This firmware release provides fixes and improvements for a network card used with UPS devices. Version 3.1.12 includes cybersecurity updates, UI improvements, and fixes an issue with communications after reconnection. Earlier versions can be upgraded according to the manual.

Uploaded by

Roberto
Copyright
© © All Rights Reserved
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views

2 Release - Notes - NetworkM2 - 3112

This firmware release provides fixes and improvements for a network card used with UPS devices. Version 3.1.12 includes cybersecurity updates, UI improvements, and fixes an issue with communications after reconnection. Earlier versions can be upgraded according to the manual.

Uploaded by

Roberto
Copyright
© © All Rights Reserved
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
You are on page 1/ 8

===================================================================================

=======
Firmware release notes for Eaton Gigabit Network Card for UPS (Network-M2, P/N 744-
A3983)

Firmware : Release 3.1.12


Date : 2024/01/19
Eaton (c) 2024
===================================================================================
=======

Upgrade/Compatibility:
This section describes the considerations for upgrading from a previous
release. It is not recommended to upgrade to 3.x.x from 1.x.x directly. 1.x.x
firmware versions should first be upgraded to 2.1.5 as an intermediate step and
then upgraded to 3.x.x. Note that upgrading to 2.x.x from any 1.x.x firmware
revision will clear all alarms and events from the user interface. A backup of
these alarms and events is available through RESTful API. See
https://www.eaton.com/network-m2 for detailed RESTful API documentation.

Earlier versions can be upgraded to 3.1.8 according to the procedure described


in the manual. Downgrade from 1.6.x or above to 1.5.x or below is not possible.
Beyond this limitation, downgrade to earlier versions is possible but not
recommended.

===============================
Release 3.1.12 January 2024
===============================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher, VPM 6.4.0 and
higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9PXM, 9SX, 9130, FERRUPS FX,
9E, 93PM (fw 1.48->), 93PM G2, 93PS (fw 2.50->), 91PS, 93E 15-80 EMEA (fw 8.00.01-
>), 93E G2 EMEA (fw 4.0.20->)

Supported ATS: Eaton EATS115, EATS16, EATS120, EATS220

Fixes:

- Recover communications with Environmental Monitoring Probe in daisy chain


configuration after reconnection
- Corrected sensor alarm messages
- HID UPS.PowerConverter.Output.Overload[1].Threshold now updating properly
- Improved data update times
- Report descriptor timeout changed from 10 sec to 60 sec
- Cybersecurity updates
- Various UI improvements
- Fixed a security vulnerability related to Active Directory

===============================
Release 3.1.8 February 2023
===============================
Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher, VPM 6.4.0 and
higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9PXM, 9SX, 9130, FERRUPS FX,
9E, 93PM (fw 1.48->), 93PM G2, 93PS (fw 2.50->), 91PS, 93E 15-80 EMEA (fw 8.00.01-
>), 93E G2 EMEA (fw 4.0.20->)

Supported ATS: Eaton EATS115, EATS16, EATS120, EATS220

Additions:

- Support for Uninterruptable Power Modules


- Location field in email body
- TCP framing option for syslog server
- Additional UPS battery thresholds: Low battery warning and minimum battery
capacity for automatic restart
- CLI access over USB for OOB management

Changes:

- Incoming traffic no longer accepted on port 123


- Device alarms can now be sent using Syslog

Fixes:

- Cybersecurity updates
- Various UI improvements

===============================
Release 3.0.5 June 2022
===============================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher, VPM 6.4.0 and
higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9PXM, 9SX, 9130, FERRUPS FX,
9E, 93PM (fw 1.48->), 93PS (fw 2.50->), 91PS, 93E 15-80 EMEA (fw 8.00.01->), 93E G2
EMEA (fw 4.0.20->)

Supported ATS: Eaton EATS115, EATS16, EATS120, EATS220

Additions:

- Remote UPS firmware upgrade if supported by connected UPS


- Selected support for management of local UPS settings
- Capability to disable HTTP redirect
- Support for RADIUS user profiles
- CA/CB compliant certificates
- Support for PredictPulse Insight (Americas only)

Changes:

- Upgrades to user management service


- Made LDAP diagnostic available

Fixes:
- Cybersecurity updates
- Various UI improvements
- Improved memory usage during firmware upgrades
- Improved sensor communications
- Improved LDAP features

===============================
Release 2.1.5 June 2021
===============================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher, VPM 6.4.0 and
higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9PXM, 9SX, 9130, FERRUPS FX,
9E, 93PM (fw 1.48->), 93PS (fw 2.50->), 91PS, 93E 15-80 EMEA (fw 8.00.01->), 93E G2
EMEA (fw 4.0.20->)

Supported ATS: Eaton EATS115, EATS16, EATS120, EATS220

Additions:

