Protective Relays
Protective Relays
Introduction
• In a power system consisting of generators,
transformers, transmission and distribution
circuits, it is inevitable that sooner or later
some failure will occur somewhere in the
system. When a failure occurs on any part of
the system, it must be quickly detected and
disconnected from the system.
Introduction
• The proper operation of the power system requires an
efficient, reliable and fast acting protection scheme, which
basically consists of protective relays and switching devices.
• A protective relay, acting as a brain behind the whole system,
senses the fault, locates it, and sends a command or signal to
appropriate circuit breaker to isolate only the faulty section,
thus keeping the rest of the healthy system functional.
• It detects abnormal conditions on a power system by
constantly monitoring the electrical quantities of the system,
which are different under normal and abnormal (fault)
conditions.
• The basic electrical quantities which are likely to change
during abnormal conditions are current , voltage, phase angle
(direction) and frequency.
Relay operation
Fundamental requirements of relaying
• Selectivity
• Speed
• Sensitivity
• Reliability
• Simplicity
• Economy
Classification of Relays
• In a power system control and protection
schemes, various types of relays are used
which can be categorized as follows:
– According to functions
– According to construction
– According to speed of operation
– According to their generation of development
– According to the method of connection
– According to the method of action
According to functions
• Relays can be divided into three classes according to
the function, they are;
– Main relay: These relays operate according to the
information received from the power system i.e. they
operate when there is a change in the actuating quantity
which may be current, voltage or power.
– Auxiliary Relays: These relays operate after the operation
of main relays and are used to perform some auxiliary
functions such as introducing time delay for the operation
of the breaker.
– Signal Relays: These are the relays used to indicate the
operation of main relays. It is also used to energize a signal
or an alarm circuit to make the operators alert to take the
necessary actions immediately.
According to construction
• Electromagnetic relays
– Attracted armature relays
– Induction relays
• Thermal relays
Attracted armature relays
• Attracted armature relays are the
simplest type which respond to
ac as well as dc.
• These relays operate through an
armature which is attracted to an
electromagnet or through a
plunger which is drawn into a
solenoid.
• All these relays use the same
electromagnetic attraction
principle for their operation.
• The electromagnetic force
exerted on the moving element
i.e. the armature or plunger, is
proportional to the square of the
flux in the air gap or the square
of the current.
• In dc relays this force is constant.
Cont…
• The following are the different types of
construction of attracted armature relays.
– Hinged armature type
– Plunger type
– Balanced beam type
– Polarised moving-iron type
– Reed type
Hinged armature type
Hinged armature type
cont
• The coil is energized by an operating quantity
proportional to the system current or voltage.
• The attractive force increases as the armature
approaches the pole of the electromagnet.
• This type of relay is used for the protection of
small machines, equipment etc. It is also used
for auxiliary relays, such as indicating flags,
alarm relays etc.
Cont…
θ ɸ1
F2
F1
Force Produced in Induction Relay
The current produced by the flux interacts with other flux and vice versa.
The force produced are:
Force Produced in Induction Relay
As these forces are in opposition, the resultant force is
Where θ is the angle between φ1 and φ2. If two actuating currents M and
N produced is
Induction Relay
• There are two types of construction of induction disc
relays:
– The shaded pole type
– Watt hour meter type
• In shaded pole type construction, a C-shaped
electromagnet is used. One half of each pole of the
electromagnet is surrounded by a copper band known as
the shading ring.
• The shaded portion of the pole produces a flux which is
displaced in space and time with respect to the flux
produced by the unshaded portion of the pole.
• Two alternating fluxes displaced in space and time cut the
disc and produce eddy current in it.
• Torques are produced by the interaction of each flux with
the eddy current produced by the other flux. The resultant
torque causes the disc to rotate.
Shaded Pole Induction Disc Relay
Plug setting
(PS)
PSM 2 3.6 5 8 10 15 20
Time in sec 10 6 3.9 3.15 2.8 2.2 2.1
Solution;
Relay 1; Relay current = 2000/200 = 10 A
Pickup current =1x1=1A
PSM = 10/1 = 10
Time of operation of relay 1 corresponding to PSM 10 is 2.8 seconds
Actual operating time of relay 1 with TSM of 0.2
= 2.8 x 0.2 = 0.56 seconds
1. Current setting.
2. Fault current level.
3. Ratio of current transformer.
4. Time / PSM curve.
5. Time setting.
Calculation of Relay Operation Time
Step – 1
From CT ratio, we first see the rated secondary current of CT. Say the CT ratio is
100 / 1 A, i.e. secondary current of CT is 1 A.
