Abb ZX2 - en
Abb ZX2 - en
Gas-insulated switchgear
Type ZX2
Gas-insulated switchgear
Medium voltage switchgear
Type ZX2
Single or double busbar systems
12 kV, …2500 A, …40 kA
24 kV, …2500 A, …40 kA
36 kV, …2500 A, …40 kA
Slide 2
Gas-insulated switchgear
Medium voltage switchgear
Type ZX2
With IAC classification
AFLR 40 kA 1s
Rated voltage kV 12 24 36 1)
Rated current b
A …2500 …2500 …2500
of busbars
Rated current
A …2500 …2500 …2500
of tee-offs
hexafluoride (SF6)
Width a mm 600/8003)5)/8404) 600/8003)/8404) 3) Rated feeder current
2500 A c
1860 (with a 500 mm
Depth c mm 5) Double feeder panel up to
a
deep LV compartment)
25 kA, 2 x 630 A
Slide 3
Gas-insulated switchgear
Slide 4
Gas-insulated switchgear
Operation of a switchgear panel without multi-functional protection- and control-unit
Type ZX2
Bay Control Unit
– Modern solution of a conventional switchgear control in ZX
– Integral control, indication and annunciation unit
– Conventional control without active components
– Control via conventional push-buttons and key operated
local / remote switch
Slide 5
Gas-insulated switchgear
Single lines of switchgear variants (SBB)
Type ZX2
Slide 6
Gas-insulated switchgear
Single lines of switchgear variants (DBB) – 1 von 2
Type ZX2
Slide 7
Gas-insulated switchgear
Single lines of switchgear variants (DBB) – 2 von 2
Type ZX2
Slide 8
Gas-insulated switchgear
Doppelsammelschienenfeld für 2000 A
Type ZX2 14
1 HMI of multifunctional protection and control unit 12
2 Three position disconnector operating mechanism
3 Three position disconnector 17
4 Pressure sensor (temperature-compensated)
5 Circuit-breaker operating mechanism 1
6 Secondary terminals of current transformer 16 2
7 Cable socket 3
8 Cable plug 15 4
9 Electronic unit of multifunctional protection and control unit 14
10 Voltage transformer 13 5
11 Multifunctional socket 12
12 Pressure relief disk 11 6
13 Current transformer 7
14 Pressure relief duct 10 8
15 Circuit-breaker
16 Measuring sockets for capacitive voltage indicator system 9
17 Busbars
SF6
Slide 9
Gas-insulated switchgear
Single busbar panel with outer cone connection for up to 1250 A
Type ZX2 8
1 HMI of multifunctional protection and control unit 9
2 Pressure sensor (temperature-compensated)
3 Circuit-breaker 12
4 Electronic unit of multifunctional protection and control unit
11 1
5 Plug-in isolatable voltage transformer
10
6 Ring type current transformer
7 Outer cone cable connector 2
9
8 Pressure relief duct 3
9 Pressure relief disc 8
10 Measuring sockets for capacitive voltage indicator system
7
11 Three position disconnector
12 Busbars 6
SF6 4
5
Slide 10
Gas-insulated switchgear
Double feeder panel up to 24 kV 630 A for each feeder
Type ZX2
11
1 Multifunctional protection and control unit 10
2 Three position disconnector operating mechanism 13 1
3 Three position disconnector
4 Pressure sensor (temperature-compensated) 2
5 Circuit-breaker operating mechanism 12 3
6 Outer cone cable bushing 11 4
7 Current transformer or Rogowski coil 10
8 Outer cone cable plug 9
9 Circuit-breaker 5
10 Pressure relief disk 8 6
11 Pressure relief duct 7
12 Measuring sockets for capacitive voltage indicator system
13 Busbars
SF6
Slide 11
Gas-insulated switchgear
Type ZX2
Integrated double busbar metering with plugged-in voltage
transformer in air on top of panels with 2000 A feeder current
Slide 12
Gas-insulated switchgear
Type ZX2
Bus coupler DBB 2000 A
Bus sectionalizer DBB 2000 A
– Optional equipped with current detection by
• Block device
• Block device + bushing current transformer
• Bushing current transformer
(also without current detection)
Slide 13
Gas-insulated switchgear
Type ZX2 – Plug-in components
BB plug-in system
Test plug
Voltage transformer
Cable plug
Type ZX2
– Partitioned function compartments ► maximum safety
– Completely shockproof enclosures
– High voltage section totally independent of environmental
influences
– No effect of site altitude on dielectric strength
– Maximum availability for the operator
– Independence of the environment makes for extremely
long system life
– Minimum maintenance requirement
– Longer life than other system types
Slide 15