- Support for BACnet IP and BBMD introduced for INDGW-M2 only


- Added PXG compatible Modbus map (UID 0) on Industrial Gatway Card (INDGW-M2)
- Added Modbus register offset setting on Industrial Gatway Card (INDGW-M2)
- Add the capability to control and monitor the battery test from the Modbus-MS
map
- Display number of EBM if supported by UPS

Changes:

- Improved support for MQTT protocol


- Updated SNMP xUPS MIB

Fixes:

- Cybersecurity updates
- Various improvements UI
- Resolved issue with SNMP test trap button
- Fix for CVE-2021-3156

===============================
Release 2.0.5 November 2020
===============================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher, VPM 6.4.0 and
higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9PXM, 9SX, 9130,
* 3 phase UPS are not supported for this release
Supported ATS: Eaton EATS115, EATS16, EATS120, EATS220

Additions:

- Alarms will auto clear when there are more than 6000 alarms
- Ats2 SNMP MIB
- Russian language support
- Support for 9130 and EATS models

Changes:

- Updated user interface


- IE11 is no longer supported
- Updated RESTful API for power distribution service
- Added option to hide IP address from email body
- Set Common Name (CN) to be the FQDN for webserver, syslog and mqtt
certificates
- Removed "Web server" prefix and -selfsigned suffix from CN
- CN and SAN are now the same
- Limitation of 20 IPP connected agents

Fixes:

- Improvements to IETF and XUPS SNMP MIB


- Resolved issue with forced reboot on 9PX/9SX
- Allow special characters in LDAP configuration
- Removed trailing "." from FQDN when no domain name is set
- Resolved issue with email service periodic reports.

===============================
Release 1.7.5 November 2019
===============================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9PXM, 9SX, 9E, 93PM (fw 1.48
->), 93PS (fw 2.50 ->), 91PS, 93E 15-80 EMEA (fw 8.00.01 ->), 93E G2 EMEA (fw
4.0.20->)

Fixes:

- Fixed communication issue with 9PX 0 - 3 kVA and 9SX 0 - 3 kVA UPS which
could lead to UPS becoming unresponsive or dropping the load.

===============================
Release 1.7.4 October 2019
===============================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9PXM, 9SX, 9E, 93PM (fw 1.48
->), 93PS (fw 2.50 ->), 91PS, 93E 15-80 EMEA (fw 8.00.01 ->), 93E G2 EMEA (fw
4.0.20->)

Improvements:

- Ability to work with IPM 1.67 to shut down VxRail systems.


- Ability to create certificates with user defined Country, State or Province,
City or Locality, Organization name and unit, Contact email address
- Sensor log download and email capability
- Improvements in configuration save and restore, support for IPM 2.0.1 mass
configuration feature
- Monitoring of card resources to help in troubleshooting.

Fixes:

- If LDAP group name contains a space login to the card will become impossible.
- SNMP: Battery alarms, Battery last replacement date, sensor index, negative
offset for temperature and humidity
- Battery status unknown on the synoptic with 9E 3K
- Invalid Recommended replacement date for battery
- Temperature compensated charging with 93PM, 93PS, 91PS, 93E
- System logs blocking when syslog is enabled without server active
configuration
- Modbus registers "Nominal VA" and "Nominal kW" on Industrial Gatway Card
(INDGW-M2)

Known issues and limitations:

- LDAP remote groupname entered in profile mapping settings must be composed


only of alphanumerics, underscore and hyphen characters
- User defined certificate fields �state�, �organization�, �organization unit�
must be composed of alphanumerics, space or following characters �,=()�
- Web UI cache needs to be cleared with CTRL+F5 after an upgrade
- Up to 30 shutdown agents can be connected.
- Environmental probe values cannot be set to trigger shutdown.
- Environmental probe settings cannot be saved or restored

===============================
Release 1.6.6 July 2019
===============================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9PXM, 9SX, 9E, 93PM (fw 1.48
->), 93PS (fw 2.50 ->), 91PS

Improvements:

- NOTE: Changed DIP switch 3 function from admin password reset to sanitization
(full reset and data purge)
- Sanitization improvements (Done at boot after command, major version downgrade
or dip switch 3 change)
- Added support for RADIUS authentication
- Added support for Syslog integration
- Added support for Li-Ion batteries
- Added 'Operator' profile
- Measurement values option on the synoptic view
- XUPS MIB enhancements
- Added email/ping6/traceroute6/whoami options in CLI
- Save and restore with passphrase and with fields including encrypted password
- Eaton sensor new MIB
- Battery page information in Meters
- Added STARTTLS to SMTP (email)
- Improved handling of network configuration data transmission to UPS

