0% found this document useful (0 votes)
103 views83 pages

GST EN54 Prodct Introduction 2023

The document provides an overview of the EN54 product line from GST, including the GST100 single loop fire panel and GST200N 1/2 loop fire panel. It describes the features and specifications of the panels and optional components that can be added like additional loop cards, communication cards, and network cards.

Uploaded by

suharmanto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
103 views83 pages

GST EN54 Prodct Introduction 2023

The document provides an overview of the EN54 product line from GST, including the GST100 single loop fire panel and GST200N 1/2 loop fire panel. It describes the features and specifications of the panels and optional components that can be added like additional loop cards, communication cards, and network cards.

Uploaded by

suharmanto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 83

EN54 PRODUCT LINE

GST100 Panel Overview

2
1-Loop Fire Panel

GST100 Addressable Fire Alarm Control Panel

⚫ Single loop panel Max. 128 loop devices


⚫ 8 zones fire and fault/disable indication
⚫ Built in Sounder output, fire output and fault output
⚫ Programming via panel keypad
⚫ Optional network card networking with other GST
intelligent fire alarm control panel
⚫ Hungary or Portuguese version available (Fascia
keypad and LCD display)
⚫ Mains supply: 230V AC
⚫ Backup battery: 24VDC/7AH

3
GST200N Panel Overview

4
1/2-Loop Fire Panel

GST200N-1 GST200N-2 1/2 Loop Addressable Fire Alarm Control


⚫ Digital communication protocol,
Panel
⚫ Loop devices capacity: 235 addresses for GST200N-1;
477 addresses for GST200N-2
⚫ 30 zones fire and fault/disable indication
⚫ PAS and Acknowledge Function
⚫ Dirty detector reporting
⚫ Walk test feature
⚫ Build in RS485 repeater output, (maximum10 repeaters)
⚫ Standard: EN54-2/EN 54-4
⚫ Mains supply: 110-240V 50/60Hz
⚫ Backup battery: 24VDC/22AH
More Languages option:
GST200N-TK (Turkish), GST200N-FR (French),
GST200N-IT(Italian), GST200N-HU(Hungary)
GST200N-SP(Spanish) GST200N-PT(Portuguese ) 5
Addressable Fire Panel

Optional Components for GST200N

P-9901A
Micro Thermal Printer
Specification:

⚫ Power: 5v (from GST200-2 internal PSU


⚫ Communication: Ribbon cable connect to
GST200-2 main board printer port
⚫ Support all ASCII character

6
Addressable Fire Panel

Optional Components for GST200N-1

LC200
Loop card (2nd Loop)

Specification:

⚫ Power: 24v (from GST200N-1 internal PSU)


⚫ Communication: Ribbon cable connect to
GST200N main board XS2
⚫ Expand one more loop for GST200N-1 panel
⚫ Loop capacity :242 points

7
Addressable Fire Panel

Optional Components for GST200N

P-9930
GST200N Communication Card

Specification:

⚫ Powered by GST200N main board


⚫ RS232 or USB communication Interface
between computer and GST200N panel
⚫ Communication: 20 pin Ribbon cable
connect to GST200N main board XS2

8
Addressable Fire Panel

Optional Components for GST200N

P-9940A
RS485 class A network card
Specification:

⚫ Powered by GST200N main board

⚫ Communication: 20 pin Ribbon cable


connect to GST200N main board XS2
port

⚫ Networking interface with all GST


intelligent FACP RS485 Class A network

9
Addressable Fire Panel

Optional Components for GST200N

P-9960
Class B CAN network card

Specification:

⚫ Powered by GST200N main board

⚫ Communication: 20 pin Ribbon cable


connect to GST200N main board XS2
port

⚫ Networking interface with all GST


intelligent FACP CAN network

10
Addressable Fire Panel

Optional Components for GST200N

P-9960A
Class A CAN network card
Specification:

⚫ Powered by GST200N main board

⚫ Communication: 20 pin Ribbon cable


connect to GST200N main board XS2
port

⚫ Networking interface with all GST


intelligent FACP CAN network

11
Panel Overview GST-200N Structure

Structures

12
Panel Overview GST-200N Fascia

Fascia

LCD Display 8x18 Control Buttons LED indicator

Buttons & 32 Zone Indication & Manual Panel Keypad


Intervention

13
www.gst.com.cn
Panel Overview GST-200N External Wiring Diagram

Output to Repeater or Mimic Panel F7.820.828V1

Terminal Monitored

A
REPEATER

XT12
RS 485
B

B
Board

REPEATER

A
XT10
A
NETWORK
No connection

XT11
Refers to Optional

RS 485
Network Board

B
B

NETWORK

A
+
LOOP OUT

XT9
Loop Out (Out to First Device)

XT4
LOOP BUS
Monitored

D2 D1 Z- Z+ B
_

GND 24V DET BUS


LOOP 1

XT1
LOOP IN
_

XT2
Loop In (In From Last Device)

+
Standby Volatge:-9 to -11VDC

XT13
OUTPUT OUTPUT
ALARM
+
LOOP OUT

XT5
+

FIRE
4.7Kohms O/P
EOL

_
Non Monitored

Output Device with Sounder with


fitted diode built-in diode
Monitored

+
LOOP OUT

F.E.P.