Step – 2
From current setting we calculate the current of the relay. Say current setting of
the relay is 150% therefore pick up current of the relay is 1 × 150% = 1.5 A.
Step – 3
Now we have to calculate PSM for the specified faulty current level. For that, we
have to first divide primary faulty current by CT ratio to get relay faulty current. Say
the faulty current level is 1500 A, in the CT primary, hence secondary equivalent of
faulty current is 1500/(100/1) = 15 A
Step – 4
Now, after calculating PSM, we have to find out the total time of operation of the
relay from Time / PSM curve. From the curve, say we found the time of operation
of relay is 3 second for PSM = 10.
Step – 5
Finally that operating time of relay would be multiplied with time setting
multiplier, in order to get actual time of operation of relay. Hence say time setting
of the relay is 0.1.
Therefore actual time of operation of the relay for PSM 10, is 3 × 0.1 = 0.3 sec or
300 ms.
Buchholz Relay
Features:
• Intentional time delay is not provided for operation. The relay
contacts are closed immediately after the current in the relay coil
exceeds the operating value. Although there will be a short time
interval between the instant of pick up value and the closing of the
relay contacts, no intentional time delay is provided.
• This characteristic can be achieved with the help of the hinged
armature relay. This relay has a unique advantage of reducing the
time of operation to a minimum for faults very close to the source
where the fault current is the greatest.
• The instantaneous relay is effective where the impedance between
the relay and source is small.
Application:
• Such type of relay is used for controlling earth fault and other types
of circulating current protection.
Time current characteristics
Features:
• Definite time overcurrent relay operates after a predetermined
time when the current exceeds its pick-up value.
• The operating time is constant, irrespective of the magnitude of the
current above the pick up value.
• The desired definite operating time can be set with the help of an
intentional time delay mechanism provided in the relaying unit.
•
Application:
• Back up protection of distance relay of transmission line with time
delay.
• Back up protection to differential relay of power transformer with
time delay.
• Main protection to outgoing feeders and bus couplers with
adjustable time delay setting.
Inverse time overcurrent relay
Features:
• In this relay, the operating time is inversely
proportional to the fault current near pick-up value.
• The relay becomes considerably constant slightly above
the pickup value of the relay as shown in the figure.
• This is achieved by using a core of the electromagnet
which gets saturated for current slightly greater than
the pick-up current.
Application:
• The relay is used for the protection of the distribution
line.
Very Inverse Relay
Features:
• In such relay, the saturation of the current occurs at a
still later stage.
• The time-current characteristic is inverse over a greater
range and after saturation tends to the definite time.
• The relay is used in the places where there the
magnitude of the short-circuit current fall rapidly
because of the large distance from the source.
Application:
• Relays with very inverse time characteristic are
employed on feeders and long sub-transmission lines.
Extremely Inverse Relay
Features:
• The characteristic time of the relay is extremely large as compared
to the IDMT and the Very inverse relay.
• In this type of relay, the core saturation occurs at the very large
stage.
• The relay can operate instantly when the pickup value of the
current is more than the relay setting time. The relay provides
faster operation.
Application:
• This relay is used for protecting the cable, transformer, etc. It is
used for sensing the overheating of the machines.
• The inverse time relay is used in the distribution networks and the
power plants.
Time current characteristics
IDMT characteristics
Induction type overcurrent relay
Induction type overcurrent relay
There are two structures of the induction disc type overcurrent relay:
1. Shaded pole structure, and
2. Watt-hour meter structure.
• Most of the induction relays are of watt-hour meter structure. The
construction of this relay is similar to the watt-hour or the AC energy
meter.
• It consists of two electromagnets. The upper electromagnet carries two
windings; primary winding and the secondary winding.
• The advantage of this type of construction is that it can provide a larger
phase angle between the two fluxes and hence a higher torque.
• An important feature of this type of relay is that its operation can be
controlled by opening or closing the secondary winding.
• If the circuit is opened, no torque will be produced and thus the relay is
made inoperative.
Induction type overcurrent relay
• The relay has two electromagnets. The upper electromagnet has two
windings; one of these is primary and is connected to the secondary of a
CT in the line to be protected and is tapped at intervals. The tappings are
connected to a plug setting bridge by which the no. of turns in use can be
adjusted thereby giving the desired current setting.