Fixes:
- Issue with Chrome and self signed certificate
- Issue with upgrading after changing admin username
- Cybersecurity updates
- Don't allow port 80 for https
- Issue with card unable to handle a hostname with a number as the first
character
- Web server performance issue with RNDIS
- IPV6 support on SNMP, LDAP, NTP
- SNMP bug fixes:
- Manage the trap UpsShutdownPending and also the related alarm in the
Eaton Xups Mib.
- Manage a trap entry related to the alarm UpsAlarmShutdownPending in
the IETF MIB.
- Manage the oid xupsBatteryLastReplaceDate in the Eaton Xups Mib.
- Oid upsConfigDateAndTime cannot be written.
- Implement the data xupsBatteryLastReplaceDate in the mib Eaton Xups.
- Suppress final 0 in Mib data oid that are part of table in the Mibs.
- Trap binded variables oid are completed either with 0 for scalar
data, or with the index for table data.
- Eaton Xups Mib data named "---AverageCurrent" renamed to "---
TotalCurrent" in the description Mib file to be consistent with the UPS measures.

Known issues and limitations:

- If LDAP group name contains a space login to the card will become impossible.
- Web UI cache needs to be cleared with CTRL+F5 after an upgrade
- Up to 30 shutdown agents can be connected.
- Environmental probe values cannot be set to trigger shutdown.
- Temperature compensated charging control with 3 phase UPS does not work

===============================
Release 1.5.3 January 2019
===============================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9SX, 9E

Fixes:
- Increased LDAP username and password length to match LDAP maximum
- Fixed IPv6 addressing issues with SNMPv3 and LDAP

Known issues and limitations:

- Web UI cache needs to be cleared with CTRL+F5 after an upgrade


- Up to 30 shutdown agents can be connected.
- Environmental probe values cannot be set to trigger shutdown.

===============================
Release 1.5.1 December 2018
===============================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9SX, 9E

Improvements:
- Added support for LDAP authentication
- Added measurements display on the synoptic view of the home screen
- Added multiphase support on the synoptic view
- Shutdown procedures disabled when no agents are connected
- Alarms page reworked
- XUPS MIB enhancements
- Added tolerance to communication losses with UPS

Fixes:
- Cybersecurity updates
- Communication and certificate issues with IPM and IPP software

Known issues and limitations:

- Web UI cache need to be cleared with CTRL+F5 after an upgrade


- Up to 30 shutdown agents can be connected.
- Environmental probe values cannot be set to trigger shutdown.
- Length of username and groupname in LDAP are both limited to 31 characters

--------------------------------------------------------------------------------
===============================
Release 1.4.9 September 2018
===============================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9SX

Improvements:

- SNMP alarms table in XUPS and IETF MIB fixed.


- Communication issue with some 9PX and 9SX models resolved.

Limitations:
- Not able to display 3 phase measurements.
- Environmental probe values cannot be set to trigger shutdown.
- Up to 30 shutdown agents can be connected.

--------------------------------------------------------------------------------
===========================
Release 1.4.3 July 2018
===========================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher

Supported UPS: Eaton 5P, 5PX, 5SC Rack, 9PX, 9SX

Improvements:

- Enabled pairing with user credentials especially for easier use with IPM.

Known issues:
- SNMP alarms table in XUPS and IETF MIB not working.

Limitations:
- Not able to display 3 phase measurements.
- Environmental probe values cannot be set to trigger shutdown.
--------------------------------------------------------------------------------

===========================
Release 1.4.2 July 2018
===========================

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher

Supported UPS: Eaton 5P, 5PX, 9PX, 9SX

Improvements:

- Added support for environmental monitoring probes (gen 2, C/N: EMPDT1H1C2,


P/N:744-A4026)
- Added capability to download measurement history in CSV format
- Added capability to save and restore settings through UI and SSH
- Added capability to download maintenance report from the UI for advanced
troubleshooting

Fixes:
- Cybersecurity updates

Known issues:
- SNMP alarms table in XUPS and IETF MIB not working.
- Pairing with IPM and IPP using user credentials does not work.
Trying this may lead to a lockup in the communication.
To recover, remove the connection and rediscover the card.

Limitations:
- Up to 30 shutdown agents can be connected.
- Not able to display 3 phase measurements.
- Environmental probe values cannot be set to trigger shutdown.
--------------------------------------------------------------------------------

===========================
Release 1.3.3 June 2018
===========================

- Initial firmware release for the Eaton Gigabit Network Card (Network-M2).

Software compatibility: IPP 1.61 and higher, IPM 1.61 and higher

Supported UPS: Eaton 5P, 5PX, 9PX, 9SX

Known issues:
- SNMP alarms table in XUPS and IETF MIB not working.

Limitations:
- Up to 30 shutdown agents can be connected.
- Does not support environmental monitoring probes.
- Environmental probe values cannot be set to trigger shutdown.
- Not able to display 3 phase measurements.