Paperless Recorder

B 70.6510.0
Operating Manual
03.08/00467986
Contents
1 Introduction 7
1.1 Preface .......................................................................................................... 7
1.2 Arrangement of the documentation ........................................................... 8
1.2.1 Structure of this operating manual ................................................................. 8
1.3 Typographical conventions ......................................................................... 9
1.3.1 Warning signs ................................................................................................. 9
1.3.2 Note signs ...................................................................................................... 9
1.3.3 Representation modes ................................................................................. 10

2 Device description 11
2.1 Displays and controls ................................................................................ 11
2.2 Operating principle and graphic elements .............................................. 12
2.3 Analog inputs .............................................................................................. 14
2.4 Digital signals (event traces) ..................................................................... 15
2.5 Counters / integrators / operating time counter ..................................... 16
2.5.1 Reporting period of the counts .................................................................... 18
2.5.2 Resetting the counters / integrators / operating time counters ................... 18
2.5.3 Response to instrument reconfiguration ...................................................... 19
2.5.4 Response at end of summer time ................................................................ 20
2.6 Math/logic module ..................................................................................... 20
2.7 Operating modes ........................................................................................ 23
2.8 Storing data ................................................................................................ 24
2.9 Read-out of data ........................................................................................ 27
2.10 Evaluating data ........................................................................................... 27
2.11 Webserver ................................................................................................... 28

3 Operation and visualization 31


3.1 Basic menu ................................................................................................. 32
Contents
3.2 Visualization ................................................................................................ 33
3.2.1 Diagram representation with digital display (small measurements) ............. 34
3.2.2 Diagram representation with scaling ............................................................ 35
3.2.3 Diagram representation with bar graph ........................................................ 35
3.2.4 Large digital display (large measurements) .................................................. 36
3.2.5 Curve representation (header switched off) ................................................. 37
3.2.6 Evaluation of the stored measurement data ................................................ 38
3.2.7 Counters / integrators / operating time ........................................................ 41
3.3 Parameterization ........................................................................................ 43
3.4 Configuration .............................................................................................. 46
3.5 Event list ...................................................................................................... 47
3.6 CompactFlash card .................................................................................... 50
3.7 Device info .................................................................................................. 53
3.8 Text entry ..................................................................................................... 55
3.9 Entering values ........................................................................................... 56
3.10 Code number (password query) ............................................................... 57

4 Configuration parameters 59
4.1 Operating example ..................................................................................... 59
4.2 Table of configuration parameters ........................................................... 60
4.2.1 Parameterization .......................................................................................... 60
4.2.2 Configuration - Instrument (device) data ...................................................... 62
4.2.3 Configuration - Analog inputs ...................................................................... 64
4.2.4 Configuration - Math channels ..................................................................... 66
4.2.5 Configuration - Counter/integrator (extra code) ........................................... 66
4.2.6 Configuration - Recording ............................................................................ 70
4.2.7 Configuration - Outputs (extra code) ........................................................... 73
4.2.8 Configuration - Control functions ................................................................. 74
4.2.9 Configuration - Texts .................................................................................... 74
4.2.10Configuration - Interfaces ............................................................................ 75
4.2.11Configuration - Undocumented parameters ............................................... 76
4.2.12Configuration - Fine calibration ................................................................... 76

5 Setup program 77
5.1 Hardware and software requirements ...................................................... 77
5.2 Installation .................................................................................................. 78
Contents
5.3 User interface ............................................................................................. 79
5.4 Configuration .............................................................................................. 81
5.5 Teleservice .................................................................................................. 84
5.6 Data transfer from and to the instrument ................................................ 86
5.6.1 Transfer via CompactFlash memory card .................................................... 86
5.6.2 Transfer via interface .................................................................................... 89
5.7 Connection between the PC and the recorder ........................................ 91
5.7.1 Assistant for device settings ........................................................................ 91
5.7.2 Device list ..................................................................................................... 95
5.8 Menu functions ........................................................................................... 96
5.8.1 File ................................................................................................................ 96
5.8.2 Edit ............................................................................................................... 97
5.8.3 Data transfer ................................................................................................. 98
5.8.4 Extras ........................................................................................................... 98
5.8.5 Window ...................................................................................................... 103
5.8.6 Info ............................................................................................................. 104
5.9 Math/logic ................................................................................................. 105
5.10 Character set ............................................................................................ 109

6 Rights 111
6.1 Rights with regard to the setup program ............................................... 111

7 PC programs 113
7.1 PC evaluation software (PCA3000) ......................................................... 113
7.2 PCA communications software (PCC) ................................................... 114

8 Identifying the instrument version 115


8.1 Type designation ...................................................................................... 115
8.2 Standard accessories .............................................................................. 116
8.3 Optional accessories ............................................................................... 116

9 Installation 117
9.1 Installation site and climatic conditions ................................................ 117
9.2 Fitting ......................................................................................................... 117
Contents
10 Electrical connection 121
10.1 Installation notes ...................................................................................... 121
10.2 Technical data ........................................................................................... 121
10.3 Approvals .................................................................................................. 122
10.4 Connection diagram ................................................................................ 122

11 TÜV Report on Data Manipulation Security 125

12 Index 129
1 Introduction
1.1 Preface

B
Please read these operating instructions before commissioning the
instrument. Keep the operating instructions in a place that is accessible to all
users at all times.
Please assist us to improve these operating instructions, where necessary.

Your comments will be appreciated.

H All necessary settings are described in this manual. If any


difficulties should arise during commissioning, you are asked not
to carry out any manipulations that could endanger your rights
under the instrument warranty!
Please contact the nearest subsidiary or the head office in such a
case.
See back cover for contact in: Germany, UK, USA

E
When returning modules, assemblies or components, the
regulations of EN 61340-5-1 and EN 61340-5-2 “Protection of
electronic devices from electrostatic phenomena” must be
observed. Use only the appropriate ESD packaging for transport.
Please note that we cannot accept any liability for damage caused
by ESD.
ESD=electrostatic discharge

7
1 Introduction
1.2 Arrangement of the documentation
The documentation for this instrument consists of the following parts:

Operating This operating manual comes with the delivery. It is addressed to the
Manual equipment manufacturer and the user with appropriate technical expertise.
B 70.6510.0
In addition to installation and electrical connection, it contains information on
commissioning, operation and parameter setting on the instrument, as well as
on the optional PC setup program and the optional evaluation program (PCA).

Interface It provides information on the serial interface (RS232 and RS485), which can
Description be supplied as an extra code. The interface description can be used to
B 70.6510.2.0 develop specific programs which can, for instance, read out current
measurement data.

1.2.1 Structure of this operating manual


This manual is arranged in a way which permits the user to enter directly into
operation and configuration of the instrument. Consequently, chapters dealing
with items that normally arise only once are placed at the end of the manual.
These include instrument description, type designation, installation and
electrical connection.

8
1 Introduction
1.3 Typographical conventions

1.3.1 Warning signs


The signs for Danger and Caution are used in this manual under the following
conditions:

Danger

V This symbol is used when there may be danger to personnel if the


instructions are ignored or not followed correctly!

Caution

A This symbol is used when there may be damage to equipment or data if the
instructions are ignored or not followed correctly!

Caution

E This symbol is used where special care is required when handling


components liable to damage through electrostatic discharge.

1.3.2 Note signs

H
Note
This symbol is used when your special attention is drawn to a remark.

Reference

v This symbol refers to further information in other manuals, chapters or


sections.

Footnote
abc1
Footnotes are remarks that refer to specific points in the text. Footnotes
consist of two parts:
A marker in the text, and the footnote text.
The markers in the text are arranged as continuous superscript numbers.

Action instruction
This symbol indicates that an action to be performed is described.
h
The individual steps are marked by this asterisk, e.g.
h Press the h key
h Confirm with E

9
1 Introduction
1.3.3 Representation modes

Keys
Keys are shown in a box. Both symbols and text are possible. If a key has a
h+E multiple function, then the text shown is the one that corresponds to the
function that is active at the moment.

Screen texts
Program
Texts that are displayed in the setup program are indicated by italic script.
Manager

Menu items
Edit Î
Menu items in the setup program which are referred to in this manual are
Device data
shown in italics. Menu name, menu item and submenu item are separated
from each other by “Δ.

10
2 Device description
2.1 Displays and controls
Color display
320 x 240 pixels, 27 colors

Menu-dependent function keys (softkeys)


screen-dependent functions, represented by text or symbols

Status LED (red)


is on continuously while
an alarm is present

Power LED (green)


This is lit continuously as
soon as power is applied.
It blinks when the screen
saver is active.

Exit
- previous window
- cancel the
present action
Menu
return to the basic menu1
Enter
- select menu item
- enter selection

Cover
for the CompactFlash® slot 2 to open the cover of the
CompactFlash slot

1
Not from the configuration level if a parameter has already been modified there.
2
CompactFlash® is a registered trademark of the SanDisk Corporation.

H The life of the background illumination can be prolonged by


making use of the screen saver.
v Chapter 4 “Configuration parameters”,
ParameterizationÎ Display off

11
2 Device description
Opening and
closing the door Header Status line
of the
instrument

To open or close the door of the


instrument, turn the knob

2.2 Operating principle and graphic elements


Keys The recorder is operated from eight keys. Three of these keys have fixed
functions, the other five (softkeys) have menu-dependent functions.
v Chapter 2.1 “Displays and controls”

Softkeys The functions of the softkeys appear in the bottom line of the display, as
symbols or in plain text.

12
2 Device description
Status line The status line is shown in the top section of the display. It provides
information on important actions and states. The status line is always visible,
irrespective of the level (operation, parameters, configuration).
Alarm
If an alarm occurs (e.g. out-of-limit), the bell (alarm) will flash in this field.

CF card / internal memory


Shows the free storage of the CompactFlash card or the internal memory, as
a percentage. In the event of a “memory alarm” or a fault on the CF card, the field is
shown with a yellow background and the symbol will flash. The error message
can be checked in the CF card menu (Chapter 3.6 “CompactFlash card”).

Storage capacity of the CF card

Available internal memory for read-out via CF card


(the diagram shows a turquoise-colored memory chip)

Available internal memory (for read-out via interface)


(the diagram shows a dark blue memory chip)

The egg timer appears whenever the instrument cannot be


operated because it is busy.

The “H” indicates that the measurements which are displayed


are derived from the past (history). The display shows
the data saved in the FLASH memory.

If a fault occurs, an “i” will flash in this position.


In the device info window (v Chapter 3.7 “Device info”)
you can ask for the cause of the fault.

If the keys are inhibited, a key will flash in this position.


Time & Date
Display of the current time
and date

Present diagram speed


Background color:
gray = normal operation,
blue = timed operation,
orange = event operation

Instrument name (maximum 16 characters).

Shows the last entry in the event list

13
2 Device description
Channel line The channel line shows the measurements of the active channels and their unit
(channel as
representation)
- a measurement
- scale or
- bar graph.
Alternatively, the header can be switched off altogether.
In addition, alarms and out-of-limit conditions are made directly visible,
depending on the display mode.

Example: Measurement (small meas.)

Numerical display
The measurements are shown in numerical form.
Unit of measurement

Overrange

Underrange
(underrange)
State of the
event traces

OFF
If a channel has been switched off, then
there will be no indication at all.
Alarm
If an alarm (e.g. out-of-limit) is present,
the measurement of the channel is shown on a red background.

Selection and visual presentation of the channel line can be controlled through
the parameter Parameterization ➔ Diagram view ➔ Channel represent. or by
using the key.
With the help of the parameter Parameterization ➔ Diagram view ➔ Channel
indication ➔ Channel 1 — 6, it is possible to suppress the display of individual
channels in the channel line. This is especially useful for scale or bar graph
display, where more space is needed to show the diagram. The channels that
have been suppressed in the display will nevertheless be recorded, and shown
on the diagram.

2.3 Analog inputs


Internal The paperless recorder can be equipped with 3 or 6 analog inputs. When
analog inputs configuring the analog inputs (Chapter 4.2 “Table of configuration
parameters”), these are designated as analog input 1 — 3 (1 — 6).

14
2 Device description
2.4 Digital signals (event traces)
Signal types In addition to the four binary inputs (extra code), digital signals generated by
the instrument itself can also be displayed in the six digital traces (event
traces):

signal Description

Binary input 1 — 4 Four binary inputs available as hardware


(extra code)

Logic channel 1 — 6 Channels which are created by using the math


and logic module (extra code required)

Low alarm 1 — 6 Underrange of the channels

Low combination alarm OR linkage of all low alarms

High alarm 1 — 6 Overlimit of channels

High combination alarm OR linkage of all high alarms

Counter/integrator alarm 1 — 6 Limit infringements of counter and


integrator channels (extra code required)

Counter/integrator combination OR linkage of all counter/integrator


alarm alarms (extra code required)

Combination alarm OR linkage of all low, high and counter/inegrator


alarms

CF card inserted The signal is set when a CF card is inserted in the


instrument. It remains active until the card is
removed.

Int. mem. alarm/CF card The alarm is triggered when the internal storage
memory available for read-out via the CF card
card has fallen below a certain value1.

Int. mem. alarm/serial The alarm is triggered when the internal storage
memory available for read-out via the interface
has fallen below a certain value1.

Mem. alarm/CF card The alarm is triggered when the storage memory
available on the CF card that has been plugged in
falls below a certain value1, or no CF card is
plugged in.

Error Alarm when the battery is empty, or the time has


to be set.
Chapter 3.7 “Device info”

MODbus flag Control flag, which can be activated through one


of the interfaces.
1 The limit for all memory alarms is the same, and is set by the parameter
Configuration Î Device data Î Memory alarm.

15
2 Device description
Representation Representation on the screen is as follows:

Representation

as symbol On/off represented as switch:

as diagram Representation as a record over time:

Outputs The digital signals can be used to operate three relays (extra code). The action
can be configured as a break (SPST-NC) or make (SPST-NO) contact
(Configuration ➔ Outputs).

External texts External texts can be called up via four binary inputs or the logic channels. If a
binary input is closed or a logic channel makes a 0-1 transition, then the
preconfigured text will be entered in the event list. Either a standard text or one
of the 18 definable texts can be used. The instrument automatically
supplements the texts in order to distinguish between the appearance and
disappearance of the signal. The external texts are configured on the
instrument, under Configuration ➔ Control functions.
v Chapter 3.5 “Event list”

Event operation The digital signals can be used to activate event operation. In event operation,
the measurements are stored with a storage cycle that is different from normal
operation.

2.5 Counters / integrators / operating time counter

These are not electrical measurement inputs (hardware), but channels which
are calculated by the paperless recorder (software).

16
2 Device description
Counters
Counter inputs Any of the digital signals can be used as input signals for the counters.
v Chapter 2.4 “Digital signals (event traces)”
Example:
- binary inputs
- logic channels
- alarms
- memory alarms
- Modbus flag (signal via interface)

Counter 30Hz max.


frequency

Evaluation The count pulses can be evaluated (weighted). A down counter can be
implemented by entering a negative weighting (e.g. weighting factor -1).
Each count change can be documented with an entry in the event list. The
new count is attached to the message.

Integrators
Integrator Analog inputs 1 — 3 or 1 — 6 and math channels 1 — 6
inputs

Integrator sec, min, hr and day


time base

Evaluation You can also enter a weighting for the integrators.