• The plug bridge is usually arranged to give seven sections of tappings to
give overcurrent range from 50% to 200% in steps of 25%. If the relay is
required to response for earth faults the steps are arranged to a range from
10% to 70% or 20% to 80% in steps of 10%.
• The values assigned to each tap are expressed in terms of percentage of
full load rating of CT with which the relay is associated and represents and
value above which the disc commences to rotate and finally closes the trip
circuit.
• The pickup current equals the rated secondary current of CT multiplied by
current setting. For example suppose that an overcurrent relay having a
current setting of 150% is connected to a supply circuit through a CT of
500/5 A. The rated secondary current of CT is 5 A and therefore the pick-up
value will be 1.5 x 5 = 7.5 A.
• It means that with above current setting, the relay will actually operate for
a relay current equal to or greater than 7.5 A.
Induction type overcurrent relay
• The second winding is energized by induction from the primary and is connected
in series with the winding on the lower magnet. By this arrangement, the leakage
fluxes of upper and lower electromagnets sufficiently displaced in space and phase
to set up a rotational torque on the aluminium disc suspended between the two
magnets. This torque is controlled by the spiral spring or by a permanent magnet
brake on disc.
• The disc spindle carries a moving contact which bridges two fixed contacts (trip
circuit contacts) when the disc has rotated through a preset angle. The angle can
be set to any value between 0o and 360o. This adjustment is known as time setting
multiplier. The multiplier setting is generally in the form of an adjustable backstop
which decides the arc length through which the disc travels, by reducing the length
of travel the operating time is reduced.
• The time setting multiplier is calibrated from 0 to 1 in steps of 0.05. this figure do
not represent the actual operating time but are multiples to be used to convert
the time known from the relay name plate curve (time – PSM curve) into the
actual operating time. Thus if time setting is 0.2 and the operating time obtained
from the time – PSM curve of the relay is 5 seconds, then actual operating time of
the relay will be equal to 0.2 x 5 = 1 second.
• Since the time required to rotate the disc through a preset angle depends upon
the torque which varies as current in the primary circuit, therefore, more the
torque lesser will be the time required. So the relay has inverse time
characteristics.
Time graded protection
• Similarly, the time required to operate the relay OC4 must be less
than that required for OC3 and so on.
• This shows that the time setting required for these relays must be
graded. The time settings for relay OC1, OC2, OC3, OC4 and OC5
will be 2 sec, 1.5 sec, 1 sec, 0.5 sec and instantaneous respectively.
• It is also essential to have the time of operation dependent on the
severity of fault. For severe fault the time of operation should
automatically be less. This is achieved by using time limit fuses in
parallel with the trip coils. Its additional advantage is that the relay
will not operate under overload conditions of very short duration.
• The graded time lag relays when connected in series require that
their time current characteristics are similar in shape. In no case
they should cross each other at any point. From this point of view
induction type inverse definite minimum time (IDMT) relays are
most suitable. Their ratings provide complete discrimination under
all fault conditions and they are most widely used.
Time graded protection
Time graded protection
• Here, IA + IB = If.
• Now, IA is flowing through CB-A, IB is flowing through CB-P.
• As the direction of flow of CB-P is reversed it will trip
instantly. But CB-Q will not trip as flow of current (power) in
this circuit breaker is not reversed.
• As soon as CB-P is tripped, the fault current IB stops flowing
through feeder.
• IA still continues to flow even CB-P is tripped. Then because
of over current IA, CB-A will trip. In this way the faulty feeder
is isolated from system.
Differential Pilot Wire Protection
• This is simply a differential protection scheme applied to
feeders. Several differential schemes are applied for protection
of line but Merz Price Voltage balance system and Translay
Scheme are most popularly used.
Merz Price Balance System
• In this scheme of line protection, identical CT is connected to each
of the both ends of the line. The polarity of the CTs is same. The
secondary of these current transformer and operating coil of two
instantaneous relays are formed a closed loop as shown in the
figure. In the loop pilot wire is used to connect both CT secondary
and both relay coil as shown.
• When the system is under normal condition, there would not be
any current flowing through the loop as the secondary current of
one CT will cancel out secondary current of other CT.
• Now, if any fault occurs in the portion of the line between these
two CTs, the secondary current of one CT will no longer equal and
opposite of secondary current of other CT.
