Spec Sheet 26RCA (L) - G4-315 (10-23c)
Spec Sheet 26RCA (L) - G4-315 (10-23c)
Multi-Fuel
LPG/Natural Gas
Standard Features
• RDC2 Controller
o One digital controller manages both the generator set
and transfer switch functions (with optional Model RXT).
o Electronic speed control responds quickly to varying
demand.
o OnCue® Plus Generator Management System for remote
monitoring is included with the generator.
• Kohler Command PRO Engine Features
o Kohler Command PRO® OHV engine with hydraulic
valve lifters for reliable performance without routine valve
adjustment or lengthy break-in requirements.
• Designed for Easy Installation
o Sturdy aluminum base can be mounted on gravel or a
concrete mounting pad.
o Fuel and electrical connections through the enclosure
The Kohler® Advantage wall eliminate the need for stub-ups through the base.
• High Quality Power o Customer connection terminal block located near the
Kohler home generators provide advanced voltage and controller allows easy access for field wiring.
frequency regulation along with ultra-low levels of harmonic o Designed for outdoor installation only.
distortion for excellent generator power quality to protect • Certifications
your valuable electronics. o Meets emission regulations for U.S. Environmental
• Premium 5-yr/2000-hr Limited Warranty Included Protection Agency (EPA) with both natural gas and LPG.
Kohler is known for extraordinary reliability and o cULus listed.
performance. Kohler’s premium limited warranty covers o Accepted by the Massachusetts Board of Registration of
parts, labor, and travel for the full warranty period. Plumbers and Gas Fitters.
o Meets 181 mph wind rating.
• Powerful Performance
• Approved for stationary standby applications in locations
Exclusive Powerboost™ technology provides excellent
§ served by a reliable utility source (on-grid).
starting power.
• Exercise Modes
• Aluminum Enclosure
o EcoExercise, unloaded, with system diagnostics
o Attractive aluminum enclosure allows installation as
(90 seconds). Reduces fuel costs and minimizes sound
close as 18 inches from your home or small business. †
disruption.
o Enclosure panels can be removed without tools to allow
o Unloaded exercise with complete system diagnostics (20
easy access for maintenance and service.
minutes).
• Enclosure Options for single-phase units o Unloaded full-speed exercise (20 minutes).
o Kohler® Exclusive Colors are available. Go to o Loaded full-speed exercise (20 minutes; Model RXT ATS
KohlerGenerators.com to see the latest colors. required).
o Camouflage Enclosures are available for single-phase o Weekly, bi-weekly, or new monthly exercise intervals.
units (optional). Go to KohlerGenerators.com/MossyOak • Model 26RCAL includes a model RXT automatic transfer
to view the available patterns. switch. See last page for more details.
Mossy Oak is a trademark used under license from Haas Outdoors, Inc., by Kohler Co.
Generator Ratings
Standby Ratings, 60 Hz Standby Ratings, 50 Hz
Natural Gas LPG Line Circuit Natural Gas LPG Line Circuit
kW/ kW/ Breaker kW/ kW/ Breaker
Model Alt. Ph. Volts kVA A kVA A A Poles Volts kVA A kVA A A Poles
26RCA/L 2F8 1 120/240 24/24 100 26/26 109 125 2 115/230 18/18 78 18/18 78 80 2
3 120/208 21/26 73 22/27 77 80 3 220/380 16/20 30 16/20 30 30 3
26RCA 2G8 3 120/240 21/26 64 22/27 67 80 3 230/400 16/20 29 16/20 29 30 3
3 277/480 21/26 32 22/27 34 40 3 240/416 16/20 28 16/20 28 30 3
Note: The line circuit breaker is automatically selected based on the generator set model and voltage configuration.
RATINGS: Standby ratings apply to installations served by a reliable utility source. All single-phase units are rated at 1.0 power factor. The standby rating is applicable to variable loads with
an average load factor of 80% for the duration of the power outage. No overload capacity is specified at this rating. Ratings are in accordance with ISO-3046/1, BS5514, AS2789, and
DIN 6271. GENERAL GUIDELINES FOR DERATING: ALTITUDE: Derate 4% per 305 m (1000 ft.) elevation above 153 m (500 ft.). TEMPERATURE: Derate 2% per 5.5°C (10°F)
temperature increase above 16°C (60°F). Availability is subject to change without notice. The generator set manufacturer reserves the right to change the design or specifications without
notice and without any obligation or liability whatsoever. Contact your local Kohler Co. generator dealer for availability.
