Models: 26RCA(L)

Multi-Fuel
LPG/Natural Gas

Standard Features
• RDC2 Controller
o One digital controller manages both the generator set
and transfer switch functions (with optional Model RXT).
o Electronic speed control responds quickly to varying
demand.
o OnCue® Plus Generator Management System for remote
monitoring is included with the generator.
• Kohler Command PRO Engine Features
o Kohler Command PRO® OHV engine with hydraulic
valve lifters for reliable performance without routine valve
adjustment or lengthy break-in requirements.
• Designed for Easy Installation
o Sturdy aluminum base can be mounted on gravel or a
concrete mounting pad.
o Fuel and electrical connections through the enclosure
The Kohler® Advantage wall eliminate the need for stub-ups through the base.
• High Quality Power o Customer connection terminal block located near the
Kohler home generators provide advanced voltage and controller allows easy access for field wiring.
frequency regulation along with ultra-low levels of harmonic o Designed for outdoor installation only.
distortion for excellent generator power quality to protect • Certifications
your valuable electronics. o Meets emission regulations for U.S. Environmental
• Premium 5-yr/2000-hr Limited Warranty Included Protection Agency (EPA) with both natural gas and LPG.
Kohler is known for extraordinary reliability and o cULus listed.
performance. Kohler’s premium limited warranty covers o Accepted by the Massachusetts Board of Registration of
parts, labor, and travel for the full warranty period. Plumbers and Gas Fitters.
o Meets 181 mph wind rating.
• Powerful Performance
• Approved for stationary standby applications in locations
Exclusive Powerboost™ technology provides excellent
§ served by a reliable utility source (on-grid).
starting power.
• Exercise Modes
• Aluminum Enclosure
o EcoExercise, unloaded, with system diagnostics
o Attractive aluminum enclosure allows installation as
(90 seconds). Reduces fuel costs and minimizes sound
close as 18 inches from your home or small business. †
disruption.
o Enclosure panels can be removed without tools to allow
o Unloaded exercise with complete system diagnostics (20
easy access for maintenance and service.
minutes).
• Enclosure Options for single-phase units o Unloaded full-speed exercise (20 minutes).
o Kohler® Exclusive Colors are available. Go to o Loaded full-speed exercise (20 minutes; Model RXT ATS
KohlerGenerators.com to see the latest colors. required).
o Camouflage Enclosures are available for single-phase o Weekly, bi-weekly, or new monthly exercise intervals.
units (optional). Go to KohlerGenerators.com/MossyOak • Model 26RCAL includes a model RXT automatic transfer
to view the available patterns. switch. See last page for more details.
Mossy Oak is a trademark used under license from Haas Outdoors, Inc., by Kohler Co.

Generator Ratings
Standby Ratings, 60 Hz Standby Ratings, 50 Hz
Natural Gas LPG Line Circuit Natural Gas LPG Line Circuit
kW/ kW/ Breaker kW/ kW/ Breaker
Model Alt. Ph. Volts kVA A kVA A A Poles Volts kVA A kVA A A Poles
26RCA/L 2F8 1 120/240 24/24 100 26/26 109 125 2 115/230 18/18 78 18/18 78 80 2
3 120/208 21/26 73 22/27 77 80 3 220/380 16/20 30 16/20 30 30 3
26RCA 2G8 3 120/240 21/26 64 22/27 67 80 3 230/400 16/20 29 16/20 29 30 3
3 277/480 21/26 32 22/27 34 40 3 240/416 16/20 28 16/20 28 30 3
Note: The line circuit breaker is automatically selected based on the generator set model and voltage configuration.