Weighting - measurement of flow volume


example
- input signal of 0 — 20mA (corresponds to 0 — 500 liters/sec)
- time base 1sec
- weighting 0.001
Result: display of the integration value (volume) in m³.

Minimum size Entering a threshold value (amount of the threshold value) has the effect that
of the input integration takes place only when the value has been exceeded. No
signal integration will occur on falling below this value. The advantage of integration
with a threshold value larger than 0 is that possible noise from a transducer
can be suppressed in this way.

H If there is an overrange or underrange on an integrator input, then


integration is stopped (the latest valid value is retained), and will
only continue when the input signal is correct again.

17
2 Device description
Operating time counter
The operating time counter will count how long a selected binary input or one
of the digital signals is closed (set). The time can be displayed in sec, min, hr
or days.

2.5.1 Reporting period of the counts


After an adjustable time (reporting period), the counts are stored for all
counters/integrators/operating time counters. The counts for the current and
the previous 7 completed reporting periods will be displayed. The following
counter/integrator types are possible:
- periodic
In addition, the time period (between 1 min and 12 hrs) must be selected in
the parameter Period.
- external
In this case, the counter/integrator is updated only when the selected
control signal is active (e.g. binary input is closed). When the control signal
is deactivated (e.g. binary input is opened), the counter/integrator value is
saved and reset to 0.
- daily
- weekly
- monthly
- yearly
- total
- daily, from ... to
The period also has to be selected, by means of the parameters “Daily start
time” and “Daily end time”. The counter/integrator will then be updated
from the start time only. When the end time has been reached, the counter/
integrator value is saved and reset to 0.

2.5.2 Resetting the counters / integrators / operating time counters

Periodic reset There is a reporting period for each counter/integrator/operating time counter.
At the end of this period, the current data (value and time) are saved and the
value reset to 0. Subsequently, the next period can be recorded.
An exception is the totalizer/integrator. It is saved whenever any count/
integration has been completed, but it is not reset to 0. It enables the totalizer
to be evaluated in the evaluation software PCA as well.

18
2 Device description
External reset You can configure one control signal for all 6 counters/integrators together,
with the result that the counters/integrators are reset to 0 without any saving
of the previous values. The period for the counter/integrator summation will be
restarted at this point. This means that after the test run of an installation, for
instance, the recording can be freshly started; the test run values that are not
required are eliminated.
v see Page 69 “Generate reset”

Reset from Another option for resetting the counter/integrator values is provided at the
keys parameter level. After entering the password, you can define a value for each
of the 6 channels. The counter/integrator will then be set to this value. When
the value is entered, after editing, a message with the new and the old count is
entered in the event list.
The time period for the counter/integrator summation will not be restarted. The
previous counter/integrator values will also not be saved.

H If you wish to save the previous counter/integrator values, you


must execute the function “Update CF incl. counters ...” in the
menu for the CompactFlash card.

In this way, the recording can be freshly started for individual counters/
integrators, e.g. after the test run of an installation; the test run values that are
not required will be eliminated in the process.
You can select a password that is different from that for accessing the
configuration. The password is set up in Configuration ➔ Device data ➔ Code
No. (password) ➔ Reset counter / int.

Reset from If, in the menu CompactFlash card, the function CF update incl. counters
CompactFlash is carried out, then the counter states will also be saved and then reset.
card menu
v See “CompactFlash card” on Page 50.

2.5.3 Response to instrument reconfiguration


When the instrument is reconfigured, the current counter/integrator reporting
periods remain unaffected. The counter/integrator values will not be reset to 0
and the reporting period will not be restarted.

H The values can only be deliberately reset through the


Parameterization menu.

19
2 Device description
2.5.4 Response at end of summer time

A
If a period of less than one hour has been set for counters/
integrators, and the change from summer time to winter time falls
precisely within this period, then the PC evaluation software
(PCA3000) will forcibly set the end time to be the same as the start
time. This prevents a negative period arising, and ensures that
further processing is error-free.

2.6 Math/logic module


The math and logic module is available as an extra code. Like the counter/
integrator/operating time counters, the math and logic module is implemented
as channels that are not available as hardware but are calculated by the
instrument software.

The math and logic module consists of 2 parts:


- the math module for calculating analog values and
- the logic module for calculating Boolean values (0 or 1).

Math module With the help of the math module, measurement inputs can be used for the
calculation of “virtual” math channels.
A total of 6 channels can be recorded (stored) in the instrument. In the
configuration, you will find an option under Configuration Î Recording Î
Analog channels Î Analog channel 1 — 6 Î Input signal for selecting which
of the analog inputs or math channels should be stored.
If more than 6 channels are to be active in the instrument (e.g. 4 analog inputs
and 3 active math channels), then you can also use the visualization in the
presentation mode “Large digital display (large measurements)” to see the
measurements that are not stored.
v Chapter 3.2.4 “Large digital display (large measurements)”

20
2 Device description
The following variables are used for the formulae:
- analog inputs (AE1 — AE6)
- math channels (MAT1 — MAT6)
- counter/integrator channels (ZI1 — ZI6)
- binary inputs (BE1 — BE4)
- alarms
- errors
- Modbus flag (signal via interface)
- instrument-specific data (only after consultation with the manufacturer)
If counter/integrator values are used for calculation, then please note that their
accuracy is reduced, since, in this case, two different data formats have to be
used for calculation. The counters/integrators are calculated in the double-
float format, whereas the math module employs a single-float format that
follows the IEEE 754 standard. Nevertheless, it is possible to include these
values in the math module.
The following fixed functions are available:
- difference
- ratio
- relative humidity (psychrometric measurement)
- moving average
For the moving average, the reference channel has to be entered (in most
cases, the analog input number) and the time period (in minutes) for
calculating the moving average.
The following operators and functions are available for the formulae: +, -, *, /,
(, ), SQRT(), MIN(), MAX(), SIN(), COS(), TAN(), **, EXP(),
ABS(), INT(), FRC(), LOG(), LN().
On going above or falling below the scalable values, the math channel is
treated as for “out-of-range”.
The formulae are entered in the PC, in the setup program. The mathematical
formulae cannot be edited by using the keys on the instrument.

H For further information, refer to


Chapter 5.9 “Math/logic”

21
2 Device description
Logic module You also have up to 6 channels available as logic channels.
As is the case with all the other digital signals, the calculated digital (Boolean)
values can be used for different functions:
- recording in the event traces,
- as a control signal for display switch-off,
- clock time synchronization,
- operating time counter,
- externally controlled counters / integrators
- counter/integr. reset
- event operation and key inhibit,
- for output to a relay and
- as count input for a counter.

The following variables are used for the formulae:


- binary inputs
- logic channels
- alarms
- errors
- Modbus flag (signal via interface)
- TRUE
- FALSE
- device-specific data (only after consultation with the manufacturer)

These functions can be used for the formulae:


- ! (NOT)
- & (AND)
- | (OR)
- ^ (XOR)
- / (rising edge)
- \ (falling edge)
- ( (open bracket)
- ) (close bracket)

H For further information, refer to


Chapter 5.9 “Math/logic”

22
2 Device description
2.7 Operating modes
3 operating The instrument has 3 operating modes:
modes
- normal operation
- timed operation
- event operation
The following settings can, among others, be made for each of the three
operating modes:
- stored value
- storage cycle

Stored value The stored value setting determines what is stored: average, minimum,
maximum or momentary value between two storage cycles, or the peak value
(envelope). The setting “peak value” means that the maximum and minimum
values from the last storage cycle are saved.

Storage cycle The storage cycle determines the interval between two stored values. The
diagram speed corresponds to the storage cycle, which means that with a
storage cycle of 5sec, for example, the stored value is entered in the diagram
every 5sec.

Normal Normal operation is active whenever event or timed operation is not active.
operation

Timed For timed operation, a period of time can be defined (up to 24 hrs) within
operation which a specific stored value and a specific storage cycle are active.

Event operation Event operation is active as long as its control signal (v Chapter 4.2.6
“Configuration - Recording”) is active. Event operation can be used, for
example, to shorten the storage cycle when an alarm is present.

Priority The respective priorities of the operating modes are allocated as follows:
Operating mode Priority
Normal low
operation
Timed operation average
Event operation high

Active The active operating mode is shown in the diagram by the background color
operating mode for the diagram speed:
Operating mode Color
Normal gray
operation
Timed operation turquoise
Event operation orange
v Chapter 2.2 “Operating principle and graphic elements”

23
2 Device description
2.8 Storing data
Life-cycle data The integrated life-cycle data management puts users in the position of being
management able to save all the process data from the system that is being monitored in an
archive file on their PCs or a server system.

The recovery of configuration-dependent system data, which may be required


for commissioning, maintenance or optimization during the life-cycle of a
system, is now enabled by the associated PC evaluation software (PCA3000)
in a dialog window.

24
2 Device description
Operating
principle

The measurements from the analog inputs are acquired continuously in a


250msec sampling cycle, and then stored in the main memory. These
measurements also serve as the basis for limit monitoring.

Main memory The data stored in the main memory are regularly copied to the CompactFlash
(FLASH card in 4 kbyte blocks. The main memory is written to as a ring memory, i.e.
memory) when it is full, the oldest data will automatically be overwritten by new data.
The capacity of the main memory is sufficient for approximately 350,000
measurements. The instrument monitors the capacity of the main memory and
activates the “Memory alarm (internal)” signal if the level falls below a
configurable residual capacity.

CompactFlash For saving the data, CompactFlash cards (industrial grade) can be used with
card the following storage capacities: 64/128/256MB.
The instrument monitors the capacity of the CompactFlash card, and activates
the “Memory alarm (CF card)” signal if the level falls below a configurable
residual capacity. This signal can be used, for instance, to operate a relay
(warning signal “Swap CF card”).

Data security The data are stored in coded form in a proprietary format. If the CompactFlash
card is removed from the instrument, no data will be lost immediately, as these
data are still stored in the FLASH memory. A loss of data will only occur if, after
the CompactFlash card has been removed, the FLASH memory is completely
rewritten as well, and no data have been read out through the interface.

Storage cycle Different storage cycles, ranging from 1sec to 32,767sec can be configured
for normal, event and timed operation under “configuration”.
The storage cycle determines the time intervals at which the measurements
are stored.

Stored value Under this parameter, separate configurations are made for normal, event and
timed operation, to decide which value is stored (average, momentary,
minimum, maximum, peak values).

25
2 Device description
Recording The recording duration depends on various factors:
duration
- number of analog channels and event traces being recorded
- storage cycle
- number of events in the event list.
Internal recording duration (without external CF card)

Number of Memory Storage Storage Storage Storage


channels size cycle cycle cycle cycle
1 min 30 sec 10 sec 1 sec

3 approx. 42.2 days 21.1 days 7 days 17 hours


1MB

6 approx. 29.5 days 14.8 days 4.9 days 12 hours


1MB

Recording duration with CF card

Number of Memory Storage Storage Storage Storage


channels size cycle cycle cycle cycle
1 min 30 sec 10 sec 1 sec

3 64 MB 8.8 years 4.4 years 1.5 years 1.8 months

3 128 MB 17.6 years 8.8 years 2.9 years 3.5 months

3 256 MB 35.3 years 17.6 years 5.9 years 7.1 months

6 64 MB 6.2 years 3.1 years 1.0 years 1.2 months

6 128 MB 12.3 years 6.2 years 2.1 years 2.5 months

6 256 MB 24.7 years 12.3 years 4.1 years 4.9 months

The calculation of the recording duration is made for the storage of


momentary, minimum, maximum or average values. If peak values are
recorded, then the times are shorter, since a maximum and minimum value is
recorded each time.
The recording capacity will be further reduced if a large number of event
messages are also stored.

Optimization of The recording duration can be optimized by process-oriented selection of the


recording storage cycle.
duration
In normal operation (no error, no alarm, ...) a storage cycle that is as long as
possible (e.g. 60sec, 180sec, …) should be selected, depending on the
particular application.
In the event of an alarm or error, the storage cycle can be shortened via event
operation, with the effect that the measurement data are recorded with a high
time resolution.

26
2 Device description
2.9 Read-out of data
In addition to automatic read-out via the external CompactFlash memory card,
measurement data can also be read out through one of the interfaces (RS232,
RS485, setup, Ethernet).
Both read-out options (card/interface) work in parallel. For this reason, there
are also two “digital signals”, which indicate when the available storage space
has fallen below a certain configurable value.

Memory alarm The limit for alarms can be set by the parameter Configuration ➔ Device data
➔ Memory alarm in the configuration level.
The parameter Configuration ➔ Memory upload can be used to determine
which storage space indication should be shown in the status line. The “digital
signals” for storage space detection function independently of the indication in
the status line.

Digital signals IntMemAlm/CF


If this signal is set, it means that no data have been fetched by the CF card for
a long time, and the available capacity of the internal memory has fallen below
the configured level.
IntMemAlm/ser
If this signal is set, it means that no data have been fetched by the interface for
a long time, and the available capacity of the internal memory has fallen below
the configured level.
MemAlmCFcard
If this signal is set, it means that not enough space is avialable on the CF card.
The program PCA3000 can help here. Use PCA3000 to read in the data, save
them to the hard disk on a network, and free up the space on the CF card.
Alternatively, you can use a new CF card.

Data lost A loss of data is only imminent if all three of the above signals are set.

Read-out via Use the PCA Communications Server software (PCC) to read out
interface measurement data via the serial, setup or Ethernet interface. The software has
been developed especially for the paperless recorder.
v Please refer to the Operating Manual B 70.9702.0 for further information.

H Use the same archive (in the PC) for reading out via the interface
as for reading out with the CF card. This saves having to put
together data from different files at a later date.

2.10 Evaluating data


Please use the PC Evaluation Software (PCA3000) for evaluating the data on
the PC. The software has been developed especially for the paperless
recorder.
v Please refer to the Operating Manual B 70.9701.0 for further information.

27
2 Device description
2.11 Webserver
If the paperless recorder is equipped with the extra code 008 “Ethernet inter-
face”, and the device-internal Ethernet software (“Ethernet version“) has the
number 183.02.03 or higher, then the paperless recorder has an inbuilt web-
server. The webserver can be started by entering the IP address in an Internet
browser on the PC (e.g. http://10.10.90.45).
Device name
Analog channels
Counters / integrators
Event traces

The variables that are shown are acquired and displayed automatically by the
webserver. The latest data are read out of the instrument every 5 seconds. Any
limit infringements show a red background. A maximum of 6 channels (analog
or math channels), up to 6 counters or integrators, and a maximum of 6 event
traces.

28
2 Device description
Display of ... Activated through menu ...
Device name Configuration - Instrument data - Device name
Analog or math channels Configuration - Recording - Analog channels
Counters or integrators Configuration - Counter/integrator
Event traces Configuration - Recording - Event traces

Only the activated signals will be displayed.

The information about the “Ethernet version” can be found in the “Device info”
menu.

v Chapter 3.7 “Device info”

H Only 1 PC (client) at a time can access the device (server) via the
Ethernet interface.

Since the paperless recorder is only polled by the Internet browser every 5 se-
conds, it is possible that, for instance, the PCC data transfer software takes
over control of the paperless recorder during this interval. After securing the da-
ta, PCC will end access to the recorder, so that the Internet browser can read
out data again.

29
2 Device description

30
3 Operation and visualization
After starting up the paperless recorder by switching on the supply (power
ON), you will see the start logo (company logo).

During screen build-up, the recorder is initialized with the data of the last
configuration.

H After the initialization phase, the measurement diagram


(visualization level) is displayed.