§ Check the appliance manufacturer’s specifications for actual power requirements. Consult a Kohler ® Power Systems professional to calculate your exact residential power system
requirements.
† Meets NFPA guidelines for 18 inch clearance to combustible materials. Check state and local codes for minimum distance required from a structure.
G4-315 (26RCA) 10/23c
Alternator Specifications
Alternator Specifications Alternator Features
Specifications Alternator • Compliance with NEMA, IEEE, and ANSI standards for
Manufacturer Kohler temperature rise.
Type 2-Pole, Rotating Field • Self-ventilated and dripproof construction.
Leads, quantity
2F8 4
• Windings are vacuum-impregnated with epoxy varnish for
2G8 12
dependability and long life.
Voltage regulator Digital • Superior voltage waveform and minimum harmonic
Insulation: NEMA MG1-1.66 distortion from skewed alternator construction.
Material Class H • Digital voltage regulator with ±1.0% no-load to full-load
Temperature rise 130°C Standby RMS regulation.
Bearing: quantity, type 1, Sealed
• Rotating-field alternator with static exciter for excellent
Coupling Direct
load response.
Amortisseur windings Full
Voltage regulation, no-load to full-load • Total harmonic distortion (THD) from no load to full load
±1.0% with a linear load is less than 5%.
RMS
One-step load acceptance 100% of Rating
Peak motor starting kVA: (35% dip for voltages below)
240 V, 1 ph, 2F8 (4 lead) 39 (60 Hz) 27 (50 Hz)
240 or 480 V, 3 ph, 2G8 (12 lead) 63 (60 Hz) 50 (50 Hz)
Application Data
Engine Exhaust
Engine Specifications 60 Hz 50 Hz Exhaust System
Manufacturer Kohler Exhaust temperature exiting the
Engine: model, type CH1006 4-Cycle enclosure at rated kW, dry, °C (°F) 260 (500)
Cylinder arrangement V-2
Displacement, cm3 (cu. in.) 999 (61)
Lubrication
Bore and stroke, mm (in.) 90 x 78.5 (3.54 x 3.1) Lubricating System
Compression ratio 10.5:1 Type Full Pressure
Main bearings: quantity, type 2, Heavy-Duty Sleeve Oil capacity (with filter), L (qt.) § 1.9 (2.0)
Bearings Oil filter: quantity, type § 1, Cartridge
Rated RPM 3600 3000 Oil cooler Integral
Max. engine power at rated RPM, kW (HP)
§ Kohler recommends the use of Kohler Genuine oil and filters.
LPG 26.1 (36.4) 22.7 (30.4)
Natural gas 24.5 (33.0) 19.5 (26.2)
Cylinder head material Aluminum
Fuel Requirements
Valve material Steel/Stellite® Fuel System
Piston type and material Aluminum Alloy Fuel types Natural Gas or LPG
Crankshaft material Heat Treated, Ductile Iron Fuel supply inlet 3/4 NPT
Governor: type Electronic Fuel supply pressure, kPa (in. H2O):
Frequency regulation, no load to full load Isochronous Natural gas 0.9-2.7 (3.5-11)
Frequency regulation, steady state ±0.5% LP 1.7-2.7 (7-11)
Air cleaner type Dry Fuel Composition Limits * Nat. Gas LPG
Engine Electrical Methane, % by volume (minimum) 90 min. —
Ethane, % by volume (maximum) 4.0 max. —
Engine Electrical System
Propane, % by volume 1.0 max. 85 min.
Ignition system Electronic, Propene, % by volume (maximum) 0.1 max. 5.0 max.
Capacitive Discharge
C4 and higher, % by volume 0.3 max. 2.5 max.
Starter motor rated voltage (DC) 12
Sulfur, ppm mass (maximum) 25 max.
Battery (purchased separately): Lower heating value,
Ground Negative MJ/m3 (Btu/ft3), (minimum) 33.2 (890) 84.2 (2260)
Volts (DC) 12 * Contact your local dealer for suitability and rating derates based
Battery quantity 1 on fuel compositions outside these limits.
Recommended cold cranking
amps:
(CCA) rating for -18°C (0°F) 500
Group size 51