). d = P ,Wb
In Figure 4.15(a), each pole of compound Number of revolution / second
machine is shown to possess shunt and N
= , sec ond
series field windings. Figure 4.17(a) 60
illustrated how these windings are arranged Hence according to Faraday’s law of
on one pole of a dc machine. In Figure 4.17 electromagnetic induction
shunt field coil is placed near yoke and emf generated / conductor
series field coil near the pole shoe just for d PN
sake of clarity. = = , volt
dt 60
For wave winding
Actually physical arrangement of these coils Number of parallel path a = 2
is shown in Figure 4.17 (b). It is seen that Number of conductors (in series) in one path
first shunt field coil is wound around the Z
pole body and over it is then wound the =
2
series field coil. The reasons for placing the
emf generated / path
series field coil outside are:
PN Z ZPN
i. convenience in the = = volt
60 2 2 60
construction and For lap winding
ii. for its better cooling
Number of parallel path a = P
EMF EQUATION OF DC Number of conductors (in series) in one path
GENERATOR =
Z
Let = flux per pole in Weber P
emf generated / path
Z = total number of armature PN Z ZN
conductors = = volt
60 P 60
= Number of slots Number of In general, the Generated emf
conductors per slot
ZN P
P = Number of poles Eg = volt
60 a
a = number of parallel paths in
armature Where, a =2 for wave winding
N= armature rotation in revolutions a=P for lap winding
per minute (rpm) Eg = Ka N
E = emf induced in any parallel path ZP
where, K a = is machine constant.
in armature 60 a
7
Example 4.1 A dc shunt generator supplies rent per armature path, and (iii) emf
a load of 10 kW at 220 V through feeders of generated. Assume a brush contact drop of
resistance 0.1. The resistance of armature 2V.
and shunt field windings is 0.05 and 100 Solution
respectively. Calculate, (i) terminal
i)
voltage, (ii) shunt field current and (iii) Terminal voltage across the armature
generated emf. terminals, V = 200 V
= 10 103 W
V 200
Voltage at the load terminals = 220 V I sh = =
R sh 80
Thus load current, = 2.5A
Pdel 10 103 Load current, IL = 100 A
IL = =
V 220 Armature current, Ia = IL + Ish
= 45.5A
= 100 + 2.5
Resistance of the feeders = 0.1
= 102.5 A
Voltage drop in the feeders = IL 0.1
= 45.5 0.1 = 4.55 V ii) Shunt generator is lap-wound, as such the
Terminal voltage across the armature number of parallel circuits in the armature
winding is equal to the number of poles.
terminals, V = 220 + 4.55
Thus number of parallel circuits a = 4
= 224.55 V Total armature current, Ia = 102.5 A
Shunt field current, Thus the current per armature path,
V' 224.55 =
102.5
I sh = =
R sh 100 4
= 2.25A = 25.625A
iii) Emf generated,
Generated emf,
E g = V + I a R a + Vbd
Eg = V' + Ia R a = 200 + 102.5 0.05 + 2
= 224.55 + 45.5 0.05 = 212.25 V
= 226.82 V
Example 4.3 A short shunt compound
Example 4.2 A 4-pole dc shunt generator generator supplies 200 A at 100 V. The
with lap-connected armature supplies a load resistance of armature, series field and shunt
of 100 A at 200 V. The armature resistance field is respectively, 0.04, 0.03 and 60 .
is 0.1 and the shunt field resistance is 80 Find the emf generated.
. Find (i) total armature current, (ii) cur-
8
Solution 1. It demagnetizes or weakens the main
flux &
Terminal voltage across the load, VL = 100
2. It cross –magnetizes or distorts it
V
Load current, IL = 200 A Let us illustrate (demonstrate) these two
Resistance of series field winding Rse = 0.03 effects of armature reaction for 2-pole d.c
generator. For better understanding let us
see three cases.