XT6
+
+
OR 4.7Kohms FPE FPE
EOL

_
FPE with
fitted diode

SOUNDER
OUTPUT
CIRCUIT
+
LOOP OUT

XT7
+

+
4.7Kohms
EOL

_
Sounder with Sounder with
fitted diode built-in diode

Output Setting refers to Table List on the Manual


Non Monitored

NC COM NO
FAULT OUTPUT
X4

XT8
HL5
CLASS CHANGE

XT3

F1

X5 HL2

Terminal/Output Board X6 X1
F2
HL3

X7 X2
F3
HL4
EARTH
X3
X8

14
Panel Overview GST-200N System Diagram

Stand-alone Architecture

GST200N-1 – Capacities
•235 devices
•1.0 km max loop length
•1.5mm2 UTP fire cable

15
www.gst.com.cn
Panel Overview GST-200NSystem Diagram

Stand-alone Architecture

GST200N-2 – Capacities
•Loop 1 -235 devices
•Loop 2 – 242 devices
•1.0 km max loop length
•1.5mm2 UTP fire cable

16
Panel Overview GST-200N Repeater and GMC connection

Stand-alone Architecture
•Built-in Repeater/Mimic Output
• Up to 10 points
• RS485 – 1000meters
• Support Total 200 drawings, 30.000 points

• GSTGMC-up to 8 users
• Required P-9930
•RS232- 15 meters

17
GST-IFP8 Panel Overview

18
8-Loop Fire Panel

GST-IFP8 8 Loop Addressable Fire Alarm Control Panel

⚫ 1 to 4 loop cards , each with 2 loops


⚫ 242 device capacity for each loop
⚫ Standard: EN54-2/EN 54-4
⚫ Mains supply: 220/230VAC 50/60Hz
⚫ Backup battery: 24VDC/40AH
⚫ Optional Language version: Portuguese &
Hungarian
⚫ (Keypad, Fascia, LCD text display)

19
Addressable Fire Panel

Optional Components for GST-IFP8

LCIFP8
GST IFP8 Loop Card

Specification :

⚫ Powered by GST IFP8 mother board

⚫ Easy installation, set card address via on board


rotary switch then fix the card on mother board
loop board slot

⚫ Maximum output current: 300mA per loop

⚫ Capacity : 2 loops 484 points

20
Addressable Fire Panel

Optional Components for GST-IFP8

P-9935
GST IFP8 communication card

Specification :

⚫ Powered by GST IFP8 mother board

⚫ Easy installation, set card address via rotary


switch then fix the card on mother board Com
board slot

⚫ interface port: RS232 or USB port

21
Addressable Fire Panel

Optional Components for GST-IFP8

P-9945A
GST IFP8 RS485 Class A network card

Specification :

⚫ Powered by GST IFP8 mother board

⚫ Easy installed, set card address via on board


rotary switch then fix the card on mother board
loop board slot

⚫ Interface port : RS485

22
Addressable Fire Panel

Optional Components for GST-IFP8

P-9965
GST IFP8 CAN network card (Class B)

Specification :

⚫ Powered by GST IFP8 mother board

⚫ Easy installed, set card address via on board


rotary switch then fix the card on mother board
loop board slot

⚫ Interface port: CAN

23
Addressable Fire Panel

Optional Components for GST-IFP8

P-9965A
GST IFP8 CAN network card (Class A)

Specification :

