IEC Timers and IEC Counter For SIMATIC S7-1200

This document provides instructions for using single instances and multi-instances when programming a SIMATIC S7-1200 controller with TIA Portal. It explains instance data blocks and shows how to add IEC timers and counters to a program block. Learners will work through an example conveyor control program that uses a timer instance.

Uploaded by

RAJESH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
171 views33 pages

IEC Timers and IEC Counter For SIMATIC S7-1200

This document provides instructions for using single instances and multi-instances when programming a SIMATIC S7-1200 controller with TIA Portal. It explains instance data blocks and shows how to add IEC timers and counters to a program block. Learners will work through an example conveyor control program that uses a timer instance.

Uploaded by

RAJESH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 33

Learn-/Training Document

Siemens Automation Cooperates with Education


(SCE) | From Version V14 SP1

TIA Portal Module 031-300


IEC Timers and IEC Counters
Multi-instances for SIMATIC S7-1200

siemens.com/sce

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved.
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

Matching SCE Trainer Packages for these Learn-/Training Document


• SIMATIC S7-1200 AC/DC/RELAY (set of 6) "TIA Portal"
Order no.: 6ES7214-1BE30-4AB3
• SIMATIC S7-1200 DC/DC/DC (set of 6) "TIA Portal"
Order no.: 6ES7214-1AE30-4AB3
• Upgrade SIMATIC STEP 7 BASIC V14 SP1 (for S7-1200) (set of 6) "TIA Portal"
Order no.: 6ES7822-0AA04-4YE5

Note that these trainer packages are replaced with successor packages when necessary.
An overview of the currently available SCE packages is available at: siemens.com/sce/tp

Continued training
For regional Siemens SCE continued training, get in touch with your regional SCE contact
siemens.com/sce/contact

Additional information regarding SCE


siemens.com/sce

Information regarding use


The SCE Learn-/Training Document for the integrated automation solution Totally Integrated
Automation (TIA) was prepared for the program "Siemens Automation Cooperates with Education
(SCE)" specifically for training purposes for public educational facilities and R&D institutions.
Siemens AG does not guarantee the contents.

This document is to be used only for initial training on Siemens products/systems, which means it
can be copied in whole or part and given to those being trained for use within the scope of their
training. Circulation or copying this Learn-/Training Document and sharing its content is permitted
within public training and advanced training facilities for training purposes.

Exceptions require written consent from the Siemens AG contact person: Roland Scheuerer
[email protected].

Offenders will be held liable. All rights including translation are reserved, particularly if a patent is
granted or a utility model or design is registered.

Use for industrial customer courses is explicitly not permitted. We do not consent to commercial
use of the Learn-/Training Document.

We wish to thank the TU Dresden, particularly Prof. Dr.-Ing. Leon Urbas and the Michael Dziallas
Engineering Corporation and all other involved persons for their support during the preparation of
this Learn-/Training Document.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 2
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

Table of contents
1 Goal ................................................................................................................................................. 4
2 Prerequisite...................................................................................................................................... 4
3 Required hardware and software ...................................................................................................... 5
4 Theory ............................................................................................................................................. 6
4.1 Instances and multi-instances in SIMATIC S7-1200 ..................................................................6
4.1.1 Instance data blocks / Single instances .............................................................................7
4.1.2 Multi-instances ..................................................................................................................8
5 Task ............................................................................................................................................... 10
6 Planning......................................................................................................................................... 10
6.1 Automatic mode - Conveyor motor with time function .............................................................. 10
6.2 Technology diagram ............................................................................................................... 11
6.3 Reference list ......................................................................................................................... 12
7 Structured step-by-step instructions................................................................................................ 13
7.1 Retrieve an existing project ..................................................................................................... 13
7.2 Addition of an IEC timer TP to function block FB1 "MOTOR_AUTO" ....................................... 15
7.3 Update the block call in the organization block ........................................................................ 22
7.4 Save and compile the program ............................................................................................... 23
7.5 Download the program............................................................................................................24
7.6 Monitor program blocks ..........................................................................................................25
7.7 Archive the project .................................................................................................................. 27
7.8 Checklist................................................................................................................................. 28
8 Exercise ......................................................................................................................................... 29
8.1 Task – Exercise ...................................................................................................................... 29
8.2 Technology diagram ............................................................................................................... 29
8.3 Reference list ......................................................................................................................... 30
8.4 Planning ................................................................................................................................. 30
8.5 Checklist – Exercise ............................................................................................................... 31
9 Additional information ..................................................................................................................... 32

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 3
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

IEC Timers and IEC Counters Multi-


instances for SIMATIC S7-1200
1 Goal
In this chapter, you will become acquainted with the use of single instances and multi-instances
for programming of SIMATIC S7-1200 with the TIA Portal programming tool.
The module explains the various types of instance data blocks and shows step-by-step how to
add IEC timers and IEC counters to a program block.
The SIMATIC S7 controllers listed in Chapter 3 can be used.