Voltage drop in series field winding = IL
Rse Case-I: Figure 4.18 shows the distribution
of magnetic flux when there is no current
= 200 0.03 (Ia=0) in the armature conductors,. For this
=6V case
= 114.07 V
Polar-axis
4.3 ARMATURE REACTION
By armature reaction is meant the effect of
magnetic field set up by armature current on
the distribution of flux under main poles. In
M.N.A
G.N.A
9
Case-II: Figure 4.19, shows the field (or seen to be crowded at the trailing pole tips
flux) set up by the armature conductors but weakened or thinned out at the leading
alone, when current carrying the field coils pole tips (the pole tip which is first met
being unexcited (If = 0). The direction of the during rotation by armature conductors are
armature current is the same as it would be known as the leading pole tip and the other
when the generator is loaded & determined as trailing pole tip). In Figure 4.20 is shown
by Fleming’s Right-hand rule. Under this the resultant mmf OFR which is found by
case, the magnetic fields, which are set up vectorally combining OFm and OFa.
by armature conductor are symmetrical to
G.N.A. and the mmf of the armature o Fm
conductor (depending on the strength of Ia)
is shown separately both in magnitude and Fa FR
direction by the Vector OFa which is parallel
A
Generator
to G.N.A
.N.
rotation
wM
Trailing
pole-tip
.
Ne
o
Generator
rotation
Fa N S
A
Leading .N. Resultant Flux
wM
Polar-axis pole-tip
distribution
G.N.A
Ne
10
.A.
vector can be resolved into two rectangular
M.N
components, Fd parallel to polar axis and Fc X
X
perpendicular to this axis, we find that X
11
Motion Motion commutation, though they do help in
A B C A B C obtaining it.
ii. By the help of inter poles, neutralize
I I the self- reactance voltage by
producing reversing emf. In this
method, arrangement is made to
2I I I neutralize the reactance voltage by
a b c a b c producing a reversing emf in the
12
the generated emf Eg at no load and at
constant given speed.
Main-Poles
N 2. External characteristic-shows the
relationship between the terminal voltage V
S
across the load and the current IL flowing in
N
13
VL II Over-compounded 4.34. Such a compound generator said to be
differential-compound generator.
VNL I Level (flat) compounded Differential compound generators find their
field of application in arc welding where a
large voltage drop is desirable, when the
III Under-compounded
4.6 DC MOTORS
IV
Working principle
Differential compounded
The principle upon which a dc motor works
IL
is very simple. If a current carrying
IFL
conductor is placed in a magnetic field,
Figure 4.34 the external characteristics of dc mechanical force is experienced on the
compound generator. conductor, the direction of which is given by
Fleming's left hand rule (also called motor
Curve I shows the external characteristic, in rule) and hence the conductor moves in the
which the series excitation is such that the direction of force. The magnitude of the
terminal voltage on full load is the same as mechanical force experienced n the
on no load and the terminal voltage remains conductor is given by
practically constant from no load to full
load. A dc compound generator giving such F = B Ic lc, [Newtons]
an external characteristic is called level- Where B is the field strength in Teslas
compounded generator. The external (wb/m2), Ic is the current flowing through
characteristic shown by curve II indicates the conductor in amperes and lc is the length
that the terminal voltage rises with the load. of conductor in meters. When the motor is
Such a compound generator with this connected to the dc Supply mains, a direct
external characteristic is said to be over current passes through the brushes and
compounded generator. The compound commutator to the armature winding. While
generator having an external characteristic it passes through the commutator it is
of the nature represented by curve III is converted in to a.c. so that the group of
called under compounded generator. conductors under successive field poles
In all the above three types of compound carries currents in the opposite directions, as
generators, i.e. level-compounded , over- shown in Figure 4.39. Also the direction of
compounded and under-compounded, the current in the individual conductor reverses
series field aids the shunt field and thus as they pass away from the influence of one
these compound generators can also be pole to that of the next.
called as cumulative compound generator. X
Resultant Torque
Force on each
Cumulative compound generator is most X N conductor
X
widely used in practice. Their external
characteristic can match to all classes of X X X
14
Figure 4.39 schematic diagram of 4-pole dc
motor X
X N
In Figure 4.39, a 4-pole d.c motor is shown X
S
experiences a force which tends to the motor X
Motion X N
Field X
X Tdrive
Eb
i
Current Rotation
15
work against this magnetic drag and the operation. However, in motor operation the
work so done is converted in to electrical Electro-magnetic torque developed causes
energy. The larger the output current, more the armature rotation, where as in a
will be the backward torque and, therefore, generator operation the Electro-magnetic
more mechanical energy will be required to torque produced opposes the rotation.
be supplied to the generator.