⚫ Powered by GST IFP8 mother board

⚫ Easy installed, set card address via on board


rotary switch then fix the card on mother board
loop board slot

⚫ Interface port: CAN

24
Panel Overview GST-IFP8 Structure

Structures

25
Panel Overview GST-IFP8 Fascia

Fascia

LED indicator

Control Buttons

2 x 70 Zone Indication

26
www.gst.com.cn
Panel Overview GST-IFP8 Internal Parts Overview

LCD ,keypad and


Main Indication board

Zone Indication board

Micro Thermal Printer


27
www.gst.com.cn
Panel Overview GST-IFP8 Internal Parts Overview

PSU Interface Board


Mother Board

Panel PSU Main Power Switch


AC Power Filter
28
www.gst.com.cn
Panel Overview GST-IFP8 Internal Wiring

Basic Internal Wiring Diagram MAIN CONTROL BOARD

XS8
F7.820.1238V2 XS1

NO COM NC
OUTPUT
FAULT
INDICATOR BOARD
COM BOARD

REPEATER
B
A
XS9 XS2

F1
XS15

BACK
FEED

F2
MAIN BOARD

ROUTING
-
OUTPUT TO ALARM
XS5

+
TO MAINBOARD

SOUNDER
-
XS10 XS3

GND +5V

+
-
OUTPUT
TO FPE
LOOP BOARD

+
I-
0-
LOOP 01
XS11 XS4

XS1

I+
0+
I-
0-
LOOP 01

I+
0+
TO MAINBOARD
LOOP BOARD

I-
0-
+5V GND

LOOP 01

I+
XS12 XS5

0+
I-
RP1

0-
LOOP 01

I+
0+
LOOP BOARD

I-
0-
LOOP 01

I+
0+
I-
XS13 XS6

0-
IO ZONE

LOOP 01

I+
0+
I-
0-
LOOP 01
LOOP BOARD

I+
TO PRINT

0+
F7.820.1238V2 XS3

I-
0-
LOOP 01
XS6

I+
XS14 XS7

0+
I-
0-
LOOP 01

I+
0+
I-
LOOP BOARD GND 5V TX RX GND 24V

0-
LOOP 01

I+
0+
24V

MAIN POWER BOARD


HL HL HL HL HL HL HL HL HL HL HL HL HL HL

+ +
HL HL
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
+
HL
ZS2
+
HL
+
HL F7.820.1311V2
+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + + + +
HL HL HL HL HL HL HL HL HL HL HL HL HL HL GND 5V TX RX 24V GND
+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+5V GND
+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL
HL HL
+ +
HL HL HL HL HL HL HL HL

27V GND
+ +
F7.820.1312V2 + + + + + + + + + +

BT1
ZONE INDICATOR BOARD

BAT+ BAT-
HL HL HL HL HL HL HL HL HL HL HL HL HL HL 90V/260/12V
+ + + + + + + + + + + + + +
HL HL HL HL HL HL HL HL HL HL HL HL
ZS2 HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ + DC Output 27V 11.7A +V AJD
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
XP1 + +
HL HL HL HL HL HL HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL
+ +
HL HL HL HL HL HL HL HL HL HL
V+

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL

+ + + + + + + + + + + +
HL HL HL HL HL HL
+ +
HL HL HL HL HL HL HL HL
V-

+ + + + + + + + + + + + + +
HL HL
HL HL HL HL HL HL HL HL HL HL Fuse
+ +
F7.820.1312V2 + + + + + + + + + +
AC Input
L N

2A AC Input
AC220V

PRINTER
AC/DC POWER
CONVERTER AC FILTER POWER SWITCH

+ - + -

29
www.gst.com.cn
Panel Overview GST-IFP8 External Wiring

XS8
F7.820.1238V2 XS1

NO COM NC

System Connections
XT18

OUTPUT
FAULT
COM BOARD

REPEATER
B

XT14

B
Output to Repeater or
XS9 XS2 Mimic Panel

A
A
XS15

F2 F1
XT19

BACK
FEED
Fitted
470 ohms
EOL
4.7Kohms

MAIN BOARD

SOUNDER ROUTING
XT13

ALARM

_
O/P EOL
4.7Kohms

+
TO MAINBOARD

GST-IFP8
Sounder with Output Device with
built-in diode fitted diode

OUTPUT TO
XT12
XS10 XS3

_
O/P EOL

+
4.7Kohms

+
+
Sounder with Output Device with
built-in diode fitted diode

OUTPUT
XT11

TO FPE
_
FPE FPE EOL
4.7Kohms

+
+
LOOP BOARD

+
FPE with
fitted diode

XS11 XS4

LOOP 01 LOOP 02 LOOP 03 LOOP 04 LOOP 05 LOOP 06 LOOP 07 LOOP 08 LOOP 09 LOOP 10

I+ I-
XT10

O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O- O+ O-
A1

O-
Out to next panel A2

LOOP 10
O+
Out to next panel B2
B1

I+ I-

XT10
XT9
Network Terminal - Class A
LOOP BOARD B2 In from next panel B1

I+
+5V GND

I+ I-
XS12 XS5

XT8
In from next panel A1

I-
A2

I+ I-
A

O-
Out to next panel A

XT7

LOOP 10
LOOP BOARD

O+
Out to next panel B
B

I+ I-

XT10
XT6
Network Terminal - Class B

I+
XS13 XS6

I+ I-
No connection

XT5

I-
I+ I-
XT4
LOOP BOARD
Out to first device

O-
I+ I-
Loop Out

XT3

LOOP 01
O+
XS14 XS7

XT1
I+ I-
XT2

I+
Loop In

I+ I-
LOOP BOARD

I-
GND 5V TX RX GND 24V In from last device

XT1
24V

30
Panel Overview GST-IFP8 External Wiring

Basic loop Terminal


Connect the loop within the panel as follows:
Loop OUT + to Loop IN+/ Loop OUT- to Loop
IN- . out to first device

O- Loop Out
LOOP 01
O+
XT1
Loop Wiring
I+

Loop In
I-

in from last device

•Loop Address: 242 A1


O-

out to next panel A2


•Output Voltage:21-27Vdc
LOOP 10
O+

•Output Current: 300mA out to next panel B2


B1
•Wiring Topology: Class A or B
XT10

•Recommended Cable length: 1000 Terminal


Network meters - Class A
•Recommended Cable: B21.5mm 2 UTP fire cable
in from next panel B1
I+