• Hence there would be a resultant circulating current in the loop.
Due to this circulating current, the coil of both relays will close the
trip circuit of associate circuit breaker. Hence, the faulty line will be
isolated from both ends.
Translay Scheme
• These type of relays are used in the feeder protection and the
scheme is called Translay scheme. In this scheme, two such
relays are employed at the two ends of feeder as shown in the
Fig.
Translay Scheme
• The secondaries of the two relays are connected to each other using pilot
wires. The connection is such that the voltages induced in the two
secondaries oppose each other. The copper coils are used to compensate
the effect of pilot wire capacitance currents and unbalance between two
currents transformers.
• Under normal operating conditions, the current at the two ends of the
feeder is same. The primaries of the two relays carry the same currents
inducing the same voltage in the secondaries. As these two voltages are in
opposition, no current flows through the two secondaries circuits and no
torque is exerted on the discs of both the relays.
• When the fault occurs, the currents at the two ends of the feeder are
different. Hence unequal voltages are induced in the secondaries. Hence
the circulating current flows in the secondary circuit causing torque to be
exerted on the disc of each relay. But as the secondaries are in opposition,
hence torque in one relay operates so as to close the trip circuit while in
other relay the torque just holds the movement in unoperated position.
The care is taken that at least one relay operates under the fault condition.
Translay Scheme
• It is convenient to incorporate
phase fault relays and earth fault
relay in a combined phase fault
and earth fault protection.
• The increase in current of phase
causes corresponding increase in
respective secondary currents.
• The secondary current flows
through respective relay units.
• Very often only two phase relays
are provided instead of three,
because in case of phase faults,
current in any at least two phases
must increase.
• Hence two relay units are
enough.
Earth fault protection with core balance current transformer
(Zero sequence ct)
• The unrestricted earth fault protection uses a residually connected earth fault
relay. It consists of three C.T.s, one in each phase. The secondary windings of three
C.T.s are connected in parallel. The earth fault relay is connected across the
secondaries which carries a residual current.
• When there is no fault, under normal conditions, vector sum of the three line
currents is zero. Hence the vector sum of the three secondary currents is also zero.
• So if Irs, Iys and Ibs C.T. secondary currents then under normal conditions we can
write,
Īrs+ Īys + Ībs = 0
• The earth fault relay is connected in such a way that the residual current flows
through the relay operating coil. Under normal condition, residual current is zero
so relay does not carry any current and is inoperative. However in presence of
earth fault condition, the balance gets disturbed and the residual current IRs is no
more zero. If this current is more than the pickup value of the earth fault relay, the
relay operates and opens the circuit breaker through tripping of of the trip circuit.
• In the scheme shown in the Fig. 1, the earth fault at any location near or away
from the location of C.T.s can cause the residual current. Hence the protected zone
is not definite. Such a scheme is hence called unrestricted earth fault protection.
Unrestricted earth fault protection
Differential protection
Introduction
• Differential protection is a method of protection in which an internal fault
is identified by comparing the electrical conditions at the terminals of the
electrical equipment to be protected. It is based on the fact that any
internal fault in an electrical equipment would cause the current entering
it, to be different from the leaving it.
• Differential protection is one of the most sensitive and effective methods
of protection of electrical equipment against internal faults. This principle
of protection is capable of detecting very small magnitudes of the
differential currents.
• Used in protection of generators, transformers, motors of large size, bus
zones, reactors, capacitors, etc.
• The differential protection is called unit protection because it is confined
to protection of a particular unit (equipment) of a power plant or
substation.
• “A differential relay is defined as the relay that operates when the phasor
difference of two or more similar electrical quantities exceeds a
predetermined value.”
Differential protection
Two CT’s are used having same ratio are connected on the either side of the
section to be protected. The secondaries of CT are connected in series, so they
carry induced currents in the same direction. Let current I is flowing through the
primary of CT towards the external fault. As the CT are identical, the secondary’s of
CT will carry equal currents. Due to the connection of relay, no current will flow
through the operating coil for the relay. Hence Relay will remain inoperative. So
relay cannot operate if there is an external fault.
Current differential relay
• Consider now that an internal fault occurs in between CT1 and CT2
• The current flows through the fault from both sides. The two secondary currents
through CTs are not equal. The current flowing through the relay coil is now I1 + I2.