In Figure 4.41(b) the same machine
4.8 LOSSES IN DC MACHINES
operating as a motor is shown. This
operation takes place when the prime mover INTRODUCTION
is uncoupled from the machine and the The dc machines are used either for
machine is connected to the dc supply converting mechanical energy into electrical
mains. With the directions of field and energy, i.e. generators or for converting
armature current shown in the Figure electrical energy into mechanical energy, i.e.
4.41(b) the torque developed by Electro- motors. This conversion of energy from one
magnetic actions will rotate the machine in a form to another obviously takes place at an
clockwise direction (as determined by efficiency of less than 100 percent. A part of
Fleming's left-hand rule). The friction of the the energy consumed by machine can not be
machine and the mechanical load that the effectively utilized in the machine proper
motor is driving will exert a torque in and is dispersed in the form of heat. This
counter-clockwise direction, opposing the part of the energy is generally termed as lost
rotation of the motor. Since the armature energy or simply the losses of the machine.
conductors are revolving in the magnetic The losses in general occur (i) in electrical
field, emf is induced in the armature circuits carrying a certain current, (ii) in
conductors. The direction of emf so induced, magnetic circuits subjected to alternating
as determined by Fleming's right hand rule, magnetization and (iii) due to mechanical
is in direct opposition to the applied voltage friction. Hence the losses occurring in an
(see Eb in Figure 4.41(b)). That is why the electrical machine constitute a source of
induced emf in motor often is called the inefficiency. In addition, these are
counter emf or back emf Eb. The applied completely converted into heat, resulting in
voltage must be large enough to overcome a rise in the temperature of the machine. If
this back emf and to send the current reliable operation of an electrical machine is
through the resistance of the armature. The desired during its normal service life, then
electric energy supplied to overcome this the temperature of the various parts of the
opposition is converted into mechanical machine should not be allowed to exceed
energy development in the armature. beyond the permissible limit, decided by the
Thus we see that an emf is generated in both type of insulating material used in the
generator and motor, therefore, there is a machine. The temperature rise also decides
generator action in both motor and the capacity to which the machine can be
generator operation. However, in generator loaded safely.
operation the generated emf produces the The losses occurring in the machine have
armature current, where as, in motor also to be paid for and as such the running
operation the generated emf opposes the cost of a less efficient machine for the same
current direction. We also observe that output is more compared to an efficient
Electro-magnetic torque is developed in machine. Hence the problem of losses in the
generator as well as motor i.e. there is a machine is closely connected with the
motor action in both generator and motor,
16
problems of its service life and other armature conductors and (iii)
economic factors. The initial cost of a more additional losses caused by short
efficient machine is certainly higher than circuit currents in the coils under
that of a machine with poor efficiency. commutation and occur in (a)
However, the higher initial cost is armature teeth, (b) armature core and
compensated by the saving in running (c) armature winding.
energy charges; moreover a more efficient For smaller machines, stray losses are quite
machine is highly reliable , less subject to negligible. For fairly large machines, it may
breakdowns which is particular important be taken arbitrarily as one percent of the
when continuity of service must be rating of the machine.
maintained. Better electrical materials are
being developed and with the use of these Of these groups of losses, copper losses vary
electrical machines are undergoing a with the load on the machine, whereas iron
continuous improvement towards reduction and mechanical losses remain substantially
in losses, so as to produce more efficient constant at all loads. Stray losses are more
machines with trouble free and continuous or less negligible in small and medium
service even under more severe working. machines. Hence the total losses occurring
in a dc machine may also be classified as
i. variable losses and
ii. Constant losses.
Classification of Losses
In case of shunt or compound dc machines,
Power losses originating in dc machines even the shunt field copper losses can be
(either a motor or a generator) can be grouped with the constant losses because it
classified into the following groups remains practically constant at all loads.