•Loop protection: Optional loop isolator (C-9503/4)


in from next panel A1
I-

A2
31
Panel Overview GST-IFP8 External Wiring

Basic Output / Input Terminal

Device Alarm Delay Time Stop – via


Output Condition Disable CE Mode
Number (Default) Program Silence Button
Alarm
Routing A 00000083 Immediate Yes No Yes No
Routing
Output to
Sounder A 00000082 Immediate Yes Yes Yes Yes
Sounder
Output to
FPE A 00000081 Immediate Yes Yes No No
FPE

Note: For output dry contact use C-9302C (output capacity 5A/220VAC or 5A/24VDC)

32
www.gst.com.cn
Panel Overview GST-IFP8 Mother Board

Basic Mother Board Slot Positioning

33
Panel Overview GST-IFP8 Card Configuration

Card addressing
Each card (except main board) must be set
unique number (via onboard rotary switch) before
install it on motherboard,
Addressing sequence :loop card network card,
repeater card and RS232 communication card,
The number must start from No.1, and
continuously
Installation: recommend the card No.1 installed
on the lowest slot. Then card No.2 on the upper
slot, one by one till last card

CARD SUM:04 LOOP SUM:06 DEVICE SUM:614


*************************************************************
1 Loop 01: Loop Card, Devices Sum:184
2 Loop 02: Loop Card, Devices Sum:160
3 Loop 03: Loop Card, Devices Sum:150
4 Loop 04: Loop Card, Devices Sum:120
5 Loop 05: Net Unit
6 Loop 06: Color CRT

->[F1] to Print All Loop Devices Info.


->[F2] – Found Devices [F3] –Missed Devices

34
www.gst.com.cn
Panel Overview GST-IFP8 Card Configuration

Card Configuration

10 Loops + Repeater
10 Loops + Communication
8 Loops + Communication + Repeater
8 Loops + Communication+ Network
8 Loops + Network + Repeater
6 Loops + Communication + Network + Repeater

35
Panel Overview GST-IFP8 Card Configuration

Card Configuration
XS1
XS8 A1
9 01
HL1 Loop 11 - CRT Card 01
HL2
8
7
2
3 P-9935- Communication Card
6 5 4

XS2
XS9 Main Card

XS3
Loop 10-Loop card - Wired on Loop 10 terminal Sample…
XS10
LED HL2 LED HL1

9 01
8
7
6 5 4
2
3 Loop 9-Loop card - Wired on Loop 09 terminal 10 Loops + Repeater
A1
LCIFP8-Dual Loop Card 10 Loops + Communication
XS4
XS11
LED HL2

9 01
LED HL1
Loop 8-Loop card - Wired on Loop 08 terminal
8 2
7 3 Loop 7-Loop card - Wired on Loop 07 terminal
6 5 4
A1
LCIFP8-Dual Loop Card
XS5
XS12
LED HL2

9 01
LED HL1
Loop 6-Loop card - Wired on Loop 06 terminal
8 2
7 3 Loop 5-Loop card - Wired on Loop 05 terminal
6 5 4
A1
LCIFP8-Dual Loop Card

XS6
XS13
LED HL2

9 01
LED HL1
Loop 4-Loop card - Wired on Loop 04 terminal
8 2
7 3 Loop 3-Loop card - Wired on Loop 03 terminal
6 5 4
A1
LCIFP8-Dual Loop Card

XS7
XS17
LED HL2

9 01
LED HL1
Loop 2-Loop card - Wired on Loop 02 terminal
8 2
7 3 Loop 1-Loop card - Wired on Loop 01 terminal
6 5 4
A1
LCIFP8-Dual Loop Card

36
www.gst.com.cn
Panel Overview GST-IFP8 Card Configuration

Card Configuration
XS1
XS8 A1
9 01
HL1 Loop 10 - CRT Card 01
HL2
8
7
2
3 P-9935- Communication Card
654

XS2
XS9 Main Card

XS3 Sample…
XS10
LED HL2

9 01
LED HL1
Loop 9-Net Unit - Wired on Loop 10 terminal
8 2
7 3 P-9945A - Network Card
654
A1 8 Loops + Network + Communication card
XS4
XS11
LED HL2

9 01
LED HL1
Loop 8-Loop card - Wired on Loop 08 terminal
8
7
654
2
3 Loop 7-Loop card - Wired on Loop 07 terminal 8 Loops + Network + Repeater
A1
LCIFP8-Dual Loop Card
XS5
XS12
LED HL2

9 01
LED HL1
Loop 6-Loop card - Wired on Loop 06 terminal
8 2
7 3 Loop 5-Loop card - Wired on Loop 05 terminal
654
A1
LCIFP8-Dual Loop Card

XS6
XS13
LED HL2

9 01
LED HL1
Loop 4-Loop card - Wired on Loop 04 terminal
8 2
7 3 Loop 3-Loop card - Wired on Loop 03 terminal
654
A1
LCIFP8-Dual Loop Card

