Analog Input Module SM 331 AI 8 X RTD X 24 Bit
Analog Input Module SM 331 AI 8 X RTD X 24 Bit
SIMATIC S7-300
X4
Analog Input Module SM 331; AI 8RTD24 Bit Release 5 6
Additional Assistance
For assistance in answering technical questions, for training on this product, or for
ordering, contact your Siemens distributor or sales office.
Order No.
6ES7 331-7PF00-0AB0
Characteristic Features
The analog input module SM 331; AI 8RTD24 Bit has the following
characteristic features:
8 differential inputs for resistance thermometers (RTD) in 4 channel groups
Measured-value resolution 23 Bit + sign (independent of integration time)
Fast update mode for up to 4 channels
Arbitrary RTD type selection per channel group
Programmable diagnostics
Programmable diagnostic interrupt
Eight channels with limit monitoring
Programmable limit interrupt
Programmable end of cycle interrupt
Galvanic isolation >500V to CPU
Special Feature
The analog input module SM 331; AI 8RTD24 Bit can only be used in the
ET200M distributed I/O configuration with the following versions of the IM153 (or
later)
IM153-1 6ES7 153-1AA03-0XB0 V.1
IM153-2 6ES7 153-2AA02-0XB0 V.5
6ES7 153-2AB01-0XB0 V.4
Note
The analog input module SM 331; AI 8RTD24 Bit can only be used with S7
PROFIBUS Masters.
1 L M 21 L+
2 22
M0+ M4+
3 ADC ADC 23
M0– DC M4–
4 to 24
CH0 CH4
Ic0+ DC Ic4+
5 25
Ic0– Ic4–
6 26
M1+ 7 27 M5+
M1– M5–
8 28
CH1 Ic5+ CH5
Ic1+ 9 29
Ic1– DAC DAC
10 Ic5–
30
M2+ M6+
11 31
M2– ADC ADC M6–
12 32
CH2 CH6
Ic2+ Logic Ic6+
13 and 33
Ic2– back Ic6–
14 34
plane
M3+ bus M7+
15 interface 35
M3– 16 36 M7–
CH3 CH7
Ic3+ Ic7+
17 37
Ic3– Ic7–
18 DAC DAC 38
19 39
20 40 M
Characteristic linearization
For RTD Resistance Pt100, Pt200, Pt500
Temperature Detector Pt1000, Ni100,
Ni120, Ni200, Ni500,
Ni1000, Cu10
(standard and
climatic range)
Note1: Resistance test for 3-wire measurments is performed once every 5 minutes.
Note2: Wirebreak test for 4-ch H/W filtering mode is preformed once every 3 seconds.
Parameter Assignment
The analog input module SM 331; AI 8RTD24 Bit is set:
With STEP 7 (see the STEP 7 User Manual) or
In the user program by means of SFCs (see the STEP 7 System and Standard
Functions Reference Manual)
Default Setting
The analog input module SM 331; AI 8RTD24 Bit has default settings for
operating mode, measuring type, diagnostics, interrupts, etc., (see Table 1).
These default settings apply, if you have not re-initialized the module with STEP 7.
Table 1 Parameters and Default Settings for the Analog Input Module
SM 331 AI8 x RTD x 24 Bit.
Measurement
Interference frequency 400 Hz; 60 Hz; 50 Hz Dynamic Channel
suppression 50 Hz group
Measurement type deactivated RTD–4W Dynamic Channel
R–4W Resistance group
(4-wire connection)
R–3W Resistance
(3-wire connection)
RTD-4W Thermal
resistance (linear,
4-wire-connection)
RTD-3W Thermal
resistance (linear,
3-wire-connection)
Measuring Range For the settable PT100Ω Cl
measuring ranges .003850
of the input
channels, please
refer to Table 17
and Table 18.
Operating Modes
The analog input module SM 331; AI 8RTD24 Bit operates in the following
modes:
8 Channel Hardware Filtering
8 Channel Software Filtering
4 Channel Hardware Filtering
Channel Isolation
If you configure the analog input module SM 331; AI 8RTD24 Bit for four
channels, with one channel connected in each group, the maximum isolation is 500
VAC. If you configure more than four channels, the common mode withstand
voltage between two channels in a group is 120 VAC.
Cycle
Time
Cycle
Time
Cycle
Ch0 CH2 CH4 CH6 Time
Measuring Methods
You can set the following measuring methods on the analog input module
SM 331; AI 8RTD 24 Bit:
RTD 4-wire measurement
RTD 3-wire measurement
Resistance 4-wire measurement
Resistance 3-wire measurement
Use the STEP 7 tool on the analog input module to make the necessary settings.
See Section 4.3.4 of the S7-300 Installation and Hardware Manual for more
information about these settings.
Measuring Ranges
Table 6 through table 12 lists the measuring ranges you can use with the analog
input module. Use STEP 7 to select the desired measuring ranges.
Wire-Break Check
The wire-break check is a module software function that is provided for all module
modes. The process for detecting a wire-break is to reduce by half the excitation
current for the given sensor and to verify that the resulting value is within nominal
limits of the prior value measured. Since the wire-break value is not reported to the
CPU, the module cycle time is doubled for the 8 Channel hardware and software
filtering mode, regardless of the number of channels with wire-break enabled.