RATINGS: Standby ratings apply to installations served by a reliable utility source. All single-phase units are rated at 1.0 power factor. The standby rating is applicable to variable loads with
an average load factor of 80% for the duration of the power outage. No overload capacity is specified at this rating. Ratings are in accordance with ISO-3046/1, BS5514, AS2789, and
DIN 6271. GENERAL GUIDELINES FOR DERATING: ALTITUDE: Derate 4% per 305 m (1000 ft.) elevation above 153 m (500 ft.). TEMPERATURE: Derate 2% per 5.5°C (10°F)
temperature increase above 16°C (60°F). Availability is subject to change without notice. The generator set manufacturer reserves the right to change the design or specifications without
notice and without any obligation or liability whatsoever. Contact your local Kohler Co. generator dealer for availability.
§ Check the appliance manufacturer’s specifications for actual power requirements. Consult a Kohler ® Power Systems professional to calculate your exact residential power system
requirements.
† Meets NFPA guidelines for 18 inch clearance to combustible materials. Check state and local codes for minimum distance required from a structure.
G4-315 (26RCA) 10/23c
Alternator Specifications
Alternator Specifications Alternator Features
Specifications Alternator • Compliance with NEMA, IEEE, and ANSI standards for
Manufacturer Kohler temperature rise.
Type 2-Pole, Rotating Field • Self-ventilated and dripproof construction.
Leads, quantity
2F8 4
• Windings are vacuum-impregnated with epoxy varnish for
2G8 12
dependability and long life.
Voltage regulator Digital • Superior voltage waveform and minimum harmonic
Insulation: NEMA MG1-1.66 distortion from skewed alternator construction.
Material Class H • Digital voltage regulator with ±1.0% no-load to full-load
Temperature rise 130°C Standby RMS regulation.
Bearing: quantity, type 1, Sealed
• Rotating-field alternator with static exciter for excellent
Coupling Direct
load response.
Amortisseur windings Full
Voltage regulation, no-load to full-load • Total harmonic distortion (THD) from no load to full load
±1.0% with a linear load is less than 5%.
RMS
One-step load acceptance 100% of Rating
Peak motor starting kVA: (35% dip for voltages below)
240 V, 1 ph, 2F8 (4 lead) 39 (60 Hz) 27 (50 Hz)
240 or 480 V, 3 ph, 2G8 (12 lead) 63 (60 Hz) 50 (50 Hz)

Application Data
Engine Exhaust
Engine Specifications 60 Hz 50 Hz Exhaust System
Manufacturer Kohler Exhaust temperature exiting the
Engine: model, type CH1006 4-Cycle enclosure at rated kW, dry, °C (°F) 260 (500)
Cylinder arrangement V-2
Displacement, cm3 (cu. in.) 999 (61)
Lubrication
Bore and stroke, mm (in.) 90 x 78.5 (3.54 x 3.1) Lubricating System
Compression ratio 10.5:1 Type Full Pressure
Main bearings: quantity, type 2, Heavy-Duty Sleeve Oil capacity (with filter), L (qt.) § 1.9 (2.0)
Bearings Oil filter: quantity, type § 1, Cartridge
Rated RPM 3600 3000 Oil cooler Integral
Max. engine power at rated RPM, kW (HP)
§ Kohler recommends the use of Kohler Genuine oil and filters.
LPG 26.1 (36.4) 22.7 (30.4)
Natural gas 24.5 (33.0) 19.5 (26.2)
Cylinder head material Aluminum
Fuel Requirements
Valve material Steel/Stellite® Fuel System
Piston type and material Aluminum Alloy Fuel types Natural Gas or LPG
Crankshaft material Heat Treated, Ductile Iron Fuel supply inlet 3/4 NPT
Governor: type Electronic Fuel supply pressure, kPa (in. H2O):
Frequency regulation, no load to full load Isochronous Natural gas 0.9-2.7 (3.5-11)
Frequency regulation, steady state ±0.5% LP 1.7-2.7 (7-11)
Air cleaner type Dry Fuel Composition Limits * Nat. Gas LPG
Engine Electrical Methane, % by volume (minimum) 90 min. —
Ethane, % by volume (maximum) 4.0 max. —
Engine Electrical System
Propane, % by volume 1.0 max. 85 min.
Ignition system Electronic, Propene, % by volume (maximum) 0.1 max. 5.0 max.
Capacitive Discharge
C4 and higher, % by volume 0.3 max. 2.5 max.
Starter motor rated voltage (DC) 12
Sulfur, ppm mass (maximum) 25 max.
Battery (purchased separately): Lower heating value,
Ground Negative MJ/m3 (Btu/ft3), (minimum) 33.2 (890) 84.2 (2260)
Volts (DC) 12 * Contact your local dealer for suitability and rating derates based
Battery quantity 1 on fuel compositions outside these limits.
Recommended cold cranking
amps:
(CCA) rating for -18°C (0°F) 500
Group size 51