This high current causes the relay to operate.
• It should be noted that the fault current need not always flow to the fault from
both sides. A flow on one side only or even some current flowing out of one side
while a large current entering the other side can cause differential relay to
operate. Thus the amount of current flowing through a relay coil depends upon
the way the fault is being fed.
Biased or percentage differential relay
• The percentage differential relay is defined as the
relay that operates on the phase difference of
two or more similar electrical quantities.
• It is the advanced form of differential protection
relay. The only difference between them is the
restraining coil.
• The percentage differential relay consists
restraining coil for overcoming the trouble arising
out of differences in the current ratio for the high
value of an external short circuit current.
Biased or percentage differential relay
• The percentage differential system consists of a restraining coil
connected in the pilot wire as shown in the figure below and the
current induced in both the CTs flows through it. The operating coil
places between the midpoint of the restraining coil.
• The restraining coil controls the sensitive characteristic of the relay. It
restricts the unwanted tripping of the transformer due to the
imbalance current. The restraining coil also restrains the harmonics in
the inrush current.
Working of Percentage Differential Relay
• The torque due to the restraining coil prevents the closing of the trip
circuit while the torque due to the operating coil tends to close the trip
circuit contacts. Under normal operating conditions and through load
condition the torque developed by the restraining coil is greater than
the operating coil torque. Thus the relay remains inoperative.
• When an internal fault occurs, the operating torque exceeds the
restraining torque then the trip circuit contacts are closed to open
the circuit breaker. The restraining torque may adjust by varying the
number of turns of the restraining coil.
• The differential current required to utilise this relay is a variable
quantity, due to the effect of the restraining coil.
• The differential current in the operating coil is proportional to (I1-I2),
and the restraining coil is proportional to (I1-I2)/2 as the operating
current is connected to the midpoint of the restraining coil. For
external faults both I1 and I2 increase and thereby the restraining
torque increase, which prevents the maloperation.
Balanced voltage differential protection
• The current differential relay is not suitable for the protection of the
feeders. For the protections of the feeders, the voltage balance
differential relays are used. In this arrangement, the two similar
current transformers are connected at either end of the system
element under protection using pilot wires.
• The relays are connected in series with the pilot wires, one at each
end. The relative polarity of the current transformers is such that
there is no current through the relay under normal operating
conditions and under fault conditions. The CTs used in such
protections should be such that they should induce voltages in the
secondary linearly with respect to the current. Since the magnitude
of the fault current is very large, so that the voltage should be a
linear function of such large currents, the CTs should be aired cored.
• When the fault occurs in the protected zone, the currents in the
two primaries will differ from one another, and so voltage induced
in the secondaries of the CTs will differ and circulating current will
flow through the operating coils of the relays. Thus the trip circuit
will be closed, and the circuit breaker will be open.
Balanced voltage differential protection
Setting of differential relay
• The circulating current differential relay has two principle settings namely,
- Setting of operating coil circuit.
- Setting of restraining coil circuit
• Setting of operating coil circuit (Basic setting). The percentage setting of
(Basic setting) of operating coil circuit is defined as the ratio:
• The -K3 is the spring effect of the relay. The V and I are the value of
the voltage and current. When the relay is in normal operating
condition, then the net torque of the relay becomes zero.
Applications
• Distance relays are used for providing the primary i.e. main
protection and backup protection for a.c. transmission and
distribution lines against the following faults,
– 1. Three phase faults
– 2. Phase to phase faults
– 3. Phase to earth fault.
Circulating Current Protection of Bus bar
• Each end of the line is provided with identical carrier current equipment
consisting of transmitter, receiver, line-tuning unit, master oscillator,
power amplifier, etc.
• In this system it is necessary to use a current of higher frequency in order
to be able to transmit current impulses from one end of the line to the
other. High frequency signals in the range of 50 kHz to 400 kHz commonly
known as the carrier, are transmitted over the conductors of the protected
line. To inject the carrier signal and to restrict it within protected section
of the line suitable coupling apparatus and line traps are used at both
ends of the protected section. Generally used in the lines above 110 kV.
The main elements of the carrier channel are;
a. transmitter b. receiver c. coupling equipment
d. line trap
• When a voltage of positive polarity is impressed on the control circuit of
transmitter, it generates a high frequency output voltage. This output
voltage is impressed between one phase conductor of the line and the
earth as shown in figure.
Carrier current protection