H By using the setup program, an individual start logo (bitmap with a


maximum of 16 colors) can be loaded into the instrument, through
the function Extras Î Start screen.

31
3 Operation and visualization
3.1 Basic menu
The basic menu is the central point from which the various instrument levels
branch out.
The following levels are available:
v Chapter 3.2 “Visualization”
v Chapter 3.3 “Parameterization”
v Chapter 3.4 “Configuration”
v Chapter 3.5 “Event list”
v Chapter 3.6 “CompactFlash card”
v Chapter 3.7 “Device info”

h Select the required level


h Enter selection with E

The basic menu is displayed after pressing the Mkey1.

1
Not from the configuration level,
if a parameter has already been modified there.

32
3 Operation and visualization
3.2 Visualization
As already mentioned in Chapter 2.2 “Operating principle and graphic
elements”, the softkeys are arranged at the bottom of the screen. They change
their function according to the menu and are shown as symbols or plain text.

Show event
list

Alter signal type (representation)


- analog inputs
- analog inputs and
event traces
Evaluation of the stored
measurement data (history)
Alter channel representation (header)
- diagram representation with digital display (small
measurements)
- diagram representation with scaling
- diagram representation with bar graph
- large digital display (large measurements)
- diagram representation (header switched off)

Hide function keys (softkeys)

If the paperless recorder is equipped with “Counters/Integrators” (extra code),


the symbol for indicating the counts will now appear below the softkey on the
right, the symbol for showing the event list is shifted to the counter display.

Show counters / integrators / operating


time counters

33
3 Operation and visualization
3.2.1 Diagram representation with digital display (small measurements)
Diagram representation can be reached from the basic menu, by calling up the
“Visualization” menu or by pressing the D key.
- current measurements of the analog inputs, including dimensional unit
- measurement on a red background ⇒ out of limit

By using the parameter Parameterization ➔ Diagram view ➔ Signal type (or


the button), it is possible to select whether, in addition to the
analog channels, the event traces are to be displayed as well. The contents of
the header are determined by means of the parameter Parameterization ➔
Diagram view ➔ Channel representation (or the button).

34
3 Operation and visualization
3.2.2 Diagram representation with scaling

Scaling start of the selected channel

Lower limit index of the selected channel


(no display when alarm is off)
Current measurement
Channel name
Upper limit index
(no display when alarm
is off)

Scaling end
of the selected channel

Which scaling (on which channel) is to be displayed can be selected through


the parameter Parameterization ➔ Diagram view ➔ Channel indication.

3.2.3 Diagram representation with bar graph

Scaling start of the selected channel

Lower limit index of the selected channel


(no display when alarm is off)

Current measurement
Channel name
Upper limit index
(no display when alarm
is off)
Scaling end
of the selected channel

Use the parameter Parameterization ➔ Diagram view ➔ Channel indication to


select which bar graph (from which channel) is to be displayed.

35
3 Operation and visualization
3.2.4 Large digital display (large measurements)

This display type is limited to the digital display.


If more than 6 signals are active (for instance, 6 analog inputs and 3 math
channels), the button is switched into the display. It can be used
to switch between the individual signals.
- recorded analog channels (channels selected through the parameter
Configuration Î Recording Î Analog channels)
- all analog inputs
- all math channels

36
3 Operation and visualization
3.2.5 Curve representation (header switched off)

This display type is limited to the curve display.

37
3 Operation and visualization
3.2.6 Evaluation of the stored measurement data

History The softkey function changes during evaluation. In addition, the current zoom
factor and cursor position (date and time) will be shown.

Scroll operation Cursor (violet) Current zoom


(magnification)

Date and time of measurements at History


the cursor position activated

Measurement at the
cursor position

Switch to
softkey functions
Zoom/Search
Scroll forwards fast
(one screen)
Scroll forwards slowly (one pixel line)
Scroll backwards slowly (one pixel line)
Scroll backwards fast (one screen)

Using these softkeys, the measurement data display can be scrolled (shifted)
on the screen within the measurement data stored in the internal memory.

H Measurement acquisition remains active during history


representation.

38
3 Operation and visualization

A Scrolling backwards within the internally stored measurement data


is possible up to the last changeover from summer time to normal
time.

Zoom If the zoom factor has to be adjusted, or specific times have to be searched,
then it is necessary to switch the softkey functions.
h Press softkey
The degree of compression of the measurement data on the screen is given as
a ratio in steps (1:1, 1:2, 1:5, 1:10, 1:20, 1:50 and 1:100).
For instance, a ratio of 1:100 means that 1 screen pixel corresponds to 100
measurements, i.e. only every hundreth stored measurement is displayed.

Cursor (violet)

Switch to
softkey
function
“Scroll”

Only for peak-value acquisition:


switch channel line between MIN
and MAX display

Position cursor on time (selectable)


Zoom -

Zoom +

39
3 Operation and visualization
Cursor After activating the button, the following dialog appears for positioning the
positioning cursor on a specific time:

After entering the date and time and activating , the cursor is
positioned on the selected time.
If no measurement data have been stored for the selected time, then the
cursor is positioned on the next possible time.

Peak-value If the data have been recorded in the “peak value” mode, then two different
acquisition measurements (one minimum and one maximum value) may be displayed
graphically for one instant of time (storage cycle). Using the key,
it is possible to switch between minimum and maximum value display within
the “measurement” display mode.

Function key Channel line

Minimum

Maximum

Peak value acquisition is programmed (activated) through the parameters:


- Configuration ➔ Measurement storage ➔ Normal display ➔ Stored value
- Configuration ➔ Measurement storage ➔ Event operation ➔ Stored value
- Configuration ➔ Measurement storage ➔ Timed operation ➔ Stored value

For further information about the “measurement” display mode, see Chapter
3.2.1 “Diagram representation with digital display (small measurements)” and
Chapter 3.2.4 “Large digital display (large measurements)”.

40
3 Operation and visualization
3.2.7 Counters / integrators / operating time

Count display is optionally available (extra code). If it is available, a screen


such as the following will appear after the softkey has been pressed, in which
the current counts are shown in a numerical form.

Expanded representation Show curves


Programmed
alarm limit
was exceeded Overrange

Press the softkey to activate the expanded representation.

41
3 Operation and visualization
Expanded
representation

Normal representation Event list


see
Current count Chapter 3.5
Concluded reporting period “Event list”

Show next concluded


reporting period

The last 7 concluded reporting periods can be


shown, one after another, by pressing the key.

42
3 Operation and visualization
3.3 Parameterization

The Parameter level is available to set


- contrast,
- speed indication
- display off
- diagram view and
- counter/integrator reset.

H All parameters are selected using the


or and
and
keys.

Contrast The contrast of the screen can be set here. This ensures that the screen is
always highly legible, even under difficult light conditions.

Speed “mm/h”, “time/div” or “storage cycle” is selected here for the speed display in
indication the diagram.
Example: a diagram speed of 1hr/div correspond to approx. 22mm/hr.

43
3 Operation and visualization
Display off Switch-off event = waiting time
(screen saving)
For screen saving, a time between 0 and 32,767min can be set under the
parameter “Waiting time”. If no key on the recorder is operated during this
time, then the screen goes dark. The power LED blinks during screen saving.
Screen saving can be canceled by pressing any key on the recorder.
If 0min is set, then screen saving is deactivated.
Switch-off event = control signal
In this case, screen saving is performed through one binary input (extra code)
or a different control signal. The binary input is selected via the parameter
“Control signal”.
As long as the signal is present, the screen remains switched off. A waiting
time is not allowed for.
Screen saving is deactivated when “Off” is selected.

H Only one type of screen saving can be active at any time.

Diagram view Diagram view ➔ Signal type


The representation mode of the measurements and event traces are
determined here:
- analog inputs
- analog inputs and event traces.
Diagram view ➔ Channel representation
The contents of the channel bar is selected here:
- small measuremenst
- scaling
- bar graph
- large measurements
- switched off.
Diagram view ➔ Channel indication
The channels which are displayed in the channel line, in the representation
mode “Small measurement“ “Scaling” and “Bar graph” are selected here.
Diagram view ➔ Paper perforations
This can only be selected if only the analog channels and no event traces are
displayed. When Yes is set, paper perforations appear in the diagram, thus
giving the picture the appearance of a conventional chart recorder.

44
3 Operation and visualization
Counter/ After the password has been successfully entered, the counts for each of the 6
integrator channels can be set to 0 or a defined value in this menu.
reset
When a value has been entered (confirm with the E key), a message with
the new and old count is entered in the event list. The time period for the
counter/integrator summation will not be restarted. The previous counter/
integrator values will also not be saved. If you wish to do so, you have to carry
out Update CF card incl. counters in the CompactFlash card menu before
resetting.

In this way, the recording can be freshly started for counters/integrators, e.g.
after the test run of an installation. The test run values that are not required will
be eliminated in the process.
You can select a password that is different from that for accessing the
configuration. The default value is also 09200.
The password can be set in the menu Configuration ➔ Device data ➔ Code
No. (password) ➔ Reset counter/int.

45
3 Operation and visualization
3.4 Configuration
When you call up the configuration level, you will be asked to enter the
password (factory setting: 09200). This also serves to prevent unauthorized
alteration of the configuration.
After entering the password, a warning appears, which must be
acknowledged with the E key.
v Chapter 3.10 “Code number (password query)”

Window As for the other levels, the configuration principle is also based on menu-led
technology window technology. Individual menu items can be selected in the windows.
The window title describes the contents of the window.
If a menu item is selected, a further window is opened with new menu items,
until the required parameter is finally reached. If several windows are open, the
window title assists in orientation.
Window title

Current setting
Parameter can be selected/edited
Parameter is inhibited

46
3 Operation and visualization
The configuration of the recorder is sub-divided into the following levels:

v Chapter 4 “Configuration parameters”

3.5 Event list


Events Various events can initiate texts which are incorporated in the event list and
saved to the internal memory or CF card. Events may include:
- alarms triggered by out-of-limit conditions on individual channels,
- external texts triggered through binary inputs or logic channels,
- system messages (e.g. power ON/OFF, summer/winter time changeover),
- count-up of a counter,
- any message text of up to 20 characters that was transmitted to the device
via one of the interfaces.

Event For all events, except for system messages, it is possible to configure
definition whether:
- the message text is to be included in the event list,
- the device-internal standard text
- or one of the texts (see below) is used.

Text The texts (standard texts or 18 freely definable texts) are assigned to events at
assignment the operating level “Configuration” (v Chapter 4 “Configuration parameters”).

Freely definable 18 texts can be freely defined, up to a length of 20 characters.


texts

47
3 Operation and visualization
Standard texts The recorder offers standard texts as listed in the following table:

Standard text Comment

Channelx low alarm ON x = channel number


Channelx low alarm OFF
y = input number
Channelx high alarm ON
Channelx high alarm OFF
Counter/int. alarm x ON
Counter/int. alarm x OFF
Binary input y ON
Binary input y OFF
Logic channel y ON
Logic channel y OFF

Counter x: y x = counter channel number


y = counter value (9 digits)

Power ON x = counter/int. channel number


Power OFF y = old counter/int.value (9 digits)
Data lost
Summer time start z = new counter/int. value (9 digits)
Summer time end
New configuration
Counter/int. x reset from y to z

“Text 1 — 18” 18 freely definable texts


with 20 characters each

Supplementary The recorder automatically supplements the texts by “ON” or “OFF” in order to
text distinguish between the appearance and disappearance of the signal.
Example:

Standard text Supplementary Entry in event list


text

Binary input 2 ON Binary input 2 ON

Binary input 2 OFF Binary input 2 OFF

48
3 Operation and visualization
Basic menu ➔ The event list is called up via the basic menu:
Event list

h Select operating level Event list


h Enter selection with E

Event list

jump back directly into diagram presentation

49
3 Operation and visualization
3.6 CompactFlash card
Automatic The data stored in the measurement data memory (FLASH) of the paperless
storage of recorder are saved at regular intervals to the CompactFlash card1 in the
measurement instrument. The PC evaluation program (v Chapter 7 “PC programs”) reads
data the data from the CF card and provides user-friendly functions for evaluation.

Loading and The configuration data can be downloaded from the CF card and saved to the
saving the CF card. A configuration can thus be copied from one instrument to another,
configuration or it can be transferred from and to the PC setup program.

A
data
Only one configuration file can be saved to the CF card at any
time. If there is a configuration on a CF card, this will be
overwritten without any further query through the function
CompactFlash card ➔ Config. data➔CF card.

Basic menu ➔ The CompactFlash menu is called up via the basic menu:
CompactFlash
card

h Select operating level CompactFlash card


h Enter selection with E

The functions
- Update CF incl. counters ...,
- Compl. meas. data ➔ CF,
- Config. data ➔ CF card and
- CF card ➔ Config. data
are protected against unauthorized access by a password query (factory
setting: 09200).

1
PC Card access made available by CSM FAT File System
Copyright © 1997-2002 CSM GmbH Filderstadt, Germany

50
3 Operation and visualization
CompactFlash Measurement data not yet saved are written to the CF card.
card
Counter/integrator reporting periods are concluded and
written to the CF card, together with the measurement data
not yet saved. Counters/integrators are reset (to 0) and
restarted.

All measurement data in the memory are written to CF card

The configuration data are written to the CF card

The configuration data are read from the CF card

Residual capacity of CF card in percent

Background flashes on error (e. g. “CF


card full”, “no CF card”,
or in the event of a memory alarm

Start action
Select action

H The function CF card Î Update reads out data that have not been
read out yet. After read-out, the data are marked as read in the
recorder.
The function Total meas. data Î CF card reads all the data from
the internal memory, including those that had already been read
out.

51
3 Operation and visualization
Status Status messages from the CompactFlash manager are shown in the
messages corresponding action window. The following status messages are possible:

Status message Description

CF CARD UPDATED Directly before removing the CF card from the


instrument, it is necessary to call up Update CF
card so that all measurement data up to the time
of removal are contained on the CF card. The data
not yet stored since the last automatic saving are
written to the CF card.

NO CF CARD If there is no CF card in the instrument, the CF


card symbol flashes in the status line.

CF CARD FAULT An error has occurred while writing to the CF card.


The CF card is faulty.
Remedy:
Insert new (FAT16-formatted) CF card.

CF CARD FULL If the CF card is full, the CF card symbol flashes in


the status line. No more data will be written to the
CF card.
Remedy:
Insert a blank CF card before the measurement
data memory of the recorder is also full. If this is
not done, measurement data will be lost.

NO CONFIG. FILE ON CF An attempt was made to read a configuration from


the CF card, but there is no suitable configuration
file on the CF card.

52
3 Operation and visualization
3.7 Device info
The device info window displays general information about the instrument. It
also includes the errors “Battery empty” and “Data lost”. If one of the
instrument errors occur, the info symbol flashes in the status line.

Basic menu ➔ The device info is called up from the basic menu:
Device info

h Select operating level Device info


h Enter selection with E

Device info

53
3 Operation and visualization
- This menu also includes the version number (e.g. 208.01.04). This is the
version number of the device software. It is important because some
functions are only available from a certain version number onwards.
- If the “Digital I/O option” is available (Yes), then the recorder also includes
an RS232/RS485 interface.
- If the Ethernet interface is available, then the field “Vers. No. Ethernet”
includes a number combination (e.g. 183.02.02). If this option is not
available, the field is filled with “-”.