XS7
XS17
LED HL2

9 01
LED HL1
Loop 2-Loop card - Wired on Loop 02 terminal
8 2
7 3 Loop 1-Loop card - Wired on Loop 01 terminal
654
A1
LCIFP8-Dual Loop Card

37
www.gst.com.cn
Panel Overview GST-IFP8 Card Configuration

Card Configuration
XS1
XS8 A1
9 01
HL1 Loop 9 - Repeater Card 01
HL2
8
7
2
3 P-9945RP - Repeater Card
65 4

XS2
XS9 Main Card

XS3
XS10
LED HL2

9 01
LED HL1
Loop 8-Net Unit - Wired on Loop 10 terminal
Sample…
8 2
7 3 P-9945A - Network Card - 01
65 4
A1

6 Loops + Network + Repeater+


XS4
XS11
LED HL2

9 01
LED HL1
Loop 7 - CRT Card 01
8 2
P-9935 - Communication Card
Communication card
7 3
65 4
A1

XS5
XS12
LED HL2

9 01
LED HL1
Loop 6-Loop card - Wired on Loop 06 terminal
8 2
7 3 Loop 5-Loop card - Wired on Loop 05 terminal
65 4
A1
LCIFP8-Dual Loop Card

XS6
XS13
LED HL2

9 01
LED HL1
Loop 4-Loop card - Wired on Loop 04 terminal
8 2
7 3 Loop 3-Loop card - Wired on Loop 03 terminal
65 4
A1
LCIFP8-Dual Loop Card

XS7
XS17
LED HL2

9 01
LED HL1
Loop 2-Loop card - Wired on Loop 02 terminal
8 2
7 3 Loop 1-Loop card - Wired on Loop 01 terminal
65 4
A1
LCIFP8-Dual Loop Card

38
www.gst.com.cn
Panel Overview GST-IFP8 System Diagram

Stand-alone Architecture

IFP8 Capacities
•LCIFP8 –dual loop
•Loop 10 -2420 devices
•1.0 km max loop length
•1.5mm2 UTP fire cable

39
Panel Overview GST-IFP8 Repeater and GMC connection

•Required P-9945RP Repeater card


• Up to 64 points (Repeater or Mimic panel)
• RS485 – 1000meters
• Support Total 200 drawings, 30.000 points

• GSTGMC-up to 8 users
• Required P-9935
•RS232- 15 meters

40
www.gst.com.cn
Panels Networking

41
Panels Networking

Network

⚫ Fire resistance cable, Min. 1.0mm2


⚫ 1.5sqmm UTP cable is recommended.
⚫ 1200 meters total distance for RS485 network Class B connection
⚫ 1200 meters distance between two panels for RS485 network Class A
connection
⚫ 3500 meters distance for each branch of CAN network.

42
Panels Networking

RS485 Class A Network •Maximum 32 FACP

RS 232 Card

Network Card RS 485 Network Card RS 485


(P-9945A) (P-9940A)

Length between panels1.2 Km (max)

Built-in Network Card RS 485


Network Card RS 485 (P-9940A)
(P-9940A)

43
Panels Networking

CAN Class A Network •Maximum 99 FACP

RS 232 Card

CAN Network Card CAN Network Card


CAN Network Card
(P-9965A) (P-9960A)
(P-9960A)

Length between panels 3.5Km (max)

CAN Network Card


CAN Network Card (P-9960A)
(P-9965A)

44
Panels Networking

Maximum 240 FACP in whole network.


CAN Class B Network Maximum 112 FACP in each branch

P-9960 P-9960
P-9965
Total Cable Length 3.5 Km (max)

P-9965

CAN HUB
CAN100H-4/8/12/16
P-9960 P-9965 P-9965

P-9960
45
Panels Networking

•Maximum 32 FACP
Fiber Optic Network

RS485 Class B Fiber Optic Network

Fibre Optic
+ +
P-9940A P-9945A

(For Single-Mode-25KM)
Interface FIB485S01
Optic

Optic
Fibre

Fibre
(For Multi Mode -4.5km)
Interface FIB485M01

+ +
P-9940A P-9940A

46
www.gst.com.cn
Panels Networking

Fiber Optic Network •Maximum 32 FACP

RS485 Class A Fiber Optic Network


Fibre Optic
+ +
P-9940A P-9945A

(For Single-Mode-25KM)
Interface FIB485S01
Fibre Optic

Fibre Optic
(For Multi Mode -4.5km)
Interface FIB485M01

Fibre Optic
+ +
P-9940A P-9940A

47
Panels Networking

TCP/IP Network

+ +

P-9935 TCPIP + NPort5230


NPort5230 + P-9930TCP/IP

TCP/IP

+
+
NPort5230 + P-9930TCP/IP
P-9935 TCPIP + NPort5230

48
Product Overview

49
Initiating Device

Intelligent Sensor ⚫ 8-bit micro-processor


⚫ Sensitive Ultraviolet sensor that detects the UV rays
produced by a flame
⚫ Dust/Corrosion/Humidity resistant
⚫ Electronically addressed by handheld programmer
⚫ Detection distance :
⚫ Level I: 25m (default) ; Level II: 17m ; Level III: 12m.
I-9104
Intelligent Ultraviolet ⚫ <Fire for Testing: 2000g industry ethanol burning in a
Flame Detector container (dimension: 33cm×33cm×5cm )>