When operating in the 4 channel hardware filtering mode, the reduction in
excitation current is performed once every three seconds, or once every 30 input
channel scans. However, there is a break in the input data when performing
wire-break detection. Since the reduction in excitation current basically is a step
function to the module input, the ADCs digital filter requires 85ms to settle and
report valid data. With a return to full excitation current, the total break in the input
data is 170 ms.
Standard-
Pt 100, Pt 200, Pt 500,
Pt 1000, Ni 100,
Ni 120, Ni 200, Ni 500,
Ni 1000, Cu 10
Resistance- Table 6 shows the digitized analog 150
4-Wire/3-Wire values in the resistance measuring 300
range. 600
Short to M or L
If you short an input channel to M or L, no damage will occur to the module.
The channel continues to report valid data and no diagnostics are reported.
Wiring Diagrams
Figure 5 shows the wiring diagrams for 4-wire and 3-wire sensor elements. When
you use a 3-wire sensor, ensure you insert the jumper between M+ and Ic+.
Incorrect wiring results in unpredictable module behavior.
M+
M+ Jumper M+ to Ic+
M–
M–
Ic+ Ic+
Ic– Ic–
Introduction
The tables in this section contain the digitized analog values for the various
measuring ranges of the analog input module. See table 6 through table 12.
Table 9 Standard Temperature Range for Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000
Table 10 Climate Temperature Range for Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000
Modifiable Parameters
You can change the parameters of record 1 and/or record 128 and pass them to
the AI 8RTD24 bit module using SFC 55. This does not change the
parameters set on the CPU. You cannot change the S7-300 parameters of record
0 in the user program.
The following section shows an overview of the parameters that are stored in
records 0, 1, and 128 for the AI 8RTD24 bit module.
Parameters
Table 14 contains all the parameters that you can set for the Analog Input Module
SM 331; AI 8RTD24 bit. The comparison shows:
Parameters you can change using STEP 7.
Parameters you can change using SFC 55 “WR_PARM”.
The parameters you set using STEP 7 can also be transferred to the module using
SFCs 56 and 57.
Table 14 Parameters for the Analog Input Module SM 331; AI 8RTD24 bit
7 6 5 4 3 2 1 0 Bit number
Byte 0
Celsius / Fahrenheit
Diagnostics enable
Limit value interrupt enable
Byte 1 Unused
Byte 2 Unused
Byte 3 Unused
Byte 4 Unused
Byte 5 Unused
Byte 6 Unused
Byte 7 Unused
Byte 8 Unused
Byte 9 Unused
Byte 10 Unused
Byte 11 Unused
Byte 12 Unused
Byte 13 Unused
7 6 5 4 3 2 1 0 Bit number
Module Mode (See Table 15)
Byte 0
Interference frequency
Byte 1 suppression
Channel group 0
Channel group 1
(See Table 16)
Channel group 2
Channel group 3
Byte 2
Byte 3
Byte 6
Byte 7
Figure 7 Data Record 128 for Parameters of the Analog Input Module
SM 331; AI 8RTD24 bit
Byte 9
Byte 10
Byte 11
Byte 12
Byte 13
Figure 6 Data Record 128 for Parameters of the Analog Input Module
SM 331; AI 8RTD24 bit (continued)
Figure 6 Data Record 128 for Parameters of the Analog Input Module
SM 331; AI 8RTD24 bit (continued)
The representation of the limit values matches the analog value representation.
Observe the range limits when setting the limit values.
Table 15 Codes for the module modes of the Analog Input Module
SM 331; AI 8RTD24 bit
Table 16 Codes for the Interference Frequency Suppression of Analog Input Module
SM 331; AI 8RTD24 bit
Table 17 Codes fortheMeasuring Ranges ofthe Analog InputModule SM331: AI 8RTD24 Bit
Measurement Type Code Measurement Range Code
Deactivated 2#0000 Deactivated 2#0000
Resistor 4-Wire Connection 2#0100 150 Ω 2#0010
300 Ω 2#0100
600 Ω 2#0110
Resistor 3-Wire Connection 2#0101 150 Ω 2#0010
300 Ω 2#0100
600 Ω 2#0110
Resistance-Type Thermo- 2#1000 Pt 100 Climate Range 2#00000000
meter + linearization 4-Wire Ni 100 Climate Range 2#00000001
Connection Pt 100 Standard Range 2#00000010
Ni 100 Standard Range 2#00000011
Pt 500 Standard Range 2#00000100
Pt 1000 Standard Range 2#00000101
Ni 1000 Standard Range 2#00000110
Pt 200 Climate Range 2#00000111
Pt 500 Climate Range 2#00001000
Pt 1000 Climate Range 2#00001001
Ni 1000 Climate Range 2#00001010
Pt 200 Standard Range 2#00001011
Ni 120 Standard Range 2#00001100
Ni 120 Climate Range 2#00001101
Cu 10 Climate Range 2#00001110
Cu 10 Standard Range 2#00001111
Ni 200 Standard Range 2#00010000
Ni 200 Climate Range 2#00010001
Ni 500 Standard Range 2#00010010
Ni 500 Climate Range 2#00010011
Table 18 Codes for the Alpha Selection of the Analog Input Module
SM 331; AI8 RTD24 Bit
Table 19 Codes for the Smoothing Selection of the Analog Input Module
SM 331; AI 8 RTD24 Bit