Error The following errors may occur:

Error Description

none no error in instrument

Data lost A discharge of the battery or storage capacitor


occurred during the last lengthy power
interruption.
The clock was set to 01.01.00 00:00:00.
Remedy:
Reset the time (v Chapter 4.2.2 “Configuration -
Instrument (device) data”) and use a new
CF card for data storage.

Battery empty This message appears on instruments with a


lithium battery, when the time was reset after a
loss of data but the battery is still empty
Please return the instrument to the supplier for a
change of battery.

H Data may be lost after separating the instrument from the supply:
after more than 10 years (on instruments with a lithium battery) or
after approx. 2 weeks (at ambient temperature 15 to 25°C) with a
storage capacitor.

54
3 Operation and visualization
3.8 Text entry
Entry options The configurable texts can be entered either through the setup program or on
the instrument itself. This section describes the entry on the instrument.

Character The display below is shown when a text (e. g. Configuration ➔ Texts) has been
selection selected at the configuration level for editing using E.

Select the character to be altered using the softkeys


Switch to character set matrix

After the character to be altered has been selected and the switch made to
character set matrix, the cursor is positioned on the current character in the
character set matrix.

Character entry The softkeys change their function, as can be seen from the picture below:

Select new character

Accept character

After the entire text has been entered, it can either be accepted or all
alterations canceled.
h Enter text with E
or
h cancel text entry with D

55
3 Operation and visualization
3.9 Entering values
The softkeys are also used to enter values in the instrument – the example
shows fine calibration being carried out.

Select the digit to


Increase (+1) or be altered Alter the number
decrease (-1) selected of decimal places
digit or change the sign

H The sign can only be altered if the value is not “0”. This means that
you cannot start the value entry with an alteration of the sign if the
current value is “0”.

The entry can be concluded with E or canceled with D.

56
3 Operation and visualization
3.10 Code number (password query)
The following functions are protected ex-factory against unauthorized access
by a password query:
- the Configuration menu
- parts of the CompactFlash card menu
- the Parameterization ➔ Reset counter / int. menu.
The factory default setting for the passwords is 09200.
You can also use a password to secure access to the recorder via one of the
interfaces (with the exception of the setup interface). However, the factory
default setting here is 0 (no password query). If you enter a value other than 0,
please take into account that this number must also be sent to the recorder by
an attached communications program.

H Further information about the password query for the interfaces


can be found in the Interface description B 70.6510.2.0.

All passwords can be programmed differently (see Chapter 4.2.2


“Configuration - Instrument (device) data”).

Password query

Increase (+1) or Select the digit to


decrease (-1) selected be altered
digit
When you have finished the entry (e.g. +09200), use the E key to confirm
it. Use D if you want to cancel the password query and quit the menu.

57
3 Operation and visualization
Password query
in the
configuration
menu

After the password has been entered in the Configuration menu, an additional
security query will appear. You will only be able to gain access to the
parameters when you have confirmed the the query with E.

58
4 Configuration parameters
4.1 Operating example

1 If required, the code number must be entered here


factory setting: 09200)
2 Cancel entry; the old settings are retained
3 Accept entry

59
4 Configuration parameters
4.2 Table of configuration parameters
The table below lists all the instrument parameters. The order in which the
parameters are explained corresponds to the order in which they appear on
the instrument (in the menu structure).
The first column describes the path to the particular parameter, via the menus
and windows.
The second column lists the possible settings for the parameters or the
possible selections. The factory default setting in this column is shown bold.
The third column contains a description of the parameter, or the possible
selections, if the parameter and its function or selection is not self-evident.

4.2.1 Parameterization
Parameter Value/Selection Description
Contrast Parameterization 0 — 16 — 31 Display contrast
➔ Contrast
Speed indication Parameterization in mm/h, The selected display mode
➔ Speed indic. mode time/div, is shown in the diagram
storage rate representation
Switch-off event Parameterization Waiting time, The type of display
➔ Display off Cntrl signal switch-off (screen saving)
➔ Switch-off event is selected here
Waiting time Parameterization 0 — 32767min Time after which the
➔ Display off display is switched off. Any
➔ Waiting time key stroke will re-activate
the display. The parameter
can only be entered if the
parameter Switch-off event
is set to “Waiting time”.
0 = display not off
Control signal Parameterization Off, If one of the 4 binary inputs
➔ Display off Bin. inp. 1 — 4, (extra code) or one of the
➔ Ctrl signal Logic channel 1 — 6, other control signals is set
Low alarm 1 — 6, to “off” and activated, then
Low comb.al., the display will be switched
High alarm 1 — 6, off. The parameter can only
High comb.al., be entered if the parameter
Count/Int/Al 1 — 6, Switch-off event is set to
C/i. comb.al., “Control signal”.
Comb. alarm,
CF inserted,
IntMemAlmCF,
IntMemAlmSer,
MemAlmCFcard,
Error, Modbus flag,
Signal type Parameterization Analog inp., This determines which
➔ Diagram view Analog&Event measurements are
➔ Signal type graphically displayed

60
4 Configuration parameters
Channel Parameterization Meas. small, This determines the
representation ➔ Diagram view Scaling contents of the channel
➔ Chan. represent. Bar graph line (header)
Meas. large,
Off
Channel indication Parameterization Yes, “Yes” means that the
➔ Diagram view No selected channels are
➔ Channel indication shown in the header
➔ Channel 1 — 6
Paper perforations Parameterization No, “Yes” means that paper
➔ Diagram view Yes perforations are shown
➔ Paper perforations within the graphic display,
on the left and right
margins of the screen.
Paper perforations can
only be activated and
shown if no event traces
have been selected (signal
type = analog input)
Counter/int. reset Parameterization -999999999 to 0 to The start value for the
➔ Reset counter/int. +999999999 counter or integrator can
➔ Channel 1 — 6 be entered here. The
current value is not saved.
Count changes are
documented in the event
list.
v Chapter 3.3
“Parameterization”
If the password query
is active (password “Reset
counter/int.” > 0), the start
values can only be set if
the password has been
entered correctly.

61
4 Configuration parameters
4.2.2 Configuration - Instrument (device) data
Parameter Value/Selection Description
Device name Configuration 16 characters
➔ Device data
➔ Device name
Date Configuration any date Entry of the current
➔ Device data date
➔ Date and time
➔ Date
Time Configuration any time Entry of the current
➔ Device data time
➔ Date and time
➔ Time
Time Configuration Off, With the help of this
synchronization ➔ Device data Bin. inp. 1 — 4, parameter (function), the
➔ Date and time Logic channel 1 — 6, system clocks of several
➔ Time Low alarm 1 — 6, paperless recoders can be
synchroniz. Low comb.al., simultaneously
High alarm 1 — 6, synchronized.
High comb.al., When a binary input has
Count/Int/Al 1 — 6, been selected and is
C/i. comb.al., activated (transition from
Comb. alarm, “Low” to “High”), then the
CF inserted, time can be synchronized.
IntMemAlmCF, The seconds are decisive
IntMemAlmSer, in the time change. They
MemAlmCFcard, are used for rounding the
Error, Modbus flag, time up or down.
Example:
12:55:29 -> 12:55:00
12:55:30 -> 12:56:00
Summer time Configuration Off, Automatic:
(switch) ➔ Device data User timed, 2:00 hrs or 3:00 hrs on the
➔ Summer time Automatic last Sunday in March or
➔ Switch October
Summer time Configuration any date Can only be set if
(start date) ➔ Device data switch is set
➔ Summer time to user timed
➔ Start date
Summer time Configuration any time Can only be set if
(start time) ➔ Device data switch is set
➔ Summer time to user timed
➔ Start time
Summer time Configuration any date Can only be set if
(end date) ➔ Device data switch is set
➔ Summer time to user timed
➔ End date
Summer time Configuration any time Can only be set if
(end time) ➔ Device data switch is set
➔ Summer time to user timed
➔ End time

62
4 Configuration parameters
Language Configuration German, English, French,
➔ Device data Dutch, Spanish, Italian,
➔ Language Hungarian, Czech,
Swedish, Polish, Danish,
Finnish, Portuguese,
Russian
Temperature unit Configuration °C, °F
➔ Device data
➔ Temperature unit
Memory upload Configuration via CF card, You can determine how
➔ Device data via RSxxx data are mainly to be
➔ Memory upload uploaded. The value for the
available capacity (shown
in the status line) will vary
according to the selection.
Memory alarm Configuration 0 — 10 — 100% The signals
➔ Device data “IntMemAlmCF”,
➔ Memory alarm “IntMemAlmInterf” and
“MemAlmCFcard” are
activated when the residual
capacity of the internal
memory or the CF card has
fallen to this value. Chapter
2.4 “Digital signals (event
traces)”
Code number for Configuration 00000 — 09200 — 09999 Code number for
the configuration ➔ Device data configuration level;
➔ Code No. (password) 0000 = off
➔ Configuration The data saved in the
FLASH memory will be
deleted when the
configuration is changed.
Code number: Configuration 00000 — 09200 — 09999 Code number for
CompactFlash ➔ Device data menu functions
card menu ➔ Code No. (password) CompactFlash card;
(CF code No.) ➔ CF manager 0000 = off
Code number: Configuration 00000 — 09200 — 09999 Code number to delete
Reset counter/int. ➔ Device data individual counts;
➔ Code No. (password) 0000 = off
➔ Reset counter/int.
Code number: Configuration 00000 — 09999 Code number as
RS232/RS485 + ➔ Device data protection against
Ethernet ➔ Code No. (password) unauthorized access to
➔ RS232/RS485+ data via one of the
Ethernet interfaces;
0000 = off
Factory setting Configuration No, Yes Yes = enter factory default
➔ Device data setting (after entry, the
➔ Enter defaults parameter automatically
returns to No)

63
4 Configuration parameters
Enable options Configuration This parameter is used to
➔ Device data enable additional
➔ Enable options functions, e.g. the math/
logic module and counter/
integrator. The parameter
will not be available if all
the recorder functions have
been enabled.
Enable options: Configuration (display a code No.) The value that is shown
Computed code ➔ Device data here must be passed on to
No. ➔ Enable options the manufacturer. The
➔ Computed manufacturer will then
code No. send you the release code.
Enable options: Configuration Authorization code Enter the authorization
Authorization code ➔ Device data entry code (release code) you
➔ Enable options received here.
➔ Authorization
code
Device-info text In the setup program, the parameter Configuration level Î Device data can be used
to enter a device-Info text (max. 500 characters). The text is saved together with the
measurement data, and can be displayed in the PCA3000 evaluation software. The
text will not be shown on the instrument.

4.2.3 Configuration - Analog inputs


Parameter Value/Selection Description
Sensor Configuration Off, Depending on the sensor
➔ Analog inputs RTD, that was selected, only the
➔ Analog input 1—6 Thermocouple, relevant parameters can be
➔ Sensor Current, selected when configuring
Voltage the analog input.
Linearization Configuration Linear, Pt100, Pt100 JIS,
➔ Analog inputs Pt100 GOST, Pt500,
➔ Analog input 1—6 Pt1000, Pt50, Ni100,
➔ Linearization Cu50, Cu100, Fe-Con J,
NiCr-Con E, NiCr-Ni K,
NiCrSi N, Cu-Con T,
PtRh-PtRh B,
PtRh-Pt R, PtRh-Pt S,
Cu-Con U, Fe-Con L,
W3W25Re D,
W5W26Re C,
ChromelCopel
Connection circuit Configuration 2 — 4 wire Only for sensor type:
➔ Analog inputs resistance thermometer
➔ Analog input 1—6
➔ Connection circuit
Cold junction Configuration Intern.Pt100
➔ Analog inputs Extern. const
➔ Analog input 1—6
➔ Cold junction

64
4 Configuration parameters
Parameter Value/Selection Description
External Configuration -50 to +150°C External cold junction
cold junction ➔ Analog inputs temperature for
temperature ➔ Analog input 1—6 thermocouples
➔ Ext. CJ temp.
Range Configuration any value
start ➔ Analog inputs
➔ Analog input 1—6
➔ Range start
0mA
Range Configuration any value
end ➔ Analog inputs
➔ Analog input 1—6
➔ Range end
20mA
Start temperature Configuration any value Only for sensor: current or
➔ Analog inputs voltage with linearization,
➔ Analog input 1—6 resistance thermometer,
➔ Start thermocouple.
temperature Only for signals that have
not yet been linearized.
End temperature Configuration any value Only for sensor: current or
➔ Analog inputs voltage with linearization,
➔ Analog input 1—6 resistance thermometer,
➔ End temperature thermocouple.
Only for signals that have
not yet been linearized.
Scaling start Configuration -99999 to 0 to +99999
➔ Analog inputs
➔ Analog input 1—6
➔ Scaling start
Scaling end Configuration -99999 to +100 to +99999
➔ Analog inputs
➔ Analog input 1—6
➔ Scaling end
Filter constant Configuration 0.0 — 0.1 — 10.0s
➔ Analog inputs
➔ Analog input 1—6
➔ Filter constant

65
4 Configuration parameters
4.2.4 Configuration - Math channels
Parameter Value/Selection Description
Scaling start Configuration -99999 to 0 to +99999 Scaling start of a math
➔ Math channels channel.
➔ Math channel 1 — 6 The setup progam is used
➔ Scaling start to determine what is
involved in a math channel.
Scaling end Configuration -99999 to +100 to +99999 Scaling end of a math
➔ Math channels channel.
➔ Math channel 1 — 6 The setup progam is used
➔ Scaling end to determine what is
involved in a math channel.

4.2.5 Configuration - Counter/integrator (extra code)


Parameter Value/Selection Description
Channel Configuration 1—6 Select channel for which
➔ Counter/integrator the subsequent
➔ Counter/int.chans. parameters are to be
configured.
Function Configuration Off, First select the required
➔ Counter/integrator Counter function.
➔ Counter/int.chans. Integrator, v Chapter 2.5 “Counters /
➔ Channel 1 — 6 Oper.time integrators / operating
➔ Function time counter”
Type Configuration Periodic, Reporting period.
➔ Counter/integrator External, Select here when the count
➔ Counter/int.chans. Daily, value is to be stored and
➔ Channel 1 — 6 Weekly, reset.
➔ Type Monthly,
Aearly,
Total,
DailyFrom-To
Input signal Configuration Off, The parameter can only be
➔ Counter/integrator Bin. inp. 1 — 4, programmed if “Counter”
➔ Counter/int.chans. Logic channel 1 — 6, or “Operating time” has
➔ Channel — 6 Low alarm 1 — 6, been selected under
➔ Input signal Low comb.al., Function.
High alarm 1 — 6, Please select which event
High comb.al., is to be counted.
Count/Int/Al 1 — 6,
C/i. comb.al.,
Comb. alarm,
CF inserted,
IntMemAlmCF,
IntMemAlmSer,
MemAlmCFcard,
Error, Modbus flag,

66
4 Configuration parameters
Input signal Configuration Analog inp. 1 — 3(6), The parameter can only be
➔ Counter/integrator Math channel 1 — 6 programmed if “Integrator”
➔ Counter/int.chans. has been selected under
➔ Channel 1 — 6 Function.
➔ Input signal Please select which input
is to be integrated.
Weighting Configuration -99999 to +1 to +99999 Select the weighting factor
➔ Counter/integrator here.
➔ Counter/int.chans. If, for instance, 0.001 is
➔ Channel 1 — 6 entered, then a conversion
➔ Weighting can be achieved from liter/
sec to m³. If a negative
weighting factor is entered
(e.g. -1), the counter will
count down.
Time base Configuration Second, The parameter can only be
➔ Counter/integrator Minute, programmed if “Integrator”
➔ Counter/int.chans. Hour, or “Operating time” has
➔ Channel 1 — 6 Day been selected under
➔ Time base Function.
Integrator:
Select the time base for
integrating the selected
channel (second, for
example, if your sensor
generates a signal in liters/
second).
Operating time:
Select the unit used for
counting the time.
Threshold value Configuration 0 — 99999 The parameter can only be
➔ Counter/integrator programmed if “Integrator”
➔ Counter/int.chans. has been selected under
➔ Channel 1 — 6 Function.
➔ Threshold Enter the threshold value
value that has to be exceeded
for integration to proceed.
Channel name Configuration 12 characters The text that has been
(line 1) ➔ Counter/integrator entered appears together
➔ Counter/int.chans. with line 2 and the current
➔ Channel 1 — 6 count on the recorder
➔ Channel name screen (visualization and
event list).
v Chapter 3.2.7
Counter/int. “Counters / integrators /
operating time”
Channel name Configuration 12 characters The text that has been
(line 2) ➔ Counter/integrator entered appears together
➔ Counter/int.chans. with line 1 and the current
➔ Channel 1 — 6 count on the recorder
➔ Channel name Channel 1 — 6 screen (visualization and
event list).