2 Prerequisite
This chapter builds on the FB programming for SIMATIC S7 CPU1214C. For this chapter, you
can use the following project, for example:
031-200_FB-Programming_S7-1200….zap14

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 4
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

3 Required hardware and software


1 Engineering station: requirements include hardware and operating system
(for additional information, see Readme on the TIA Portal Installation DVDs)
2 SIMATIC STEP 7 Basic software in TIA Portal – as of V14 SP1
3 SIMATIC S7-1200 controller, e.g. CPU 1214C DC/DC/DC with ANALOG OUTPUT SB1232
signal board, 1 AO – Firmware as of V4.2.1
Note: The digital inputs should be fed out to a control panel.
4 Ethernet connection between engineering station and controller

2 SIMATIC STEP 7
Basic (TIA Portal) as of
1 Engineering Station V14 SP1

4 Ethernet connection

3 SIMATIC S7-1200 controller Control panel

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 5
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

4 Theory
4.1 Instances and multi-instances in SIMATIC S7-1200
The call of a function block is referred to as an instance. An instance is assigned to every call of
a function block and serves as a data memory. It stores the actual parameters and the static data
of the function block.
The tags declared in the function block determine the structure of the instance data block.

Use of single instances and multi-instances


You can assign instances as follows:

Call as a single instance:


– A separate instance data block for each instance of a function block

Call as a multi-instance:
– One instance data block for several instances of one or more function blocks

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 6
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

4.1.1 Instance data blocks / Single instances


The call of a function block that is assigned its own instance data block is called a single
instance.
If the function block was created according to the rules for library-compatible standard blocks, it
can also be called multiple times.
However, you must assign another instance data block for each call as a single instance.

Example of single instances:

The following figure shows the control of two motors using one function block FB10 and two
different data blocks:
The different data for the individual motors, such as speed, acceleration time and total operating
time, are saved in the instance data blocks DB10 and DB11.

OB1

Call of FC1 FC1


DB10
Call of FB10 FB10
with instance Instance DB for
DB10 for control Standard block second call with
of Motor 1 with motor data for Motor 1
program

DB11
Call of FB10 FB10
with instance Instance DB for
DB11 for control Standard block second call with
of Motor 2 with motor data for Motor 2
program

Note: Some commands, such as timers and counters, behave like function blocks. When these
are called, they also require an assigned memory area, e.g., in the form of an instance data
block.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 7
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

4.1.2 Multi-instances

You may want to limit the number of data blocks used for instances or this may be necessary due
to lack of memory in the utilized CPU.
If other function blocks, timers, counters, etc. that already exist are to be called in a function block
in your user program, you can call these other function blocks without separate (i.e. additional)
instance DBs.
Simply select ‘Multi-instance’ for the call options:

Notes: Multi-instances enable a called function block to store its data in the instance data block
of the calling function block.

In this case, the calling block must always be a function block.

This allows you to concentrate the instance data in one instance data block and thus make better
use of the number of DBs available.

Incidentally, this is always required when the calling block is to remain available for reuse as a
standard block.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 8
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

Example of multi-instances:
The following figure shows two calls of an IEC timer of type TP (pulse) within a function block.
The different data for the two counters is stored as different multi-instances in the instance data
block DB1 of the calling function block FB1.

OB1
DB1
Call of FB1 FB1
(Instance DB
with instance for FB1)
DB1 Call of IEC_Timer #Timer1
as multi-instance of type IEC_Timer
#Timer1
Static tag (Static)

#Timer1
Call of IEC_Timer IEC_Timer
as multi-instance #Timer2 #Timer2
#Timer2 IEC_Timer of type IEC_Timer
as multi-instance

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 9
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

5 Task
In this chapter, an IEC timer will be added to the function block from chapter "SCE_EN_031-200
FB Programming S7-1200".

