Rac CH 5.1
Rac CH 5.1
INSTITUTE OF TECHNOLOGY
HAWASSA UNIVERSITY
By: Million M.
AC System Design
2
AC System Design
• Design conditions are indoor and outdoor environmental conditions that are to be
expected at “design time”.
Comfort zone representing the optimal range with which at least 80% of the
building occupants are expected to express satisfaction.
• are the set of extreme outdoor conditions under which a heating or cooling
system must be able to maintain a building at the indoor design conditions
The ambient temperature and moisture content vary from hour-to-hour and
from day-to-day and from place-to-place.
• To answer this question, we need to know what the weather will be like in the
future.
• But even the best weather forecasters cannot help us with that.
• Therefore, we turn to the past instead of the future and bet that the past
weather data averaged over several years will be representative of a typical year
in the future.
• Meteorological data is available in the form of mean daily or monthly maximum
and minimum temperatures and corresponding relative humidity or wet bulb
temperature.
Summer
• Similarly, It is not economical to design a winter air conditioning for the worst
condition on record as this would give rise to very high heating
capacities.(December, January, and February)
• it is recommended that the outdoor design conditions for winter be chosen based
on the values of dry bulb temperature that is equaled or exceeded 99.6, 99.0, or
97.5 % of total hours.
Critical applications such as health care facilities and certain process industries may
require the more stringent 99.6 percent level.
Outdoor winter Design Conditions for some city’s ,Ethiopia
• In the absence of any special requirements, Design condition For comfort
cooling, use of the 2.5% occurrence and for heating use of 97.5% values
are recommended. That is,
The heating system will provide thermal comfort 97.5 percent of the time
but may fail to do so during 2.5 percent of the time
For example,
The 97.5 percent winter design temperature for Dire Dawa, is 12.8oC, and thus the
temperatures in Dire Dawa may fall below 12.8oC about 2.5 percent of the time
during winter months in a typical year.
1. Determine the outdoor design conditions for Addis Ababa, for summer
for the 2.5 percent level and for winter for the 97.5 percent and 99
percent levels.
Heating or Cooling load calculations
• Heating or Cooling loads of a building represent the heat that must be supplied
to or removed from the interior of a building to maintain it at the desired
conditions.
• The cooling load experienced by a building varies in magnitude from zero (no
cooling required) to a maximum value.
• There are four related but distinct heat flow rates, in the context of air
conditioning analyses each of which varies with time. These are:
Space heat gain: is the rate at which heat is transferred to and/or generated
in a space at a given time.
Space cooling rate: is the rate at which heat must be removed to maintain
space air temperature at a constant value.
Space heat extraction rate: is the rate at which heat is removed from the
conditioned space by the cooling and dehumidifying equipment.
Cooling coil load: is the rate at which energy is removed at the cooling coil
which serves one or more conditioned spaces in any central air-conditioning
system.
• The total building cooling load consists of
• Also the total cooling load on any building consists of both sensible as well as
latent load components.
2. The load on the building due to solar radiation is estimated for clear sky
conditions.
3. The building occupancy is assumed to be at full design capacity.
Orientation
Size and shape
Construction material
Windows, doors, openings
Surrounding conditions
Ceiling
Occupants (activity, number, duration)
Appliances (power, usage)
Air leakage (infiltration or exfiltration)
Lighting
Cooling load calculation method
• This is the most complex of the methods proposed by ASHRAE and requires the
use of a computer program or advanced spreadsheet.
• This method is derived from the TFM method and uses tabulated data to simplify
the calculation process.
• The method can be fairly easily transferred into simple spreadsheet programs
but has some limitations due to the use of tabulated data.
Rules of thumb
• They are useful in preliminary estimation of the equipment size and cost.
The heat gain is latent when moisture is added/ removed to the space.
Estimation of external loads
Heat transfer through opaque surfaces
• The heat transfer rate through opaque surfaces such as walls, roof, floor,
doors etc. is given by
D-Type wall = 100-mm face brick with 200-mm concrete block and interior
finish
• The above tables are valid for
• For inside and average outside temperatures (Ti and Tavg) other than the above,
the following adjustment has to be made to CLTD:
• An air conditioned room is surrounded by other air conditioned rooms, with all
of them at the same temperature, the CLTD values of the walls of the interior
room will be zero.
Heat transfer through fenestration:
• The heat transfer due to solar radiation through the window is given:
𝑸𝒔,𝒊𝒏𝒇 = 𝒎𝒔 𝑪𝒑 𝒎 𝑻 −𝑻 = 𝑽𝒐𝝆𝒐𝑪𝒑 𝒎 𝑻 −𝑻 _
, 𝒐 𝒊 , 𝒐 𝒊
• The internal cooling load due to occupants consists of both sensible and latent
heat components.
𝒈𝒂𝒊𝒏
𝑸𝒔,𝒐𝒄𝒄𝒖𝒑𝒂𝒏𝒕 = (𝑵𝒐. 𝒐𝒇 𝒑𝒆𝒐𝒑𝒍𝒆)(𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒑𝒆𝒓𝒔𝒐𝒏). 𝑪𝑳𝑭
• The value of Cooling Load Factor (CLF) for occupants depends on the total hours
spent in the conditioned space and type of the building.
• The latent heat gain due to occupants is given by:
𝒈𝒂𝒊𝒏
𝑸𝒍,𝒐𝒄𝒄𝒖𝒑𝒂𝒏𝒕 = (𝑵𝒐. 𝒐𝒇 𝒑𝒆𝒐𝒑𝒍𝒆)(𝑳𝒂𝒕𝒆𝒏𝒕 𝒉𝒆𝒂𝒕 𝒑𝒆𝒓𝒔𝒐𝒏)
Load due to lighting
• For any lamps that are installed but are not switched on at
the time at which load calculations are performed.
• The equipment and appliances used in the conditioned space may add both
sensible as well as latent loads to the conditioned space.
• The installed wattage and usage factor depend on the type of the appliance or
equipment.
• The CLF values are available in the form of tables in ASHARE handbooks.
• The latent load due to appliances is given by:
𝑸𝒔,𝒓 𝑸𝒔,𝒓
𝑹𝑺𝑯𝑭 = =
𝑸𝒕,𝒓 𝑸𝒔,𝒓 + 𝑸𝒍,𝒓
An air conditioned room that stands on a well ventilated basement
measures 3 m wide, 3 m high and 6 m deep. One of the two 3 m walls
faces west and contains a double glazed glass window of size 1.5 m by 1.5
m, mounted flush with the wall with no external shading. There are no heat
gains through the walls other than the one facing west. Calculate the
sensible, latent and total heat gains on the room, room sensible heat factor
from the following information.