67
4 Configuration parameters
Unit Configuration 5 characters Enter the unit which is
➔ Counter/integrator displayed on the recorder
➔ Counter/int.chans. screen, together with the
➔ Channel 1 — 6 entered text and the
➔ Unit current count.
Decimal place Configuration Automatic, Specify the decimal place
➔ Counter/integrator X.XXXX, XX.XXX, for displaying the count on
➔ Counter/int.chans. XXX.XX, XXXX.X, the recorder screen.
➔ Channel 1 — 6 XXXXX.
➔ Decimal place
Counter text Configuration Standard text, The text selected here will
➔ Counter/integrator Text 1 — 18, appear in the status line
➔ Counter/int.chans. No text and the event list if the
➔ Channel 1 — 6 counter is incremented
➔ Counter text (decremented).
Alarm Configuration Off,
➔ Counter/integrator Activated
➔ Counter/int.chans.
➔ Channel 1 — 6
➔ Alarm
➔ Alarm
Limit value Configuration -99999 to 100 to +99999 An alarm is triggered when
➔ Counter/integrator the limit is infringed. Using
➔ Counter/int.chans. the parameter Weighting, it
➔ Channel 1 — 6 is possible to differentiate
➔ Alarm between going above or
➔ Limit below the limit (positive
weighting factor = alarm on
going above the limit)
Alarm text Configuration Standard text, On going above/below the
➔ Counter/integrator Text 1 — 18, limit, the text selected here
➔ Counter/int.chans. No text will appear in the status
➔ Channel 1 — 6 line and the event list.
➔ Alarm
➔ Alarm text
Synchroniz. Configuration any time Please enter the time at
time ➔ Counter/integrator (00:00:00) which the daily, weekly,
➔ Synchronizat. time monthly or yearly counter/
integrator value is to be
saved.
Period Configuration 1min, 2min, 3min, 4min, Only programmable, if the
➔ Counter/integrator 5min, 10min, 15min, parameter Type is set to
➔ Period 30min, 1h, 2h, 3h, 4h, 6h, “periodic” on at least one
8h, 12h counter/integrator.
The counter/integrator
values are saved at the
selected interval.

68
4 Configuration parameters
Ext. Ctrl signal Configuration Bin. inp. 1 — 4, Only programmable, if the
➔ Counter/integrator Logic channel 1 — 6, parameter Type is set to
➔ Ext. ctrl signal Low alarm 1 — 6, “external” on at least one
Low comb.al., counter/integrator.
High alarm 1 — 6, Summation of the counter/
High comb.al., integrator values will only
Count/Int/Al 1 — 6, take place if the selected
C/i. comb.al., digital signal is set to “1”.
Comb. alarm, When changing to “0”, the
CF inserted, values will be saved and
IntMemAlmCF, reset.
IntMemAlmSer,
MemAlmCFcard,
Error, Modbus flag,
Weekday Configuration Monday, Only programmable, if the
➔ Counter/integrator Tuesday, parameter Type is set to
➔ Weekday Wednesday, “Weekly” on at least one
Thursday, counter/integrator.
Friday, The counter/integrator
Saturday, values are saved on the
Sunday selected day on reaching
the synchronizing time.
Daily start time Configuration any time Only programmable, if the
➔ Counter/integrator (06:00:00) parameter Type is set to
➔ Daily start time “Daily from-to” on at least
one counter/integrator.
Daily end time Configuration any time Only programmable, if the
➔ Counter/integrator (18:00:00) parameter Type is set to
➔ Daily end time “Daily from-to” on at least
one counter/integrator.
Generate reset Configuration Off, Here you can determine
➔ Counter/integrator Bin. inp. 1 — 4, the event which will reset
➔ Generate reset Logic channel 1 — 6, all counter and integrator
Low alarm 1 — 6, counts (without saving).
Low com.al., v Page 19
High alarm 1 — 6, “External reset”
High comb.al.,
Count/Int/Al 1 — 6,
C/i. comb.al.,
Comb. alarm,
CF inserted,
IntMemAlmCF,
IntMemAlmSer,
MemAlmCFcard,
Error, Modbus flag,

69
4 Configuration parameters
4.2.6 Configuration - Recording
Parameter Value/Selection Description
Analog channels
Input signal Configuration Analog input 1 — 6, Select which channel is to
➔ Recording Math channel 1 — 6 be recorded (stored).
➔ Analog channels
➔ Analog channel 1 — 6
➔ Input signal
Channel name Configuration 16 characters The channel name is
➔ Recording Analog channel 1 — 6 shown in the channel line
➔ Analog channels (header) for bar graph and
➔ Analog channel 1 — 6 scaling.
➔ Channel name
Unit Configuration 5 characters
➔ Recording
➔ Analog channels
➔ Analog channel 1 — 6
➔ Unit %
Decimal place Configuration Automatic, Automatic: representation
➔ Recording X.XXXX, XX.XXX, with maximum resolution
➔ Analog channels XXX.XX, XXXX.X,
➔ Analog channel 1 — 6 XXXXX.
➔ Decimal place
Line width Configuration Thin, Line width of the
➔ Recording Thick measurement curve within
➔ Analog channels the graphical display
➔ Analog channel 1 — 6
➔ Line width
Alarm Configuration Off,
➔ Recording Activated
➔ Analog channels
➔ Analog channel 1 — 6
➔ Alarm
➔ Alarm
Low limit Configuration -99999 to 0 to +99999
➔ Recording
➔ Analog channels
➔ Analog channel 1 — 6
➔ Alarm
➔ Low limit
High limit Configuration -99999 to 0 to +99999
➔ Recording
➔ Analog channels
➔ Analog channel 1 — 6
➔ Alarm
➔ High limit

70
4 Configuration parameters
Differential Configuration -99999 to 0 to +99999
➔ Recording
➔ Analog channels
➔ Analog channel 1 — 6
➔ Alarm
➔ Differential
(1) = Low limit
(2) = High limit
(3) = Differential

Text Low alarm Configuration Standard text, v Chapter 3.5 “Event list”
➔ Recording Text 1 — 18,
v Configuration ➔ Texts,
➔ Analog channels No text
Page 74
➔ Analog channel 1 — 6
➔ Alarm
➔ Text
Low alarm
Text High alarm Configuration Standard text,
➔ Recording Text 1 — 18,
➔ Analog channels No text
➔ Analog channel 1 — 6
➔ Alarms
➔ Text
High alarm
Alarm delay Configuration 0 — 32767s Alarm delay is activated at
➔ Recording a value > 0.
➔ Analog channels When activated, an alarm
➔ Analog channel 1 — 6 will only be generated
➔ Alarms when it has been present
➔ Alarm delay for at least as long as it
takes for the set time to
elapse.

71
4 Configuration parameters
Event traces
Input signal Configuration Off, The event (digital signal)
➔ Recording Bin. inp. 1 — 4, which is to be recorded is
➔ Event traces Logic channel 1 — 6, assigned to an event trace
➔ Event traces 1 — 6 Low alarm 1 — 6, here.
➔ Input signal Low comb.al.,
High alarm 1 — 6, Event traces 5 and 6 are
High comb.al, switched off in the factory
Count/Int/Al 1 — 6, setting.
C/i. comb.al.,
Comb. alarm,
CF inserted,
IntMemAlmCF,
IntMemAlmSer,
MemAlmCFcard,
Error, Modbus flag,
Trace designation Configuration 7 characters
➔ Recording
➔ Event traces
➔ Event traces 1 — 4
➔ Trace design. BE 1 — 4
Operating modes
Memory status: Configuration Off,
Normal operation ➔ Recording On
➔ Normal operation
➔ Memory status
Stored value: Configuration Average val., v Chapter 2.7 “Operating
Normal operation ➔ Recording Instant val., modes”
➔ Normal operation Minimum, Chapter 2.8 “Storing
➔ Stored value Maximum, data”
Peak value
Storage cycle: Configuration 1 — 60 — 32767s v Chapter 2.7 “Operating
Normal operation ➔ Recording modes”
➔ Normal operation Chapter 2.8 “Storing
➔ Storage cycle data”
Start time: Configuration any time Off when
Timed operation ➔ Recording Start time = End time
➔ Timed operation
➔ Start time

End time: Configuration any time


Timed operation ➔ Recording
➔ Timed operation
➔ End time
Stored value: Configuration Average val., v Chapter 2.7 “Operating
Timed operation ➔ Recording Instant val., modes”
➔ Timed operation Minimum, Chapter 2.8 “Storing
➔ Stored value Maximum, data”
Peak value
Storage cycle: Configuration 1 — 5 — 32767s v Chapter 2.7 “Operating
Timed operation ➔ Recording modes”
➔ Timed operation Chapter 2.8 “Storing
➔ Storage cycle data”

72
4 Configuration parameters
Control signal: Configuration Off, If the configured signal is
Event operation ➔ Recording Bin. inp. 1 — 4, active, the instrument will
➔ Event operation Logic channel 1 — 6, switch to event operation.
➔ Control signal Low alarm 1 — 6,
Low comb.al.,
High alarm 1 — 6,
High comb.al.,
Count/Int/Al 1 — 6,
C/i. comb.al.,
Comb. alarm,
CF inserted,
IntMemAlmCF,
IntMemAlmSer,
MemAlmCFcard,
Error, Modbus flag,
Stored value: Configuration Average val., v Chapter 2.7 “Operating
Event operation ➔ Recording Instant val., modes”
➔ Event operation Minimum, Chapter 2.8 “Storing
➔ Stored value Maximum, data”
Peak value
Storage cycle: Configuration 1 — 5 — 32767s v Chapter 2.7 “Operating
Event operation ➔ Recording modes”
➔ Event operation Chapter 2.8 “Storing
➔ Storage cycle data”

4.2.7 Configuration - Outputs (extra code)


Parameter Value/Selection Description
Action of Configuration Off, As standard, relay K1 is
outputs ➔ Outputs make (SPST-NO), configured as break (SPST-
➔ Relay K1 — K3, break (SPST-NC) NO), K2 and K3 are
➔ Action inactive.
Control signal: Configuration Off, The configured signal is
Outputs ➔ Outputs Bin. inp. 1 — 4, output to the relay.
➔ Relay K1 — K3, Logic channel 1 — 6, The default setting for K1 is
➔ Control signal Low alarm 1 — 6, Error.
Low comb.al.,
High alarm 1 — 6,
High comb.al.,
Count/Int/Al 1 — 6,
C/i. comb.al.,
Comb. alarm,
CF inserted,
IntMemAlmCF,
IntMemAlmSer,
MemAlmCFcard,
Error, Modbus flag

73
4 Configuration parameters
4.2.8 Configuration - Control functions
Parameter Value/Selection Description
External texts: Configuration Standard text, v Chapter 3.5 “Event list”
Binary input 1 — 4 ➔ Control functions Text 1 — 18,
v Chapter 4.2.9
➔ External texts No text
“Configuration - Texts”
➔ Binary input
1…4
External texts: Configuration Standard text, Can only be used if the
Logic channel ➔ Control functions Text 1 — 18, “Math/logic module”
1—6 ➔ External texts No text option is available.
➔ Logic channel v Chapter 3.5 “Event list”
1—6
v Chapter 4.2.9
“Configuration - Texts”
Key inhibit Configuration Off, The keys will be locked as
➔ Control functions Bin. inp. 1 — 4, soon as the selected
➔ Key inhibit Logic channel 1 — 6, signal is activated
Low alarm 1 — 6,
Low comb.al.,
High alarm 1 — 6,
High comb.al.,
Count/Int/Al 1 — 6,
C/i. comb.al.,
Comb. alarm,
CF inserted,
IntMemAlmCF,
IntMemAlmSer,
MemAlmCFcard,
Error, Modbus flag,

4.2.9 Configuration - Texts


Parameter Value/Selection Description
Texts Configuration 20 characters
➔ Texts
➔ Text1 — 18 Text 1 — 18

74
4 Configuration parameters
4.2.10Configuration - Interfaces
Parameter Value/Selection Description
Serial interface
Interface type Configuration RS232, Parameters for the serial
➔ Interfaces RS485 interface (extra code)
➔ RS232/RS485
➔ Interface type
Protocol Configuration MODbus,
➔ Interfaces Jbus
➔ RS232/RS485
➔ Protocol
Baud rate Configuration 9600 bps,
➔ Interfaces 19200 bps,
➔ RS232/RS485 38400 bps
➔ Baud rate
Data format Configuration 8-1-none,
➔ Interfaces 8-1-odd,
➔ RS232/RS485 8-1-even,
➔ Data format 8-2-none
Device address Configuration 1 — 254
➔ Interfaces
➔ RS232/RS485
➔ Device address
Min. response time Configuration 0 — 500ms
➔ Interfaces
➔ RS232/RS485
➔ Min. response time
Ethernet interface
IP address Configuration 000.000.000.000 … The IP address for the
➔ Interfaces 192.168.000.010 … recorder is set here.
➔ Ethernet 255.255.255.255
➔ IP address
Subnet mask Configuration 000.000.000.000 … The subnet mask is set
➔ Interfaces 255.255.000.000 … here.
➔ Ethernet 255.255.255.255 Devices are combined into
➔ Subnet mask subnets through the sub-
net mask. All devices
whose IP address, when
AND-linked, is identical to
the subnet mask, belong to
one subnet and can thus
communicate with each
other.
Gateway Configuration 000.000.000.000 … The address for the
➔ Interfaces 255.255.255.255 standard gateway is set
➔ Ethernet here. Devices that do not
➔ Gateway belong to a subnet can
communicate through the
standard gateway.

75
4 Configuration parameters
4.2.11Configuration - Undocumented parameters
Parameter Value/Selection Description
Undocumented Configuration These parameters are
parameter 1 — 40 ➔ Undoc. parameters intended for customer-
➔ Par. 1 — 40 specific adaptation.
Alteration to the settings
may only be carried on the
express instruction of the
equipment manufacturer.