DZ-03
Standard Base
50
Detector

⚫ Advance digital communication


Digital Intelligent Sensor
⚫ Drift compensation, reject false alarm from environment
changing, dust accumulation and component aging.
⚫ Electrically addressed by handheld programmer
⚫ Built-in remote indicator output
⚫ Special LED blink under dirty
⚫ A2R Heat alarming
⚫ Typical Fixed Alarm Temperature:62℃
⚫ Magnetic test
DI-9101E
Intelligent Combination ⚫ LED blink could be optionally disabled
Heat Photoelectric Smoke ⚫ Detector store most recent 5 fire alarms and fault alarms,
Detector
as well as total number of alarms.
⚫ IP Rate: IP2X

DB-01 C-9314P
Standard Base Remote Indicator
51
Detector

⚫ Advance digital communication


Digital Intelligent Sensor
⚫ Drift compensation, reject false alarm from environment
changing, dust accumulation and component aging.
⚫ Electrically addressed by handheld programmer
⚫ Built-in remote indicator output
⚫ Special LED blink under dirty
⚫ LED blink could be optionally disabled
⚫ Magnetic test
⚫ Detector store most recent 5 fire alarms, and fault
alarms, as well as total number of alarms.
DI-9102E
Intelligent Photoelectric ⚫ IP Rate: IP2X
Smoke Detector

DB-01 C-9314P
Standard Base Remote Indicator
52
Detector

⚫ Advance digital communication


Digital Intelligent Sensor
⚫ A1R/A2S/BS Selectable(LPCB)
⚫ Typical Fixed Alarm Temperature:
A1: 58℃ A2:62℃ B:77℃
⚫ Electrically addressed by handheld programmer
⚫ Built-in remote indicator output
⚫ LED blink could be optionally disabled
⚫ Magnetic test
⚫ Detector store most recent 5 fire alarms, and fault

DI-9103E alarms, as well as total number of alarms.


Intelligent Rate of Rise ⚫ IP Rate: IP2X
and Fixed Temperature
Heat Detector

DB-01 C-9314P
Standard Base Remote Indicator
53
Initiating Device

Beam Detector

⚫ Infrared beam detector


⚫ Detection range 8 to 100 meters
⚫ Path width 7 meters each side
⚫ 1 to 4 reflectors for different path length
⚫ Standard EN54-12
⚫ Electronically addressed by programmer
⚫ Additional Fire and Fault dry contact relay output
⚫ 24VDC supply required

I-9105R
Reflective Beam Detector

54
Initiating Device

Manual Call Points ⚫ Semi-flush or Surface mounted


⚫ Standard EN54-11
⚫ Re-settable (non-breaking glass)
⚫ LED indicator
⚫ Electronically addressed by handheld programmer
⚫ Friendly installation and test
⚫ Optional flipping plastic cover (D-92FC)
⚫ Optional weatherproof box(D-92WPB)
⚫ Optional back box for surface mount
DI-9204E
Digital manual Call Point

D-92FC D-92WPB
Protective Flip Cover Waterproof Box 55
Notification Device

I-9401N Sounder Strobe

⚫ Addressable combined flashing high intensity LED


beacon and sounder
⚫ Sound pressure level 95db@1M
⚫ external 24VDC required
⚫ Electronically addressed by handheld programmer
⚫ Easy installation and connection

56
Notification Device

I-9403 Sounder Strobe ⚫ 16 selectable tone


⚫ High sound level
⚫ Low/high power consumption modes
⚫ Loop powered or external 24VDC
⚫ Max. 30 pieces per loop when powered by loop
⚫ High intensity LED cluster
⚫ Programmable evacuate only or alert/evacuate mode
⚫ Standard EN54-3
⚫ Electronically addressed by handheld programmer
⚫ Easy installation and connection

C-94DB
Optional deep base for I-9403

57
Notification Device

I-9404 Intelligent Sounder ⚫ 16 selectable tone


⚫ High sound level
⚫ Low/high power consumption modes
⚫ Loop powered or external 24VDC
⚫ Max. 30 pieces per loop when powered by loop
⚫ Programmable evacuate only or alert/evacuate mode
⚫ Standard EN54-3
⚫ Electronically addressed by handheld programmer
⚫ Easy installation and connection

C-94DB
Optional deep base for I-9404

58
Notification Device

DI-9405 Addressable ⚫ “sandwich” structure


Sounder Base ⚫ Termination suitable for “DI” range detectors
⚫ Loop powered
⚫ Maximum 30 pieces per loop
⚫ Three working modes settable (Mode I, II, III,
and the latter two available with pre-alarm state).
⚫ 16 tones of sound.
⚫ Electronically addressed. The address and
tones can be modified in field.
⚫ Tone 14 and 16 are certified by EN54-3.
⚫ IP Rate: IP21C