G4-315 (26RCA) 10/23c


Fuel Pipe Size Operation Requirements
Minimum Gas Pipe Size Recommendation, in. NPT Fuel Consumption, m3/hr. (cfh) @ 60Hz
Pipe Length, Natural Gas LPG % Load Natural Gas LPG
m (ft.) 290,000 Btu/hr. 322,500 Btu/hr.
100 8.2 (290) 3.6 (129)
8 (25) 1 3/4
75 6.7 (238) 3.1 (111)
15 (50) 1 1/4 1
50 5.1 (180) 2.4 (85)
30 (100) 1 1/4 1
25 3.9 (137) 1.8 (64)
46 (150) 1 1/4 1
Exercise 1.9 (67) 0.9 (31)
61 (200) 1 1/2 1 1/4
Fuel Consumption, m3/hr. (cfh) @ 50Hz
% Load Natural Gas LPG
Generator Set Sound Data
100 6.9 (245) 2.9 (102)
Model 26RCA sound levels are 56 dB(A) during engine
75 6.2 (220) 2.5 (89)
exercise and 67 dB(A) during full-speed generator
50 5.4 (190) 1.8 (65)
diagnostics and normal operation.*
25 3.7 (131) 1.3 (46)
All sound levels are measured at a distance of 23 ft. (7 m)
Exercise 1.9 (67) 0.9 (31)
from the generator set.
Nominal fuel rating: Natural gas: 37 MJ/m3 (1000 Btu/ft.3)
* Lowest of 8 points measured around the generator. Sound levels LPG: 93 MJ/m3 (2500 Btu/ft.3)
at other points around generator may vary depending on LPG conversion factors: 8.58 ft.3 = 1 lb.
installation parameters. 0.535 m3 = 1 kg
36.39 ft.3 = 1 gal.

RDC2 Controller Features


• Exercise modes:
o New 90-second Eco Exercise with complete system
diagnostics (factory default setting)
o Lowers fuel cost
o Minimizes sound disruption
o In cold temperatures, limits condensation build-up
in the crankcase
o Unloaded 20-minute exercise with complete system
diagnostics
o Unloaded 20-minute full-speed exercise
The RDC2 controller provides integrated control for the o Loaded 20-minute full-speed exercise (Model RXT
generator set, Kohler® Model RXT transfer switch, ATS required)
programmable interface module (PIM), and load shed kit. • Weekly, bi-weekly, or new monthly exercise intervals
• Membrane keypad: • Front-access mini USB connector for SiteTech™ or USB
o OFF, AUTO, and RUN pushbuttons Utility connection
o Select and arrow buttons for access to system • Integral Ethernet connector for Kohler® OnCue® Plus
configuration and adjustment menus • Remote two-wire start/stop capability for optional
connection of a Model RDT transfer switch
• LED indicators for OFF, AUTO, and RUN modes
• Diagnostic messages: Displays diagnostic messages for
• LED indicators for utility power and generator set source the engine, generator, Model RXT transfer switch,
availability and ATS position (Model RXT transfer switch programmable interface module (PIM), and load
required) management device.
• LCD display: • Maintenance reminders
o Two lines x 16 characters per line • System settings:
o Backlit display with adjustable contrast for excellent o System voltage, frequency, and phase
visibility in all lighting conditions o Voltage adjustment
• Scrolling system status display: o Measurement system, English, or metric
o Generator set status • ATS status (Model RXT ATS required):
o Voltage and frequency o Source availability
o ATS position (normal/utility or emergency/generator)
o Engine temperature
o Source voltage and frequency
o Oil pressure • ATS control (Model RXT ATS required):
o Battery voltage o Source voltage and frequency settings
o Engine runtime hours o Engine start time delay
• Date and time displays o Transfer time delays
• Smart engine cooldown senses engine temperature o Voltage calibration
o Fixed pickup and dropout settings
• Digital isochronous governor maintains steady-state
speed at all loads • Programmable Interface Module (PIM) status displays:
o Input status (active/inactive)
• Digital voltage regulation: ±1.0% RMS no-load to full-load o Output status (active/inactive)
• Automatic start with programmed cranking cycle • Load control menus:
• Built-in 2.5 amp battery charger o Load status
• Programmable exerciser can be set to start automatically o Test function
on any future day and time
G4-315 (26RCA) 10/23c
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920‐457‐4441, Fax 920‐459‐1646
For the nearest sales and service outlet in
the US and Canada, phone 1‐800‐544‐2444
KOHLERPower.com