4.2.12Configuration - Fine calibration


Parameter Value/Selection Description
Calibration status Configuration Off, A calibration (adjustment)
➔ Fine calibration On of the analog
➔ Analog input 1 — 6 measurements can be
➔ Calibration status activated here. The
adjustment is carried out
using a linear equation.
Actual start value Configuration -99999 to 0 to +99999 Start value for
➔ Fine calibration actual line.
➔ Analog input 1 — 6 Only active when
➔ Actual start value calibration status = On.
Set start value Configuration -99999 to 0 to +99999 Start value for
➔ Fine calibration target line.
➔ Analog input 1 — 6 Only active when
➔ Set start value calibration status = On.
Actual end value Configuration -99999 to 1000 to +99999 End value for
➔ Fine calibration actual line.
➔ Analog input 1 — 6 Only active when
➔ Actual end value calibration status = On.
Set end value Configuration -99999 to 1000 to +99999 End value for
➔ Fine calibration target line.
➔ Analog input 1 — 6 Only active when
➔ Set end value calibration status = On.

H Systematic errors, such as those caused by an unsuitable probe


mounting, for example, can be compensated through fine
calibration.
Example:
A sensor covers temperatures from 200 to 300°C.
It is built into a tunnel oven so unfavorably that it always indicates
10°C less than the temperature of the oven contents. The incorrect
measurement can be corrected through fine calibration.
Actual start value : 200°C
Set start value : 210°C
Actual end value : 300°C
Set end value : 310°C

76
5 Setup program
The setup program is used for the easy creation of configuration files, and to
configure the instruments from a PC.

5.1 Hardware and software requirements


The following hardware and software requirements have to be met for
installing and operating the setup program:

Minimum - Intel Pentium1 III or higher,


configuration
- Microsoft Windows2 NT4.0 (SP6a), 2000 or XP,
- 128Mbyte main memory,
- CD drive,
- mouse,
- one free serial interface or network connection, or CompactFlash memory
cards (depending on the type of data transmission to the paperless
recorder), and
- 120Mbyte available on hard disk.
In addition, the following items are required for communication between the
PC and the recorder, such as:
- reader/writer for CompactFlash memory card or
- PC interface cable including adapter (only when using the setup interface)
or
- serial interface cable (when using the RS232 or RS485 interface) or
- network connection (when using the Ethernet connection).

Recommended - Intel Pentium 4


configuration
- Windows XP or 2000
- 512Mbyte main memory
- 2Gbyte free space on hard disk for data

1
Intel and Pentium are registered trademarks of Intel Corporation
2
Microsoft and Windows are registered trademarks
of Microsoft Corporation

77
5 Setup program
5.2 Installation
Run the h Start Microsoft Windows

H
installation
program If Microsoft Windows has already been started, all Windows
programs must be shut down before installing the setup program.

h Insert the CD into the drive, then close the drive.


After the CD has been inserted, the installation program will start
automatically. If not, proceed as follows:
h Start the file “Launch.exe” in the main directory of the CD.
The installation program will lead you through the rest of the installation with
screen messages.

H If no valid license number is entered during the installation, the


setup program will remain fully functional for 30 days. After this
time, the data transmission, data storage and printout functions
will be disabled.

Program start h Start the setup program by selecting the entry “Setup program ...“ in the
chosen program folder.
When the software has just been installed for the first time, there will not yet be
a query of the user name and password. In the menu Extras, the query at the
start of the program can be activated by the function Renew log-in / Alter
password.
The activation of the log-in function can be used to distinguish between the
user types “Specialist” and “Maintenance”. These two users have different
access rights with regard to the functions in the setup program.
v “Renew log-in / Alter password” on page 101
v Chapter 6 “Rights”
If the query is active, proceed as follows:
h Log in.

H Please note that not all functions are available to all users.

78
5 Setup program
5.3 User interface
Menu bar

Toolbar

Working area

Connection status Teleservice

Menu bar The individual functions of the setup program can be started by using the
menu bar.
v Chapter 5.8 “Menu functions”

Toolbar The toolbar contains selected functions of the menu bar. They can be started
from the left mouse button. If you rest the mouse pointer on one of the icons
(tool tips), you will see the function title after a short delay.

79
5 Setup program
Shifting the The position of the toolbar can be changed, if desired.
toolbar
h Move the mouse pointer between two icon groups.

h Press the left mouse button.


h Keeping the left mouse button pressed, drag the toolbar to the required
position.
h Now release the mouse button.

Possible positions are:


- the left or right window border (vertical orientation),
- below the menu bar (horizontal orientation),
- at the bottom edge, above the user details (horizontal orientation) or
- any position (in own window - horizontal orientation).

Working area Here you are provided with an overview of the current settings of a
configuration file.
v Chapter 5.4 “Configuration”

Connection In the “Connection status” line you can check whether a connection to a
status device has been established, and which interface data are being used. The
line can be made visible or hidden through Window ➔ Connection status.
Example: No connection

Example: Connection to a device

The line can be moved (like the toolbar). In order for the shift to work, first
position the mouse pointer on the position shown below, before you press the
left mouse button.

Teleservice Using Teleservice, you can view the latest data from the paperless recorder
and alter the Modbus flag. Teleservice can be made visible or hidden through
the function Window ➔ Teleservice.
v Chapter 5.5 “Teleservice”

80
5 Setup program
5.4 Configuration
By using the function File ➔ New (or File ➔ Open) you can create a new
configuration file (setup) or open an already existing one. The working area will
be filled with the corresponding settings.

Current setup

Navigation tree
for finding the settings Dialog window
quickly The settings are displayed here.

Navigation tree A single click with the left mouse button in the navigation tree will position the
entry visibly in the dialog window.
Clicking on will reduce the size of the display, one click on will enlarge
the display again.

A double-click on an entry (e.g. ) will start the change dialog.


Alternatively, a change can also be started via the menu bar (Edit ➔
Configuration level ➔ Device data).

Dialog window By double-clicking on an entry in the dialog window, you can start the change
dialog. One click on “Arrow to right” ( ) before the entry will list the current
setting in the dialog window, one click on “Arrow down” ( ) will hide the
current setting again.

Current setup If several setup settings are open at the same time, just one simple click on the
name and ...

81
5 Setup program
... the window becomes an active window.

Functions If you use the right mouse button in the dialog window, different functions will
of the right be available. These functions concern that part of the configuration on which
mouse button the mouse pointer was positioned when the right mouse button was pressed.
Example:
The right mouse button was pressed when it was on the entry “Analog inputs”.

Analog inputs Î Edit


This function starts the change dialog for configuring the analog inputs.
Alternatively, configuring can also be started by a double-click with the left
mouse button.
Analog inputs Î Maximize
This function prompts the display of the current configuration of the analog
inputs. As an alternative, the current configuration can also be displayed by a
click (left mouse button) on “Arrow to right” ( ).

82
5 Setup program
Analog inputs Î Online edit
The current settings of the analog inputs are read out directly from the
instrument, and the change dialog is opened. Now you can alter the
configuration. After alteration, the new setting is transmitted back to the
instrument and entered in the dialog window.
If necessary, additional information that is required will be read out from the
instrument and also entered in the dialog window. For instance, when editing
the analog inputs online, the device data will also be read out from the
instrument.
Copy data to clipboard Î Analog inputs
This function copies the current configuration of the analog inputs to the
Windows clipboard. The contents of the clipboard can, for instance, be
imported into an editor or a text processing program.
Copy data to clipboard Î All data
This function copies the complete current configuration – not just that for the
analog inputs – to the Windows clipboard. The contents of the clipboard can,
for instance, be imported into an editor or a text processing program.
Print
This function enables the print-out of the latest setting. You can select which
parameter groups are printed out, and which are not. Alternatively, printing out
can also be carried out via the File menu.

83
5 Setup program
5.5 Teleservice
You can use Teleservice to request the latest data from a paperless recorder. In
addition, the Modbus flag can be switched (activated).
In order to use Teleservice, there must be an existing connection to a device.
v Chapter 5.7 “Connection between the PC and the recorder”

You can switch Teleservice into or out of display via the Window menu.

Click here to select the register as


the active register

Active register

Click here to switch further registers


into the display (if available)
Close Teleservice window

Shift the Teleservice window


v “Shifting the toolbar” on page 80

84
5 Setup program
Setting the h With the left mouse button, click on the arrow pointing to the right
Modbus flag ( ), until the register “Additional binary signals” appears
on the screen ( ).
h Click on the register “Additional binary signals”. This automatically turns it
into an active register.

h Clicking into the box with the left mouse button (single click) will switch the
Modbus flag.

Shifting the The Teleservice window, too, can be shifted. The same possibilities apply as
Teleservice for shifting the toolbar.
window
v “Shifting the toolbar” on page 80

Position the mouse pointer here, and,


holding the left mouse button down, shift the
Teleservice window to a different position.

85
5 Setup program
5.6 Data transfer from and to the instrument
There are two ways of transferring the setup data to or from a recorder:
- transfer via the CompactFlash memory card and
- transfer via interface.

H A new configuration will delete the data in the instrument (FLASH


memory). If you want to retain the data, then the function
CompactFlash card ➔ Update CF card must be started, or the
data must be read out with the PCA communications software
(PCC) before the configuration is transmitted.

5.6.1 Transfer via CompactFlash memory card


In order to be able to read or write to CompactFlash memory cards from a PC,
you will need a card reader/writer.
When you have installed the card reader/writer, and have inserted a
CompactFlash memory card, you will automatically have a new drive under
Windows. You can access the new drive just like a normal hard disk, using
Windows Explorer.

A
CompactFlash memory cards must only be removed from the card
reader/writer if the function “Eject removable medium” (a function
in the PC operating system) has been activated first.

H Only one configuration file can be saved to the CF card at any


time, since there is no file name as a variable.
Measurement data from several instruments can be on the same
CF card, since they have unambiguous identifications.

86
5 Setup program
Paperless You can use the paperless recorder to write setup data to the CompactFlash
recorder memory card, or to read from it.
v Chapter 3.6 “CompactFlash card”

Import/export errors
If an error occurs on the paperless recorder side during transfer from or to a
CF card, it will be indicated in the CompactFlash card menu and will remain
until the error has been eliminated or is overwritten by a fresh error message.

Setup program Use the toolbar or the Data transfer menu with its functions “Data export to CF
card” and “Data import from CF card” in order to transfer the setup data.

Data import from CF card


Data export to CF card

H Do not use the menu function “File ‘ Save as ...”.


It cannot be used to create a valid CF card for the paperless
recorder.

87
5 Setup program
Formatting the

A
CF card A CompactFlash memory card (CF card) must be formatted for FAT
(not FAT32 or NTFS).
If you format a CF card yourself, you must not use fast-formatting
(Quickformat). If this is disregarded, a fault-free exchange of data
cannot be ensured.

To format a CF card using the Windows workplace (e. g. Windows XP):


h Make a double-click on the workplace symbol in the “Desktop” area for the
PC, using the left mouse button.
h Click with the right mouse button on the drive letter for the CF card.
h Select the function Format.

h Select FAT file system.


h Click on the “Start” button.

88
5 Setup program
5.6.2 Transfer via interface
Data transfer is possible via one of the following interfaces:
Paperless recorder PC
Setup interface RS232
Setup interface USB
RS232 RS232
RS485 RS485
(plug-in card or converter)
Ethernet Ethernet
v The settings for the interface parameters can be found in Chapter 4.2.10
“Configuration - Interfaces”.

Setup - RS232 You will need the interface cable (including adapter) in this case. It is available
as an accessory for the recorder.

Setup - USB You will need the interface cable (including adapter) in this case. It is available
as an accessory for the recorder.

v See Installation Instructions B70.9720.3.

RS232 v For the pin assignment, please refer to the Interface Description
B 70.6510.2.0.

RS485 v For the pin assignment, please refer to the Interface Description
B 70.6510.2.0.

89
5 Setup program
Ethernet The paperless recorder or a PC can be connected to the network using
normal, commercially available network cables (with RJ45 connector). If the
recorder and a PC are to be connected directly together, please use a
crossover cable.

H Only one 1 PC (client) at a time can access the instrument (server)


via the Ethernet interface.

Starting the Use the toolbar or the Data transfer menu with its functions “Data export to
transfer device” and “Data transfer from device” in order to transfer the setup data.

Data transfer from device


Data transfer to device

90
5 Setup program
5.7 Connection between the PC and the recorder
If data are to be exchanged between a recorder and a PC, it is essential to
define which instrument and which route is used for communication, and to
establish a connection between the instrument and the PC.
Connection to an instrument is made by using the function Data transfer ➔
Establish connection or by a click on the symbol.

H If a connection already exists (communication is active) between


the setup program and a recorder, then no other software
components (e.g. PCC) can access the instrument through the
same interface.

5.7.1 Assistant for device settings


If there has never been any previous communication with an instrument, the
“Assistant for Device Settings” will automatically be started when the first
attempt is made to access the instrument. This helps you to set up a device
list.

If the option is active ( ), a check is


made at the end whether the
chosen device can be accessed via
the selected interface.

Here you can choose whether the


device should be defined as the
default device ( ). The system will
automatically access a default
device, other devices must be
linked through the device list.

91
5 Setup program
h First select the device version.
h Enter an additional description, if appropriate.
h Set one of the option fields, if appropriate.
h Activate the button.

h Select the interface which you want to use to access the device.
The next steps depend on the interface or type of connection that has been
selected.

92
5 Setup program
TCP/IP PORT The following parameters must be selected:

IP address / xxx.xxx.xxx.xxx Enter the IP address of


HOST name (Example: 192.168.0.10) your device. If you enter
the name, the IP
address can be
determined by clicking
on the button “Convert
HOST name to IP
address”.
Port number, 502 The port used for
port name communication.
Communications Modbus TCP/IP, Set the
protocol Modbus protocol Modbus TCP/IP here.
Communications 0 The communications
password password must match
the one that has been
set in the device.

Analog The following parameters must be selected:


modem /
ISDN Telephone number Enter the telephone
number for connecting
to the required device.
Connect via Select the modem that
is to be used to make
the connection.
Communications Modbus TCP/IP, Set the
protocol Modbus protocol Modbus protocol
here.
Device address 1 — 255 (255 can only Device address for the
be set if just one device Modbus protocol.
is connected)
Communications 0 The communications
password password must match
the one that has been
set in the device.

Serial The following parameters must be selected:


interface
Connected to COM1, COM2 The PC interface to
which the paperless
recorder is connected.

93
5 Setup program
Transmission rate 9600, 19200, 38400 The transmission rate
must match the one set
in the device. If “RS232
setup interface (TTL)”
has been selected as
the control signal, then
9600 must be set,
Control signal RS232 If the RS232 interface
on the device is used.
RS232 setup interface If the setup interface on
(TTL) the device is used.
RS422-RTS If the RS422/485
RS422-DTR interface on the device
is used.
RS485-RTS
RS485-DTR
Expanded Stop bit and The parameters under
parity the “Expanded” button
must also match those
in the device.
Standard and obligatory
setting for the control
signal “RS232 setup
interface (TTL)”:
Stop bit = 1
Parity = none
Communications Modbus TCP/IP, Set the Modbus
protocol Modbus protocol protocol here.
Device address 1 — 255 Device address for the
(255 can only be set if Modbus protocol. If the
just one device is “RS232setup interface”
connected to the is used as the control
interface) signal, then the device
address will be ignored
– it does not have to
match the address in
the device.
Communications 0 The communications
password password must match
that set in the device.

Exception:
Communication via the
setup interface can
always be established
without a
communications
password.