59
Notification Device

DI-9406 Addressable
Sounder Beacon Base ⚫ “sandwich” structure
⚫ Termination suitable for “DI” range detectors
⚫ 16 selectable tone
⚫ Loop powered
⚫ Maximum 30 pieces per loop
⚫ Three working modes settable (Mode I, II, III, and
the latter two available with pre-alarm state).
⚫ 16 tones of sound and bright flashing light.
⚫ Electronically addressed. The address and tones
can be modified in field.
⚫ Tone 14 and 16 are certified by EN54-3.
⚫ IP Rate: IP21C

60
Isolator

Loop Isolator Base

⚫ Termination suitable for “DI” range detectors


⚫ Isolates faulty part of the loop in case short circuit
⚫ Auto resume when trouble removed
⚫ LED status indicator
⚫ Not occupy loop address
⚫ Maximum 128 pcs per loop
⚫ IP Rate: IP33 With Cover / IP22 Without Cover

DC-9504E
Base Mount Short Circuit Isolator

61
Module

⚫ Din-Rail Mounted or Surface mounted


⚫ Loop Powered
⚫ Low Power consumption
Standby loop current: ≤0.26mA
Active loop current: ≤0.5mA
⚫ Electronically addressed by handheld programmer
⚫ LED status indication for fault or activation
⚫ Programmable N/O or N/C dry contact input
⚫ Cable monitored
⚫ Standards:UL864
⚫ IP Rate: IP30

DI-9300E ⚫ Dimension:78x45.3x28.4mm
Digital Single Input Module

62
Module

⚫ Din-Rail Mounted or Surface mounted


⚫ Loop Powered
⚫ Low Power consumption
Standby loop current: ≤0.26mA
Active loop current: ≤0.7mA
⚫ Electronically addressed by handheld programmer
⚫ LED status indication for fault or activation
⚫ N/O or N/C dry contact output (30VDC@2A)
⚫ Programmable taken 1 address (monitor and control
one equipment) or 2 individual address (monitor and
control different equipment)
DI-9301E
Digital Single Input / Output ⚫ IP Rate: IP30
Module ⚫ Dimension: 85.3x78x30.6 mm

63
Module

⚫ Din-Rail Mounted or Surface mounted


⚫ Low Power consumption,
Standby loop current: ≤0.26mA
Active loop current: ≤0.5mA
⚫ Maximum Output Load:2A @ 30VDC,0.35PF
⚫ Electronically addressed by handheld programmer
⚫ LED status indication for fault or activation
⚫ Provide 24V output with cable monitoring ( external
24V input needed)
⚫ Interface with GST Voice alarm system connect to
DI-9305E field speakers
Digital Single Riser
⚫ Relay capacity: 30VDC 2A / 125VAC 0.5A
Output Module
⚫ IP Rate: IP30
⚫ Dimension: 85.3x78x30.6 mm

64
Module

⚫ Din-Rail Mounted or Surface mounted


⚫ Low Power consumption
Standby loop current: ≤0.23mA
Active loop current: ≤0.25mA
Standby external 24V input current: ≤10mA
Active external 24V input current : ≤60mA
⚫ Interface with conventional fire devices
⚫ 24VDC required
⚫ Cable monitored
⚫ Electronically addressed by handheld programmer
DI-9319E ⚫ LED status indication for fault or alarm condition
Digital Zone Monitor Module ⚫ Provide on board NO/NC dry contact relay output , auto to
triggered by input circuit alarm signal
⚫ IP Rate: IP30
⚫ Dimension: 85.3x78x30.6 mm
65
Module

⚫ Din-Rail Mounted or Surface mounted


⚫ Low Power consumption
Standby loop current: ≤0.15mA
Active loop current: ≤1.5mA
⚫ Isolates faulty part of the loop in case short
circuit
⚫ Auto resume when trouble removed
⚫ LED status indicator
⚫ Not occupy loop address
⚫ Maximum 128 pcs per loop
⚫ IP Rate: IP30
DC-9503E ⚫ Dimension:78x45.3x28.4mm
Loop Isolator

66
Programmer

Handheld Programmer

⚫ Set address to loop devices


⚫ Change parameter setting of loop device
⚫ Program graphic repeater panel LEDs

P-9910B Programmer

67
Commissioning Tool

• Small and Exquisite with large LCD screen


• Portable and easy carry
• Register loop devices, change parameters ( replacing P-9910B)
• Loop devices checking, type, quantity, address, status etc.
• Single device test, group devices test
• Duplicated address checking
• Device functional test: start/stop module outputs, start/stop
sounders, On/Off devices status indicators etc.