6 Planning
The IEC timer is programmed as an addition to the MOTOR_AUTO [FB1] function block from the
"031-200_FB-Programming_S7-1200.zap13" project. This project must be retrieved in order to
now add the IEC timer TP (latching pulse). A multi-instance will be created as a memory for the
timer.

6.1 Automatic mode - Conveyor motor with time function


The Memory_automatic_start_stop is latched with Start but only if the reset conditions are not
present.
The Memory_automatic_start_stop is reset if Stop is present or safety shutoff is active or
automatic mode is not activated (manual mode).
The Conveyor_motor_automatic_mode output is activated when Memory_automatic_start_stop is
set, the enable conditions are met and Memory_conveyor_start_stop is set.
To save energy, the conveyor should only run when a part is present.
For this reason, the Memory_conveyor_start_stop is set when Sensor_chute_occupied signals a
part and reset when Sensor_end_of_conveyor produces a negative edge or safety shutoff is
active or automatic mode is not activated (manual mode).
Addition of time function:
Because the Sensor_end_of_conveyor is not able to be mounted directly at the end of the
conveyor, the Sensor_end_of_conveyor signal must be stretched.
To achieve this, a latching pulse will be inserted between Sensor_end_of_conveyor and the
negative edge detection.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 10
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

6.2 Technology diagram


Here, you see the technology diagram for the task.

Figure 1: Technology diagram

Figure 2: Control panel

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 11
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

6.3 Reference list


The following signals are needed as global operands for this task.

DI Type Identifier Function NC/NO


I 0.0 BOOL -A1 Return signal emergency stop ok NC
I 0.1 BOOL -K0 Main switch "ON" NO
Manual = 0
I 0.2 BOOL -S0 Mode selector manual (0)/ automatic (1)
Auto = 1

I 0.3 BOOL -S1 Pushbutton automatic start NO

I 0.4 BOOL -S2 Pushbutton automatic stop NC

I 0.5 BOOL -B1 Sensor cylinder M4 retracted NO


I 1.0 BOOL -B4 Sensor at chute occupied NO
I 1.3 BOOL -B7 Sensor part at end of conveyor NO

DO Type Identifier Function


Q 0.0 BOOL -Q1 Conveyor motor M1 forwards fixed speed

Legend for reference list

DI Digital Input DO Digital Output

AI Analog Input AO Analog Output

I Input Q Output

NC Normally Closed

NO Normally Open

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 12
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

7 Structured step-by-step instructions


You can find instructions on how to carry out planning below. If you already have a good
understanding of everything, it will be sufficient to focus on the numbered steps. Otherwise,
simply follow the detailed steps in the instructions.

7.1 Retrieve an existing project


→ Before we can expand the "MOTOR_AUTO [FB1]" function block, we must retrieve the "031-
200_FB-Programming_S7-1200.zap14" project from chapter "SCE_EN_031-200 FB
Programming S7-1200". To retrieve an existing project that has been archived, you must
select the relevant archive with → Project → Retrieve in the project view. Confirm your
selection with Open (→ Project → Retrieve → Select a .zap archive → 031-200_FB-
Programming_S7-1200.zap14 → Open).

→ The next step is to select the target directory where the retrieved project will be stored.
Confirm your selection with "OK".

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 13
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

→ Save the opened project under the name 031-300_IEC_Timers_Counters


(→ Project → Save as ... → 031-300_IEC_Timers_Counters → Save)

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 14
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

7.2 Addition of an IEC timer TP to function block FB1


"MOTOR_AUTO"
→ First, open the "MOTOR_AUTO [FB1]" function block with a double-click.

→ Insert another network at the beginning of the "MOTOR_AUTO [FB1]" function block by

selecting the → "block title" and clicking the → icon for "Insert network".

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 15
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

→ Add helpful information to the block comment and the network title of "Network 1:".

→ On the right side of your programming window, you will see the timer functions in the list of
instructions. Under → Basic instructions → Timer operations, find function (Generate
pulse) and use a drag & drop operation to move it to Network 1 (green line appears, mouse
pointer with + symbol).

(→ Instructions → Basic instructions → Timer operations → )

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 16
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

→ The timer function requires a memory. This memory is provided in this case within the
instance data block of the function block without creating a new instance data block. Select
the →"Multi-instance" option for this. Enter a name for the multi-instance and confirm with →
"OK". (→ Multi-instance → IEC_Timer_overrun → OK)

→ As a result, a tag structure of "Static" type suitable for TP Timer will be created in the
interface description.