94
5 Setup program
Device list When all settings have been made, the device is entered in the device list.

5.7.2 Device list


All devices that have been defined are shown in a device list. The interface
parameters are also administered here, and new, additional devices can also
be defined in the device list.
Make a connection
with the selected device.
Remove device(s) from the list.
Alter properties
Add a new device

Automatically search the


interfaces for devices

Use the assistant to carry out the function “Add new device” or
“Alter properties”.

Use the button to make a connection to a device. By using the


Ctrl key on the PC keyboard and the left mouse button, you can select several
devices at the same time (only for deleting devices from the device list).
A successful connection produces a change in the toolbar.

Not
connected

Connected

95
5 Setup program
5.8 Menu functions

5.8.1 File

New Opens a new setup in the working area. The values will be preset to the factory
default settings.

Open Opens an existing setup from a file, and present the contents in the working
area.

Save Saves the setup that is shown in the working area to a file. It is only necessary
to enter the file name once. If the file is saved again, no query is made about
the file name.

Save as Saves the setup that is shown in the working area to a file. Unlike the Save
function, this always asks for a file name.

Close Removes a complete setup from the working area. If changes have not yet
been saved, this can still be done immediately after calling up the Close
function.

Delete Deletes a file from a hard disk or another data storage medium.

A
Deleted files cannot be recovered.

Export as RTF The current setup can be saved as an RTF file on the PC.
text

Print When you have called up the function, the selection of what is to be printed
appears first. Printing will start when the selection has been concluded.

Print preview The printed result is displayed on the screen. You can let several pages be
displayed, and alter the size of the pages on the screen.

Printer setup Here you can make alterations to the settings for your printer. When the
program is started, the Windows default printer will always be set as the active
printer.

Default settings Here you can make alterations to the default settings for the program. Many
alterations will only take effect after a fresh start of the setup program.

Exit This closes the setup program.

96
5 Setup program
5.8.2 Edit

Undo ... Undoes the last editing action. In the menu, the item Undo shows which
setting will be undone.

Restore ... The Restore function will only be available when the Undo function has been
activated. This function repeats the setting that was previously canceled by
the Undo function.

Parameter- This function has the same effect as a double-click with the left mouse button
ization on the following function in the dialog window.

Configuration This function has the same effect as a double-click with the left mouse button
level on one of the following functions in the dialog window.

Settings This function has the same effect as a double-click with the left mouse button
through setup on the following function in the dialog window.
only

v Chapter 5.9 “Math/logic”

97
5 Setup program
Setup data info This function has the same effect as a double-click with the left mouse button
on one of the following functions in the dialog window.

5.8.3 Data transfer

Make This function establishes a connection to a device. A connection to a device is


connection a precondition for transferring a setup to or from a device via an interface
(serial or Ethernet).

Disconnect This breaks an existing connection. A connection to a device must be broken


before a new connection can be established to another devices.

Data transfer to Transmits a setup to a device.


device

Data transfer Read in a setup from a device. If there is no connection, the program will
from device automatically attempt to access the default device.

Data export The setup will be saved on a CompactFlash card. The CompactFlash card can
to CF card be read by the device.

Data import This reads a setup from a CompactFlash card, and displays it in the working
from CF card area.

5.8.4 Extras

H All the functions in the Extras menu which require access to a


device must have a connection to the device.
If there is no connection, the setup program will try to access the
default device from the device list. If no default device has been
defined, then the device list will appear on the screen and the user
must set up a connection by hand.

Enable program If no valid serial number was entered during the installation of a program, then
options it will only run in a 30-day test or demo mode. This function can be used to
register a program at a later date, to convert it into a full version.

98
5 Setup program
Enable extra This function is intended for later extensions within the paperless recorder
codes (e. g. enabling the extra code for “Integrators, counters, math and logic
module”).
After starting up the function, the function must be used
to read out a code number from the device, and then passed on to the
manufacturer. The manufacturer will then generate a “release number”. The
function is used to transmit this release number to the
device, which will then enable the new device functions.

Calibration/ This carries out a calibration and various test functions. Calibration can only
Test be carried out with a special license number, and is reserved for the
manufacturer’s service personnel.
After activating Extras ➔ Calibration / Test and confirming the security
instruction, a device must be selected, if one is not already connected. The
dialog window will then appear, the hardware and software are automatically
read out, and information about the result will be displayed.
Test functions

H Some test functions cannot be terminated as long as there is a


connection to the instrument. If necessary, use the dialog window
to close down the connection.

Break
connection

99
5 Setup program
Date and time This function is used to match the date and time for a PC and a device.

Terminates the function.

Send the date and time to a device.

The button is used to make date and time settings for a device.
This function uses the information in the “New setting” selection as the basis
for adjustment.
ensures that the device clock is read out continually
(cyclically). The continual read-out can be ended by activating . The
clock cannot be adjusted while it is is being continually read out.

Create screen This function provides you with another option for documenting settings or
printout events.
Start the function and operate the “Create” button. A screenshot (printout) will
be created for the device that is connected. You can save the screenshot as a
bitmap, or print it out directly.

Start picture With this function, the start screen (start logo after power-on) can be read,
altered or swapped, and transmitted to the recorder.

Write message This function can be used to transmit a message text to a device.
text
The message text can be used to make an entry in the event list for a device.
The functions are independent of the present setting in the dialog window. The
data can be transmitted to a device, without causing a new configuration.

Ethernet Using this function, the Ethernet parameters “IP address”, “Subnet mask” and
interface “Gateway” can be transmitted to the recorder. They are transmitted to that
device which has been linked to the setup program via the device list.
When transferring setup data through “data transfer to device“, “data transfer
from device”, “data export to CF card“ or “data import from CF card”, the
Ethernet parameters are not transmitted with this data, to avoid a collision of
data in the network due to identical IP addresses.

100
5 Setup program
Renew log-in / The function Renew log-in / Alter password is used to
Alter password
- activate the user and password query at the program start and
- alter the current password.
This function only has an affect on the operation of the setup program, not the
recorder.
Activation of the user and password query at the program start
When the setup program is installed for the first time, there will not yet be a
query of the user name and password when the program starts. You will
automatically be logged in as “Specialist”, with a blank password.
Proceed as follows:
h Start the function “Renew log-in / Alter password”.
h Show the options.

Show the options.

h Activate the option “After log-in – alter password” and click on the
button.

101
5 Setup program
h Enter the password - the “Old password” field remains empty.

When the entry has been concluded, the new password is activated by
clicking . From now on, the user name and the password will be
requested at the program start.

H Initially, no start password is assigned to the “Maintenance” user


either. At program start, log in with the “Maintenance” user name
and enter a password as described above.

Password alteration
Altering a password is very much like activating the password query. The only
difference is that, in this case, the “Old password” field must not remain
empty.

102
5 Setup program
5.8.5 Window

H The usual Windows options are available for the positioning of


the dialog windows.

Enlarging and minimizing

Reducing and maximizing

Close

A double-click with the left mouse button


produces maximum enlargement.

Cascade If several dialog windows are open at the same time, this function has the
effect that all windows are shown with an offset to one another. You can use
the left mouse button to bring a window into the foreground.

Tiled If several dialog windows are open at the same time, this function has the
horizontally effect that the various windows are shown one above another. You can use the
left mouse button in a window to make that window active.

Arrange All open windows are minimized – they disappear from the screen, but are not
symbols closed.

Teleservice You can switch Teleservice into or out of display by using this function. The
position is independent of the position of the dialog window.
v Chapter 5.5 “Teleservice”

Connection You can switch the connection status into or out of display by using this
status function. The position is independent of the position of the dialog window.
v See “Connection status” on page 80.

103
5 Setup program
5.8.6 Info

Info on setup Here you can find out the version number of the setup program. Please have
the version number available if you contact the service hotline.

Software This function calls up the available instrument and software documentation in
documentation PDF format.

Registered Here you can find out the license number of the setup program. Please have
license the license number available if you contact the service hotline.
numbers

Program Here you can obtain information as to which folders (directories) on the hard
folder disk or in the network are used by the setup program. If you activate the
button, the contents of the folder will be displayed.

104
5 Setup program
5.9 Math/logic
The math and logic module is available as an extra code. It has to be ordered
from the start, or subsequently enabled through the function Extras ➔ Enable
extra codes (Page 98).
The math/logic module is composed of channels that are not available as
hardware but are calculated by the instrument software.

Math You can activate the math channels in the setup program, in the “Math / logic”
area, or through the menu Edit ➔ Settings through setup only ➔ Math / logic.

In the following example, math channel 3 will be configured:

105
5 Setup program

Function selection

The function is selected here. All other fields can


subsequently be edited according to the function.

You must edit the input fields “Variable a”, “Variable b” or “Time for moving
average” if one of the standard functions (difference, ratio, humidity, moving
average) has been set.
If you have set the “Formula” function, then the input field “Formula” must be
edited. Entry can either be direct or via a ( ) dialog.

Example:
humidity

H With humidity measurement, the channel for dry bulb temperature


has to be specified as variable a, the channel for the wet bulb
temperature as variable b.

106
5 Setup program
Example:
Formula

The formula can be entered directly from the PC keys or by calling up the
function.

When you have called up the function, this dialog box will appear:

In the left window you can select the required signal, in the right window the
required operator, and enter them into the formula by activating the
corresponding button ( ). Instead of using , you can also
make a selection by a double-click with the left mouse button.

H For functions ending with ( ), you will have to add


the closing bracket yourself.
Example: 1. add in SQRT() --> SQRT(
2. add in AE1 --> SQRT(AE1
3. add in ) --> SQRT(AE1)

H The functions “Pointer to float values”, “Pointer to integer values”


and “Pointer to byte values” may only be used on express
instruction from the manufacturer.

107
5 Setup program
Operator
overview Operator Explanation Example
+ addition AE1 + AE2
- subtraction AE1 - AE2
* multiplication AE1 * AE2
/ division AE1 / AE2
( opening bracket (
) closing bracket )
SQRT() root SQRT (AE1)
MIN() minimum value MIN (AE1, AE2)
MAX() maximum value MAX (AE1, AE2, AE3)
SIN() sine SIN (AE1)
COS() cosine COS (AE1)
TAN() tangent TAN (AE1)
** x to the power y AE1 ** AE2
EXP() exponential function EXP (AE1)
ABS() absolute value ABS (AE1)
INT() integer portion INT (AE1)
FRC() decimal portion FRC (AE1)
LOG() logarithm LOG (AE1)
LN() natural logarithm LN (AE1)

Operator Math calculation signs and functions


priorities
Priority Math sign / function Comment
high () brackets
SQRT, MIN, MAX, LOG, LN, SIN, functions
COS, TAN, ABS, EXP, INT, FRC
** exponent (xy)
+, - sign
*, / multiplication, division
low +, - addition, subtraction
Logic operators
Priority Operator Comment
high () brackets
NOT, ! negation
AND, & AND linkage
XOR, ^ exclusive OR linkage
low OR, ¦ OR linkage

108
5 Setup program
5.10 Character set
032 080 P 0161 ¡ 0209 Ñ
033 ! 081 Q 0162 ¢ 0210 Ò
034 " 082 R 0163 £ 0211 Ó
035 # 083 S 0164 ¤ 0212 Ô
036 $ 084 T 0165 ¥ 0213 Õ
037 % 085 U 0166 ¦ 0214 Ö
038 & 086 V 0167 § 0215 ×
039 ’ 087 W 0168 ¨ 0216 Ø
040 ( 088 X 0169 © 0217 Ù
041 ) 089 Y 0170 ª 0218 Ú
042 * 090 Z 0171 « 0219 Û
043 + 091 [ 0172 ¬ 0220 Ü
044 , 092 \ 0173 - 0221 Ý
045 - 093 ] 0174 ® 0222 Þ
046 . 094 ^ 0175 ¯ 0223 ß
047 / 095 _ 0176 ° 0224 à
048 0 096 ‘ 0177 ± 0225 á
049 1 097 a 0178 ² 0226 â
050 2 098 b 0179 ³ 0227 ã
051 3 099 c 0180 ´ 0228 ä
052 4 0100 d 0181 µ 0229 å
053 5 0101 e 0182 ¶ 0230 æ
054 6 0102 f 0183 · 0231 ç
055 7 0103 g 0184 ¸ 0232 è
056 8 0104 h 0185 ¹ 0233 é
057 9 0105 i 0186 º 0234 ê
058 : 0106 j 0187 » 0235 ë
059 ; 0107 k 0188 ¼ 0236 ì
060 < 0108 l 0189 ½ 0237 í
061 = 0109 m 0190 ¾ 0238 î
062 > 0110 n 0191 ¿ 0239 ï
063 ? 0111 o 0192 À 0240 ð
064 @ 0112 p 0193 Á 0241 ñ
065 A 0113 q 0194 Â 0242 ò
066 B 0114 r 0195 Ã 0243 ó
067 C 0115 s 0196 Ä 0244 ô
068 D 0116 t 0197 Å 0245 õ
069 E 0117 u 0198 Æ 0246 ö
070 F 0118 v 0199 Ç 0247 ÷
071 G 0119 w 0200 È 0248 ø
072 H 0120 x 0201 É 0249 ù
073 I 0121 y 0202 Ê 0250 ú
074 J 0122 z 0203 Ë 0251 û
075 K 0123 { 0204 Ì 0252 ü
076 L 0124 | 0205 Í 0253 ý
077 M 0125 } 0206 Î 0254 þ
078 N 0126 ~ 0207 Ï 0255 ÿ
079 O 0128 € 0208 Ð

109
5 Setup program
Entering Any (special) characters that cannot be entered directly from the keyboard of
special the PC can be entered with the help of the A key and the numerical
characters combinations that are specified in the table.

Example The special character © has to be entered:


h Position the cursor with the mouse, or by using the cursor keys, on the
point where the character is to be inserted.
h Press the A key and hold it down
h Enter the number combination 0169 in the number block (on the right-hand
side of the keypad) (the leading zero must be entered as well)
h Release the A key
The character © is inserted at the cursor position.

Cyrillic
characters
H The character set depends on the language of the operating
system that is used, and may be different from the example.

If “Russian” has been selected as the language for the instrument, then the
characters 0192 … 0255 will be replaced by Cyrillic letters in the instrument.

110
6 Rights
6.1 Rights with regard to the setup program
Depending on the installation and the log-in, individual users will have different
rights within the setup program.
The differences are summarized in the table below:

Right Demo Maintenance Specialist


installation
Write interface texts - X X
New X X X
Open X X X
Save, Save as, Delete - X X
Configure undocumented
parameters - - X
Export to CF card - X X
Import from CF card - X X
Print - X X
Enable program options X - X
Enable extra codes - - X
Edit interface settings - X X
Edit device settings X X X
Delete device - - X
Create new device X - X
X = right is available

111
6 Rights

112
7 PC programs
7.1 PC evaluation software (PCA3000)

H Operating Instructions B 70.9701.0 describe PCA300 in detail.

PCA3000 is the professional evaluation software for data-analysis of the archived


instrument process data.

PCA3000 is the ideal software for the best-quality graphic and alphanumeric
display of electronically stored measurement data. The software supports
multi-user functionality, so that different users can access the same data.
PCA3000 runs under Windows NT, Windows 2000 and Windows XP.

Data storage The life-cycle archive data structure enables on-demand saving and
archiving of all process data, clearly and simply, in a single file.