1. Copper losses, caused by the current Thus for a shunt or compound dc machine,
flow and occur in (i) armature the constant and variable losses include:
winding, (ii) series field winding ,
• Constant losses including (i) iron
(iii) commutating pole winding , (iv)
losses, (ii) mechanical losses and
compensating winding , (v) shunt
(iii) shunt field Cu losses.
field winding and (vi) loss due to
brush contact resistance. • Variable losses including (i)
copper losses in armature
2. Iron losses caused by varying
winding (ii) copper losses in
magnetization and occur in (armature
series field winding (iii) copper
core and (ii) armature teeth , as
losses in commutating pole
hysteresis loss and eddy current loss.
winding (iv) copper losses in
3. Mechanical losses caused by the compensating winding if any and
rotation of the machine and occur as (v) losses due to brush contact
(i) bearing friction (ii) brush friction resistance.
and (iii) air friction (windage). These
Copper Losses
losses are also called friction and
windage losses. In general copper losses will occur in those
parts of dc machines that carry electric
4. Stray load losses include (i) increase
current. These losses could be further
in iron losses at load (ii) increases in
subdivided into three groups.
copper losses due to eddy currents in
17
1. Armature copper loss Terminal voltage and Ish are practically
2. Field copper loss , and constant as such this loss can be taken into
the group of constant losses in the dc
3. Loss due to brush contact
machine.
resistance.
Losses due to Brush contact
Armature copper loss
Resistance
Let the current flowing in the armature
In dc machines, brushes makes a sliding
winding be designated Ia amperes and its
contact with the commutator and the
resistance Ra .
conduction of current is through minute
Then armature copper losses = I a2 Ra watts. arcs. The contact voltage drop for a
particular grade of brush is more or less
Moreover, series field winding, interpole constant, varying from 1 to 2 volts for
winding and compensating windings are normal carbon brushes. The brush contact
connected in series with the armature loss is equal to the product of contact
winding. As such the current flowing in voltage drop and the armature current.
these winding is also equal to the armature Strictly speaking, it is not a copper loss;
current, Ia. however it is normally included in the
Thus, the total armature copper losses classification of copper losses.
18
particular material. Its value for 4% silicon The bearing friction losses occurring in dc
steel and sheet steel is 275 and 500 machine depend upon (i) the pressure on
respectively. Hysteresis loss is reduced by bearing, (ii) Peripheral speed of the shaft at
choosing a core material with low hysteresis the bearing and (iii) coefficient of friction
coefficient such as alloy steel. between the bearing and the shaft.
Eddy current losses The brush friction losses are quite
appreciable in dc machines. These losses are
As the armature core rotates relative to the
dependent upon (i) the brush pressure, (ii)
magnetic field, it cuts the flux. Thus as per
the peripheral speed of the commutator and
the lows of electromagnetic induction, a
(iii) the type of the brush.
small emf is induced in the armature core
body, which circulates a large current in the The windage losses are mainly produced by
armature core due to its small resistance. the rotation of armature. These losses
Such a circulating current is called eddy depend upon (i) peripheral speed of the
current and the power losses due to the flow armature, (ii) armature diameter, (iii)
of this current are called eddy current losses. armature core length and (iv) construction of
The resistance can be greatly increased by the machine
laminating the armature core of the dc These three components added together give
machine, thereby reducing the magnitude of the total mechanical losses occurring in the
eddy current to an appreciable value. The machine these are practically constant
eddy current losses depend upon the provided the speed remains the same during
following factors: the loading of the machine.
i. Thickness of laminations, t
EFFICIENCY
ii. Frequency of flux reversal, f
iii. Maximum value of flux density, Bmax The ratio of output of the machine to its
input is generally called the efficiency of the
iv. Volume of armature core V and machine.
v. Quality of iron.
Hence the eddy current losses occurring in output
the armature core and teeth of the dc Efficiency =
input
machine are given by
Input to the machine = output + total losses
Pc = KB2max f 2 t 2 V, watts
Thus,
Mechanical Losses Output
efficiency =
Mechanical losses are due to the rotation of Output + total losses
the armature and can be subdivided into Total losses in dc machine = constant losses
three categories. + variable losses
1. bearing friction
= Wc + Wv
2. brush friction and
Hence,
3. air friction (winding)
There are also termed as friction and Output
windage losses. efficiency η =
Output + constant losses+ variable losses
19