P-9920 Commisioning Tool

68
Power Supply

Intelligent Power Supply Unit

PSU24-5/5A 5A Power Supply Unit

PSU24-10/10A 10A Power Supply Unit

⚫ Indication of output voltage, output current, main's


fault, battery fault, output fault and charger fault
⚫ 24VDC power unit for high consumption devices
⚫ Integrated battery charger

69
Repeater Panel

GST-852RP Passive Repeater Panel

⚫ Compatible with all GST intelligent fire alarm


control panel
⚫ Fire Event Display
⚫ Local Sounder mute and Scroll alarm buttons
⚫ Connect to RS485 repeater loop

70
Repeater Panel

GST-NRP00 Network Repeater Panel

⚫ Display network message (Fire, Plant and Fault)


⚫ Achieve remote control of systems
⚫ Password protected
⚫ Connect in GST panel network

Note: Optional network card (P-9940A or P-9960A)


need ordered separate and installed on site

71
Repeater Panel

GST-8903 –A1/A2/A3 Graphic Repeater Panel

⚫ Up to 100 LED per module


⚫ Custom graphical layout
⚫ Display individual points and zone wise fire
and fault signal
⚫ Display individual points action signal.
⚫ Connect to RS485 repeater loop (can be
mixed with GST852RP)

72
Graphic Station

GST-GMC Graphic Monitor Center

⚫ Display message (Fire, Fault, Action, Disable)


⚫ Remote full control and monitor of systems
⚫ Multi-level Password protected
⚫ Historic data of all the system events
⚫ Clock synchronization with panels
⚫ Up to 8 users plus the server in a Network
⚫ Connect with panel through RS232 cable
⚫ Support Total 200 drawings, 30.000 points

73
Intrinsically Safe
&
Explosion Proof Products
Intrinsically Safe Detector

DC-9101(IS) DC-9102(IS) DC-9103(IS)


Intrinsically Safe Intrinsically Safe Intrinsically Safe
Conventional Combination Conventional Conventional Rate of Rise
Heat Photoelectric Smoke Photoelectric Smoke and Fixed Temperature Heat
Detector Detector Detector

• Applicable to zone 1 and zone 2 of areas


• with explosion-proof requirement in petroleum and chemical industries

75
Intrinsically Safe Initiating Device

⚫ Reusable button, can be reset manually by special key;


⚫ Plug-in structure.
⚫ Explosion-proof Mark: Exib ⅡCT6
⚫ IP43

DC-9202(IS)
Intrinsically Safe
Conventional Manual Call Point

76
Intrinsically Safe Notification Device

DC-9404(IS)
DC-9404(IS)
Intrinsically Safe Conventional Sounder
Intrinsically Safe Conventional Sounder

• Sound level: 85dB~115dB


• Strobe: Flashing Frequency: 1.4×(1±20%)Hz
• Tone Modification Period:0.7s±20%
• Explosion-proof Mark: Exib ⅡCT6
• IP33

77
Intrinsically Safe Module

• Built-in safety barrier, connect Intrinsically Safe


devices into GST intelligent system.
• Electrically addressing,1 address
• Operating Voltage :Loop voltage:24V
Power voltage:24VDC
• Loop Current : Standby current≤0.5mA;
Alarm current≤5mA
I-9332/I-9333 • Safety Barrier Parameters:
Flame Proof Zone
U0=28V, I0=93mA,
Monitor Interface
L0=4mH, C0=0.083F
• IP65

78
Explosion Proof Detector

⚫ Addressable mode and conventional working mode


optional
⚫ Dust-proof, damp-proof and corrosion-proof.
⚫ Detection Distance : 25m for Level I, 17m for Level II and
12m for Level III.
⚫ IP66
⚫ -20℃~+60℃ ambient, ≤95%RH , non-condensing
DI-9104Exd ⚫ Ex & ATEX
Digital Flame Proof
UV Flame Detector

79
Explosion Proof Detector

⚫ Addressable and Conventional mode optional


⚫ Two sensitivity levels can be set in field
⚫ Maximum monitoring area: 14×100=1400m2
⚫ Maximum width: 14m
⚫ Length of Optical Pathway: 8m~100m
⚫ IP66
⚫ -20℃~+40℃ ambient, ≤95%RH , non-condensing
D-9105RExd ⚫ Ex
Digital Flame Proof
Reflective Beam Detector

80
Explosion Proof Detector

⚫ Addressable mode and conventional working


mode optional
⚫ Dual-band infrared light detection
⚫ Detection Distance:
⚫ Sensitivity Level I: 25m (furthest)
⚫ Sensitivity Level II: 17m
⚫ Sensitivity Level III: 12m
⚫ IP66, -20℃~+55℃ ambient, ≤95%RH , non-
D-9107RExd condensing
Digital Flame Proof Dual
IR Flame Detector ⚫ Ex & ATEX

81
Explosion Proof Initiating Device

⚫ Addressable mode and conventional working


mode optional
⚫ Reusable button, that can be reset manually;
⚫ Electrically addressed by handheld
programmer;
⚫ IP65, -40℃~+70℃ ambient, ≤95%RH , non-
condensing
DI-9204Exd
Digital Flame-proof Manual ⚫ Ex & ATEX
Call Point

82
THANK YOU

83