Note: A multi-instance can only be used for programming within a function block because static
tags are only available there.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 17
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

→ Use drag & drop to move input parameter #Sensor_end_of_conveyor to <??.?> in front of
parameter "IN" of TP Timer so that this will be started at a positive edge at input
#Sensor_end_of_conveyor. The best way to select a parameter in the interface description is

by "grabbing" it at the blue symbol (→ Sensor_end_of_conveyor).

→ Enter the required pulse duration of 2 seconds in front of parameter "PT" (→2s ).

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 18
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

→ The entry of 2s is converted automatically to the IEC-Time format suitable for the IEC timer
and is shown as constant "T#2s".

→ Now move output "Q" from tag structure "IEC_Timer_overrun" onto input "CLK" of negative
edge "N_TRIG" in Network 2. This will replace the #Sensor_end_of_conveyor input tag
previously entered there and the conveyor will be stopped by a negative edge of the
IEC_Timer_overrun pulse.

(→ Network 2 → IEC_Timer_overrun→ Q → #Sensor_end_of_conveyor)

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 19
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

→ Do not forget to click regularly. The finished function block "MOTOR_AUTO"


[FB1] with the timer is shown in FBD below.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 20
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

→ Under "General" in the properties of the block, you can change the "Language" to LAD
(Ladder Logic) (→Properties → General → Language: LAD)

→ This is what networks 1 and 2 look like in LAD.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 21
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

7.3 Update the block call in the organization block


→ Open the "Main [OB1]" organization block with a double-click.

→ In Network 1 of the "Main [OB1" organization block, instance data block


"MOTOR_AUTO_DB1" for the "MOTOR_AUTO [FB1]" function block appears incorrect,
because the additional memory for the TP Timer has not yet been added there. Click the → "

" icon for "Update inconsistent block calls". This will add the "MOTOR_AUTO_DB1"

instance data block correctly again (→ ).

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 22
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

7.4 Save and compile the program


→ To save your project, select the button in the menu. To compile all blocks, click

the "Program blocks" folder and select the icon for compiling in the menu

(→ → Program blocks → ).

→ The "Info", "Compile" area shows which blocks were successfully compiled.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 23
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

7.5 Download the program


→ After successful compilation, the complete controller with the created program including the

hardware configuration, as previously described in the modules, can be downloaded (→ ).

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 24
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

7.6 Monitor program blocks


→ The desired block must be open for monitoring the downloaded program. Monitoring can now

be activated/deactivated by clicking the icon (→ Main [OB1] → ).

Note: The monitoring here is signal-related and controller-dependent. The signal states at the
terminals are indicated with TRUE or FALSE.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 25
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

→ The "MOTOR_AUTO" [FB1] function block called in the "Main [OB1]" organization block can
be selected directly for "Open and monitor" after right-clicking, thereby allowing the program
code in the function block with the TP Timer to be monitored

(→ "MOTOR_AUTO" [FB1] → Open and monitor).

Note: The monitoring here is function-related and controller-independent. The actuation of


sensors and the station status are shown here with TRUE or FALSE.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 26
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

7.7 Archive the project


→ As the final step, we want to archive the complete project. Select the → "Archive ..."
command in the → "Project" menu. Select a folder where you want to archive your project
and save it with the file type "TIA Portal project archive". (→ Project → Archive → TIA Portal
project archive → SCE_EN_031-300_IEC_Timers_Counters_S7-1200…. → Save)

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 27
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

7.8 Checklist
No. Description Completed

1 Compiling successful and without error message

2 Download successful and without error message

Switch on station (-K0 = 1)


Cylinder retracted / Feedback activated (-B1 = 1)
EMERGENCY OFF (-A1 = 1) not activated
AUTOMATIC mode (-S0 = 1)
3 Pushbutton automatic stop not actuated (-S2 = 1)
Briefly press the automatic start pushbutton (-S1 = 1)
Sensor at chute activated (-B4 = 1)
Conveyor motor forwards fixed speed then switches on (-Q1 = 1)
and stays on.