Data backup Archive data can be read out and visualized directly from a CD-ROM or DVD (a
transfer to the hard disk is not necessary).

Data export Data export at the HTML level, or as an ASCII text file (for evaluation in Excel).

Communication The data transfer program PCC (communications software) is perfectly


matched to PCA3000, and enables the comfortable read-out of data through
the interface, using RS232/ RS422, Ethernet, a modem, or through the setup
interface.

113
7 PC programs
7.2 PCA communications software (PCC)

H PCC is described in detail in the


Operating Instructions B 70.9702.0.

PCC is the professional archive software: it transfers the data via an inerface
(setup, serial or Ethernet) from the recorder (or several recorders and
controllers), and deposits them on a PC or a network.

114
8 Identifying the instrument version
8.1 Type designation
Entry-level paperless recorder with CompactFlash card as storage medium
and life-cycle data management
(1) Basic version
706510/14 Paperless recorder with 3 analog inputs

706510/24 Paperless recorder with 3 analog inputs


incl. setup and PC evaluation program (PCA3000)
706510/15 Paperless recorder with 6 analog inputs

706510/25 Paperless recorder with 6 analog inputs


incl. setup and PC evaluation program (PCA3000)

(2) Supply voltage


xxxx 22 20 — 53V AC/DC, 48 — 63Hz
xxxx 23 110 — 240 V AC +10/-15%, 48 — 63Hz

(3) Extra codes


xxxx 008 Ethernet interface
xxxx 020 Lithium battery for memory buffering (ex-factory)
xxxx 021 Storage capacitor (instead of extra code 020)
xxxx 260 Integrators and counters, as well as math and
logic module (the math and logic module can only be
configured through the setup program).
xxxx 261 4 binary inputs, 3 relay outputs,
serial interface RS232/RS485 (Modbus, Jbus)
xxxx 265 Door with lock (IP54)
xxxx 266 IP65 seal, 4 wide mounting brackets
xxxx 350 Universal carrying case TG-35
(1) (2) (3)
Order code - / , ...1

Order example 706510/14 - 23 / 020


1
List extra codes in sequence, separated by commas.

115
8 Identifying the instrument version
8.2 Standard accessories
- 1 Operating Instructions B 70.6510.0
- 2 mounting brackets, or 4 mounting brackets with extra code 266
- 1 control panel seal with extra code 266
- 2 cover plates for fixing holes
- Cable tie with foot (can be released)
for strain relief of the sensor connecting cables

8.3 Optional accessories


- Setup program, multilingual
- PC interface with TTL/RS232 converter and adapter (socket)
- PC interface with USB/TTL converter, adapter (socket) and adapter (plug)
- PC evaluation software (PCA3000), multilingual
- PCA communications software (PCC), multilingual
- Inputs configured to customer specification

116
9 Installation
9.1 Installation site and climatic conditions
The installation site should be free from vibration. Electromagnetic fields,
caused by motors, transformers etc. should be avoided.
The ambient temperature at the site should be 0 to +45°C, with a relative
humidity of ≤75%, no condensation.
v Chapter 10.1 “Installation notes”

9.2 Fitting

Views

Size 26 increases to 27 if the IP65 seal is used.

Panel mounting

117
9 Installation
Installation h Insert the paperless recorder from the front into the panel cut-out.
h From behind the panel, hook the two mounting brackets into the grooves
on the sides of the housing. The flat faces of the mounting brackets must lie
against the housing.

Cutout for fixing bracket

h Push the fixing brackets up against the back of the panel


and tighten them evenly.

h Use the cover plates to close the remaining cutouts for mounting brackets.

Cover plate

118
9 Installation
Extra code 266 The following instructions must be followed when installing the paperless
(IP65) recorder with extra code 266 (IP65).
- The seal for the control panel must be fitted before the recorder is installed.

Caution!

Make sure that the seal is correctly


positioned.
The two large indentations c on the
front frame must be closed by the two
lugs d on the seal.

- Instead of the 2 mounting brackets, there are 4 wide mounting brackets


that have to be used (one element for each side of the housing).
- The cover plates for closing the cutouts for the mounting brackets must not
be used.

119
9 Installation

120
10 Electrical connection
10.1 Installation notes
k The choice of cable, the installation and the electrical connection must
conform to the requirements of VDE 0100 “Regulations on the
Installation of Power Circuits with Nominal Voltages below 1000V” or the
appropriate local regulations.
k Work inside the instrument must only be carried out to the extent
described and, like the electrical connection, only by qualified personnel.
k The instrument must be disconnected on both poles from the electrical
supply if contact with live parts is possible while work is carried out.
k Electromagnetic compatibility (EMC) conforms to the standards and
regulations cited in the technical data.
v Data Sheet 70.6510
k Run input, output and supply cables separately and not parallel to one
another.
k All input and output cables without connection to the mains supply must
be arranged as twisted and screened cables. Earth the screen on the
instrument side to the earth potential.
k Earth the instrument at the PE terminal to the protective earth conductor.
This cable must have the same cross-section as that used for the supply
cables. Earthing cables must be wired in a star configuration to a
common earth point that is connected to the protective earth conductor
of the electrical supply. Do not loop earthing cables, i.e. do not run them
from one instrument to another.
k Do not connect any additional loads to the supply terminals of the
instrument.
k The device is not suitable for use in areas with an explosion hazard
(Ex areas).
k Inductive loads close to the instrument, such as contactors or solenoid
valves, should have RC modules fitted for interference suppression.
k The instrument must be provided with external fusing and disconnection.
Depending on the supply voltage, the following fuse values apply for the
external fusing:
20 — 53V AC/DC, 48 — 63Hz 5A fuse, slow-blow
110 — 240V AC +10/-15%, 48 — 63Hz 5A fuse, slow-blow

10.2 Technical data


v Data Sheet 70.6510

121
10 Electrical connection
10.3 Approvals

10.4 Connection diagram

V
The electrical connection must only be carried out by qualified
personnel.

Rear view

Terminal assignment Diagram


(for pluggable screw terminals)
3/6 channel paperless recorder

Supply voltage
Supply voltage PE
N (L-)
L1 (L+)

122
10 Electrical connection
Terminal assignment Diagram
(for pluggable screw terminals)
3/6 channel paperless recorder

Analog inputs Connector

Thermocouple 1 to 6

If sizeable supply interference is present on a thermocouple input, then the


corresponding analog input requires a link from terminal 2 to terminal 4.
Increased interference voltages can, for example, be generated by ceramic
insulation becoming conductive at temperatures of several hundred °C.
Resistance thermometers 1 to 6
in 2-wire circuit

Resistance thermometers 1 to 6
in 3-wire circuit

Resistance thermometers 1 to 6
in 4-wire circuit

Voltage input ≤ 210mV 1 to 6

Voltage input > 210mV 1 to 6

Current input 1 to 6

123
10 Electrical connection

Terminal assignment Diagram


Setup interface (included in delivery)
The setup interface can
be found on the front of
the instrument, behind
the cover for the
CompactFlash
memory card.

Setup interface

Interfaces (extra code)


RS232 20 2 RxD receive data
9-pole SUB-D socket 3 TxD transmit data
5 GND ground
RS485 20 3 TxD+/RxD+
9-pole SUB-D socket transmit/receive data +
5 GND ground
8 TxD-/RxD-
transmit/receive data -
Ethernet 21
RJ45 socket 1 8

1 TX+ transmit data +


2 TX- transmit data -
3 RX+ receive data +
6 RX- receive data -
Relay outputs (extra code)
Relays K1, K2, K3 30, 31, 32
(changeover)

Binary inputs (extra code)


33
Supply voltage 6 +24V
24V / 50mA 5 GND
Example:
Binary inputs, 4 binary input 1
binary input 4, operated
voltage-controlled 3 binary input 2
from the internal supply
2 binary input 3
voltage
LOW = -3 to +5V DC 1 binary input 4
HIGH = 12 to 30V DC

124
11 TÜV Report on Data Manipulation Security

H Type 706510/... corresponds to type 706500/.... or 955015/...., with the only difference
that the 706510/... recorder employs a different storage medium. It uses CompactFlash
memory cards for transferring data, and not diskettes.

125
11 TÜV Report on Data Manipulation Security

126
11 TÜV Report on Data Manipulation Security

127
11 TÜV Report on Data Manipulation Security

128
12 Index
A
Action (outputs) 73
Active operating mode 23
Alarm 70
Alarm (counter/integrator) 68
Alarm delay 71
Alarm text (counter/integrator) 68
Alter password 101
Analog inputs 64–65, 70–71
Approvals 122
Arrange symbols 103
Authorization code 64

B
Basic menu 11, 32
Battery empty 53–54
Baud rate 75

C
Calibration status 76
Cascade 103
CF card code number 63
Channel (counter/integrator) 66
Channel indication 35, 61
Channel line 14, 61, 70
Channel name 70
Channel name (counter/integrator) 67
Channel representation 14, 33, 61
Character entry 55
Character selection 55
Climatic conditions 117
Close 96
Code number 46, 50, 57, 59, 63
Cold junction 64
Color display 11
Commissioning 7
CompactFlash 86
Errors 52
Computed code No. 64
Configuration
Analog inputs 64
Control functions 74
Counter/integrator 66
Event traces 66
Fine calibration 76
Interface 75
Meas. storage 70
Outputs 73

129
12 Index
Texts 74, 76
Connection circuit 64
Connection diagram 122
Connection status 80, 103
Contrast 60
Control function 74
Control signal 60, 73
Control signal (outputs) 73
Counter 66
Counter frequency (counters/integrators) 17
Counter text (counter/integrator) 68
Counters 17
Create screen printout 100

D
Daily end time (counter/integrator) 69
Daily start time (counter/integrator) 69
Data
Evaluation 27
Read-out via interface 27
Data export to CF card 98
Data format 75
Data import from CF card 98
Data lost 53–54
Data manipulation security 125
Data transfer from device 98
Data transfer to device 98
Date 62
Date and time 100
Decimal place 70
Decimal place (counter/integrator) 68
Default settings 96
Delete 96
Device address 75
Device info 53
Device name 62
Device software 54
Diagram speed 13, 23
Diagram view 44
Differential 71
Digital display 33, 36
Disconnect 98
Display 11
Display off 44
Display printout 100
Displays and controls 11

E
Electrostatic discharge (ESD) 7

130
12 Index
Enable extra codes 99
Enable options
Authorization code 64
Computed code No. 64
Enable options 64
Enable program options 98
End temperature 65
End time (timed operation) 72
End value
Target 76
Enter key 11
Error 54
Ethernet 28, 75
Evaluation of measurement data 38
Evaluation program 50
Event definition 47
Event list 47
Event operation 23
Storage cycle 73
Stored value 73
Event traces 15
Exit 96
Exit key 11
Ext. control signal (counter/integrator) 69
External cold junction temperature 65
External text 74
External texts 16

F
Factory setting 63
Falling below range 14
Filter constant 65
Fine calibration 76
Function (counter/integrator) 66

G
Gateway 75

H
Header 12, 33, 61, 70
High limit 70
History 38
Humidity measurement 106

I
Import/export errors 87

131
12 Index
Info on setup 104
Input signal 72
Input signal (counter/integrator) 66–67
Installation 117
Installation notes 121
Installation site 117
Integrator 17, 66
Interface type 75
Internal analog inputs 14
IP address 75
IP65 115, 119

K
Key inhibit 74
Keys 10, 12

L
Language 63
Life-cycle data management 24
Limit index 35
Limit value (counter/integrator) 68
Line width 70
Linearization 64
Logic module 22, 105
Operator priorities 108
Low limit 70

M
Make connection 98
Math module 20, 105
Operator overview 108
Operator priorities 108
Meas. range 65
Memory alarm 27, 63
Memory status 72
Memory upload 63
Menu key 11, 32
Modbus flag 84–85

N
New 96
Normal operation 23
Control signal 73
Memory status 72
Storage cycle 72
Stored value 72

132
12 Index
Note signs 9

O
Open 96
Operating modes 23
Operating time counter 18
Outputs 16, 73–74
Action 73
Control signal 73
Overrange 14

P
Panel mounting 117
Paper perforations 61
Parameterization 60
Password 45–46, 50, 57, 59, 63
Password activation 101
Password alteration 101–102
PCA3000 20, 27, 64, 113, 115–116
PCC 27, 86, 91, 113–114, 116
Peak value 40
Period (counter/integrator) 68
Power LED 11
Principle of operation 46
Print 96
Print preview 96
Printer setup 96
Program folder 104
Program options, enabling 98
Protocol 75

R
Range end 65
Rear view 122
Registered license numbers 104
Renew log-in 101
Reporting period (counter/integrator) 18
Representation modes 10
Reset (counter/integrator) 18, 61
Reset counter/int. 63
Reset generation (counter/integrator) 69
Returning 7
RS232/RS485+Ethernet code number 63

S
Save 96

133
12 Index
Save as 96
Scaling 35
Scaling end 65–66
Scaling start 65–66
Screen off 44
Screen saver 11, 44, 60
Screen texts 10
Scroll operation 38
Sensor 64
Sensor monitoring 14
Setup program
Assistant for device settings 91
CompactFlash 86
Configuration 81
Current setup 81
Data transfer 86
Device list 95
Hardware and software requirements 77
Installation 78
Menu bar 79
Menu functions 96
Modbus flag 84–85
Navigation tree 81
Program start 78
Shifting the Teleservice window 85
Teleservice 80, 84
Toolbar 79
Toolbar shifting 80
Transfer 86
User interface 79
Working area 80
Signal type 33–34, 60
Signal types 15
Softkey 11–12
Speed 13
Speed indic. mode 60
Standard text 48
Start temperature 65
Start time (timed operation) 72
Start value,
Actual 76
Target 76
Status LED 11
Status line 13
Status message 52
Storage cycle 23, 72–73
Stored value 23, 72–73
Subnet Mask 75
Summer time 62
Supplementary text 48
Switch-off event 60
Synchronizing time (counter/integrator) 68

134
12 Index
T
Teleservice 103
Temperature unit 63
Text entry 55
Text High alarm 71
Text Low alarm 71
Texts 47, 74
Threshold value (counter/integrator) 67
Tiled horizontally 103
Time 62
Time base (counter/integrator) 67
Time synchronization 62
Timed operation 23
End time 72
Start time 72
Trace design. 72
Type (counter/integrator) 66
Type designation 115

U
UL approval 122
Underrange 14
Undocumented parameter 1 — 40 76
Unit 70
Unit (counter/integrator) 68
Unit of measurement 34

V
Version number 53
Views 117

W
Waiting time 60
Warranty 7
webserver 28
Weekday (counter/integrator) 69
Weighting (counter/integrator) 17, 67
Window technology 46
Write interface texts 100
Writing configuration data to CF card / reading from CF card 51

Z
Zoom 39

135
12 Index

136
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Street address: JUMO House 8 Technology Boulevard
Moritz-Juchheim-Straße 1 Temple Bank, Riverway Canastota, NY 13032, USA
36039 Fulda, Germany Harlow, Essex CM20 2TT, UK Phone: 315-697-JUMO
Delivery address: Phone: +44 1279 635533 1-800-554-JUMO
Mackenrodtstraße 14 Fax: +44 1279 635262 Fax: 315-697-5867
36039 Fulda, Germany e-mail: [email protected] e-mail: [email protected]
Postal address: Internet: www.jumo.co.uk Internet: www.jumo.us
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
e-mail: [email protected]
Internet: www.jumo.net