Generator Set Standard Features Literature


• Aluminum sound enclosure (cashmere color standard) ❑ General maintenance literature kit
• Battery cables ❑ Overhaul literature kit
❑ Production literature kit
• Critical silencer
• EPA certified fuel system Maintenance
• Field-connection terminal block ❑ Maintenance kit (includes air filter, oil, oil filter, and
spark plugs)
• Fuel solenoid valve and secondary regulator
❑ Premium 300 hour/2 year oil for fewer oil changes
• Line circuit breaker
• Multi-fuel system, LPG/natural gas, field-convertible Automatic Transfer Switches and Accessories
• Oil drain extension with shutoff valve ❑ Model RDT ATS
• Oil level sensor ❑ Model RXT ATS with combined interface/load
management board
• Oil pressure sensor
❑ Load shed kit for RXT or RDT
• OnCue® Plus Generator Management System
❑ Power relay modules (use up to 4 relay modules for
• Premium 5-year/2000 hour limited standby warranty. each load management device)
Covers parts, labor, and travel for the entire warranty period 26RCAL Model Package
• RDC2 generator set/ATS controller ❑ 26RCAL with 200 amp service entrance-rated Model
• Rodent-resistant construction RXT with combined interface/load management board
• Sound-deadening, flame-retardant foam per UL 94, and corrosion-resistant NEMA 3R aluminum enclosure
class HF-1 Warranty
Available Options ❑ 7-Year Limited Warranty
❑ 10-Year Limited Warranty
Concrete Mounting Pads
Warranties cover parts, labor, and travel for the entire
❑ Concrete mounting pad, 3 in. thick warranty period.
❑ Concrete mounting pad, 4 in. thick
(recommended for storm-prone areas)
Electrical Accessories
❑ Battery
❑ Battery heater, 120 VAC *
❑ Carburetor heater, 120 VAC †
Generator Set Dimensions and Weights
❑ Cold weather kit, 120 VAC †‡
Generator Set Size, L x W x H: 1193 x 660 x 820 mm
o Includes oil and breather tube heaters. fuel regulator heater, and (47 x 26.0 x 32.3 in.)
pressure sensor cover Shipping Weights: L
o QS model with factory-installed kit is available. 26RCA Generator Set: 283 kg (625 lb.)
❑ Emergency stop kit 26RCAL with 200 A RXT SE ATS: 304 kg (670 lb.)
❑ Programmable interface module (PIM)
(provides 2 digital inputs and 6 relay outputs) H
* Battery heater is recommended below -17°C (0°F).
‡ Do not use a carburetor heater with a cold weather kit.
† Cold weather kit is recommended below 0°C (32°F).
W
Enclosure Options (single-phase only)
❑ Kohler® Exclusive Colors
Go to KohlerGenerators.com to see the latest colors.
❑ Mossy Oak® camouflage enclosures. NOTE: Dimensions are provided for reference only and should not be used for planning
Go to KohlerGenerators.com/MossyOak to see available installation. Contact your local dealer for more detailed information.
patterns.
Mossy Oak is a trademark used under license from Haas Outdoors, Inc., by Kohler Co.
DISTRIBUTED BY:

Fuel System Accessories


❑ Flexible fuel line (included on QS models)

© 2023 Kohler Co. All rights reserved.

G4-315 (26RCA) 10/23c

You might also like