4 Sensor at end of conveyor activated (-B7 = 1) → -Q1 = 0 (after 2


seconds)

5 Briefly press the automatic stop pushbutton (-S2 = 0) → -Q1 = 0

6 Activate EMERGENCY OFF (-A1 = 0) → -Q1 = 0

7 Manual mode (-S0 = 0) → -Q1 = 0

8 Switch off station (-K0 = 0) → -Q1 = 0

9 Cylinder not retracted (-B1 = 0) → -Q1 = 0

10 Project successfully archived

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 28
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

8 Exercise
8.1 Task – Exercise
In this exercise, an IEC counter is to be added to the MOTOR_AUTO [FB1] function block. The
expanded function block will be planned, programmed and tested:

The magazine for plastic holds only 5 parts. The parts are therefore be counted at the end of the
conveyor.
When 5 parts are stored in the magazine, automatic mode is to be stopped.
Once the magazine has been emptied, automatic mode will be restarted with Start_command is
started again and the counter is reset.

8.2 Technology diagram


Here, you see the technology diagram for the task.

Figure 3: Technology diagram

Figure 4: Control panel

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 29
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

8.3 Reference list


The following signals are needed as global operands for this task.

DI Type Identifier Function NC/NO


I 0.0 BOOL -A1 Return signal emergency stop ok NC
I 0.1 BOOL -K0 Main switch "ON" NO
Manual = 0
I 0.2 BOOL -S0 Mode selector manual (0)/ automatic (1)
Auto = 1

I 0.3 BOOL -S1 Pushbutton automatic start NO

I 0.4 BOOL -S2 Pushbutton automatic stop NC

I 0.5 BOOL -B1 Sensor cylinder M4 retracted NO


I 1.0 BOOL -B4 Sensor at chute occupied NO
I 1.3 BOOL -B7 Sensor part at end of conveyor NO

DO Type Identifier Function


Q 0.0 BOOL -Q1 Conveyor motor M1 forwards fixed speed

Legend for reference list

DI Digital Input DO Digital Output

AI Analog Input AO Analog Output

I Input Q Output

NC Normally Closed

NO Normally Open

8.4 Planning
Plan the implementation of the task on your own.

Note: Learn about the use of IEC counters in SIMATIC S7-1200 in the online help.

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 30
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

8.5 Checklist – Exercise

No. Description Completed

1 Compiling successful and without error message

2 Download successful and without error message

Switch on station (-K0 = 1)


Cylinder retracted / Feedback activated (-B1 = 1)
EMERGENCY OFF (-A1 = 1) not activated
AUTOMATIC mode (-S0 = 1)
3 Pushbutton automatic stop not actuated (-S2 = 1)
Briefly press the automatic start pushbutton (-S1 = 1)
Sensor at chute activated (-B4 = 1)
Conveyor motor forwards fixed speed then switches on (-Q1 = 1)
and stays on.
Sensor at end of conveyor activated (-B7 = 1) → -Q1 = 0 (after 2
4
seconds)

5 Briefly press the automatic stop pushbutton (-S2 = 0) → -Q1 = 0

6 Activate EMERGENCY OFF (-A1 = 0) → -Q1 = 0

7 Manual mode (-S0 = 0) → -Q1 = 0

8 Switch off station (-K0 = 0) → -Q1 = 0

9 Cylinder not retracted (-B1 = 0) → -Q1 = 0

10 5th part in magazine → -Q1 = 0

11 Project successfully archived

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 31
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

9 Additional information

More information for further practice and consolidation is available as orientation, for example:
Getting Started, videos, tutorials, apps, manuals, programming guidelines and trial software /
firmware, under the following link:

www.siemens.com/sce/s7-1200

Preview „Additional information“

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 32
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx
Learn-/Training Document | TIA Portal Module 031-300, Edition 2018 | Digital Factory, DF FA

Further Information

Siemens Automation Cooperates with Education


siemens.com/sce
SCE Learn-/Training Documents
siemens.com/sce/documents
SCE Trainer Packages
siemens.com/sce/tp
SCE Contact Partners
siemens.com/sce/contact
Digital Enterprise
siemens.com/digital-enterprise
Industrie 4.0
siemens.com/future-of-manufacturing
Totally Integrated Automation (TIA)
siemens.com/tia
TIA Portal
siemens.com/tia-portal
SIMATIC Controller
siemens.com/controller
SIMATIC Technical Documentation
siemens.com/simatic-docu
Industry Online Support
support.industry.siemens.com
Product catalogue and online ordering system Industry Mall
mall.industry.siemens.com

Siemens AG
Digital Factory
P.O. Box 4848
90026 Nuremberg
Germany

Subject to change and errors


© Siemens AG 2018

siemens.com/sce

For unrestricted use in educational / R&D institutions. © Siemens AG 2018. All rights reserved. 3
SCE_EN_031-300 IEC-Times and Counters S7-1200_R1709.docx